CALCULATED FOR 160 POUNDS PRESSURE AND 60 DEGREES TEMPERATURE

+---------------------------------------------------------------------+

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| | | | | | | | ||

|| Pipe | |1/2 |3/4 | 1 |1-1/4|1-1/2| ||

||Inches| Thickness of Covering |inch|inch|inch|inch |inch |Bare ||

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| |B. t. u. per lineal foot | | | | | | ||

|| | per hour |149 |118 | 99 | 86 | 79 | 597 ||

|| |B. t. u. per square foot | | | | | | ||

|| | per hour |240 |190 |161 | 138 | 127 | 959 ||

|| 2 |B. t. u. per square foot | | | | | | ||

|| | per hour per one degree | | | | | | ||

|| | difference in temperature|.770|.613|.519|.445 |.410 |3.198||

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| |B. t. u. per lineal foot | | | | | | ||

|| | per hour |247 |193 |160 | 139 | 123 |1085 ||

|| |B. t. u. per square foot | | | | | | ||

|| | per hour |210 |164 |136 | 118 | 104 | 921 ||

|| 4 |B. t. u. per square foot | | | | | | ||

|| | per hour per one degree | | | | | | ||

|| | difference in temperature|.677|.592|.439|.381 |.335 |2.970||

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| |B. t. u. per lineal foot | | | | | | ||

|| | per hour |352 |269 |221 | 190 | 167 |1555 ||

|| |B. t. u. per square foot | | | | | | ||

|| | per hour |203 |155 |127 | 110 | 96 | 897 ||

|| 6 |B. t. u. per square foot | | | | | | ||

|| | per hour per one degree | | | | | | ||

|| | difference in temperature|.655|.500|.410|.355 |.310 |2.89 ||

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| |B. t. u. per lineal foot | | | | | | ||

|| | per hour |443 |337 |276 | 235 | 207 |1994 ||

|| |B. t. u. per square foot | | | | | | ||

|| | per hour |196 |149 |122 | 104 | 92 | 883 ||

|| 8 |B. t. u. per square foot | | | | | | ||

|| | per hour per one degree | | | | | | ||

|| | difference in temperature|.632|.481|.394|.335 |.297 |2.85 ||

|+------+---------------------------+----+----+----+-----+-----+-----+|

|| |B. t. u. per lineal foot | | | | | | ||

|| | per hour |549 |416 |337 | 287 | 250 |2468 ||

|| |B. t. u. per square foot | | | | | | ||

|| | per hour |195 |148 |120 | 102 | 89 | 877 ||

|| 10 |B. t. u. per square foot | | | | | | ||

|| | per hour per one degree | | | | | | ||

|| | difference in temperature|.629|.477|.387|.329 |.287 |2.83 ||

|+------+---------------------------+----+----+----+-----+-----+-----+|

+---------------------------------------------------------------------+

Covering--Magnesia, canvas covered.

For calculating radiation for pressure and temperature other than 160

pounds, and 60 degrees, use B. t. u. figures for one degree difference.

Radiation from Pipes--The evils of the presence of condensed steam in

piping systems have been thoroughly discussed above and in some of the

previous articles. Condensation resulting from radiation, while it

cannot be wholly obviated, can, by proper installation, be greatly

reduced.

Bare pipe will radiate approximately 3 B. t. u. per hour per square foot

of exposed surface per one degree of difference in temperature between

the steam contained and the external air. This figure may be reduced to

from 0.3 to 0.4 B. t. u. for the same conditions by a 1½ inch insulating

covering. Table 64 gives the radiation losses for bare and covered pipes

with different thicknesses of magnesia covering.

Many experiments have been made as to the relative efficiencies of

different kinds of covering. Table 65 gives some approximately relative

figures based on one inch covering from experiments by Paulding,

Jacobus, Brill and others.