CHAPTER XI.

SWITCHES, FUSES, AND CIRCUIT-BREAKERS.

Electrical transmission has worked a revolution in the art of switching.

As long as the distances to be covered by distribution lines required

pressures of only a few hundred volts, the switch contacts for

generators and feeders could well be exposed in a row on the surface of

vertical marble slabs and separated from each other by distances of only

a few inches. These switches were capable of manual operation even at

times of heavy overload without danger of personal injury to the

operator or of destructive arcing between the parts of a single switch

or from one switch to another near-by. On the back of these marble slabs

one or more sets of bare bus-bars could be located without much

probability that an accidental contact between them would start an arc

capable of destroying the entire switchboard structure and shutting down

the station.

The rise of electric pressures to thousands and tens of thousands of

volts in distribution and transmission systems has vastly increased the

difficulty of safe and effective control with open-air switches. The

higher the voltage of the circuit to be operated under load the greater

must be the distance between the contact parts of each switch and also

between adjacent switches. Such switches must also be farther removed

from the operators as the voltages of their circuits go up, as a person

cannot safely stand very close to an electric arc of several feet or

even yards in length. In the West, where long transmissions are most

common, long break-stick switches have been much used with high

voltages. These switches depend on the length of the break to open the

circuit and on the length of the stick that moves the switch-jaw or plug

to insure the safety of the operator. Where switches of this sort are

used it is highly important to have ample distances between the contact

points of each switch and also between the several switches. On circuits

of not more than 10,000 volts an arc as much as a yard long will in some

cases follow the opening switch blade and hold on for several seconds.

On the 33,000-volt transmission line at Los Angeles a peculiar form of

switch is used which makes a break between a pair of curved wire horns

that are ten inches apart at their nearest points. When the contact

between these horns is broken the arc travels up between portions of the

horns that curve apart and is thus finally ruptured. Besides the very

large space required for open switches on circuits of 5,000 to 10,000

volts or more, there is a further objection that the arcs developed by

opening such switches under heavy loads rapidly destroy the contact

parts and produce large quantities of metallic vapor that is

objectionable in a central station. In some experiments performed at

Kalamazoo (A. I. E. E., vol. xviii., p. 407) with open-air switches the

voltages ranged from 25,000 to 40,000. The loads on circuits broken by

the switches were highly inductive and mounted from 1,200 to 1,300

kilovolt-amperes. At 25,000 volts the arc produced by the open-air

switch held on for several seconds. At 40,000 volts the arc following

the opening of this switch was over thirty feet long, and being out of

doors near the pole line the arc struck the line wires and

short-circuited the system. It has been shown that the oscillations of

voltage occurring when a circuit under heavy load is opened by an

open-air switch may be very dangerous to insulation (A. I. E. E., vol.

xviii., p. 383). In the Kalamazoo test the oscillations of this sort

were reported to have reached two or three times the normal voltage of

the system when the open-air switch was used.

[Illustration: FIG. 55.--Connections between Power-houses 1 and 2 at

Niagara Falls.]

