CHAPTER XXVII

TESTING AND TESTING APPARATUS

The practical electrician frequently has to make tests of various kinds

which require the rapid and accurate measurement of voltage, current

and resistance. It is therefore essential that he understand the methods

employed in testing and the operation of the instruments used.

Most tests are made with a galvanometer, and the devices, such as

resistances, switches, etc., which are used in connection with the

galvanometer may be obtained put up in a neat and substantial box together

with the galvanometer, the combination being called a "testing set."

Numerous forms of testing set are illustrated in this chapter.

The construction, use, and operation of the various types of galvanometer

have been explained in chapter twenty-six. Ammeters and voltmeters, which

are simply special forms of galvanometer, and which are largely used are

fully described in the preceding chapter.

Pressure Measurement.--An electromotive force has been defined as that

which causes or tends to cause a current; it is analogous to water

pressure; potential difference corresponds to difference of level. The

_total_ electromotive force of a circuit is independent of resistance or

current, and cannot be limited to mean the fall of pressure between any

two points, as for instance the terminals of a battery.

If the pressure of a battery be two volts when measured on open

circuit by a static voltmeter, there will still be two volts on closed

circuit, but there will now be a loss of pressure through the internal

resistance of the battery and the voltage across the terminals will

be less than the _total_ voltage. The static voltmeter, never closing

the circuit, actually measures the total voltage.

[Illustration: Fig. 540.--Clark cell (Kahle's modification of the Rayleigh

H form), the standard for the International volt. The cell has for its

positive electrode, mercury, and for its negative electrode, amalgamated

zinc. The electrolyte consists of a saturated solution of zinc sulphate

and mercurous sulphate. The pressure is 1.434 volts at 15°C., and between

10°C. and 25°C. the pressure decreases .00115 of a volt for each increase

of 1°C. The containing glass vessel consists of two limbs, closed at

bottom and joined above to a common neck fitted with a ground glass

stopper. The diameter of the limbs should be at least 2 cms., and their

length at least 3 cms. The neck should be not less than 1.5 cms. in

diameter. At the bottom of each limb a platinum wire of about .4 mm. in

diameter is sealed through the glass. To set up the cell, place mercury in

one limb, and in the other hot liquid amalgam, containing 90 parts mercury

and 10 parts zinc. The platinum wires at the bottom must be completely

covered by the mercury and the amalgam, respectively. On the mercury,

place a layer 1 cm. thick of the zinc and mercurous sulphate paste.

Both this paste and the zinc amalgam must be covered with a layer of the

neutral zinc sulphate crystals 1 cm. thick. The whole vessel must then be

filled with the saturated zinc sulphate solution, and the stopper inserted

so that it shall just touch it, leaving, however, a small bubble to guard

against breakage when the temperature rises. Before finally inserting the

glass stopper a strong alcoholic solution of shellac is applied to the

upper edge, after which the stopper is pressed firmly in place.]

Ques. What error is introduced in measuring the pressure of a battery with

an ordinary voltmeter?

Ans. Since the measurement is made on _closed circuit_ the reading does

not give the total pressure of the battery.

The error is very slight because the resistance of the voltmeter is

very high and the current so small that the loss of pressure in the

battery can be neglected.

[Illustration: Fig. 541.--Weston Cadmium Cell. It is made in two forms;

one known as the Weston normal cell, in which the solution of cadmium

sulphate is saturated at all temperatures at which the cell may be used.

The other, known as the Weston standard cell, in which the cadmium

sulphate solution is unsaturated at all temperatures above 4°C. The

Weston normal cell, or saturated form is slightly affected by changes

in temperature, but, on account of the fact that it can be accurately

reproduced, it was adopted by the London Conference in 1908, as a

convenient voltage standard. The value of its voltage suggested by the

committee of the London Conference on Electrical Units and Standards,

and adopted by the Bureau of Standards at Washington, Jan. 1st, 1911, is

1.0183 International volts at 20°C. At any other temperature its voltage

is:

E_{t} = E_{20} - 0.0000406(t-20) - 0.00000095(t-20)^{2} + 0.00000001(t-20)^{3}

The Weston standard cell, or unsaturated form is practically unaffected by

changes in temperature and is the form most commonly used for laboratory

work and general testing. The average pressure of this form is 1.0187 Int.

volts.]

