CHAPTER IX.

ALTERNATORS FOR ELECTRICAL TRANSMISSION.

Dynamos in the generating station of an electric transmission system

should be so numerous that if one of them is disabled the others can

carry the maximum load. If only two generators are installed, it is thus

desirable that each be large enough to supply the entire output, so that

the dynamo capacity exceeds the greatest demand on the station by 100

per cent. To avoid so great excess of dynamo capacity it is common

practice to install more than two generators.

Other considerations also tend to increase the number of dynamos in the

generating station of a transmission system. Thus one transmission line

may be devoted exclusively to lighting, another to stationary motors,

and a third to electric railway service; and it may be desirable that

each line be supplied by an independent dynamo to avoid any effect of

fluctuations of railway or motor load on the lighting system.

At the generating station of the transmission system that supplies

electric light and power in Portland, Me., the idea of independent units

has been carried out with four 500-kilowatt dynamos, each driven by a

pair of wheels fed with water through a separate penstock from the dam.

Each of these dynamos operates one of the four independent transmission

circuits. Where a number of water-power stations feed into a single

sub-station the requirement that each generating station have its

capacity divided up among quite a number of dynamos may not exist, since

one station may be entirely shut down for repairs and the load carried

meantime by the other stations. A good illustration of this point may be

seen at Manchester, where a single sub-station receives energy

transmitted from four water-power plants. At one of these plants the

entire capacity of 1,200 kilowatts is in a single generator.

The foregoing considerations as to the number of dynamos apply with

equal force to both steam- and water-driven stations, but other factors

tend to increase the number of dynamos in water-power plants where the

head of water is comparatively small. This tendency is due to the fact

that the peripheral speeds of pressure turbine water-wheels should be

about twenty-five per cent less than the velocity at which water would

issue from an opening under the head of water at which these wheels

operate in order to secure high efficiency. This velocity of water and

therefore the peripheral speed of pressure turbine wheels varies with

the square root of the head of water.

[Illustration: FIG. 40.--Generators at Sault Ste. Marie Power Plant.]

Since the peripheral speed of turbines is thus determined by the heads

of water under which they operate, and since the diameters of turbines

must increase with their capacities, the rate of revolution for pressure

turbines under any given head decreases as the power goes up. For this

reason it is often desirable to use a larger number of dynamos in a

water-power plant than would otherwise be required in order to avoid

very low speeds of revolution on the direct-connection to the turbines.

A notable illustration of this practice exists in the great water-power

plant of the Michigan-Lake Superior Power Company, at Sault Ste. Marie,

Mich., where a generating capacity of 32,000 kilowatts is divided up

between 80 dynamos of 400 kilowatts each. The head of water available at

the pressure turbines in this plant is about 16 feet, and their speed is

180 revolutions per minute. In order to obtain even this moderate speed

under the head of 16 feet it was necessary to select turbines of only

140 horse-power each. Four of these turbines are mounted on each shaft

that drives a 400-kilowatt dynamo, direct-connected, so that there are

320 wheels in all. Had a smaller number of wheels been employed to yield

the total power their speed and that of direct-connected dynamos must

have been less than 180 revolutions per minute. As the cost of dynamos

increases with very low speeds it is often cheaper to install a larger

number of dynamos at a higher speed than a smaller number at a lower

speed for a given total capacity.

The use of a larger number of units than would otherwise be necessary in

order to avoid a very low speed is further illustrated by the

7,500-kilowatt plant of the Missouri River Power Company, at Cañon

Ferry, Mont. This capacity is made up of ten generators, each rated at

750 kilowatts and direct-connected to a pair of pressure turbine wheels

operating at 157 revolutions per minute, under a head of about 32 feet.

Under comparatively high heads of water pressure turbines operate at

speeds that are ample for direct-connection to even the largest dynamos.

[Illustration: FIG. 41.--Interior of Power-house No. 2, Niagara Falls.]

Thus in the Niagara Falls plant, where the head of water is 136 feet,

each pair of turbines drives a direct-connected dynamo of 3,750

kilowatts at 250 revolutions per minute. In the rare case where the

power to be developed is so great that the number of generators

necessary to give security and reliability to the service leaves each

generator with a capacity larger than is desirable for structural

reasons, the number must be increased simply to reduce the size of each

generator. Such a state of facts existed at Niagara Falls, where the

first station contains ten dynamos of 3,750 kilowatts each, and the

second station contains eleven units of like capacity.

