CHAPTER X.

TRANSFORMERS IN TRANSMISSION SYSTEMS.

Transformers are almost always necessary in long electric systems of

transmission, because the line voltage is greater than that of

generators, or at least that of distribution. As transformers at either

generating or receiving stations represent an increase of investment

without corresponding increase of working capacity, and also an

additional loss in operation, it is desirable to avoid their use as far

as is practicable. In short transmissions over distances of less than

fifteen miles it is generally better to avoid the use of transformers at

generating stations, and in some of these cases, where the transmission

is only two or three miles, it is even more economical to omit

transformers at the sub-stations.

Thus, where energy is to be transmitted two miles and then applied to

large motors in a factory, or distributed at 2,500 volts, the cost of

bare copper conductors for the three-phase transmission line will be

only about $6 per kilowatt of line capacity at 2,500 volts, with copper

at 15 cents per pound, and a loss of 5 per cent at full load. The

average loss in such a line will probably be as small as that in one set

of transformers and a line of higher voltage. Furthermore, the first

cost of the 2,500-volt generators and line without transformers will be

less than that of generators and line of higher voltage with step-down

transformers at the sub-station.

As generators up to 13,500 volts are now regularly manufactured, it is

quite common to omit step-up transformers at the main stations of rather

short transmission systems. This practice was followed in the

13,500-volt transmission to Manchester, N. H., the 10,000-volt

transmission to Lewiston, Me., and the 12,000-volt transmission to

Salem, N. C.

In most transmission over distances of twenty-five miles or more,

step-up transformers at generating stations as well as step-down

transformers at sub-stations are employed. As yet the highest voltages

that have been put into practical use on transmission lines (that is,

50,000 to 60,000) are much below the pressures that have been yielded by

transformers in experimental work. These latter voltages have in a

number of instances gone above 100,000. The numbers and capacities of

transformers used at main stations vary much in their relation to the

numbers and individual capacities of generators there. In some cases

there are three times as many transformers as three-phase generators,

and the capacity of each transformer is either equal to or somewhat

greater than one-third of the capacity of each generator.

[Illustration: FIG. 53.--Transformers at Central Sub-station, Montreal.]

Thus in the station at Spier Falls on the Hudson, whence power is

transmitted to Albany and other cities, the number of step-up

transformers will be thirty and their aggregate capacity will be 24,014

kilowatts, while the total number of three-phase generators will be ten,

with a combined capacity of 24,000 kilowatts. Another practice is to

give each transformer a capacity greater than one-third of that of the

three-phase generator with which it is to be connected, and make the

total number of transformers less than three times as great as the

number of generators. An example of this sort exists in the station on

Apple River, whence power is transmitted to St. Paul. This station

contains four three-phase generators of 750 kilowatts each, and six

transformers of 500 kilowatts each, these latter being connected in two

sets of three each. The use of three transformers for each three-phase

generator instead of three transformers for each two or three

generators, tends to keep transformers fully loaded when in use, and

therefore to increase their efficiency. On the other hand, efficiency

increases a little with the size of transformers, and the first cost per

unit capacity is apt to be less the greater the size of each.

Another solution of the problem is to provide one transformer for each

three-phase generator, each transformer being wound with three sets of

coils, so that the entire output of a generator can be sent into it.

This practice is followed at the Hochfelden water-power station, whence

power is transmitted to Oerlikon, Switzerland, also in the water-power

station at Grenoble, France, whence energy at 26,000 volts is

transmitted to a number of factories. With three-phase transformers each

generator and its transformer may form an independent unit that can be

connected with the line at pleasure, thus tending to keep transformers

at full load.