Ques. Define the International volt.

Ans. _It is the electromotive force that, steadily applied to a conductor

whose resistance is one International ohm, will produce a current of

one International ampere, and which is represented sufficiently well for

practical use by 1,000/1,434 of the voltage between the poles of the Clark

cell at a temperature of 15° C., when prepared as in fig. 540._

The relation between the units volt, ampere and ohm, are shown

graphically in figs. 542 and 543.

[Illustration: Figs. 542 and 543.--Diagrams showing hydraulic analogy

illustrating the difference between amperes and coulombs. The _rate_

of current flow of one ampere in fig. 543 may be compared to the rate

of discharge of a pump as in fig. 542. Assuming the pump to be of such

size that it discharges a gallon per stroke and is making 60 strokes

per minute, the quantity of water discharged per hour (coulombs in fig.

543) is 1 × 60 × 60 = 3,600 gallons. Following the analogy further (in

fig. 543), the pressure of one volt is required to force the electricity

through the resistance of one ohm between the terminals A and B. In fig.

542, the boiler must furnish steam pressure on the pump piston to overcome

the friction (resistance) offered by the pipe and raise the water from the

lower level A' to the higher level B'. The difference of pressure between

A and B in the electric circuit corresponds to the difference of pressure

between A' and B'. The cell furnishes the energy to move the current by

maintaining a difference of pressure at its terminals C and D; similarly,

the boiler furnishes energy to raise the water by maintaining a difference

of pressure between the steam pipe C and exhaust pipe D'.]

[Illustration: Fig. 543. If the current strength in fig. 543 be one

ampere, the quantity of electricity passing any point in the circuit per

hour is 1 × 60 × 60 = 3,600 coulombs.]

Current Measurement.--It is necessary to adopt some arbitrary standard in

order to compare currents of different strengths. The term _strength of

a current_, or current strength means the _rate of flow_ past any point

in the circuit in a given unit of time. The unit of current, called the

_ampere_, is defined as _the unvarying current which, when passed through

a solution of nitrate of silver in water (15 per cent. by weight of the

nitrate) deposits silver at the rate of .001118 gramme per second_.

[Illustration: Fig. 544.--Queen weight voltameter for determining the

strength of current by the weight of metal deposited in a given time.

The two outside plates form the anode and are joined together and to one

binding post, while the cathode is placed between them and connected to

the other binding post. The cathode thus receives a deposit on both sides.

An adjustable arm serves to lower the plates into the electrolyte. To

calculate the strength of an unknown current which has passed through a

weight voltameter, _divide the gain in weight by the number of seconds

the current flows through the instrument and by the weight deposited by

one ampere in one second_. That is, current strength in amperes = gain in

weight ÷ (time in seconds × .0003286).]

Ques. How much copper or zinc will one ampere deposit in one second?

Ans. .0003286 gramme of copper in a copper voltameter, or .0003386 gramme

of zinc in a zinc voltameter.

Ques. What is the difference between an ampere and a coulomb?

Ans. An ampere is the unit _rate of flow_ of the current, and a coulomb

is the unit _quantity_ of electricity, that is, the ampere is the rate of

current flow that will deposit .0003286 grammes of copper in one second

and a coulomb is the _quantity_ of electricity that passes a given point

in one second when the current strength is one ampere. In other words a

coulomb is one _ampere second_.