In the greater number of transmission systems the generators are

direct-connected to either steam-engines or water-wheels, and their

speeds of rotation are largely determined by the requirements of these

prime movers. Steam-engines can be designed with some regard to the

desirable speeds for direct-connection to dynamos, but water-wheels are

less flexible in this particular. Each type of wheel has its peripheral

speed mainly determined by the head of water under which it may be

required to operate, and variation from this speed means serious loss of

efficiency.

[Illustration: FIG. 42.--10,000 H. P. 12,000 Volt Generator in Canadian

Power-house at Niagara Falls.]

Under heads of much more than 100 feet pressure turbines operate at

rather high speeds in all except very large sizes. It is much the more

common to see water-wheels at a lower speed belted to dynamos at a

higher speed; but in some instances, as at the lighting plant of

Spokane, Wash., wheels of a higher speed are belted to dynamos of a

lower speed. Another plan by which moderate dynamo speeds are obtained

with water-wheels under rather high heads mounts a dynamo at each end of

the shaft of a large turbine or pair of turbines. This plan is followed

at the plant of the Royal Aluminum Company, Shawinigan Falls, Quebec,

where there are two pairs of horizontal turbine wheels, each pair

developing 3,200 horse-power under a head of 125 feet, and driving a

dynamo direct-coupled on each end of its shaft. Where vertical wheels

are employed it is sometimes more desirable to drive some standard type

of dynamo with horizontal shaft by means of bevel gears than to design a

special dynamo to mount directly on the vertical shaft. This latter plan

is warranted in very large work like that at two of the Niagara Falls

generating stations, where the twenty-one 3,750-kilowatt dynamos are

direct-connected, each on the vertical shaft of a turbine. This type of

connection is not one that will be frequently followed, but at one other

point--Portland, Ore.--each dynamo is mounted directly on the shaft of

its vertical turbine wheel.

Where water-wheels must operate under heads of several hundred feet, it

is usually necessary to abandon pressure turbines and to adopt one of

the types of impulse-wheels. In this class of wheels the peripheral

speed of highest efficiency is only one-half the spouting velocity of

the water under any particular head. This gives the impulse-wheels about

two-thirds the peripheral speed of pressure turbines of equal diameter

and consequently about two-thirds as many revolutions per minute. But as

the water may be applied at one or more points on the circumference of

an impulse-wheel, as desired, such wheels may have much greater

diameters than pressure turbines for equal power under a given head.

[Illustration: FIG. 43.--Generators in Power-station at Mechanicsville

on the Hudson River.]

[Illustration: FIG. 44.--Generators at Chamblay, Quebec, Power-house.]

These properties of low peripheral speed, as to head and great diameter,

as to power developed, fit impulse-wheels for direct-connection to

dynamos where great heads of water must be employed, and they are

generally used in such cases. This is particularly true for the Pacific

coast, where water-powers depend more on great heads than on large

volumes. In the generating plant of the Bay Counties’ Power Company, at

Colgate, Cal., the dynamos are direct-connected to impulse-wheels that

operate under a head of 700 feet. The three 2,250-kilowatt dynamos in

this plant are each mounted on a wheel shaft operating at 285

revolutions per minute, and each of the four 1,125-kilowatt dynamos is

direct-driven by an impulse-wheel at 400 revolutions per minute. At the

Electra, Cal., plant of the Standard Electric Company the impulse-wheels

operate at 240 revolutions per minute under a head of 1,450 feet. Each

of the five pairs of these wheels drives a 2,000-kilowatt generator,

direct-connected. As the head of water at these wheels is 1,450 feet,

its spouting velocity is about 300 feet per second, or 18,000 feet per

minute. Each wheel is eleven feet in diameter, so that a speed of 240

revolutions per minute gives the periphery a little less than 9,000 feet

per minute, or about one-half of the spouting velocity of the water.

These two great plants are excellent illustrations of the way in which

impulse-wheels, under great heads, may be given speeds that are suitable

for direct-connected dynamos.

[Illustration: FIG. 51_a_. Plan and Elevation of Water Wheels and

Generators at Power Station on Burrard Inlet, near Vancouver, B. C.]

Three types of alternators, the revolving armature, the revolving

magnet, and the inductor, are used in the generating plants of electric

transmission systems.

