CHAPTER IV.

ADVANTAGES OF THE CONTINUOUS AND ALTERNATING CURRENT.

Electrical transmissions over long distances in America have been mainly

carried out with alternating current. In Europe, on the other hand,

continuous current is widely used on long transmissions at high

voltages. So radical a difference in practice seems to indicate that

neither system is lacking in points of superiority.

A fundamental feature of long transmissions is the high voltage

necessary for economy in conductors, and this voltage is attained by

entirely different methods with continuous and alternating currents. In

dynamos of several hundred or more kilowatts capacity the pressure of

continuous current has not thus far been pushed above 4,000 volts,

because of the danger of sparking and flashing at the commutator. Where

10,000 or more volts are required on a transmission line with continuous

current a number of dynamos are connected in series so that the voltage

of each is added to that of the others. In this way the voltage of each

dynamo may be as low as is thought desirable without limiting the total

line voltage. There is no apparent limit to the number of

continuous-current dynamos that may be operated in series or to the

voltage that may be thus obtained. In the recently completed

transmission from St. Maurice to Lausanne, Switzerland, with continuous

current, ten dynamos are connected in series to secure the line voltage

of 23,000. When occasion requires twenty or thirty or more dynamos to be

operated in series, giving 50,000 or 75,000 volts on the line, machines

exactly like those in the transmission just named, may be used. No

matter how many of these dynamos are operated in series the electric

strain on the insulation of the windings of each dynamo remains

practically constant, because the iron frame of each dynamo is insulated

in a most substantial manner from the ground. The electric strain on the

insulation of the windings of each dynamo in the series is thus limited

to the voltage generated by that dynamo. There is no practical limit to

the thickness or strength of the insulation that may be interposed

between the frame of each dynamo and the ground, and hence no limit to

line voltage as far as dynamo insulation is concerned.

It is impracticable to operate alternating dynamos in series so as to

add their voltages, and the pressure available in transmission with

alternating current must be that of a single dynamo or must be obtained

by the use of transformers. The voltage of an alternating may be carried

much higher than that of a continuous-current dynamo of very large

capacity, and in many cases pressures of 13,200 volts are now supplied

to transmission lines by alternating dynamos. Just how high the voltage

of single alternating dynamos will be carried no one can say, but it

seems probable that the practical limit will prove to be much less than

the voltages now employed in some transmissions. As the voltage of

alternating dynamos is carried higher the thickness of insulation on

their armature coils and consequently the size or number of slots in

their armature cores and the size of these cores increase rapidly. The

dimensions and weight of an alternating dynamo per unit of its capacity

thus go up with the voltage, and at some undetermined point the cost of

the high-voltage dynamo is greater than that of a low-voltage dynamo of

equal capacity with raising transformers. To the voltage that may be

supplied by transformers there is no practical limit now in sight. Lines

have been in regular operation from one to several years on which

transformers supply 40,000 to 50,000 volts; some large transformers have

been built for commercial use at 60,000 volts, and other transformers

for experimental and testing purposes have been employed in a number of

cases for pressures of 100,000 volts and more.

Available voltages for continuous- and alternating-current transmissions

are thus on a practically equal footing as to their upper limit. The

amount of power that may be generated and delivered with either the

alternating- or continuous-current system of transmission is practically

unlimited. Single alternating dynamos may be had of 5,000 or even 8,000

kilowatts capacity if desired, but it is seldom that these very large

units are employed, because the capacity of a generating station should

be divided up among a number of machines. It is perhaps impracticable to

build single continuous-current dynamos with capacities equal to those

of the largest alternators, but as any number of the continuous-current

machines may be operated either in series or multiple, the power that

may be applied to a transmission circuit is unlimited.