Though three-phase transformers are much used in Europe, they have thus

far had little application in the United States. Single-phase

transformers may, of course, be limited in number to that of the

three-phase generators with which they are used, but such transformers

must regularly be connected to the generators and line in groups of two

or three. Such an equipment was provided in part at the 7,500-kilowatt

station on the Missouri River at Cañon Ferry, which contains ten

three-phase generators of 750 kilowatts each. The transformers at this

station include twelve of 325 kilowatts each, connected in four groups

of three each, also six transformers of 950 kilowatts each which are

also connected in groups of three. Three of these larger transformers

have a capacity of 2,850 kilowatts, or nearly equal to that of four

generators.

With two-phase generators single-phase transformers must be connected in

pairs, and it is common to provide two transformers for each generator.

Thus, in the Rainbow station on the Farmington River, whence energy is

transmitted to Hartford, there are two generators of the two-phase type

and rated at 600 kilowatts each, also four transformers rated at 300

kilowatts each.

As the regulation of transformers on overloads is not as good as that of

generators, it seems good practice to give each group of transformers a

somewhat greater capacity than that of the generator or generators whose

energy is to pass through it. This plan was apparently followed at the

Cañon Ferry station, where the total generator capacity is 7,500

kilowatts and the total capacity of step-up transformers is 9,600

kilowatts. Each group of the 325-kilowatt transformers there has a

capacity of 975 kilowatts, while each generator is only of 750

kilowatts. Usually the number of groups of transformers at a two-phase

or three-phase generating station is made greater than the number of

transmission circuits supplied by the station, for some of the reasons

just considered. When this is not the case it is commonly desirable in

any event to have as many groups of step-up transformers as there are

transmission circuits, so that each circuit may be operated with

transformers that are independent of the other circuits.

At sub-stations it is desirable to have a group of transformers for each

transmission circuit, and it may be necessary to subdivide the

transformer capacity still further in order to keep transformers in

operation at nearly full load, or to provide a group of transformers for

each sort of service or for each distribution circuit. All of the

transformers at a sub-station should have a total capacity at least

equal to that of the generators whose energy they are to receive, minus

the losses in step-up transformers and the line. Transformers at

sub-stations do not necessarily correspond in number or individual

capacity with those at generating stations, and the number of

sub-station transformers bears no necessary relation to the number of

generators by which they are fed.

Two transmission circuits extend from Cañon Ferry to a sub-station at

Butte, and in that sub-station there are six transformers divided into

two groups for three-phase operation, each transformer being rated at

950 kilowatts. This sub-station equipment thus corresponds to only the

six 950-kilowatt transformers in the generating station, because the

four groups of smaller transformers there are used to supply the

transmission line to Helena.

In the sub-station at St. Paul that receives the entire output of the

plant on Apple River, where the six transformers of 500 kilowatts each

are located, ten transformers receive energy from two three-phase

transmission circuits. Six of these transformers are rated at 300

kilowatts each. The 300-kilowatt transformers are connected in two

groups of three each, and the 200-kilowatt in two groups of two each,

transforming current from three-phase to two-phase. The aggregate

capacity of the sub-station transformers is thus 2,600 kilowatts, while

that of transformers at the generating station is 3,000 kilowatts. With

four generators at the water-power plant there are ten transformers at

the sub-station, where all the energy, minus losses, is delivered.

At Watervliet, where one of the several sub-stations of the system with

its larger generating plant at Spier Falls is located, the capacity of

each transformer is 1,000 kilowatts, though each transformer at Spier

Falls has a rating below this figure.

In the sub-station at Manchester, N. H., that receives nearly all of the

energy from four water-power plants, containing eight generators with an

aggregate capacity of 4,030 kilowatts, there are located twenty-one

step-down transformers that have a total rating of 4,200 kilowatts.

These twenty-one transformers are fed by six circuits, of which five are

three-phase and one is two-phase. A part of the transformers supply

current to motor-generators, developing 500-volt current for a street

railway, and the remaining transformers feed circuits that distribute

alternating current.

From these examples it may be seen that in practice either one or more

groups of transformers are employed in sub-stations for each

transmission circuit, that the total number of these transformers may be

just equal to or several times that of the generators from which they

receive energy, and that the individual capacities of the transformers

range from less than one-third to more than that of a single generator.