[Illustration: Fig. 545.--Gas voltameter for determining the strength of

current by the volume of gas evolved. To use, connect up as shown in the

illustration. Adjust so that the zero position of the burette is about

one-half inch below the level of the top of the U tube. Pour acidulated

water into the mouth of the burette till the water in the U tube is about

one-half inch from the top. With the electrodes inserted through the

corks, _carefully_ place each one in position by giving a slight twist to

the right as the cork enters. The water level in the U tube and burette

should now be the same, or further adjustment must be made to attain this

result. The level in the burette does not necessarily have to correspond

with the zero graduation, but must not be below it. Unclamp the burette

and hold it nearly horizontal. The liquid will not run out if the corks

be tight, so that this is the _air leakage test_. Attach the connectors

and wires from the current source (which should have a pressure of 2 or

more volts) placing a switch in the circuit. When the switch is closed,

bubbles of gas will rise in the U tube from both electrodes, displacing

the water and forcing it up the burette. Hydrogen will be liberated over

the negative electrode, and oxygen over the positive electrode in the

proportion of twice as much hydrogen as oxygen. To calculate the current

strength, _divide the volume of gas liberated by the time in seconds, and

by the volume of gas liberated (in cubic centimeters) by one ampere in one

second and by .1733_; that is: amperes = volume of gas liberated ÷ (time

in seconds × .1733).]

EXAMPLE.--If an arc lamp require a current of 8 amperes, how much

electricity does it consume per hour?

Since one coulomb = one ampere second, the quantity of electricity

consumed per hour is

8 amperes × ( 60 × 60 ) = 28,800 coulombs.

Voltameter.--A voltameter is an electrolytic cell employed to measure

an electric current by the amount of chemical decomposition the current

causes in passing through the cell. There are two classes of voltameter:

1. Weight voltameters;

2. Gas voltameters.

Ques. What is the difference between these two classes of voltameter?

Ans. In one, the current strength is determined by the weight of metal

deposited or weight of water decomposed, and in the other by the volume

of gas liberated.

Fig. 544 shows a weight voltameter and fig. 545 a gas voltameter.

Ques. How should the plates of a weight voltameter be treated before use?

Ans. They must be thoroughly cleaned and polished with sandpaper, the

sand being afterwards removed by placing them in running water. _The

fingers must not be placed on any part of the plate which is to receive

the deposit._

Ques. What form of voltameter has been selected to measure the

International ampere?

Ans. The silver voltameter arranged as here specified:

The cathode on which the silver is to be deposited shall take the form

of a platinum bowl, not less than 10 cms. in diameter, and from 4 to

5 cms. in depth.

The anode shall be a disc or plate of pure silver some 30 sq. cms.

in area, and 2 or 3 cms. in thickness. This shall be supported

horizontally in the liquid near the top of the solution by a silver

rod riveted through its center.

To prevent the disintegrated silver which is formed on the anode

falling upon the cathode, the anode shall be wrapped around with pure

filter paper, secured at the back by suitable folding.

The liquid shall consist of a neutral solution of pure silver nitrate

containing about 15 parts by weight of the nitrate to 85 parts of

water.

Ques. What is the value of the International ampere as measured with the

silver voltameter?

Ans. The International ampere is represented sufficiently well for

practical use by the unvarying current which, when passed through a silver

voltameter (as described above) deposits _silver at the rate of .001118

gramme per second_.

[Illustration: Fig. 546.--Single contact and short circuiting key. This

key is intended especially for use with D'Arsonval galvanometers in zero

deflection methods. The key is connected in circuit with the galvanometer

so that whenever the key is not depressed, the galvanometer is short

circuited, and its oscillations quickly damped out by the currents induced

in its coil. The back end of the spring is held in a slot in a rubber

block attached to the base.]

Ohm's Law and the Ohm.--The various tests here described depend for their

truth upon the definite relation existing between the electric current,

its pressure, and the resistance which the circuit offers to its flow.

This relation was fully investigated by Ohm in 1827. Using the same

conductor, he proved not only that the current varies with the pressure,

but that it varies in direct proportion.

