CHAPTER V.

THE PHYSICAL LIMITS OF ELECTRIC-POWER TRANSMISSION.

Electrical energy may be transmitted around the world if the line

voltage is unlimited. This follows from the law that a given power may

be transmitted to any distance with constant efficiency and a fixed

weight of conductors, provided the voltage is increased directly with

the distance.

The physical limits of electric-power transmission are thus fixed by the

practicable voltage that may be employed. The effects of the voltage of

transmission must be met in the apparatus at generating and receiving

stations on the one hand, and along the line on the other. In both

situations experience is the main guide, and theory has little that is

reliable to offer as to the limit beyond which the voltage will prove

unworkable.

Electric generators are the points in a transmission system where the

limit of practical voltage is first reached. In almost all high-voltage

transmissions of the present day in the United States alternating

generators are employed. Very few if any continuous-current dynamos with

capacities in the hundreds of kilowatts and voltages above 4,000 have

been built in Europe, and probably none in the United States. Where a

transmission at high voltage is to be accomplished with continuous

current, two or more dynamos are usually joined in series at the

generating station, and a similar arrangement with motors is made at the

receiving station, so that the desired voltage is available at the line

though not present at any one machine.

Alternating dynamos that deliver current at about 6,000 volts have been

in regular use for some years, in capacities of hundreds of kilowatts

each, and may readily be had of several thousand kilowatts capacity. But

even 6,000 volts is not an economical pressure for transmissions over

fifteen to fifty miles, such as are now quite common; consequently in

such transmissions it has been the rule to employ alternators that

operate at less than 3,000 volts, and to raise this voltage to the

desired line pressure by step-up transformers at the generating station.

More recently, however, the voltage of alternating generators has been

pushed as high as 13,000 in the revolving-magnet type where all the

armature windings are stationary. This voltage makes it practicable to

dispense with the use of step-up transformers for transmissions up to or

even beyond 30 miles in some cases. This voltage of 13,000 in the

armature coils is attained only by constructions involving some

difficulty because of the relatively large amount of room necessary for

the insulating materials on coils that develop this pressure. The

tendency of this construction is to give alternators unusually large

dimensions per given capacity. It seems probable, moreover, that the

pressures developed in the armature coils of alternating generators must

reach their higher limits at a point much below the 50,000 and 60,000

volts in actual use on present transmission lines. In the longest

transmissions with alternating current there is, therefore, little

prospect that step-up transformers at the generating stations and

step-down transformers at receiving stations can be dispensed with. The

highest voltage that may be received or delivered at these stations is

simply the highest that it is practicable to develop by transformers and

to transmit by the line.

A very high degree of insulation is much more easy to attain in

transformers than in generator armatures, because the space that can be

readily made available for insulating materials is far greater in the

transformers, and further because their construction permits the

complete immersion of their coils in petroleum. This oil offers a much

greater resistance than air to the passage of electric sparks, which

tend to set up arcs between coils at very high voltages and thus destroy

the insulation. Danger to insulation from the effect known as creeping

between coils at widely different pressures is largely avoided by

immersion of the coils in oil. For several years groups of transformers

have been worked regularly at 40,000 to 60,000 volts, and in no instance

is there any indication that the upper limit of practicable voltage has

been reached. On the contrary, transformers have repeatedly been worked

experimentally up to and above 100,000 volts.

From all these facts, and others of similar import, it is fair to

conclude that the physical limit to the voltages that it is practicable

to obtain with transformers is much above the 50,000 or 60,000 volts now

in practical use on transmission systems. So far as present practice is

concerned, the limit to the use of high voltages must be sought beyond

the transformers and outside of generating and receiving stations. As

now constructed, the line is that part of the transmission system where

a physical limit to the use of higher voltages will first be reached.