Groups of transformers at a main station must correspond in voltage with

that of the generators in the primary and that of the transmission line

in the secondary windings. Sub-station transformers receive current at

the line voltage and deliver it at any of the pressures desired for

local distribution. Where step-up transformers are employed the

generator pressure in nearly all cases is at some point between 500 and

2,500 volts.

At the Cañon Ferry station the voltage of transformers is 550 in in the

primary and 50,000 in the secondary windings. In the Colgate

power-house, whence energy is transmitted to Oakland, the generator

pressure of 2,400 volts is raised to 40,000 volts by transformers.

Generator voltage in the power-house on Apple River is 800 and

transformers put the pressure up to 25,000 for the line to St. Paul.

Transformers at the Niagara Falls station raise the voltage from 2,200

to 22,000 for the transmission to Buffalo.

As transformers can be wound for any desired ratio of voltages in their

primary and secondary coils, a generator pressure that will allow the

most economical construction can be selected where step-up transformers

are employed. In general it may be said that the greater the capacity of

each generator, the higher should be its voltage and that of the primary

coils of step-up transformers, for economical construction. At

sub-stations the requirements of distribution must obviously fix the

secondary voltages of transformers.

Weight and cost of transformers depend in part on the frequency of the

alternating current employed, transformers being lighter and cheaper the

higher the number of cycles completed per second by their current, other

factors remaining constant. In spite of this fact the tendency during

some years has been toward lower frequencies, because the lower

frequencies present marked advantages as to inductive effects in

transmission systems, the distribution of power through induction

motors, the construction and operation of rotary converters, and the

construction of generators. Instead of the 133 cycles per second that

were common in alternating systems when long transmissions first became

important, sixty cycles per second is now the most general rate of

current changes in such transmission systems. But practice is constantly

extending to still lower frequencies. The first Niagara Falls plant with

its twenty-five cycles per second reached the lower limit for general

distribution, because incandescent lighting is barely satisfactory and

arc lighting decidedly undesirable at this figure.

In contrast with the great transmissions from Cañon Ferry to Butte,

Colgate to Oakland, and Electra to San Francisco, which operate at sixty

cycles, the system between Cañon City and Cripple Creek, in Colorado, as

well as the great plant at Sault Ste. Marie, employs thirty-cycle

current, and the lines from Spier Falls to Schenectady, Albany, and Troy

are intended for current at forty cycles per second. From these examples

it may be seen that the bulk and cost of transformers is not the

controlling factor in the selection of current frequency in a

transmission system.

[Illustration: FIG. 54.--First Floor of Saratoga Sub-station.]

Transformers used at either generating or sub-stations are cooled by

special means in many cases.

The advantages of so-called artificial cooling are smaller weight and

first cost in transformers, and perhaps longer life for the insulation

of windings. For these advantages a small increase in the cost of

operation must be paid. Station transformers are usually cooled either

by forcing air through their cases under pressure, or else by passing

water through pipes in the oil with which the transformer cases are

filled. If cooling with air-blast is adopted, a blower, with electric

motor or some other source of power to operate it, must be provided.

Where transformers are oil-insulated and cooled with water there must be

some pressure to maintain the circulation. If free water under a

suitable head can be had for the cooling of transformers, as in most

water-power plants, the cost is very slight. Where water must be

purchased and pumped through the transformers its cost will usually be

greater than that of cooling with air-blast. One manufacturer gives the

following as approximate figures for the rate at which water at the

temperature of 15° centigrade must be forced through his transformers to

prevent a rise of more than 35° centigrade in their temperature,

probably when operating under full loads.

Transformers--Kilowatts. Gallons per minute.