Ohm's law has already been discussed in a previous chapter and the several

ways of expressing it are repeated here for convenience:

volts

1. Amperes = -------;

ohms

2. Volts = amperes × ohms;

volts

3. Ohms = ---------.

amperes

Various values have been assigned, from time to time, to the ohm or unit

of resistance, the unit in use at the present time being known as the

_International ohm_. This was recommended at the meeting of the British

Association in 1892, was adopted by the International Electrical Congress

held in Chicago in 1893, and was legalized for use in the United States

by act of Congress in 1894. The International ohm in graphically defined

in fig. 548. The previous values given to the ohm which were more or less

generally accepted are as follows:

The Siemens' Ohm.--A resistance due to a column of mercury 100 cm. long

and 1 sq. mm. in cross section at 0° C.

B. A. (British Association) Ohm.--A resistance due to a column of mercury

approximately 104.9 cm. long and 1 sq. mm. in cross section at 0° C.

Legal Ohm.--A resistance due to a column of mercury 106 cm. long and

1 sq. mm. in cross section at 0° C. This unit was adopted by the Paris

conference of 1884.

OHM TABLE[A]

| | Inter-| | | |

| Date |national| Legal|B. A. |Siemens'|

| | Ohm| Ohm|Ohm | Ohm|

-------------------------+------+--------+--------+--------+--------|

International Ohm |1893-4| 1.0000| 1.0028| 1.0136| 1.0630|

Legal Ohm | 1884 | .9972| 1.0000| 1.0107| 1.0600|

B. A. Ohm | 1864 | .9866| .9894| 1.0000| 1.0488|

Siemens' Ohm | | .9407| .9434| .9535| 1.0000|

[A] NOTE.--In the above table to reduce, for instance, British Association

ohms to International ohms, multiply by .9866, or divide by 1.0136; to

reduce legal ohms to International ohms, multiply by .9972, or divide by

1.0028, etc.

[Illustration: Fig. 547.--Double contact key. It is of especial value in

connection with a Wheatstone bridge. When used with the latter it forms

a combination battery and galvanometer key. The battery is wired to the

top leaves of the key and the galvanometer to the lower leaves. Hence,

when operated, the battery circuit will be closed before the galvanometer

circuit, as it is desirable to avoid undue disturbance of the needle.]

[Illustration: Fig. 548.--The international ohm. It is defined as the

resistance of 14.452 grammes of mercury in the form of a column of uniform

cross section 106.3 centimeters in length, at a temperature of 0° C. This

is approximately equivalent to a column 106.3 cm. long, having a uniform

cross section of 1 sq. mm. In the figure the international ohm is defined

graphically. The resistance of the external circuit and the standard one

volt cell is assumed to be zero.]

[Illustration: Fig. 549.--Leeds and Northrup one ohm standard resistance

(Reichsanstalt form); adjusted at 20° C. Low resistance standards may be

properly divided into two classes: 1. those which are designed primarily

as resistance standards, and 2. those designed as current carrying

standards. Those of the first mentioned class are often used to measure

currents up to their capacity. The above standard has both pressure and

current terminals. The binding posts for the former are mounted on high

posts so as to be easily accessible when the standard is immersed in

oil. When used as a resistance standard of precision, it should not be

subjected to a current of more than one ampere, and when used as a current

carrying standard of lesser accuracy, a current of 2 or 3 amperes may be

used.]

Practical Standards of Resistance.--The column of mercury as shown in fig.

548, is the recognized standard for resistance, however, in practice, it

is not convenient to compare resistances with such a piece of apparatus,

and therefore secondary standards are made up and standardized with a

great degree of precision. These secondary standards are made of wire.

The material generally used being manganin or platinoid.

[Illustration: Fig. 550.--Direct deflection method of testing

resistances; a useful and simple method which may be used in numerous

tests. Galvanometer readings are taken through the known, and unknown

resistances, and the current being proportional to the deflections, the

value of the unknown resistance is easily calculated.]

Resistance Measurement.--_Resistance is that which offers opposition to

the flow of electricity._ Ohm's law shows that the strength of the current

falls off in proportion as the resistance in the circuit increases. This

gives a basis for measuring resistance.

There are various methods by which an unknown resistance may be measured,

as by the:

1. Direct deflection method;

2. Method of substitution;

3. Fall of potential method;

4. Differential galvanometer method;

5. Drop method;

6. Voltmeter method;

7. Wheatstone bridge method.

Direct Deflection Method.--This method is based on the fact that the

greater the current through a galvanometer the greater the deflection of

the needle; it is a simple method and is capable of extended application.