At the plant or plants where the power transmitted by continuous current

is received, a number of motors must be connected in series to operate

at the high-line voltage. These motors may all be located in a single

room, may be connected to machinery in different parts of a building, or

may be in use at points miles apart. The vital requirement is that the

motors must be in series with each other so that the line voltage

divides between them. If simply mechanical power is wanted at the places

where the motors are located, they complete the transmission system and

no further electrical apparatus is required. Where, however, as at

Lausanne, the transmitted power is to be used in a system of general

electrical supply, the motors that receive the current at the line

voltage must drive dynamos that will deliver energy of the required

sorts. In the station at Lausanne four of the motors to which the

transmission line is connected each drives a 3,000-volt three-phase

alternator for the distribution of light and power. The fifth motor at

this station drives a 600-volt dynamo which delivers continuous current

to a street railway. A sixth motor in the same series drives a cement

factory some distance from the station. Neglecting minor changes in

capacity due to losses in the line and motors, this continuous-current

system must thus include three kilowatts in motors and dynamos for each

kilowatt delivered for general electrical distribution at the receiving

station. In a case in which only mechanical power is wanted at the

receiving station, the dynamos and motors concerned in the transmission

must have a combined capacity of two horse-power for each horse-power

delivered at the motor shaft. In contrast with these figures, the

electrical equipment in a transmission with alternating current for

mechanical power alone includes two kilowatts capacity in generators and

motors, besides two kilowatts capacity in transformers for each

corresponding unit of power delivered at the motor shaft unless

generators and motors operate at the full line voltage. If a general

electrical supply is to be operated by the alternating system of

transmission, either motors and dynamos or rotary converters must be

added to transformers where continuous current is required. An

alternating transmission may thus include as little as one kilowatt in

dynamos and one in transformers, or as much as two kilowatts capacity in

dynamos, two in transformers, and one in motors for each kilowatt

delivered to distribution lines at the receiving station.

Line construction from the continuous-current transmission is of the

most simple character apart from the necessity of high insulation. Only

two wires are necessary and they may be of any desired cross-section,

strung on a single pole line and need not be transposed. On these wires

the maximum voltage for which insulation must be provided is the nominal

voltage of the system. It is possible under these conditions to build a

single transmission line with two conductors of such size and strength

and at such a distance apart that a high degree of reliability is

attained against breaks in the wires or arcing between them. In a

transmission of power by two- or three-phase alternating current at

least three wires are necessary and six or more are often employed. If

six or more wires carrying current at the high voltages required by long

transmissions are mounted on a single line of poles, it is not

practicable to obtain such distances between the wires as are desirable.

The repair of one set of wires while the other set is in operation is a

dangerous task, and an arc originating between one set of the wires is

apt to be communicated to another set. For these reasons two pole lines

are frequently provided for a transmission with alternating current, and

three or more wires are then erected on each line. Compared with a

continuous-current transmission, one with alternating current often

requires more poles and is quite certain to require more cross-arms,

pins, insulators, and labor of erection. For a given effective voltage

of transmission it is harder to insulate an alternating- than a

continuous-current line. In the first place the maximum voltage of the

alternating line with even a true sine curve of pressure is 1.4 times

the nominal effective voltage, but the insulation must withstand the

maximum pressure. Then comes the matter of resonance, which may carry

the maximum voltage of an alternating circuit up to several times its

normal amount, if the period of electrical vibration for that particular

circuit should correspond to the frequency of the dynamos that operate

it. Even where the vibration period of a transmission circuit and the

frequency of its dynamos do not correspond, and good construction should

always be planned for this lack of agreement, resonance may and often

does increase the normal voltage of an alternating transmission by a

large percentage. The alternating system of transmission must work at

practically constant voltage whatever the state of its load, so that the

normal stress on the insulation is always at its maximum. In a

transmission with continuous current on the other hand, if the

prevailing practice of a constant current and varying pressure on the

line is followed, the insulation is subject to the highest voltage only

at times of maximum load on the system. Lightning is a very real and

pressing danger to machinery connected to long transmission lines, and

this danger is much harder to guard against in an alternating system

than in a system with continuous constant current. The large degree of

exemption from damage by lightning enjoyed by series arc dynamos is well

known, the magnet windings of such machines acting as an inductance that

tends to keep lightning out of them. Moreover, with any

continuous-current machines lightning arresters having large

self-induction may be connected in circuit and form a most effective

safeguard against lightning, but this plan is not practicable on

alternating lines.

