CHAPTER XII.

REGULATION OF TRANSMITTED POWER.

Regulation of voltage at incandescent lamps is a serious problem in the

distribution of electrically transmitted energy. Good regulation should

not allow the pressure at incandescent lamps rated at 110 to 120 volts

to vary more than one volt above or below the normal.

Electric motor service is much less exacting as to constancy of voltage,

and the pressure at motor terminals may sometimes be varied as much as

ten per cent without material objection on the part of users. A mixed

service to these three classes of apparatus must often be provided where

transmitted energy is used, and the limitations as to variations at

incandescent lamps are thus the ones that must control the regulation of

pressure.

Transmission systems may be broadly divided into those that have no

sub-stations and must therefore do all regulation at the generating

plant, and those that do have one or more sub-stations so that

regulation of voltage may be carried out at both ends of the

transmission line.

[Illustration: FIG. 64.--Arc-lighting Switchboard at Central

Sub-station, Montreal.]

As a rule, a sub-station with an operator in attendance is highly

desirable between transmission and distribution lines, and this is the

plan generally followed at important centres of electrical supply, even

though the transmission is a short one. One example of this sort may be

noted at Springfield, Mass., where energy for electrical supply is

transmitted from two water-power plants on the Chicopee River only about

four and a half and six miles, respectively, from the sub-station in the

business centre of the city. The voltage of transmission for two-phase

current in this case is 6,000, and is reduced to about 2,400 volts at

the sub-station for the general distribution of light and power. A

similar instance may be seen at Concord, N. H., where electrical energy

at both 2,500 and 10,000 volts is delivered to a sub-station in the

business section from a water-power plant at Sewall’s Falls, on the

Merrimac River, four and one-half miles distant. From this sub-station

the current is distributed at about 2,500 volts for the supply of lamps

and motors. A sub-station was found desirable at Concord for purposes

of regulation before the voltage of transmission was raised above that

of distribution. Subsequently, when the load increased, the voltage of

10,000 was adopted on a part of the transmission circuit in order to

avoid an increase in the size of their conductors.

[Illustration: FIG. 65.--Area of Electrical Distribution at Montreal.]

[Illustration: FIG. 66.]

[Illustration: FIG. 67.]

[Illustration: FIG. 68.]

In some instances, however, transmission and distribution lines are

joined without the intervention of a sub-station, where regulation of

voltage can be accomplished, though this practice has little to

recommend it aside from the savings in first cost of installation and

subsequent cost of operation. These savings are more apparent than real

if fairly constant pressure is to be maintained at the lamps, because

what is gained by the omission of sub-stations will be offset, in part

at least, by additional outlays on the lines if good regulation is to be

maintained. This fact may be illustrated by reference to Figs. 66, 67,

and 68, in each of which _D_ represents a generating station and _A_,

_B_, and _C_ towns or cities where energy from the station is to be

distributed. In the case of each figure it is assumed that the distance

between the generating station and each of the cities or towns is such

that distributing lines with a loss of, say, not more than two per cent

in voltage at full load cannot be provided between the generating

station and each city or town because of the cost of conductors. This

being so, one or more centres of distribution must be located in each

town, and the transmission lines must join the distribution lines at

these centres either on poles or in sub-stations. If several of these

towns are in the same general direction from the generating plant so as

to be reached by the same transmission line, as _A_, _B_, and _C_ in

Fig. 66, this one line will be all that is necessary with a sub-station

in each town. Where sub-stations are not employed a separate

transmission circuit must be provided between the generating plant and

each town for reasons that will appear presently. The percentage of

voltage variation in a transmission line under changing loads will be

frequently from five to ten, and is thus far beyond the allowable

variations at incandescent lamps. To give good lighting service the

centre of distribution, where the transmission line joins the

distribution circuits, must be maintained at very nearly constant

voltage if no sub-station is located there. Regulation at a generating

station will compensate for the changing loss of pressure in a line

under varying loads so as to maintain a nearly constant voltage at any

one point thereon. No plan of station regulation, however, can maintain

constant voltages at several points on the same transmission line when

there is a varying load at each. The result is that even though the

several towns served are in the same general direction from the

generating station, as in Fig. 67, yet each town should have its

separate transmission line where no sub-stations in the towns are

provided. In the case illustrated by Fig. 68, where the towns served are

in very different directions from the generating station, there should

be a separate transmission line to each, regardless of whether there is

a sub-station or only a centre of distribution there.

Even in the case illustrated by Fig. 68, as in each of the others, there

is a large saving effected in the cost of distribution lines by the

employment of a sub-station at the point where these lines join the

transmission circuit, provided that the variation of pressure at lamp

terminals is to be kept within one volt either way from the standard.