The apparatus required consists of battery, galvanometer, known

resistance, and double contact key. The connections are made as in fig.

550. The known resistance is put in circuit with the galvanometer and

after noting the deflection, the key is moved so as to cut out the known

resistance and throw into circuit the unknown resistance. The deflection

of the galvanometer is again noted and compared with the first deflection.

[Illustration: Fig. 551.--Charge and discharge key, adapted to condenser

testing where the condenser is to be alternately charged and discharged.

The insulated handle enables the key to be used without insulating the

body.]

[Illustration: Fig. 552.--Pohl commutator. This is equivalent to a two

pole double throw switch. The depressions in the base are filled with

mercury into which the contacts dip in closing the circuit.]

If the deflections be proportional to the current, the unknown resistance

will be as many times the known resistance as the deflection with

the known resistance is greater than the deflection with the unknown

resistance.

Method of Substitution.--This is the simplest method of measuring

resistance. The resistance to be measured is inserted in series with a

galvanometer and some constant source of current, and the galvanometer

deflection noted. A known adjustable resistance is then substituted for

the unknown and adjusted till the same deflection is again obtained. The

value of the adjustable resistance thus obtained is equal to that of the

resistance being tested.

[Illustration: Fig. 553.--Substitution method of testing resistances.

The connections and apparatus are the same as in fig. 550, except that

a resistance box is used in place of the known resistance. In making the

test, first note deflection with unknown resistance in circuit, then press

key so that the current will pass through the resistance box, and adjust

the resistance in the box so that the deflection of the galvanometer is

about the same as with the unknown. Now switch from one circuit to the

other, changing the resistance in the box until equal deflections are

obtained. When this obtains, the resistance in the box is the same as the

resistance being tested.]

Ques. What kind of adjustable resistance is used in making the above test?

Ans. A resistance box.

Ques. Describe a resistance box.

Ans. It consists of a box containing numerous resistance coils with their

ends connected to terminals and provided with plugs so that they may be

thrown into or out of circuit at will, thus varying the resistance in the

circuit.

[Illustration: Fig. 554.--Ordinary resistance box. It contains sets of

standard resistances consisting of coils of insulated wire having low

conductivity and small temperature coefficient. The ends of the coils are

joined to the section of the bar between the plugs. The insertion of a

plug cuts out a coil. In using, care should be taken to put the plugs in

with a slight twist so that there shall be no resistance introduced by

poor contact.]

Fall of Potential Method.--This is a very simple method of measuring

resistances, and one that is convenient for practical work in electrical

stations because it requires only an ammeter, voltmeter, battery and

switch--apparatus to be found in every station. The connections are made

as shown in fig. 555.

In making the test the ammeter and voltmeter readings are taken at

the same time, and the unknown resistance calculated from Ohm's law.

Accordingly, since:

(1) amperes = volts / ohms

solving for the resistance,

(2) ohms = volts / amperes

[Illustration: Fig. 555.--Fall of potential method of testing resistances;

a convenient method for testing at stations, requiring only the usual

instruments to be found at a station. The resistance of the voltmeter must

be very high, otherwise the test must be made as in fig. 556.]

EXAMPLE.--If in fig. 555 the readings show 6 volts and 2 amperes how many

ohms is the resistance being tested?

Substituting in formula (2)

ohms = 6/2 = 3

Ques. Can this test be made with any kind of voltmeter?

Ans. Its resistance must be very high to avoid error. When a voltmeter

having small resistance is used, it should be connected so as to measure

the fall of pressure across both ammeter and unknown resistance as shown

in fig. 556.

[Illustration: Fig. 556.--Fall of potential method of testing resistances;

diagram showing connections for testing with low resistance voltmeter.

The resistance measured with this connection will be the sum of the

resistances of the coil and the ammeter. The resistance of the ammeter is

usually known and can be subtracted from the sum to obtain the required

resistance.]