150 0.5

400 .75

400 1.00

1,000 1.5

75 .37

An air-blast to cool transformers at main or sub-stations may be

provided in either of two ways. One plan is to construct an air-tight

compartment, locate the transformers over openings in its top, and

maintain a pressure in the compartment by means of blower-fans that draw

cool air from outside. Such an arrangement has been carried out at the

sub-station in Manchester, N. H. The basement underneath this

sub-station is air-tight, and in the concrete floor over it there are

twenty-seven rectangular openings, each twenty-five by thirty inches,

and intended for the location of a 200-kilowatt transformer. Aggregate

transformer capacity over these openings will thus be 5,400 kilowatts.

Pressure in this basement is maintained by drawing outside air through a

metal duct that terminates in a hood on the outside of the sub-station

about nine feet above the ground. In the roof of this sub-station there

are ample skylight openings to permit the exit of hot air that has been

forced through the transformers. In the air-tight basement are two

electric motors of ten horse-power each, connected to the blower that

maintains the pressure. It may be noted that in this case there is less

than one-horse power of motor capacity for each 200 kilowatts capacity

in transformers.

Where there are not more than six or nine transformers to be cooled, it

is common practice to provide a separate motor and blower for each group

of three transformers, and lead the air directly from each blower to its

group of transformers by a metal duct, thus avoiding the necessity for

an air-chamber. In such cases a blower giving a three-eighth-ounce air

pressure per square inch and a motor of one horse-power capacity are

generally provided for each group of three transformers rated at 100 to

150 kilowatts each. Where cooling with air-blast is adopted,

oil-insulation cannot be carried out because the air must come into

intimate contact with the transformer coils and core. Both

oil-insulation with water cooling and dry insulation with cooling by

air-blast have been widely used in transmission systems of large

capacity and high voltage.

In the Colgate plant, where the line pressure is 40,000 volts, the

700-kilowatt transformers are oil-insulated and water-cooled, and this

is also true of the 950-kilowatt transformers in the 50,000-volt

transmission between Cañon Ferry and Butte. On the other hand, the

transmission system between Spier Falls, Schenectady, and Albany,

carried out at 26,500 volts, includes transformers that range from

several hundred to 1,000 kilowatts each in capacity and are all

air-cooled. Either a water-cooled transformer or one cooled by air-blast

may be safely overloaded to some extent, if the circulation of air or

water is so increased that the overload does not cause heating beyond

the allowable temperature.

The circulation of air or water through a transformer should never be

forced to an extent that cools the transformer below the temperature of

the air in the room where it is located, as this will cause the

condensation of water on its parts.

In some cases it is desirable that means for the regulation of

transformer voltages through a range of ten per cent or more each way

from the normal be provided. This result is reached by the connection of

a number of sections at one end of the transformer winding to a terminal

board, where they may be cut in or out of action at will. Regulation is

usually desired, if at all, in a secondary winding of comparatively low

voltage, and the regulating sections generally form a part of such

winding, but these sections may be located in the primary winding.

In order to keep the number of transformers smaller and the capacity of

each larger than it would otherwise be, it is practicable to divide the

low-voltage secondary winding of each transformer into two or more

parts that have no electrical connection with each other. These

different parts of the winding may then be connected to distinct

distribution lines or other services. An example of this sort exists in

the Hooksett sub-station of the Manchester, N. H., transmission system.

Three-phase current at about 11,000 volts enters the primary windings of

three transformers at this sub-station. Each of these transformers has a

single primary, but two distinct secondary windings. Three of these

secondaries, one on each transformer, are connected together and feed a

rotary converter at about 380 volts, three-phase. The other three

secondary windings are connected in like manner to a second rotary

converter. Each of these transformers is rated at 250 kilowatts, and

each rotary is rated at 300 kilowatts, so that the transformer capacity

amounts to 750 kilowatts and that of the converters to 600 kilowatts,

giving a desirable margin of transformer capacity for railway service.

With the ordinary method of connection and windings, six transformers of

125 kilowatts each would have been required in this sub-station.