Revolving armatures are used in the dynamos of comparatively few

transmission systems and hardly at all in those of recent date. The

prevailing type of alternator for transmission work is that with

internal revolving magnets and external stationary armature. This type

is employed in the great water-power plants at Cañon Ferry, Mont.; Sault

Ste. Marie, Mich., and for all of the generators installed in the later

Niagara Falls plants. For the sixteen earlier vertical generators at

Niagara Falls the revolving magnets are external to the stationary

armatures, but this construction has the disadvantage of high first cost

and inaccessibility of the internal armature, and is not likely to be

often adopted elsewhere.

[Illustration: FIG. 46.--Elevations of Water-wheels and Generators at

Power-station on Burrard Inlet, near Vancouver, B. C.]

Inductor alternators are those in which both the armature and magnet

coils are stationary and only a suitable structure of iron revolves;

they are employed in a comparatively small number of transmission

systems, but this number includes some of the largest plants. The seven

alternators in the Colgate, Cal., plant aggregating 11,250 kilowatts

capacity, and the five alternators in the plant at Electra in the same

State, with a capacity of 10,000 kilowatts, are all of the inductor

type. As more commonly constructed the magnet winding of the inductor

alternator consists of only one or two very large coils, which are in

some cases as much as ten feet in diameter. The repair of these large

magnet coils seems to present a more serious problem, in case of

accident, than the repair of the small coils used on interval, revolving

magnets. As far as satisfactory operating qualities are concerned,

inductor alternators and those with revolving magnets seem to be on an

equality, but for structural reasons inductor alternators will probably

be built less freely in the future than in the past.

Nearly all long transmissions are now carried out with either two- or

three-phase current. The most notable two-phase installation is that at

Niagara Falls, where the original ten generators, as well as the eleven

dynamos later added in two of the large plants, are all of the two-phase

type. At Cañon Ferry, Mont., the first four of the 750-kilowatt

generators were two-phase, but the six machines of like capacity

installed later are three-phase. In the latest plants of large capacity

or involving very long transmissions three-phase machines have been

generally employed. This is true of the Colgate and Electra plants in

California, and of that at Sault Ste. Marie, Mich.

[Illustration: FIG. 47.--Interior of Power-house at Garvin’s Falls on

the Merrimac River.]

[Illustration: FIG. 48.--500-Kilowatt Generator in Station at Great

Falls on the Presumpscot River.]

As to frequency, existing practice extends all the way from 133 cycles

per second on the lines at Marysville, Cal., down to only 15 cycles on

the transmission for the Washington & Baltimore Electric Railway.

More common practice ranges between 25 and 60 cycles. Niagara Falls saw

the first great plant installed for 25 cycles, but others of that

frequency are now engaged in the supply of light and power for general

distribution. For transmission to electric railway lines a frequency of

25 cycles has been and is being widely used, prominent examples of which

may be seen in the New Hampshire traction, the Berkshire, and the Albany

& Hudson systems.

[Illustration: FIG. 49.--Columbus, Ga., Water-power Station.]

The strong feature of a system at 25 cycles is that it is well suited to

the supply of continuous currents through rotary converters with

reasonable numbers of poles, armature slots, and commutator bars.

[Illustration: FIG. 50.--1065-Kilowatt, 2300 volt Generator Connected to

Motor in Shawinigan Sub-station at Montreal.]

On the other hand, the cost of transformers is greater with current at

25 cycles per second than with a higher frequency, and this current is

only just bearable for incandescent lighting and quite unsuited for arc

lamps, because of the fluctuating character of the light produced. At 15

cycles per second a current can be employed for incandescent lighting

with satisfactory results only by means of some special devices, as

lamps with very thick filaments, to avoid the flicker. Very low

fluctuations cut down undesirable effects in the way of inductance and

resonance, but these effects can be avoided to a large degree in other

ways.

Where power is the most important element in the service of an electric

water-power and transmission system there is a decided tendency to adopt

a rather small number of periods for the system, even at some

disadvantage as to lighting facilities. This is illustrated by the

transmission from St. Anthony’s Falls, Minn., at 35 cycles, from Cañon

City to Cripple Creek, Col., at 30 cycles, by the Sault Ste. Marie plant

of 32,000 kilowatts at 30 cycles, as well as by the two Niagara Falls

plants of 78,750 kilowatts at 25 cycles.