In the matter of switches, controlling apparatus, and switchboards, an

alternating transmission requires much more equipment than a system

using continuous, constant current. The ten dynamos in the generating

station at St. Maurice, with a capacity of 3,450 kilowatts at 23,000

volts, are each connected and disconnected with the transmission by a

switch in a small circular column of cast-iron that stands hardly breast

high. An amperemetre and voltmetre are mounted on each dynamo. The

alternating generators in a station of equal capacity and voltage would

require a large switchboard fitted with bus-bars, oil switches, and

automatic circuit-breakers. Relative efficiencies for the

continuous-current and the alternating-transmission systems vary with

the kind of service required at receiving stations and with the extent

to which transformers are used in the alternating system, other factors

being constant. For purposes of comparison the efficiency at full load

of both alternating- and continuous-current dynamos and motors, also of

rotary converters, may be fairly taken at 92 per cent, and the

efficiency of transformers at 96 per cent.

For the line an efficiency of 94 per cent may be assumed at full load,

this being the actual figure in one of the Swiss transmissions of 2,160

kilowatts at 14,400 volts to a distance of 32 miles. Where the

continuous current system must simply deliver mechanical power at the

receiving stations, its efficiency under full load amounts to 92 × .94 ×

.92 = 79.65 per cent from dynamo shaft to motor shaft. An alternating

system delivering mechanical power will have an efficiency of 92 × .94 ×

.96 × .92 = 76.46 per cent between dynamo shaft and motor shaft, if the

line voltage is generated in the armature coils of the dynamo and the

line loss is 6 per cent. If step-up transformers are employed to secure

the line voltage the efficiency of the alternating transmission

delivering mechanical power drops to the figure of 92 × .96 × .94 × .96

× .92 = 73.40 per cent. It thus appears that for the simple delivery of

mechanical power the continuous current transmission has an advantage

over the alternating of three to six per cent in efficiency, depending

on whether step-up transformers are employed.

When the receiving station must deliver a supply of either continuous or

alternating current for general distribution, the efficiency of the

continuous-current transmission amounts to 92 × .94 × .92 × .92 = 73.27

per cent. The alternating-transmission system in a case in which no

step-up transformers are employed will deliver alternating current of

the same frequency as that on the transmission line at any desired

pressure for general distribution at an efficiency of 92 × .94 × .96 =

83.02 per cent, if step-down transformers are used, but the efficiency

drops to 83.02 × .96 = 79.70 per cent. when step-up transformers are

introduced. If the alternating transmission uses no step-up transformers

and delivers either alternating or continuous current by means of motor

generators, its efficiency at full load is 83.02 × .92 × .92 = 70.26 per

cent, but with step-up transformers added the efficiency drops to 70.26

× .96 = 67.43 per cent. In a transmission where electrical energy must

be delivered for general distribution, the full-load efficiency of an

alternating system ranges either higher or lower than that of a

continuous-current system depending on whether the current from the

transmission line must be converted or not.

Line loss is the same whatever the load in a constant-current

transmission, so that line efficiency falls rather rapidly with the

load. On the other hand, at constant pressure the percentage of energy

loss on the line varies directly with the load, but the actual rate of

energy loss with the square of the load. On partial loads the line

efficiency is thus much higher with alternating than with continuous

constant current.

Efficiency of electrical machinery is generally low at partial loads, so

that in cases in which the number or capacity of alternating dynamos,

transformers, motors, or rotary converters for a transmission would be

greater per unit of delivered power than the corresponding number or

capacity of machines for a transmission by continuous current, the

latter would probably have the advantage in the combined efficiency of

machinery at partial loads. In this way the lower-line efficiency of one

system might offset the lower efficiency of machinery in the other.

Energy is usually very cheap at the generating station of a transmission

system. For this reason small differences in the efficiencies of

different systems should be given only moderate weight in comparison

with the items of first cost, reliability, and expense of operation.

In the matter of first cost at least the continuous-current system seems

to have a distinct advantage over the alternating. Without going into a

detailed estimate, it is instructive to consider the figures given by a

body of five engineers selected to report on the cost of continuous- and

alternating-current equipments for the St. Maurice and Lausanne

transmission. According to the report of these engineers, a three-phase

transmission system would have cost $140,000 more than the

continuous-current system actually installed, all other factors

remaining constant. It should be noted that the conditions of this

transmission are favorable to three-phase working and unfavorable to

continuous-current equipment, because all of the energy except that

going to the 400 horse-power motor at the cement mill must be delivered

at the receiving station for general distribution. Moreover, four out of

the five motors at Lausanne drive three-phase generators, and only one

drives a continuous-current dynamo for the electric railway, so that a

three-phase transmission would have required only one rotary converter.