High voltage for transmission lines may be obtained by the combination

of two or more transformers with their secondary coils in series. This

method was followed in some of the early transmissions, as in that at

10,000 volts to San Bernardino and Pomona, begun in 1891, where twenty

transformers, giving 500 volts each, were used with their high-voltage

coils in series. Some disadvantages of such an arrangement are its high

cost per unit of transformer capacity and its low efficiency.

In a single-phase system the maximum line pressure must be developed or

received in the coils of each transformer, unless two or more are

connected in series. This is also true as to either phase of a two-phase

system with independent circuits. In three-phase circuits the coils of a

transformer connected between either two wires obviously operate at the

full line pressure. The same result is reached when the three

transformers of a group are joined to the line in mesh or Δ-fashion. If

the three transformers of a group are joined in star or Y-fashion, the

coils of each transformer are subject to fifty-eight per cent of the

voltage between any two wires of the three-phase line on which the group

is connected. It is no longer the practice to connect two or more

transformers in series either between two wires of a two-phase or

between two wires of a three-phase circuit, because it is cheaper and

more efficient to use a single transformer in each of these positions.

Where very high voltage must be developed or received with a three-phase

system, the star or Y-connection of each group of three transformers has

the advantage of a lower strain on the insulation of each transformer

than that with the mesh or Δ-grouping. Thus if the Δ-grouping is used,

the line pressure equals that of each transformer coil, but if the

Y-grouping is used the line voltage is 1.73 times that of each

transformer coil.

At the Colgate power-house, the 700-kilowatt transformers are designed

for a maximum pressure of 60,000 volts on the three-phase line when

Y-connected, so that the corresponding voltage is 34,675 in their

secondary coils. The primary coils of these same transformers are

connected in mesh or Δ-form and each coil operates at 2,300 volts, the

generator pressure.

Transformers are in some cases provided with several sets of connections

to their coils so that they may be operated at widely different

pressures. Thus, in the Colgate plant, each transformer has taps brought

out from its secondary coils so that it can be operated at either

23,175, 28,925, or 34,675, with 2,300 volts at its primary coil.

Corresponding to the three voltages named in each secondary coil are

voltages of 40,000, 50,000, and 60,000 on a three-phase line connected

with three of these transformers in Y-fashion.

The mesh or Δ-connection is used between the coils of transformers on

some transmission lines of very high voltage. The 950 kilowatt

transformers in the system between Cañon Ferry and Butte illustrate this

practice, being connected Δ-fashion to the 50,000-volt line.

When transformers that will operate at the desired line voltage on

Δ-connection can be obtained at slight advance over the cost of

transformers requiring Y-connections, it is often better practice to

select the former, because this will enable an increase of seventy-three

per cent in the voltage of transmission to be made at any future time by

simply changing to Y-connections. Such an increase of voltage may become

desirable because of growing loads or extension of transmission lines.

An example of this sort came up some time ago in connection with the

transmission between Ogden and Salt Lake City, which was operating at

16,000 volts, three-phase, with the high-pressure coils of transformers

connected in Δ-form. By changing to Y-connections the line voltage was

raised seventy-three per cent without increasing the strain on

transformer insulation.

In some cases it is desirable to change alternating current from

two-phase to three-phase, or _vice versa_, for purposes of transmission

or distribution, and this can readily be done by means of static

transformers. One method often employed to effect this result includes

the use of two transformers connected to opposite phases of the

two-phase circuit. The three-phase coil of one of these transformers

should be designed for the desired three-phase voltage, and should have

a tap brought out from its central point. The three-phase coil of the

other transformer should be designed for 87 per cent of the desired

three-phase voltage. One end of the coil designed for 87 per cent of the

three-phase voltage should be connected to the centre tap of the

three-phase coil in the other transformer. The other end of the 87 per

cent coil goes to one wire of the three-phase circuit. The other two

wires of this circuit should be connected, respectively, to the outside

end of the coil that has the central tap. As a matter of illustration it

may be required to transform 500-volt, two-phase current from

generators, to 20,000-volt, three-phase current for transmission. Two

transformers designed for 500 volts in their primary coils are necessary

for this work. One of these transformers should have a secondary coil

designed for 20,000 volts, so that the ratio of transformation is 20,000

÷ 500 or 40 to 1, and a tap should be brought out from the centre of

this coil. The other transformer should have a secondary voltage of 0.87

× 20,000 = 17,400, so that its ratio of transformation is 34.8 to 1.