The factors that tend most directly to this limit are two: temporary

arcing between the several wires on a pole, and the less imposing but

constant passage of energy from one wire to another. On lines of very

high voltage arcing is occasionally set up by one of several causes. At

a point where one or more of the insulators on which the wires are

mounted become broken or defective, the current is apt to flow from one

wire to another along a wet cross-arm, until the wood grows carbonized

and an arc is formed that ends by burning up the cross-arm or even the

pole. Where lines are exposed to heavy sea fog, the salt is in some

cases deposited on the insulators and cross-arms to an extent that

starts an arc between the wires, and ends often in the destruction of

the cross-arm. In some instances the glass and porcelain insulators

supporting wires used with high voltages are punctured by sparks that

pass right through the material of the insulator to the pin on which it

is mounted, thus burning the pin and ultimately the cross-arm. This

trouble is easily met, however, by the adoption of a better grade of

porcelain or of an insulator with a greater thickness of glass or

porcelain between the wires and the supporting pin. Arcs between lines

at high voltages usually start by sparks that jump from the lower edges

of insulators, when they are wet or covered with salt deposit, to the

cross-arm. As the lower edges of insulators are only a few inches from

their cross-arms, the sparks find a path of comparatively low resistance

by passing from insulator to cross-arm and thence to the other insulator

and wire. The wood of a wet cross-arm is a far better conductor than the

air. Where wires are several feet or more apart, sparks probably never

jump directly through the air from one to the other. Large birds flying

close to such wires, however, have in some instances started momentary

arcs between them. The treatment of cross-arms with oil or paraffine

reduces the number of arcs that occur on a line of high voltage, but

does not do away with them.

As the voltages of long transmissions have gone up, the distance through

the air between wires and the distances between the lower wet edges of

insulators and the cross-arms have been much increased. Most of the

earlier transmission lines for high voltages were erected on insulators

spaced from one to two feet apart. In contrast with this practice, the

three wires of the transmission line in operation at 50,000 volts

between Cañon Ferry and Butte are arranged at the corners of a triangle

seventy-eight inches apart, one wire at the top of each pole and the

other two at opposite ends of the cross-arm. A voltage that would just

start an arc along a wet cross-arm between wires eighteen inches apart

would be quite powerless to do so over seventy-eight inches of

cross-arm, the lower wet edges of insulators being equidistant from

cross-arms in the two cases. To reach the cross-arm, the electric

current passes down over the wet or dirty outside surface of the

insulator to its lower edge. In the older types of insulators the lower

wet edge often came within two inches of the cross-arm. For the

50,000-volt line just mentioned the insulators (see illus.) are mounted

with their lower wet edges about eight inches above the cross-arms. At

its lower edge each insulator has a diameter of nine inches, and a small

glass sleeve extends several inches below this edge and close to the

wooden pin, to prevent sparking from the lower wet edge of the insulator

to the pin. These increased distances between wires in a direct line

through the air, and also the greater distances between the lower wet

edges of insulators and their pins and cross-arms, are proving fairly

effective to prevent serious arcing under good climatic conditions, for

the maximum pressures of 50,000 to 60,000 volts now in use. If these

voltages are to be greatly exceeded it is practically certain that the

distance between wires, and from the lower wet edges of insulators to

the wood of poles or cross-arms, must be still further increased to

avoid destructive arcing.

The nearest approach to an absolute physical limit of voltage with

present line construction is met in the constant current of energy

through the air from wire to wire of a circuit. A paper in vol. XV.,

Transactions American Institute Electrical Engineers, gives the tests

made at Telluride, Col., to determine the rates at which energy is lost

by passing through the air from one wire to another of the same circuit.

The tests at Telluride were made with two-wire circuits strung on a pole

line 11,720 feet in length, at first with iron wires of 0.165 inch

diameter and then with copper wires of 0.162 inch diameter. Measurements

were made of the energy escaping from wire to wire at different voltages

on the line, and also with the two wires at various distances apart. It

was found that the loss of energy over the surfaces of insulators was

very slight, and that the loss incident to the passage of energy

directly through the air is the main one to be considered. This leakage

through the air varies with the length of the line, as might be

expected. Tests were made with pairs of wires running the entire length

of the pole line and at distances of 15, 22, 35, and 52 inches apart

respectively. Losses with wires 22 or 35 inches apart were intermediate

to the losses when wires were 15 and 52 inches apart respectively.

Results given in the original paper for the pair of wires that were 15

inches apart and for the pair that were 52 inches apart are here reduced

to approximate watts per mile of two-wire line. At 40,000 volts the loss

between the two wires that were 15 inches apart was about 150 watts per

mile, and between the two wires that were 52 inches apart the loss was

84 watts per mile. The two wires 15 inches apart showed a leakage of

approximately 413 watts per mile when the voltage was up to 44,000, but

the wires 52 inches apart were subject to a leakage of only 94 watts per

mile at the same voltage. At 47,300 volts, the highest pressure recorded

for the two wires 15 inches apart, the leakage between them was about

1,215 watts per mile, while an equal voltage on the two wires 52 inches

apart caused a leakage of only 122 watts per mile, or one-tenth of that

between the wires that were 15 inches apart. When about 50,000 volts

were reached on the two wires 52 inches apart, the leakage between them

amounted to 140 watts per mile; but beyond this voltage the loss went up

rapidly, and was 225 watts per mile at about 54,600 volts. For higher

pressures the loss between these two wires still more rapidly increased,

and amounted to 1,368 watts per mile with about 59,300 volts, the

highest pressure recorded. With a loss of about 1,215 watts per mile

between the two wires 52 inches apart, the voltage on them was 58,800,

in contrast with the 47,300 volts producing the same leakage on the two

wires 15 inches apart.