Where the main purpose of a transmission system is the supply of light

and power for general distribution, sixty periods per second are adopted

as the standard in many cases. This number of periods in comparison with

a smaller one tends to increase the cost of rotary converters but

decreases the cost of transformers, and is suitable for both

incandescent and arc lighting.

[Illustration: FIG. 51.--Efficiency Curves for Motor Generators at

Montreal Sub-station of the Shawinigan Transmission Line.]

Few, if any, transmission systems have recently been installed for

frequencies above sixty cycles, and the older plants that worked at

higher figures have in most cases been remodelled.

During the past decade the voltages of alternators have been greatly

increased, but have not caught up with the demand for high pressures on

long-transmission lines. Ten years ago when the first long transmissions

were going into operation 2,000 volts was considered high for an

alternator. As this voltage is too low for economy of conductors longer

than three or four miles, the important early transmissions were all

carried out with the aid of step-up transformers at generating stations.

The practice then was, and to a large extent still is, to design the

alternators for a transmission with a voltage well suited to their

economical construction, and then give the step-up transformers any

ratio necessary to attain the required line voltage.

ALTERNATORS IN TRANSMISSION SYSTEMS.

+----------------------+----------------------------------------------+

| |Number at Plant. |

| | |Kilowatts Each. |

| | | |Alternator Voltage. |

| | | | |Phase. |

| | | | | |Cycles. |

| | | | | | |R. P. M. |

| | | | | | | |Type of |

|Location of System. | | | | | | |Magnet. |Method |

| | | | | | | | |of |

| | | | | | | | |Connec-|

| | | | | | | | |tions. |

+----------------------+--+-----+------+-+----+-----+---------+-------+

|Niagara Falls[A] |16|3,750| 2,300|2|25 |250 |External |Direct |

| | | | | | | |revolving| |

|Niagara Falls[A] | 5|3,750| 2,300|2|25 |250 |Internal | „ |

|Colgate to Oakland | 3|2,250| 2,400|3|60 |285 |Inductor | „ |

|Colgate to Oakland | 4|1,125| 2,400|3|60 |400 | „ | „ |

|Electra to S.Francisco| 5|2,000| ....|3|60 |240 | „ | „ |

|Portsmouth to Pelh’m | 1|2,000|13,200|3|25 | 83.3|Internal | „ |

|Portsmouth to Pelh’m | 2|1,000|13,200|3|25 | 94 | „ | „ |

|Virginia City | 2| 750| 500|3|60 |400 |External | „ |

|Ogden & Salt Lake | 5| 750| 2,300|3|60 |300 |Internal | „ |

|Chaudière Falls | 2| 750|10,500|3|66.6|400 | „ | „ |

|Yadkin River Falls | 2| 750|12,000|3|66 |166 | „ | „ |

|Lewiston, Me. | 3| 750|10,000|3|60 |180 | „ | „ |

|Farmington River }| | | | | | | | |

| to }| 2| 750| 500|3|60 |... | „ | „ |

|Hartford, Conn. }| 2| 600| 500|2|60 |... | „ | „ |

|Cañon Ferry to Butte |10| 750| 500|3|60 |157 | „ | „ |

|Apple Riv. to St. Paul| 4| 750| 800|3|60 |300 | „ | „ |

|Edison Co., L. Angeles| 4| 700| 750|3|50 |... | „ | „ |

|Madrid to Bland | 2| 600| 605|3|60 | 90 | „ | „ |

|Cañon City to Cripple | | | | | | | | |

|Creek | 3| 450| 500|3|30 |... | ..... | „ |

|Sault Ste. Marie |80| 400| 2,400|3|30 |180 | „ | „ |

|St. Hyacinthe, Que. | 3| 180| 2,500|3|60 |600 | „ | „ |

|Great Falls to | | | | | | | | |

|Portland, Me. | 4| 500|10,000|3|60 |225 | „ | „ |

+----------------------+--+-----+------+-+----+-----+---------+-------+

[A] Niagara Falls Power Company.

Thus in the two water-power plants connected with the electrical supply

system of Hartford, Conn., the alternators operate at 500 volts with

transformers that put the line voltage up to 10,000. In the station on

Apple River that supplies the lighting system of St. Paul, Minn., the

alternators operate at 800 volts, and this is raised to 25,000 volts for

the line. At Cañon Ferry the alternator voltage of 500 is multiplied by

100 in the transformers giving 50,000 on the line.