Differential Galvanometer Method.--This is what is known as a _nil_ or

zero method, that is, a method of making electrical measurements in which

comparison is made between two quantities by reducing one to equality with

the other, the absence of deflection from zero of the instrument scale

showing that the equality has been obtained.

The test is made with a differential galvanometer, and resistance box

connected as in fig. 557. The current then will divide so that part of

it flows through the resistance being tested and around one set of coils

of the galvanometer while the other part will flow through the resistance

box and the other set of coils as indicated. When the resistance box has

been so adjusted that its resistance is the same as the unknown resistance

the current in the two branches will be equal, and the needle of the

galvanometer will show _no deflection_.

[Illustration: Fig. 557.--Differential galvanometer method of testing

resistances. In making the test, the resistance box is adjusted till the

galvanometer needle shows no deflection. When this condition obtains,

the resistance in circuit in the resistance box is equal to the unknown

resistance, hence, a reading of the box gives the value of the unknown

resistance.]

Ques. What name is given to this method of testing?

Ans. It is called a _zero_ method, distinguishing it from _deflection_

methods.

Ques. For what kind of resistance is the method adapted?

Ans. Since it is a nil or zero method, it is better adapted to the

measurement of non-inductive than of inductive resistances.

Ques. What precaution should be taken with inductive resistances?

Ans. The current must be allowed to flow until it becomes steady to

overcome the influence of self-induction.

Ques. What may be said with respect to the differential galvanometer

method?

Ans. With an accurate instrument it is very reliable.

[Illustration: Fig. 558.--Drop method of testing resistances. The

apparatus is connected as shown and readings taken with voltmeter across

known and unknown resistance. The unknown resistance is then easily

calculated.]

Drop Method.--This is a convenient method, and one which may be used for

measuring either high or low resistances with precision. It is used for

many practical measurements, and requires only a voltmeter, battery, known

resistance and a two way switch.

The instruments are connected as in fig. 558, and in making the test,

the voltmeter is switched into circuit across the known resistance and

then across the unknown resistance, readings being taken in each case.

The value of the unknown resistance, is then easily calculated from the

following proportion:

drop across known resistance known resistance

------------------------------ = ------------------

drop across unknown resistance unknown resistance

from which

unknown known resistance × drop across unknown resistance

resistance = ---------------------------------------------------------

drop across known resistance

[Illustration: Fig. 559.--Leeds and Northrup portable galvanometer

(pointer type A). The sensitiveness of this instrument is such that it may

be substituted in numerous cases for the non-portable reflecting type of

galvanometer; as for instance, in the checking of ammeters and voltmeters

to an accuracy of .2% by the potentiometer method, and on almost all

Wheatstone bridge measurements to commercial accuracies. A current of 2

micro-amperes will cause the pointer to move 1 mm. over the scale, that

is, it has a sensibility of 500,000 ohms. The method of suspending the

moving system is such as to practically eliminate initial friction which

is of value in all zero deflecting methods. The suspensions and moving

system are guarded by springs, which together with the solid construction

of the case render the instrument capable of withstanding rough usage.

Overall dimensions are 5-1/4" × 2-5/8" × 3-1/2"; weight about 3 pounds.]

Ques. What may be substituted for the voltmeter?

Ans. A high resistance galvanometer, whose deflections are proportional

to the current, the value of the deflections being substituted in the

formula.

Ques. What precaution should be taken in making the test?

Ans. The current used should not be strong enough to appreciably heat the

resistance, and if the current be not very steady, several readings should

be taken of each measurement and the average values used in the formula.

Ques. How are the most accurate results obtained?

Ans. By selecting the known resistance as near as possible to the supposed

value of the unknown resistance.

[Illustration: Fig. 560.--Voltmeter method of testing resistances.

Knowing the resistance of the voltmeter, turn switch to the left and from

reading calculate resistance corresponding to one division of the scale.

Turn switch to right and multiply reading by resistance required for

deflection of one division. This gives resistance of voltmeter and unknown

resistance; subtracting from this the resistance of voltmeter gives value

of the unknown resistance.]