With the variations of loads the loss of pressure in the distribution

lines will range from zero to its maximum amount and the connected lamps

will be subjected to the change of voltage represented by this total

loss, unless the distribution start from a sub-station where the loss in

distribution lines can be compensated for by regulation. To give good

service the distribution lines should be limited to a loss of one per

cent at full load if there is no sub-station where they join

transmission lines. With opportunity for regulation at a sub-station the

maximum loss in distribution lines may easily be doubled, thus reducing

their weight by one-half in comparison with that required where there is

no sub-station.

Another advantage of connecting transmission and distribution lines in a

sub-station, where regulation of voltage can be had, lies in the fact

that it is practically impossible to maintain an absolutely constant

pressure miles from a generating plant at the end of a transmission line

that is carrying a mixed and varying load. A result is that without the

intervention of regulation at a sub-station it is almost impossible to

give good lighting service over a long transmission line. Furthermore,

the labor of regulation at a generating station is much increased where

there are no sub-stations, because it must be much more frequent and

accurate. The absence of sub-stations from a transmission system thus

implies more transmission circuits, heavier distribution circuits, more

labor at the generating plant, and a poor quality of lighting service.

Where stationary motors form the great bulk of the load on a

transmission system, and good lighting service is of small importance,

it may be well to omit sub-stations at some centres of distribution.

This is a condition that sometimes exists in the Rocky Mountain region

where the main consumers of power along a transmission line may be mines

or works for the reduction of ores. An example of this sort exists in

the system of the Telluride Power Transmission Company, in Utah, which

extends from Provo Cañon, on the river of the same name, entirely around

Utah Lake by way of Mercur, Eureka, and Provo, and back to the

power-house in Provo Cañon, a continuous circuit of 105 miles.

The transmission voltage on this line is 40,000, and at intervals where

there are distributing points the voltage is reduced to about 5,000 by

transformers on poles, and without the aid of regulation at sub-stations

in some cases. The power thus transmitted is largely used in mines and

smelters for the operation of motors, but also for some commercial

lighting.

Regulation at generating stations of the voltage on transmission lines

may be accomplished by the same methods whether there are sub-stations

at centres of distribution or not. In any such regulation the aim is to

maintain a certain voltage at some particular point on the transmission

line, usually its end, where the distribution circuits are connected. If

more than one point of distribution exists on the same transmission

line, the regulation at the generating plant must be designed to

maintain the desired pressure at only one of these points, leaving

regulation at the others to be accomplished by local means. One method

of regulation consists in the overcompounding of each generator so that

the voltage at its terminals will rise at a certain rate as its load

increases. If a generator and transmission line are so designed that the

rise of voltage at the generator terminals just corresponds with the

loss of voltage on the line when the output of that generator alone

passes over it to some particular point, then the pressure at that point

may be held nearly constant for all loads if no energy is drawn from the

line elsewhere. These several conditions necessary to make regulation by

the compounding of generators effective can seldom be met in practice.

If a varying number of generators must work on the same transmission

line, or if varying loads must be supplied at different points along the

line, no compound winding of generators will suffice to maintain a

constant voltage at any point on the line that is distant from the

power-station. For these reasons the compound winding of generators is

of minor importance so far as the regulation of voltage on transmission

lines is concerned, and on large alternators is not generally attempted.

An example may be noted on the 3,750-kilowatt generators at Niagara

Falls, where the single magnet winding receives current from the

exciters only.

A much more effective and generally adopted method of regulation of

voltage at the generating plants of transmission systems is based on the

action of an attendant who varies the current in the magnet coils of

each generator so as to raise or lower its voltage as desired. The

regulation must be for some one point on the transmission line, and the

attendant at the generating plant may know the voltage at that point

either by means of a pair of pressure wires run back from that point to

a voltmeter at the generating plant, by a meter that indicates the

voltage at the point in question according to the current on the line,

or by telephone connection with a sub-station at the point where the

constant voltage is to be maintained. Pressure wires are a reliable

means of indicating in the generating station the voltage at a point of

distribution on the line, but the erection of these wires is quite an

expense in a long transmission, and in such cases they are only

occasionally used. Owing to inductive effects and to variable

power-factors the amperes indicated on a line carrying alternating

current are far from a certain guide as to the drop in voltage between

the generating station and the distant point. In long transmissions,

telephone communication between the generating plant and the

sub-stations is the most general way in which necessary changes to

maintain constant voltage at sub-stations are brought to the attention

of the attendant in the generating plant. Few, if any, extensive

transmission systems now operate without telephone connection between a

generating plant and all of its sub-stations, or between a single

sub-station and the several generating plants that may feed into it.