[Illustration: FIG. 52.--Transmission Line of New Hampshire Traction

Company.]

Where the generating station of a transmission system is located close

to a part of its load the alternators are given a voltage suitable for

distribution, say about 2,400, and any desired pressure on the line is

then obtained by means of step-up transformers. Two of the Niagara

Falls plants are an illustration of this practice, the voltage of all

the alternators there being 2,200, which is raised to 22,000 for the

transmission of a part of the energy to Buffalo. A similar practice is

followed in the water-power plant at Ogden, where the generators furnish

current at 2,300 volts for local distribution, and transformers raise

the pressure to 26,000 volts for the transmission to Salt Lake City. In

the 32,000-kilowatt plant at Sault Ste. Marie, Mich., the alternators

operate at 2,400 volts and a large part of their load is local, but this

voltage will no doubt be raised by transformers when transmission lines

are operated.

For generating stations that carry little or no local loads the cost of

transformers can be saved if the generators develop the voltage required

on the transmission lines. This possible saving has led to the

development of alternators that generate voltages as high as 15,000 in

their armature coils. Such alternators have stationary armatures in all

cases and are of either the revolving magnet or inductor type.

At the present time many transmission systems in the United States

operating at 10,000 or more volts develop these pressures in the

armature coils of their alternators, and the number of such systems is

rapidly increasing. It is now the rule rather than the exception to

dispense with step-up transformers on new work where the line voltage is

anything under 15,000. Perhaps the longest transmission line now in

regular operation with current from the armature coils of an alternator

is that at 13,200 volts between the generating station at Portsmouth and

one of the sub-stations of the New Hampshire Traction system at Pelham,

a distance of forty-two miles.

In at least one transmission system now under construction, that of the

Washington, Baltimore & Annapolis Electric Railway, the voltage of

generators to supply the line without the intervention of step-up

transformers will be 15,000.

The company making these alternators is said to be ready to supply

others that generate 20,000 volts in the armature coils whenever the

demand for them is made. In quite a number of cases alternators of about

13,000 volts have been installed for transmissions along electric

railway lines.

Alternator

Systems Using High-voltage Alternators. Voltages.

Electrical Development Co. of Ontario, Niagara Falls 12,000

Lighting and Street Railway, Manchester, N. H. 10,000

Lighting and Street Railway, Manchester, N. H. 12,500

Lighting and Power, Portland, Me. 10,000

Lighting and Power, North Gorham, Me. 10,000

Mallison Power Co., Westbrook, Me. 10,000

Lighting and Power, Lewiston, Me. 10,000

Electric Railway, Portsmouth, N. H. 13,200

Electric Railway, Pittsfield, Mass. 12,500

Ludlow Mills, Ludlow, Mass. 13,200

Electric Railway, Boston to Worcester, Mass. 13,200

Electric Railway, Albany & Hudson, N. Y. 12,000

Empire State Power Co., Amsterdam, N. Y. 12,000

Lehigh Power Co., Easton, Pa. 12,000

Hudson River Power Co., Mechanicsville, N. Y. 12,000

Light and Power, Anderson, S. C. 11,000

Fries Mfg. Co., Salem, N. C. 12,000

Light and Power, Ouray, Col. 12,000

Washington & Baltimore Electric Railway 15,000

Canadian Niagara Power Co., Niagara Falls 12,000

Ontario Power Co., Niagara Falls 12,000

This list of high-voltage alternators is not intended to be exhaustive,

but serves to indicate their wide application. If such alternators can

be purchased at a lower price per unit of capacity than alternators of

low voltage plus step-up transformers, there is an apparent advantage

for transmission systems in the high-voltage machines. This advantage

may rest in part on a higher efficiency in the alternators that yield

the line voltage than in the combination of low-voltage alternators plus

step-up transformers. It is not certain, however, that depreciation and

repairs on the generators of high voltage will not be materially greater

than the like charges on generators of low voltage, and some advantage

in price should be required to cover this contingency.

Just how far up the voltage of alternators can be pushed for practical

purposes is uncertain, but it seems that the limit must be much below

that for transformers where there is ample room for solid insulation and

the coils can be immersed in oil. The use of generators at 10,000 volts

and above tends to lower the volts per mile on transmission lines,

because it seems better in some cases to increase the weight of line

conductors rather than to add step-up transformers, as in the 42-mile

transmission from Portsmouth to Pelham.