Facts of the nature just outlined have led to the development of oil

switches. The general characteristic of oil switches is that the contact

parts are immersed in, and the break between these contacts takes place

under, oil. Two types of the oil switch are made, one having all of its

contact parts in the same bath of oil and the other having a separate

oil-bath for each contact. Compared with those of the open-air type, oil

switches effect a great saving of space, develop no exposed arcs or

metallic vapors, cause little if any oscillation or rise of voltage in

an alternating circuit, and can be depended on to open circuits of any

voltage and capacity now in use. In the tests above mentioned at

Kalamazoo, a three-phase oil switch making two breaks in each phase and

with all the six contacts in a single oil-bath was used to open circuits

of 25,000 volts and 1,200 to 1,300 kilovolt-arcs with satisfactory

results. At 40,000 volts, however, this type of switch spat fire and

emitted smoke, indicating that it was working near its ultimate

capacity. A three-phase switch with each of its six contacts in a

separate cylindrical oil-chamber was used to open the 40,000-volt 1,300

kilovolt-arc circuit at Kalamazoo with perfect success even under

conditions of short-circuit and without the appearance of fire or smoke

at the switch. The three-phase switch used in the tests at Kalamazoo

and having each of its contacts in a separate oil-chamber was similar in

construction to the switches used in the Metropolitan and Manhattan

railway stations in New York City. In each of these switches the two

leads of each phase terminate in two upright brass cylinders. These

cylinders have fibre linings to prevent side-jumping of the arcs when

the switch is opened, and each cylinder is filled with oil. Into the two

brass cylinders of each phase dips a ∩-shaped contact piece through

insulating bushings, and the ends of this contact piece fit into

terminals at the bottom of the oil pots. A wooden rod joins the centre

or upper part of the ∩-contact piece, and the three rods of a

three-phase switch pass up through the switch compartment to the

operating mechanism outside. The six brass cylinders and their three

∩-contact pieces are usually mounted on a switch cell built entirely of

brickwork and stone slabs. For a three-phase switch the brick and stone

cell has three entirely separate compartments, and each compartment

contains the two brass cylinders that form the terminals of a single

phase. On top of and outside the cell the mechanism for moving the

wooden switch rods is mounted. In the Metropolitan station, where the

voltage is 6,000, the vertical movement of the ∩-shaped contact piece

with its rod is twelve inches. At the Manhattan station, where the

operating voltage is 12,000, the vertical movement of the ∩-contacts in

opening a switch is seventeen inches. The total break in each phase in a

switch at the Metropolitan station is thus twenty-four inches, or four

inches per 1,000 volts, and the total break per phase in switches at

the Manhattan station is thirty-four inches, or 2.66 inches per 1,000

volts total pressure.

Oil switches are now very generally employed on alternating circuits

that operate at 2,000 volts or more for purposes of general

distribution. On circuits of moderate voltage like that just named, and

even higher, it is common practice to use oil switches that have only a

single reservoir of oil each, the entire six contacts in the case of a

three-phase switch being immersed in this single reservoir. Such

switches are usually operated directly by hand and are located on the

backs of or close to the slate or marble boards on which the handles

that actuate the switch mechanism are located. A good example of this

sort of work may be seen at the sub-station in Manchester, N. H., where

energy from four water-power stations is delivered over seven

transmission lines and then distributed by an even larger number of

local circuits at 2,000 volts three-phase. At the Garvin’s Falls

station, one of the water-power plants that delivers energy to the

sub-station in Manchester, the generators operate at 12,000 volts

three-phase, and these generators connect directly with the bus-bars

through hand-operated oil switches on the back of the marble

switchboard. These last-named switches, like those at the Manchester

sub-station, have all the contacts of each in a single reservoir of oil.

With very high voltages, where only a few hundred kilowatts are

concerned, and also with powers running into thousands of kilowatts at

as low a pressure as 2,000 volts, it is very desirable to remove even

oil switches from the switchboard and the vicinity of the bus-bars.

Great powers as well as very high voltages not only increase the element

of personal danger to an attendant who must stand close to a switch

while operating it, but also render the damage to other apparatus that

may result from any failure of or short-circuit in a switch much more

serious.

[Illustration: FIG. 56.--Wire-room Back of Switchboard in Power-station

on French Broad River, North Carolina.]

As soon as the switches are removed to a distance from the operating

board the necessity for some method of power control becomes evident,

since the operator at the switchboard should be able to make or break

connections of any part of the apparatus quickly. The necessity for the

removal of switches for very large powers to a distance from the

operating boards and for the application of mechanical power to make and

break connections was met before the development of oil switches. Thus

at the first Niagara (A. I. E. E., vol. xviii., p. 489) power-house, in

1893, the switches for the 3,750-kilowatt, 2,200-volt generators, though

of the open-air type, were located in a special switch compartment

erected in the generator room and over a cable subway at some distance

from the operating board. These switches were actuated through

compressed-air cylinders into which air was admitted by the movement of

levers near the switchboard. Evidently a switch of this capacity--1,000

amperes per pole and 2,200 volts, two-phase--could not well be operated

by hand-power wherever located, because of the large effort required. In

the second generating station at Niagara Falls oil switches similar to

those used at the Manhattan Elevated Railway plant in New York, but

two-phase, were employed. Each of these oil switches at Niagara Falls

has a capacity of 5,000 horse-power, like the previous open-air

switches, and is electrically actuated.

[Illustration: FIG. 57.--Section through Cable Subway under Oil Switches

in Niagara Power-house No. 2.]