Thus, the generating plant at Spier Falls, on the Hudson River, will be

connected by telephone with sub-stations at Schenectady, Albany, Troy,

and some half-dozen smaller places. On the other hand, the single

sub-station in Manchester, N. H., that receives the energy from four

water-power plants has a direct telephone line to each.

Where two or more transmission lines from the same power-station are

operated from the same set of bus-bars the voltage at a distant point on

each line cannot be held constant by changes of pressure on these

bus-bars. One generator only may be connected to each transmission line

and be regulated for the loss on that line, but this loses the

advantages of multiple operation. Another plan is to connect a

regulator in each transmission line before it goes from the generating

plant. One type of regulator for this purpose consists of a transformer

with its secondary coil divided into a number of sections and the ends

of these sections brought out to a series of contact segments. The

primary coil of this transformer may be supplied with current from the

bus-bars and the secondary coil is then connected in series with the

line to be regulated, so that the secondary voltage is added to or

subtracted from that of the main circuit. A movable contact arm on the

segments to which the sections of the secondary coil are connected makes

it possible to vary the secondary voltage by changing the number of

these sections in circuit. In another transformer used for regulating

purposes the primary coil is connected to the bus-bars as before and the

movable secondary coil is put in series with the line to be regulated.

The regulation is accomplished in this case by changing the position of

the secondary relative to that of the primary coil and thus raising or

lowering the secondary voltage. Both of these regulators require hand

adjustment, and the attendant may employ the telephone, pressure wires,

or the compensating voltmeter above mentioned, to determine the voltage

at the centre of distribution. The voltage indicated by this so-called

“compensator” is that at the generating station minus a certain amount

which varies with the current flowing in the line to be regulated. The

voltmeter coil of the compensator is connected in series with the

secondary coils of two transformers, which coils work against each

other. One transformer has its secondary coil arranged to indicate the

full station voltage, and the other secondary coil is actuated by a

primary coil that carries the full current of the regulated line. By a

series of contacts the effect of this last-named coil can be varied to

correspond with the number of volts that are to be lost at full load

between the generating station and the point on the transmission line at

which the voltage is to be held constant. If there is no inductive drop

on the transmission line, or if this drop is of known and constant

amount, the compensator may give the actual voltage at the point for

which the regulation is designed.

Automatic regulators are used in some generating stations to maintain a

constant voltage either at the generating terminals or at some distant

distributing point on a line operated by a single generator. These

regulators may operate rheostats that are in series with the magnet

windings of the generators to be regulated, and raise or lower the

generator voltage by varying the exciting current in these windings.

These regulators are much more effective to maintain constant voltage at

generating stations than at the distributing end of long transmission

lines with variable power-factors. In spite of the compound winding of

generators, of automatic regulators for the exciting currents in their

magnet coils, and of regulating transformers in the transmission

circuits, hand-adjustment of rheostats in series with the magnet coils

of generators remains the most generally used at the generating stations

of long transmission systems. Automatic regulators at the ends of

transmission lines in sub-stations are now being introduced, and may

prove very desirable.

[Illustration: FIG. 69.--Motor-generators in Shawinigan Sub-station at

Montreal.]

The more exacting and final work of regulation in transmission systems

is usually done at the sub-stations. After a nearly constant voltage is

delivered at the high-pressure coils of step-down transformers in a

sub-station, there remains the varying losses in these transformers, in

motor-generators or converters, in distribution lines and in service

transformers, to be compensated for. In general, three or four sorts of

loads must be provided for, namely, arc or incandescent lamps for street

lighting on series circuits, usually of 4,000 to 10,000 volts. Arc and

incandescent lamps on constant-pressure circuits of 2,000 to 2,500 volts

for commercial lighting, direct-current stationary motors on

constant-pressure circuits of about 500 volts, and alternating motors

which may be served at either 2,500 or 500 volts according to their

sizes and locations. To these loads may be added that of street-car

motors of 500 volts, direct current. Both the stationary and the

street-car motors, but more especially the latter, by their changes of

load give rise to large and rapid fluctuations of voltage on the

distribution lines to which they are connected. The problem of

regulation with combined lamp and motor loads is not, therefore, so much

to maintain a nearly constant voltage at the motors as to protect the

lamps from the fluctuations of voltage which the motors set up.

[Illustration: FIG. 70.--One of the 1,065-kilowatt Motor-generators in

the Shawinigan Sub-station at Montreal.]

