D = KH. (25)

For average conditions the atmospheric pressure may be considered 14.7

pounds per square inch, and the temperature 60 degrees Fahrenheit. For

these values and various stack temperatures K becomes:

_Temperature Stack Gases_ _Constant K_

750 .0084

700 .0081

650 .0078

600 .0075

550 .0071

500 .0067

450 .0063

400 .0058

350 .0053

Draft Losses--The intensity of the draft as determined by the above

formula is theoretical and can never be observed with a draft gauge or

any recording device. However, if the ashpit doors of the boiler are

closed and there is no perceptible leakage of air through the boiler

setting or flue, the draft measured at the stack base will be

approximately the same as the theoretical draft. The difference existing

at other times represents the pressure necessary to force the gases

through the stack against their own inertia and the friction against the

sides. This difference will increase with the velocity of the gases.

With the ashpit doors closed the volume of gases passing to the stack

are a minimum and the maximum force of draft will be shown by a gauge.

As draft measurements are taken along the path of the gases, the

readings grow less as the points at which they are taken are farther

from the stack, until in the boiler ashpit, with the ashpit doors open

for freely admitting the air, there is little or no perceptible rise in

the water of the gauge. The breeching, the boiler damper, the baffles

and the tubes, and the coal on the grates all retard the passage of the

gases, and the draft from the chimney is required to overcome the

resistance offered by the various factors. The draft at the rear of the

boiler setting where connection is made to the stack or flue may be 0.5

inch, while in the furnace directly over the fire it may not be over,

say, 0.15 inch, the difference being the draft required to overcome the

resistance offered in forcing the gases through the tubes and around the

baffling.

One of the most important factors to be considered in designing a stack

is the pressure required to force the air for combustion through the bed

of fuel on the grates. This pressure will vary with the nature of the

fuel used, and in many instances will be a large percentage of the total

draft. In the case of natural draft, its measure is found directly by

noting the draft in the furnace, for with properly designed ashpit doors

it is evident that the pressure under the grates will not differ

sensibly from atmospheric pressure.

Loss in Stack--The difference between the theoretical draft as

determined by formula (24) and the amount lost by friction in the stack

proper is the available draft, or that which the draft gauge indicates

when connected to the base of the stack. The sum of the losses of draft

in the flue, boiler and furnace must be equivalent to the available

draft, and as these quantities can be determined from record of

experiments, the problem of designing a stack becomes one of

proportioning it to produce a certain available draft.

The loss in the stack due to friction of the gases can be calculated

from the following formula:

f W² C H

[Delta]D = -------- (26)

A³

in which

[Delta]D = draft loss in inches of water,

W = weight of gas in pounds passing per second,

C = perimeter of stack in feet,

H = height of stack in feet,

f = a constant with the following values at sea level:

.0015 for steel stacks, temperature of gases 600 degrees

Fahrenheit.

.0011 for steel stacks, temperature of gases 350 degrees

Fahrenheit.

.0020 for brick or brick-lined stacks, temperature of gases

600 degrees Fahrenheit.

.0015 for brick or brick-lined stacks, temperature of gases

350 degrees Fahrenheit.

A = Area of stack in square feet.

[Illustration: 24,420 Horse-power Installation of Babcock & Wilcox

Boilers and Superheaters, Equipped with Babcock & Wilcox Chain Grate

Stokers in the Quarry Street Station of the Commonwealth Edison Co.,

Chicago, Ill.]

This formula can also be used for calculating the frictional losses for

flues, in which case, C = the perimeter of the flue in feet, H = the

length of the flue in feet, the other values being the same as for

stacks.

The available draft is equal to the difference between the theoretical

draft from formula (25) and the loss from formula (26), hence:

f W² C H

d^{1} = available draft = KH - -------- (27)

A³

Table 53 gives the available draft in inches that a stack 100 feet high

will produce when serving different horse powers of boilers with the

methods of calculation for other heights.