In these electrically operated oil switches a small motor is located on

top of the brick cell that contains the contact parts, and this motor

releases and compresses springs that open and close the switch. While it

is not desirable to employ open-air switches to open circuits of several

thousand or even hundreds of kilowatts at voltages of 2,000 or more, it

is nevertheless possible to do so. This is shown by the experience of

the first Niagara Falls station, where the 2,200-volt two-phase switches

are reported to have opened repeatedly currents of more than 600 amperes

per phase without injurious sparking. The great rise of voltage that was

shown by the experiments at Kalamazoo to follow the opening of a simple

open-air switch was avoided at the first Niagara switches by a simple

expedient. In these 5,000 horse-power open-air switches a shunt of high

resistance was so connected between each pair of contacts that the

blades and jaws that carried the main body of the current never

completely opened the circuit. When the main jaws of one of these

switches were opened the shunt resistance continued in circuit until

subsequently broken at auxiliary terminals. That no excessive rise of

voltage took place when one of these switches was open was shown by

connecting two sharp terminals in parallel with the switch and by

adjusting these terminals to a certain distance apart. Had the voltage

risen on opening the switch above the predetermined amount there would

have been an arc formed by a spark jumping the distance between the

pointed terminals.

[Illustration: FIG. 58.--Schenectady Switch-house on Spier Falls Line.]

[Illustration: FIG. 59.--Second-floor Plan of Saratoga Switch-house on

Spier Falls Line.]

Safety and reliability of operation at high voltages, say of 5,000 or

more, require that each element of the equipment be so isolated as well

as insulated from every other element that the failure or even

destruction of one element will not seriously endanger the others. With

this end in view the cables from each generator to its switch should be

laid in a conduit of brick or concrete that contains no other cables.

The brick or stone compartment for each phase of each switch should be

so substantial that the contacts of that phase may arc to destruction

without injury to the contacts of another phase. Bus-bars, like

switches, should be removed from the operating switchboard, because an

arc between them might destroy other apparatus thereon, and even the

board itself. It is not enough to remove bus-bars from the switchboard

where very high voltages are to be controlled, but each bar should be

located in a separate brick compartment so that an arc cannot be started

by accidental contact between two or more of the bars. It is convenient

to have the brick and stone compartments for bus-bars built horizontally

one above the other. The top and bottom of each compartment may

conveniently be formed of stone slabs with brick piers on one side and a

continuous brick wall on the other to hold the stone slabs in position.

Connections to the bus-bars should pass through the continuous brick

wall that forms what may be termed the back of the compartments. To

close the openings between the brick piers at the front of the

compartments movable slabs of stone may be used. Feeders passing away

from the bus-bars, like dynamo cables running to these bars, should not

be grouped close together in a single compartment, but each cable or

circuit should be laid in a separate fireproof conduit to the point

where it passes out of the station.

[Illustration: FIG. 60.--Ground Floor of Saratoga Switch-house.]

The folly of grouping a large number of feeders that transmit great

powers together in a single combustible compartment was well illustrated

by the accident that destroyed the cables that connected the first

Niagara power-station with the transformer-house on January 29th, 1903.

On the evening of that day lightning short-circuited one of the cables

in the short bridge that connects No. 1 station with the

transformer-house, and all the cables in this bridge, supplying local

consumers as well as railways and lighting in Buffalo, were destroyed.

This bridge contained probably more than thirty-six cables, as that

number of new cables was put in position within twenty-four hours after

the accident, and these cables, covered with inflammable insulation,

were close together. The result was not only the loss of the cables, but

also the damage to power users. If these cables had been located in

separate fire-proof conduits, it is highly probable that only the one

directly affected by lightning would have been destroyed.

