TABLE 65

APPROXIMATE

EFFICIENCIES OF VARIOUS

COVERINGS REFERRED TO

BARE PIPES

+--------------------------------+

|+-------------------+----------+|

|| Covering |Efficiency||

|+-------------------+----------+|

||Asbestocel | 76.8 ||

||Gast's Air Cell | 74.4 ||

||Asbesto Sponge Felt| 85.0 ||

||Magnesia | 83.5 ||

||Asbestos Navy Brand| 82.0 ||

||Asbesto Sponge Hair| 86.0 ||

||Asbestos Fire Felt | 73.5 ||

|+-------------------+----------+|

+--------------------------------+

Based on one-inch covering.

The following suggestions may be of service:

Exposed radiating surfaces of all pipes, all high pressure steam

flanges, valve bodies and fittings, heaters and separators, should be

covered with non-conducting material wherever such covering will improve

plant economy. All main steam lines, engine and boiler branches, should

be covered with 2 inches of 85 per cent carbonate of magnesia or the

equivalent. Other lines may be covered with one inch of the same

material. All covering should be sectional in form and large surfaces

should be covered with blocks, except where such material would be

difficult to install, in which case plastic material should be used. In

the case of flanges the covering should be tapered back from the flange

in order that the bolts may be removed.

All surfaces should be painted before the covering is applied. Canvas is

ordinarily placed over the covering, held in place by wrought-iron or

brass bands.

Expansion and Support of Pipe--It is highly important that the piping be

so run that there will be no undue strains through the action of

expansion. Certain points are usually securely anchored and the

expansion of the piping at other points taken care of by providing

supports along which the piping will slide or by means of flexible

hangers. Where pipe is supported or anchored, it should be from the

building structure and not from boilers or prime movers. Where supports

are furnished, they should in general be of any of the numerous sliding

supports that are available. Expansion is taken care of by such a method

of support and by the providing of large radius bends where necessary.

It was formerly believed that piping would actually expand under steam

temperatures about one-half the theoretical amount due to the fact that

the exterior of the pipe would not reach the full temperature of the

steam contained. It would appear, however from recent experiments that

such actual expansion will in the case of well-covered pipe be very

nearly the theoretical amount. In one case noted, a steam header 293

feet long when heated under a working pressure of 190 pounds, the steam

superheated approximately 125 degrees, expanded 8¾ inches; the

theoretical amount of expansion under the conditions would be

approximately 9-35/64 inches.

[Illustration: Bankers Trust Building, New York City, Operation 900

Horse Power of Babcock & Wilcox Boilers]