Had the transmission been concerned merely with the delivery of

mechanical power, as at the cement mill, the advantage of the

continuous- over the alternating-current system in the matter of first

cost would have been much greater than it was.

Long-distance transmission with three-phase current began at Frankfort,

in 1891, when 58 kilowatts were received over a 25,000-volt line from

Lauffen, 109 miles away. Shortly after this historic experiment,

three-phase transmission in the United States began on a commercial

scale, and plants of this sort have multiplied rapidly here. Meantime

very little has been done in America with continuous currents in long

transmissions. In Europe, the birthplace of the three-phase system, it

has failed to displace continuous current for transmission work. About a

score of these continuous-current transmissions are already at work

there. If the opinion of European engineers as to the lower cost of the

continuous-current system, all other factors being equal, is confirmed

by experience, this current will yet find important applications to long

transmissions in the United States.

Systems of transmission with continuous-current may operate at constant

voltage and variable current, at constant current and variable voltage,

or with variations of both volts and amperes to correspond with changes

of load. Dynamos of several thousand kilowatts capacity each can readily

be had at voltages of 500 to 600, but the attempt to construct dynamos

to deliver more than two or three hundred kilowatts each at several

thousand volts has encountered serious sparking at the commutator. Thus

far, dynamos that yield between 300 and 400 kilowatts each have been

made to give satisfactory results at pressures as high as 2,500 volts.

Another one of the Swiss transmissions takes place over a distance of

thirty-two miles at 14,400 volts, the capacity being 2,160 kilowatts. To

give this voltage and capacity, eight dynamos are connected in series at

the generating station, each dynamo having an output of 150 amperes at

1,800 volts, or 216 kilowatts.

Continuous-current motors are, of course, subject to the same

limitations as dynamos in the matter of capacity at high voltage, so

that a series of motors must be employed to receive the high-pressure

energy from the line. The number of these motors may just equal, or may

be less or greater than the number of dynamos, but the total working

voltage of all the motors in operation at one time must equal the total

voltage of the dynamos in operation at that time minus the volts of drop

in the line.

Each constant-current motor may have any desired capacity up to the

practicable maximum, but it must be designed for the current of the

system. The voltage at the terminals of each motor varies with its load,

being greatest when the motor is doing the most work. Constant speed is

usually attained at each motor by means of a variable resistance

connected across the terminals of the magnet coils. The amount of this

resistance is regulated by a centrifugal governor, driven by the motor

shaft. This governor also shifts the position of the brushes on the

commutator to prevent sparking as the current flowing through the magnet

coils is changed.

For a constant-current transmission the magnet and armature windings of

both dynamos and motors are usually connected in series with each other

and the line so that the same current passes through every element of

the circuit, except that each motor may have some current shunted out of

its magnet coil for the purpose of speed regulation.

In some cases, however, the magnet coils of the dynamos are connected in

multiple with each other and receive their current from a separate

dynamo designed for the purpose. With this separate excitation of the

magnet coils, the dynamo armatures are still connected in series with

each other and the line.

The total voltage at the generating station and on the line of a

constant-current system varies with the rate at which energy is

delivered, and has its maximum value only at times of full load. To

obtain this variation of voltage, it is the general practice to change

the speed of the dynamos by means of an automatic regulator which is

actuated by the line current. Any increase of the line current actuates

the regulator and reduces the speed of the dynamos, while a decrease of

the line current raises the dynamo speed. With a good regulator the

variations of the line current are only slight. Under this method of

regulation the dynamos in operation have a substantially constant

current in both armature and magnet coils at all times, so that there is

no reason to shift the position of the brushes on the commutator.

Generating stations of constant current transmission systems are

generally driven by water-power and the speed regulator operates to

change the amount of water admitted to each wheel. Each turbine wheel

usually drives a pair of dynamos, but one or any number of dynamos might

be driven by a single wheel. The two dynamos driven by a single wheel

are generally connected in series at all times, and are cut in or out of

the main circuit together. When the load on a constant-current

generating station is such that the voltage can be developed by less

than all the dynamos, one or more dynamos may be stopped and taken out

of the circuit.

To do this the dynamo or pair of dynamos to be put out of service may be

stopped, their magnet coils having first been short-circuited, and then

a switch across the connections of their armatures to the lines closed,

after which the connections of the armatures to the line are opened. By

a reverse process, any dynamo or pair of dynamos may be cut into the

operating circuit.