The brick and stone compartments for bus-bars may be located in the

basement underneath the switchboard, as at the Portsmouth station of the

New Hampshire Traction Company, or at any other place in a station where

they are sufficiently removed from the other apparatus. In power-house

No. 2 at Niagara Falls a cable subway beneath the floor level runs the

entire length, parallel with the row of generators (A. I. E. E., vol.

xix., p. 537). In this subway, which is thirteen feet nine and

three-quarter inches wide and ten feet six inches high, the two

structures for bus-bar compartments are located. Each of these

structures measures about 6.6 feet high and 1.8 feet wide, and contains

four bus-bar compartments. In each compartment is a single bar, and the

four bars form two sets for two-phase working. Above the bus-bar

compartments and rising from the floor level are the oil switches. A

space over the cable subway midway of its length and between the two

groups of oil switches is occupied by the switchboard gallery which is

raised to some elevation above the floor and carries eleven generator,

twenty-two feeder, two interconnecting, and one exciter panels. In

power-house No. 1 the bus-bars are located in a common space above the

5,000 horse-power open-air switches already mentioned, and each bar has

an insulation of vulcanized rubber covered with braid and outside of

this a wrapping of twine. Of course; an insulation of this sort would

amount to nothing if by any accident an arc were started between the

bars. Where each bus-bar is located in a separate fireproof compartment,

as at Niagara power-house No. 2, the application of insulation directly

to each bar is neither necessary nor desirable. Consequently the general

practice where each bar has its own fireproof compartment is to

construct the bars of bare copper rods.

With main switches for generators and feeders removed from the operating

board and actuated by electric motors or magnets, the small switches at

the board with which the operator is directly concerned must of course

control these magnets or motors. The small switches at the operating

board are called relay switches, and the current in the circuits opened

and closed by these switches and used to operate the magnets or motors

of the oil switches may be conveniently obtained from a storage battery

or from one of the exciting dynamos.

Probably the best arrangement of the relay switches is in connection

with dummy bus-bars on the face of the switchboard, so that the

connections on the face of the board constitute at all times a diagram

of the actual connections of the generator and feeder circuits. It is

also desirable for quick and correct changes in the connections of the

main apparatus that all the relay switches and instruments necessary for

the control of any one generator or any one feeder be brought together

on a single panel of the switchboard. If this plan is followed, the

operator at any time will have before him on a single panel all of the

switches and instruments involved in the connections then to be made,

and the chance for mistakes is thus reduced to a minimum. The plan just

outlined was that adopted at the Niagara power plant No. 2, where a

separate panel is provided for each of eleven generators and each of

twenty-two feeders. On each of the eleven generator panels there are two

selector relay switches, one generator relay switch, and one relay

generator field switch. On each of the twenty-two feeder panels there

are two relay selector switches. The relay switches on the two

interconnecting panels serve to make connections between the two groups

of five and six generators respectively in power-house No. 2 and the ten

generators of power-house No. 1. On each panel there are relay

indicators to show whether the oil switches that carry the main current

respond to the movements of their relay switches.

Where the electric generators operate at the maximum voltage of the

system, as at Garvin’s Falls and in the power-house of the Manhattan

Elevated Railway, there may be said to be only one general plan of

connections possible. That is, the generators must connect directly with

the main bus-bars at the voltage of the system, and the feeders or

transmission lines must also connect to these same bars. Of course there

may be several sets of bus-bars for different circuits or classes of

work, but this does not change the general plan of through connections

from generators to lines. So, too, the arrangement of switches is

subject to variations, as by placing two switches in series with each

other in each dynamo or feeder cable, or by connecting a group of

feeders through their several switches to a particular set of bus-bars

and then supplying this set of bars from the generator bus-bars through

a single switch.

[Illustration: FIG. 61.--Switchboard Wiring, Glens Falls Sub-station on

Spier Falls Line.]

Where the voltage of transmission is obtained by the use of step-up

transformers, the connections of these transformers may be such as to

require nearly all switching to be done on either the high- or

low-tension circuits. The more general practice was formerly to do all

switching in the generator circuits and on the low-tension side of

transformers, except in the connection and disconnection of transformers

and transmission lines with the high-tension bus-bars, when not in

operation. Where generators operate at the maximum voltage of the system

only two main groups of switches are necessary, one group connecting

generators to bus-bars, and the other group connecting bus-bars to the

transmission lines. As soon as step-up transformers are introduced the

number of switch groups must be increased to four if the usual method of

connection is followed, and there must be both a high voltage and a low

voltage set of bus-bars. That is, one set of switches must connect

generators with low-tension bus-bars, another group must connect

low-tension bars with the primary coils of transformers, a third group

joins the secondary coils of transformers with the high-tension bars,

and the fourth group of switches joins the transmission lines to the

high-tension bus-bars. Switches connecting the secondary coils of

step-up transformers to the high-tension bus-bars, and also the

transmission lines to these same bars, have often been of the simple

open-air type with short knife-blade construction. These switches have

been used to disconnect the secondary coils of transformers and also the

transmission lines from the high-tension bus-bars when no current was

flowing, and switches of the simple knife-blade construction with short

breaks could of course be used for no other purpose. With switches of

this sort on the high-tension side of apparatus the practice is to do

all switching of line circuits on the low-tension side.

