TABLE 54

STACK CAPACITIES, CORRECTION FACTORS FOR

ALTITUDES

_______________________________________________________________________

| | | | | |

| Altitude | | R | | R^{2/5} |

| Height in Feet | Normal | Ratio Barometer | | Ratio Increase |

| Above | Barometer | Reading | R² | in Stack |

| Sea Level | | Sea Level to | | Diameter |

| | | Altitude | | |

|________________|___________|_________________|_______|________________|

| | | | | |

| 0 | 30.00 | 1.000 | 1.000 | 1.000 |

| 1000 | 28.88 | 1.039 | 1.079 | 1.015 |

| 2000 | 27.80 | 1.079 | 1.064 | 1.030 |

| 3000 | 26.76 | 1.121 | 1.257 | 1.047 |

| 4000 | 25.76 | 1.165 | 1.356 | 1.063 |

| 5000 | 24.79 | 1.210 | 1.464 | 1.079 |

| 6000 | 23.87 | 1.257 | 1.580 | 1.096 |

| 7000 | 22.97 | 1.306 | 1.706 | 1.113 |

| 8000 | 22.11 | 1.357 | 1.841 | 1.130 |

| 9000 | 21.28 | 1.410 | 1.988 | 1.147 |

| 10000 | 20.49 | 1.464 | 2.144 | 1.165 |

|________________|___________|_________________|_______|________________|

These figures show that the altitude affects the height to a much

greater extent than the diameter and that practically no increase in

diameter is necessary for altitudes up to 3000 feet.

For high altitudes the increase in stack height necessary is, in some

cases, such as to make the proportion of height to diameter

impracticable. The method to be recommended in overcoming, at least

partially, the great increase in height necessary at high altitudes is

an increase in the grate surface of the boilers which the stack serves,

in this way reducing the combustion rate necessary to develop a given

power and hence the draft required for such combustion rate.

Steam, Its Generation and Use · 第 148 / 217 题