At the terminals of each dynamo in the series, while in operation, the

voltage is simply that developed in its armature, so that the insulation

between the several windings is subject to only a corresponding stress.

The entire voltage of the line, however, tends to force a current from

the coils of the dynamo at one end of the series into its frame, thence

to any substance on which that frame rests, and so on to the frame and

coils of the dynamo at the other end of the series. To protect the

insulation of the dynamo coils from the line voltage, thick blocks of

porcelain are placed beneath the dynamo frames, and the armature shafts

are connected to those of the turbines by insulating couplings.

Besides the switches, already mentioned, a voltmeter and ammeter should

be provided for each dynamo and also for the entire series of machines.

This completes the switchboard equipment, which is, therefore, very

simple. As the line loss of a constant-current system is the same

whatever the load that is being operated, this loss may be a large

percentage of the total output when the load is light. If, for

illustration, five per cent of the maximum voltage of the station is

required to force the constant current through the line, the percentage

of line loss will rise to ten when the station voltage is one-half the

maximum, and to twenty when the station is delivering only one-quarter

of its full capacity.

In view of this property of constant-current working, the line loss

should be made quite small in its ratio to the maximum load, as most

stations must work on partial loads much of the time. Five per cent of

maximum station voltage is a fair general figure for the line loss in a

constant-current transmission, but the circumstances of a particular

case may dictate a higher or a lower percentage.

On the 32-mile transmission, above named, the loss in the line is six

per cent of the station output at full load.

If a transmission with continuous current is to be carried out at

constant pressure the limitation as to the capacity and voltage of each

dynamo is about the same as with constant current. Probably more energy

is now transmitted by continuous current at constant pressure than by

any other method, the greater part being devoted to electric railway

work at 500 to 600 volts. Dynamos for about these voltages can readily

be had in capacities up to several thousand kilowatts each, but the

length of transmission that can be economically carried out at this

pressure is comparatively small. For each kilowatt delivered to a line

at 500 volts and to be transmitted to a distance of five miles at a ten

per cent loss in the line, the weight of copper conductors must be 372

pounds, costing $56.80 at 15 cents per pound. This sum is twice to four

times the cost of good continuous-current dynamos per kilowatt of

capacity. If the distance of transmission is ten miles and the voltage

and line loss remain as before, the weight of copper conductor must be

increased to 1,488 pounds per kilowatt delivered to the line, costing

$227.20.

Experience has shown that in sizes of not more than 400 kilowatts,

continuous-current dynamos may safely have a voltage of 2,000 each, and

any number of such dynamos may be operated in multiple, giving whatever

capacity is desired. At 2,000 volts and a loss of 10 per cent in the

line the weight of copper conductors per kilowatt would be 93 pounds,

costing $13.95, for each kilowatt delivered to the line on a 10-mile

transmission. With 2,000 volts on a 20-mile transmission the weight of

conductors per kilowatt would be the same as their weight on a 5-mile

transmission at 500 volts, the percentage of loss being equal in the two

cases. Large continuous-current motors of, say, 50 kilowatts or more can

be had for a pressure of 2,000 volts, so that any number of such motors

might be operated from a 2,000-volt, constant-pressure line entirely

independent of each other. From these figures it is evident that a

transmission of 10 miles may be carried out with continuous-current at

constant pressure from a single dynamo with good efficiency and a

moderate investment in conductors.

When the distance is such that much more than 2,000 volts are required

for the constant-pressure transmission, with continuous current, resort

must be had to the connection of dynamos and motors in series. Any

number of dynamos may be so connected as in the case of constant-current

work. The combined voltages of the series of motors connected to the

constant-pressure transmission line must equal the voltage of that

line, so that the number of motors in any one series must be constant.

If the voltage of transmission is so high that more than two or three

motors must be connected in each series, there comes the objection that

motors must be operated at light loads during much of the time.

Moreover, each series of motors must be mechanically connected to the

same work, as that of driving a single dynamo or other machine, because

if the loads on the motors of a series vary differently, these motors

will not operate at constant speed. Continuous-current transmission at

constant pressure with motors in series thus lacks the flexibility of

transmission at constant current where any motor may be started and

stopped without regard to the others in the series, the line voltage

being automatically regulated at the generating station according to the

number of motors in use at any time and to the work they are doing.