Evidently, however, at even 52 inches between line wires the limit of

high voltage is not far away. When the voltage on the 52-inch line was

raised from 54,600 to 59,300, the leakage loss between the two wires

increased about 1,143 watts per mile. If the leakage increases at least

in like proportion, as seems probable, for still higher pressures, the

loss between the two wires would amount to 6,321 watts per mile with

80,000 volts on the line. On a line 200 miles long this loss by leakage

between the two wires would amount to 1,264,200 watts. Any such leakage

as this obviously sets an absolute, physical limit to the voltage, and

consequently the length of transmission.

Fortunately for the future delivery of energy at great distances from

its source, the means to avoid the limit just discussed are not

difficult. Other experiments have shown that with a given voltage and

distance between conductors the loss of energy from wire to wire

decreases rapidly as their diameters increase. The electrical resistance

of air, like that of any other substance, increases with the length of

the circuit through it. The leakage described is a flow of electrical

energy through the air from one wire to another of the same circuit. To

reduce this leakage it is simply necessary to give the path from wire to

wire through the air greater electrical resistance by increasing its

length, that is, by placing the wires at greater distances apart. The

fact demonstrated at Telluride, that with 47,300 volts on each line the

leakage per mile between the two wires 15 inches apart was ten times as

great as the leakage between the two wires 52 inches apart, is full of

meaning. Evidently, leakage through the air may be reduced to any

desired extent by suitable increase of distance between the wires of the

same circuit. But to carry this increase of distance between wires very

far involves radical changes in line construction. Thus far it has been

the uniform practice to carry the two or three wires of a transmission

circuit on a single line of poles, and in many cases several such

circuits are mounted on the same pole line. For the 65 mile transmission

into Butte, Mont., only the three wires of a single circuit are mounted

on one pole line, and this represents the best present practice. The

cross-arms on this line are each 8 feet long, and one is attached to

each pole. The poles are not less than 35 feet long and have 8-inch

tops. One wire is mounted at the top of each pole, and the other two

wires near the ends of the cross-arm, so that the three wires are

equidistant and 78 inches apart. By the use of still heavier poles the

length of cross-arms may be increased to 12 or 14 feet, for which their

section should be not less than 4 by 6 inches. Placing one wire at the

pole top, the 12-foot cross-arm would permit the three wires of a

circuit to be spaced about 10.5 feet apart. The cost of extra large

poles goes up rapidly and there are alternative constructions that seem

better suited to the case. Moreover, a few tens of thousands of volts

above present practice would bring us again to a point where even 10.5

feet between wires would not prevent a prohibitive leakage. Two poles

might be set 20 feet apart, with a cross-piece between them, extending

out 5 feet beyond each pole and having a total length of 30 feet. This

would permit three wires to be mounted along the cross-piece at points

about 14 feet apart.

If the present transmission pressures of 50,000 to 60,000 volts are to

be greatly exceeded, the line structure may involve the use of a

separate pole for each wire of a circuit, each wire to be mounted at the

top of its pole. This construction calls for three lines of poles to

carry the three wires of a three-phase transmission. Each of these poles

may be of only moderate dimensions, say 30 feet long with 6- or 7-inch

top. The cost of three of these poles will exceed by only a moderate

percentage that of a 35- or 40-foot pole with an 8- to 10-inch top, such

as would be necessary with 12-foot cross-arms. The distance between

these poles at right angles to the line may be anything desired, so that

leakage from wire to wire through the air will be reduced to a trifling

matter at any voltage. Extra long pins and insulators at the pole tops

will easily give a distance of two feet or more between the lower wet

edge of each insulator and the wood of pin or pole. Such line

construction would probably safely carry two or three times the maximum

voltage of present practice, and might force the physical limit of

electrical transmission back to the highest pressure at which

transformers could be operated. With not more than 60,000 volts on the

line the size of conductors is great enough in many cases to keep the

loss of energy between them within moderate limits when they are six

feet apart, but with a large increase of voltage the size of conductors

must go up or the distances between them must increase.