It is possible to avoid some of this multiplication of switches if each

generator with its transformers is treated for switching purposes as a

unit and the switching for this unit is done on the secondary or

high-voltage side of the step-up transformers. The adoption of this

plan, of course, implies the use of switches that are competent to break

the secondary circuit of any group of transformers under overload

conditions and at the maximum voltage of the system, but oil switches as

now made are competent to meet this requirement. When all switching of

live circuits is confined to those of high voltage there is also the

incidental advantage that heavy contact parts carrying very large

currents are avoided in the operating switches. Where each generator is

connected directly to its own group of transformers the secondary coils

of these transformers will pass through oil switches to high-tension

bus-bars, and the use of low-tension bus-bars may be avoided. From these

high-tension bus-bars the transmission lines will pass through oil

switches, so that on this plan there are only two sets of oil switches,

namely, those connecting the secondary coils of transformers to the

high-tension bus-bars, and those connecting the transmission lines to

the same bars. Each group of two or three transformers, according as

two or three are used with each generator, should be connected to its

generator through short-break, open-air knife switches for convenience

in disconnecting and changing transformers that are not in operation,

but these switches are not intended or required to open the circuit of

the generators and primary coils when in operation.

[Illustration: FIG. 62.--Distributing Switchboard, Central Sub-station,

Montreal.]

A plan similar to that just outlined was followed at the station of the

Independent Electric Light and Power Company, San Francisco, where each

of the 550-volt generators is ordinarily connected directly to the

primary coils of two transformers that change the current from two-phase

to three-phase and then deliver it through oil switches to the

high-tension bus-bars at 11,000 volts. To these bus-bars the 11,000-volt

feeders for five sub-stations are connected through switches. At this

station there is a set of 550-volt bus-bars to which any of the

generators may be connected, but to which no generator is connected in

ordinary operation. The generators alone have switches connecting with

these bars. When it is desirable to operate any particular generator on

some pair of transformers other than its own, that generator is

disconnected from its own transformers and connected to the 550-volt

bus-bars. The generator whose transformers are to be operated by the

generator before mentioned next has its switch connected to the 550-volt

bus-bars, while the brushes of the contact rings of the former generator

are raised. As the leads from each generator to its two switches are

permanently joined, the switching operations just named connect the

transformers of one generator with the other generator that has its

switch closed on the 550-volt bars.

[Illustration: FIG. 63.--Switchboard at Chambly Power-station.]

Where it is desired that a single reserve transformer may be readily

substituted for any one of a number of transformers in regular use, the

connections to each of these latter transformers may be provided with

double-pole double-throw knife switches on both the primary and

secondary sides, so that when these switches are thrown one way at any

transformer in regular use the reserve transformer will be connected in

its place.

Fuses and automatic circuit-breakers alike are intended to break

connections without the intervention of human agency under certain

predetermined conditions. In the fuse the heat generated by a certain

current is sufficient to melt or vaporize a short length of special

conductor. In the circuit-breaker a certain current gives a magnet or

motor sufficient strength to overcome the pressure of a spring, and

contact pieces through which the current is passing are pulled apart.

The primary object of both the fuse and the circuit-breaker is thus to

open connections and stop the flow of energy when more than a certain

current passes. When any current passes through a circuit in the reverse

of its regular direction the circuit-breaker can be arranged to break

the connections, though the fuse cannot. A fuse must carry the current

at which it is designed to melt during some seconds before enough heat

is developed to destroy it, and the exact number of seconds for any

particular case is made a little uncertain by the possibility of loose

connections at the fuse tips which develop additional heat and also by

the heat-conducting power of its connecting terminals. A circuit-breaker

may be set so as to open its connections in one or more seconds after a

certain current begins to flow. When connections are broken by a fuse

the molten or vaporized metal forms a path that an arc may easily

follow. A circuit-breaker with its contacts under oil offers a much

smaller opportunity than a fuse for the maintenance of an arc. These

qualities of fuses and circuit-breakers form the basis of their general

availability and comparative advantages in transmission circuits.