In the efficiency of its dynamos, motors and line, a constant-pressure

system of transmission is substantially equal to one with constant

current at full load. At partial loads the constant-pressure line has

the advantage because the loss of energy in it varies with the square of

the load. Thus at constant pressure the line loss in energy per hour at

half-load is only one-fourth as great as the loss at full load. On the

other hand, the energy loss in the constant-current line is the same at

all stages of load. Because of these facts it is good practice to allow,

say, a ten-per-cent loss in a constant-pressure line and only five per

cent in a constant-current line at full load.

In a generating station at 2,000 volts or more constant pressure, it is

desirable to have the magnet coils of the main dynamos connected in

multiple and separately excited by a small dynamo at constant pressure.

This plan is especially desirable when the armatures of several dynamos

are connected in series to obtain the line voltage. Separately excited

magnet coils make it easier to control the operation of the several

dynamos, coils of low-voltage are cheaper to make than coils of high

voltage, and the low voltage windings are less liable to burn out. If a

series of constant-pressure motors is in use at one point, it may be

cheaper and safer to excite its magnet coils from a special dynamo than

from the line.

In a transmission carried out with series-wound dynamos and motors, the

speed of the motors may be constant at all loads without any special

regulating mechanism. To attain this result it is necessary that all the

motors be coupled so as to form a single unit mechanically and that the

dynamos be driven at constant speed. A transmission system of this sort

may include a single dynamo and a single motor, or two or more dynamos,

and two or more motors may be used in series.

When the dynamos of such a system are driven at constant speed and a

variable load is applied to the single motor, or to the mechanically

connected motors, both the voltage of the system and the amperes flowing

in all its parts change together so that practically constant speed is

maintained at the motors, provided that the design of both the dynamos

and motors is suitable for the purpose. With the maximum load on the

motors the volts and amperes of the system have their greatest values,

and these values both decline with smaller loads. The chief disadvantage

of this system lies in the fact that where more than one motor is

employed all the motors must be mechanically joined together so as to

work on the same load.

Compared with the constant-current system, this combination of series

dynamos with mechanically connected series motors has the distinct

advantage that neither the dynamos nor motors require any sort of

regulators in order to maintain constant motor speed. It is only

necessary that the dynamos be driven at constant speed and that both the

dynamos and motors be designed for the transmission. In comparison with

a constant-pressure system, the one under consideration has the

advantage that neither its dynamos nor motors require magnet coils with

a high voltage at their terminals and composed of fine wire or separate

excitation by a special dynamo. These features of the system with series

dynamos and motors, the latter being joined as a mechanical unit, make

it cheaper to install and easier to operate than either of the other

two. This system is especially adapted for the delivery of mechanical

power in rather large units. The voltage available may be anything

desired, but is subject to the practical limitations that all the motors

must deliver their power as a mechanical unit, so that unless the power

is quite large the number of motors in the series and, therefore, the

voltage is limited.

An interesting illustration of the system of transmission just described

exists between a point on the River Suze, near Bienne, Switzerland, and

the Biberest paper mills. At the river a 400 horse-power turbine

water-wheel drives a pair of series-wound dynamos, each rated at 130

kilowatts and 3,300 volts. These dynamos are connected in series, giving

a total capacity of 260 kilowatts and a pressure of 6,600 volts. At the

Biberest mills are located two series-wound motors, mechanically coupled

and connected in series with each other and with the two-wire

transmission line, which extends from the two dynamos at the River Suze.

Each of these motors has a capacity and voltage equal to that of either

of the dynamos previously mentioned. The coupled motors operate at the

constant speed of 200 revolutions per minute at all loads and deliver

over 300 horse-power when doing maximum work. Between the generating

plant at the river and the Biberest mills the distance is about 19

miles, and the two line wires are each of copper, 275 mils, or a little

more than one-fourth inch in diameter. The dynamos and motors of this

system are mounted on thick porcelain blocks in order to protect the

insulation of their windings from the strain of the full-line voltage.

Either of the three systems of transmission by continuous-current that

have been considered requires a smaller total capacity of electrical

apparatus for a given rate of mechanical power delivery than any system

using alternating current except that where both the dynamos and motors

operate at line voltage.