For street-car motors using direct current at about 500 volts, the

sub-station equipment includes either step-down transformers and

converters or motor-generators with or without transformers. It is the

practice in some cases where both lighting and street-railway service

are drawn from the same transmission system to keep these two kinds of

service entirely separate, devoting independent generators and

transmission lines, as well as independent transformers and converters

or motor-generators, to the street-car work. This is done in the

transmission system centring at Manchester, N. H., in which each one of

the four water-power plants, as well as the sub-station, has a double

set of bus-bars on the switchboard; and from each water-power plant to

the sub-station there are two transmission circuits. In operation, one

set of generators, bus-bars, transmission circuits, and transformers

supply converters or motor-generators for the street-car motors; and

another set of generators, bus-bars, transmission circuits, and

transformers are devoted to lighting and stationary motors in this

system. Where street-car motors draw their energy from the same

generators and transmission lines that supply commercial incandescent

lamps, some means must be adopted to protect the lighting circuits from

the fluctuations of voltage set up by the varying street-car loads. One

way to accomplish this purpose is to operate the lighting circuits with

generators driven by synchronous motors in the sub-stations. These

generators may, of course, be of either direct or alternating type and

of any desired voltage. The synchronous motors driving these generators

take their current from the transmission line either with or without the

intervention of step-down transformers. By this use of synchronous

motors the lighting circuits escape fluctuations of voltage

corresponding to those on the transmission line, because synchronous

motors maintain constant speeds independently of the voltage of the

circuits to which they are connected. This plan was followed at Buffalo,

where the street-car system and the lighting service are operated with

energy from the Niagara Falls stations over the same transmission line.

In one of the sub-stations at Buffalo, both 2,200-volt, two-phase

alternators, and 150-volt continuous-current generators for lighting

service, are driven by synchronous motors connected to the Niagara

transmission line through transformers. At other sub-stations in

Buffalo, the 500-volt continuous current for street-car motors is

obtained from the same transmission system through transformers and

converters. Another solution of the problem of voltage regulation where

street-railway and commercial lighting service are to be drawn from the

same transmission line is found in the operation of 500-volt

continuous-current generators in the sub-stations by synchronous motors

fed from the line either directly or through transformers. This plan has

been adopted in the transmission system of the Boston Edison Company,

which extends to a number of cities and towns within a radius of

twenty-five miles. The sub-stations at Natick and Woburn in this system,

where there are street-railway as well as lighting loads, contain

500-volt continuous-current generators driven by synchronous motors

connected directly to the three-phase transmission lines. In a case like

this the synchronous motors maintain their speed irrespective of the

voltage on the line and thus tend to hold that voltage steady in spite

of the variable losses due to fluctuating loads.

Stationary motors should not as a rule be operated from the same

distribution lines that supply incandescent lamps, especially in sizes

above one horse-power, and this is the better practice. Motor circuits

of about 2,400 volts and two- or three-phase, alternating, or 500 volts,

alternating or direct current, may be supplied at a sub-station either

by transformers alone in the first case or by transformers and

converters in the second. In either case no especial provision is

usually necessary for the regulation of constant pressure on the motor

circuits.

[Illustration: FIG. 71.--1,100-kilowatt, 2,300-volt, Three-phase,

30-cycle, Synchronous Motor at Sub-station of Shawinigan Line in

Montreal.]

In some transmission systems the distribution circuits for stationary

motors are not fed by the same transmission lines that carry the

lighting load, but draw their energy from lines that do no other work.

This practice is certainly desirable, as it frees the lighting circuits

from all fluctuations of voltage due to line losses with changing motor

loads. Examples of this sort may be seen at Springfield, Mass., and

Portland and Lewiston, Me., in each of which the load of stationary

motors is operated over independent transmission as well as distribution

lines.

In transmission systems series arc and incandescent lamps for street

lighting are commonly operated either by direct-current arc dynamos or

by constant-current transformers or constant-pressure transformers with

automatic regulators at the sub-stations. The arc dynamos are driven by

either induction or synchronous motors supplied directly from the

transmission line or through transformers. As the arc dynamos regulate

automatically for constant current no further regulation is required. If

the series arc and incandescent lamps are to be supplied with

alternating current, the constant-current transformer or the

constant-current regulator come into use. This type of transformer and

regulator alike depend for their regulating effect on the movement of a

secondary coil on a transformer core in such a way that the current in

this coil, which is in series with the lamps, is held nearly constant.

Such constant-current transformers and regulators are usually supplied

from the transmission line through regular constant-pressure

transformers, and they hold their currents sufficiently constant for the

purposes of their use.

The main problem of regulating thus comes back to the 250- or

2,200-volt, constant-pressure circuits for incandescent lighting,

supplied from transmission lines through transformers or motor

generators or both at the sub-station. For this regulation one of the

most reliable instruments is the hand of a skilful attendant, guided by

voltmeters connected with pressure wires from minor centres of

distribution, and adjusting the regulating transformers above mentioned,

or other regulating devices.