Much variation exists in practice as to the use of fuses and

circuit-breakers on transmission circuits. One view often followed is

that fuses and circuit-breakers should be entirely omitted from the

generator and transmission lines. The argument in favor of this practice

is that temporary short circuits due to birds that fly against the lines

or to sticks and loose wires that are thrown onto them will interrupt

all or a large part of the transmission service if fuses or

circuit-breakers that operate instantly are employed. On the other hand,

it may be said that if fuses and circuit-breakers are omitted from the

generator and transmission circuits a lasting short circuit will make it

necessary to shut down an entire plant in some cases until it can be

removed. Electric transmission at high voltages became important before

magnetic circuit-breakers competent to open overloaded circuits at such

voltages were developed. Consequently the early question was whether a

transmission line and the generators that fed it should be provided with

fuses or be solidly connected from generators to the distribution

circuits of sub-stations. The original tendency was strong to use fuses

in accord with the practice at low voltages. The great importance of

continuous service from transmission systems and the many interruptions

caused by temporary short circuits where fuses were used led to their

abandonment in some cases. An example of this sort may be seen at the

first Niagara station. In 1893, when this station was equipped, no

magnetic circuit-breaker was available for circuits of either 11,000 or

2,200 volts, carrying currents of several thousand horse-power, and

fuses were employed in lines at both these pressures (A. I. E. E., vol.

xviii., pp. 495, 497). The fuses adopted in this case were the same for

both the 2,200 and the 11,000-volt lines and were of the explosive type.

Each complete fuse consisted of two lignum-vitæ blocks that were hinged

together at one end and were secured when closed at the other. In these

blocks three parallel grooves for fuses were cut and in each groove a

strip of aluminum was laid and connected to suitable terminals at each

end. Vents were provided for the grooves in which the aluminum strips

were placed so that the expanding gas when a fuse was blown would

escape. When these fuse blocks were new and the blocks of lignum vitæ

made tight joints the metallic vapor produced when a fuse was blown was

forced out at the vents and the connections of the line were thus

broken. After a time, however, when the joints between the blocks were

no longer tight because of shrinkage, the expanding gas of the fuse

would reach the terminals and an arc would continue after the fuse had

blown. These aluminum fuses, which were adopted about 1893, were

abandoned at the Niagara plant in 1898. Since this later date the

2,200-volt feeders from the No. 1 power-house to the local consumers

have had no fuses at the power-house, nor have circuit-breakers been

installed there in the place of the fuses that were removed. At the

large manufacturing plants supplied through these local Niagara feeders,

the feeders formerly terminated in fuses, but these have since been

displaced by circuit-breakers. In the second Niagara power-station,

completed in 1902, the local 2,200-volt feeders are provided with

circuit-breakers, but no fuses. Between the generators and bus-bars of

the first Niagara plant the circuits were provided with neither fuses

nor automatic circuit-breakers, and this practice continues there to the

present time.

Besides the aluminum fuses in the 11,000-volt transmission line at the

first Niagara station, there were lead fuses in the 2,200-volt primary

circuits of the step-up transformers that supplied these lines. At the

other end of these lines, in the Buffalo sub-station, another set of

aluminum fuses was inserted before connection was made with the

step-down transformers. Between the secondary coils of these

transformers and the 550-volt converters there were no fuses, but these

converters were connected to the railway bus-bars through direct current

circuit-breakers. These lead fuses, which contained much more metal than

those of aluminum, when blown set up arcs that lasted until power was

cut off by opening a switch, and usually destroyed their terminals. An

effort was made to so adjust the sizes of the fuses in this transmission

system that in case of a short circuit in distribution lines at Buffalo

only the fuses in the sub-station would be blown, leaving those at

Niagara entire. This plan did not prove effective, however, and a severe

overload on the distribution lines in Buffalo would blow out fuses clear

back to the generator bus-bars at the Niagara station.