These two transformers, with the connections above indicated, will

change the 500-volt, two-phase current to 20,000 volts, three-phase.

At one of the water-power stations supplying energy for use in Hartford,

four transformers of 300 kilowatts each change 500-volt, two-phase

current from the generators to 10,000-volt, three-phase, for the

transmission line.

In the Niagara water-power station the generators deliver two-phase

current at 2,200 volts, and 975-kilowatt transformers are connected in

pairs to change the pressure to 22,000 volts, three-phase, for

transmission to Buffalo.

A transformer is used in some cases to raise the voltage and compensate

for the loss in a transmission line. For this purpose the secondary of a

transformer giving the number of volts by which the line pressure is to

be increased is connected in series with the line. The primary winding

of this transformer may be supplied from the line boosted or from

another source.

Transformers ranging in capacity from 100 to 1,000 kilowatts each, such

as are commonly used for transmission work, have efficiencies of 96 to

98 per cent at full loads, when of first-class construction. Efficiency

increases slowly with transformer capacity within the limits named, and

98 per cent can be fairly expected in only the larger sizes. In any

given transformer the efficiency may be expected to fall a little, say

one or two per cent, between full load and half load, and another one

per cent between half load and quarter load. These figures for

efficiencies at partial loads vary somewhat with the design and make of

transformers. In general, it may be said that step-up or step-down

transformers will cost approximately $7.50 per kilowatt capacity, or

about one-half of the like cost of low-voltage dynamos. If dynamos of

voltage sufficiently high for the transmission line can be had at a

figure below the combined cost of low-volt dynamos and raising

transformers, it will usually pay to avoid the latter and develop the

line voltage in the armature coils. This plan avoids the loss in one set

of transformers.

TRANSFORMERS IN TRANSMISSION SYSTEMS.

+-------------------------------+----------+---------+---------+

| | Trans- | Trans- | Genera- |

| | formers | formers | tors at |

| |at Power- |at Sub- | Power- |

|Transmission System. |stations. |stations.|stations.|

| +----+-----+---+-----+---+-----+

| |No. | Kw. |No.| Kw. |No.| Kw. |

| | |Each.| |Each.| |Each.|

+-------------------------------+----+-----+---+-----+---+-----+

|Cañon Ferry to Butte | 12| 325 |[A]| [A] |...| ... |

| | 6| 950 | 6| 950 | 10| 750 |

|Apple River to St. Paul | ...| ... | 6| 300 |...| ... |

| | 6| 500 | 4| 200 | 4| 750 |

|White River to Dales | 3| 400 | 3| 375 | 2| 500 |

|Farmington River to Hartford | 4| 300 |...| ... | 2| 600 |

|Ogden to Salt Lake |[B]9| 250 |...| ... | 5| 750 |

|Colgate to Oakland | ...| 700 |...| ... | {3|1125 |

| | | | | | {4|2250 |

|Presumpscot River to Portland | ...| ... | {6| 200 |...| ... |

| | | | {3| 150 | 4| 500 |

| | | | | | {1| 180 |

| | | | | | {3| 300 |

|Four water-powers to Manchester| ...| ... | 21| 200 | {1| 450 |

| | | | | | {4| 650 |

| | | | | | {1|1200 |

+-------------------------------+----+-----+---+-----+---+-----+

[A] Other transformers at Helena sub-stations.

[B] Part of energy distributed directly from generators.