In order to accomplish the opening of overloaded circuits with greater

certainty, to delay such opening where the overload might be of only a

momentary nature, and to confine the open circuit to the lines where the

overload existed, automatic circuit-breakers were substituted for the

fuses named in the Niagara and Buffalo transmission system. This system

was also changed from 11,000 to 22,000 volts on the transmission lines,

thus rendering the requirements as to circuit-opening devices more

severe. These circuit-breakers were fitted with time-limit attachments

so that any breaker could be set to open at the end of any number of

seconds after the current flowing through it reached a certain amount. A

circuit-breaker with such a time-limit attachment will not open until

the time for which it is set, after the amperes flowing through it reach

a certain figure, has elapsed, no matter how great the current may be.

Moreover, if the overload is removed from a line before the number of

seconds for which its time-limit circuit-breaker is set have elapsed,

the circuit-breaker resets itself automatically and does not open the

connections. If a circuit-breaker is set to open a line after an

interval of say three seconds from the time when its current reaches the

limit, the line will not be opened by a mere momentary overload such as

would blow out a fuse. By setting the time-limit relays of

circuit-breakers in transmission lines to actuate the opening mechanism

after three seconds from the time that an overload comes on, and then

leaving the breakers on distribution lines to operate without a

time-limit, it seems that the opening of breakers on the distribution

lines should free the system from an overload there before the breakers

on the transmission lines have time to act. Such a result is very

desirable in order that the entire service of a transmission system may

not be interrupted every time there is a fault or short circuit on one

of its distribution lines. This plan was followed in the Niagara and

Buffalo system. In the 22,000-volt lines at the Niagara station the time

relays were set to actuate the breakers after three seconds, at the

terminal house in Buffalo, where the transformers step down from 22,000

to 11,000 volts, the circuit-breakers in the 11,000 volt lines to

sub-stations had their relays set to open in one second. Finally the

circuit-breakers in the distribution lines from the several sub-stations

were left to operate without any time limit. By these means it was

expected that a short circuit in one of the distribution circuits from a

sub-station would not cause the connections of the underground cable

between that sub-station and the terminal house to be broken, because of

the instant action of the circuit-breaker at the sub-station.

Furthermore, it was expected that a short circuit in one of the

underground cables between the terminal house and a sub-station would be

disconnected from the transmission line at that house and would not

cause the circuit-breakers at the Niagara station to operate. It is

reported that the foregoing arrangement of circuit-breakers with time

relays failed of its object because the breakers did not clear their

circuits quick enough and that the time-limit attachments on the 22,000

and 11,000 volt lines are no longer in use (A. I. E. E., vol. xviii., p.

500). As the circuits under consideration convey thousands of

horse-power at 11,000 and 22,000 volts it may be that time-limit devices

with circuit-breakers would give good results under less exacting

conditions. Time-limit relays are perhaps an important aid toward

reliable operation of transmission systems, but they are subject to the

objection that no matter how great the overload they will not open the

circuit until the time for which they are set has run. In the case of a

short circuit the time-limit relay may lead to a prolonged drop in

voltage throughout the system, which is very undesirable for the

lighting service and also allows all synchronous apparatus to fall out

of step. With a mere momentary drop in voltage the inertia of the

rotating parts of synchronous apparatus will keep them in step. For

these reasons it is desirable to have circuit-breakers that will act

immediately to open a line on which there is a short circuit or very

great overload, but will open the line only after an interval of one or

more seconds when the overload is not of a very extreme nature. This

action on the part of circuit-breakers at the second Niagara

power-station was obtained by the attachment of a dash-pot to the

tripping plunger of each circuit-breaker (A. I. E. E., vol. xviii., p.

543). With moderate overloads of a very temporary nature this dash-pot

so retards the action of a tripping plunger that the circuit-breaker

does not open. When a short circuit or great overload comes onto a line

the pull on the tripping plunger or the circuit-breaker on that line is

so great that the resistance of the dash-pot to the movement is overcome

at once and the line is disconnected from the remainder of the system.

The fact that a circuit-breaker may be designed to open the line which

it connects, whenever the direction from which the flow of energy takes

place is reversed, is taken advantage of at some sub-stations to guard

against a flow of energy from a sub-station back toward the generating

station. By this means a flow of energy from a sub-station to a short

circuit in one of the lines or cables connecting it with the generating

plant is prevented.