Voltmeter Method.--This is a direct deflection method and consists in

determining first the resistance that will deflect the needle through

one division of the scale on a given battery current, then with this

as a basis for comparison the voltmeter is connected across the unknown

resistance whose value is easily calculated from the reading.

In making the test, the instruments are connected as in fig. 560. The

current from battery is first passed through the galvanometer by turning

switch as shown.

[Illustration: Fig. 561.--Megohm box or set of standard high resistances.

The box contains five resistances of 200,000 ohms each. The six pillars

are petticoat insulated, the resistances being placed between each pair

of pillars. There is a double contact post on top of each pillar so that

these can be connected together with copper links.]

Assuming that the resistance of the instrument is 8,000 ohms and that

the current deflects the needle through 10 divisions of the scale,

then for a deflection of one division the resistance is

8,000 × 10 = 80,000 ohms.

Accordingly, if, when the switch is moved to the right, connecting the

voltmeter across the unknown resistance, the needle be moved through

6 divisions of the scale, the combined resistance of the voltmeter

and unknown resistance is

80,000 ÷ 6 = 13,333-1/3 ohms,

and subtracting the resistance of the voltmeter, the value of the

unknown resistance is

13,333-1/3 - 8,000 = 5,333-1/3 ohms.

Ques. For what kinds of test is the voltmeter method best adapted?

Ans. For measuring high resistances, as the insulation of wires, etc.

Ques. What may be said with respect to the current used?

Ans. Its voltage should be as high as possible within the limits of the

voltmeter scale.

[Illustration: Fig. 563.--Standard resistance box: 100,000 ohms, in four

units of 10,000, 20,000, 30,000, and 40,000 ohms. An "infinity" plug

separates each coil from the ones adjacent. Segments are elevated from

the hard rubber top by special washers in order to increase insulation.

Binding posts are so arranged as not to be in the way when plugs are used.]

[Illustration: Fig. 562.--Standard high resistance box: 100,000 ohms. It

is mounted in a brass box with a hard rubber top. Connections should be

made to terminals marked 3 and 4. When the flexible cord is on plug 1,

the box is short circuited, but when on plug 2, the resistance of 100,000

ohms is in series. The box is especially suited to rapid cable testing.]

Ques. In testing cable insulation what is desirable with respect to

voltmeter and current?

Ans. A low reading voltmeter should be used in connection with a large

battery.

[Illustration: Fig. 564.--Diagram showing principle of Wheatstone's

bridge. A, B, C, and D, are the four members which constitute the bridge.

The current from the battery divides at P, part traversing DC, and part

traversing BA. The galvanometer connected to M and N will indicate when

the currents are equal in the two branches by giving _no_ deflection.

This is then a _zero_ or _nil method_ of testing. The resistances and keys

required in testing are shown in fig. 565. In the actual instrument, the

members A, B, C, and D are known by the names given in the figure.]

Wheatstone Bridge Method.--For accurate measurements of resistance this

method is almost universally used. The so-called "Wheatstone" bridge was

invented by Christie, and improperly credited to Wheatstone, who simply

applied Christie's invention to the measurement of resistances.

[Illustration: Fig. 565.--Diagram showing arms of Wheatstone bridge,

resistances and method of connecting galvanometer, battery and unknown

resistance.]

The bridge consists of a system of conductors as shown in fig. 564. The

circuit of a constant battery is made to branch at P into two parts, which

re-unite at Q, so that part of the current flows through the point M,

the other part through the point N. The four conductors A, B, C, D, are

spoken of as the _arms_ of the balance or bridge. It is by the proportion

existing between the resistances of these arms that the resistance of

one of them can be calculated when the resistances of the other three

are known. When the current which starts from the battery arrives at P,

the pressure will have fallen to a certain value. The pressure in the

upper branch falls again to M, and continues to fall to Q. The pressure

of the lower branch falls to N, and again falls till it reaches the value

at Q. Now if N be the same proportionate distance along the resistances

between P and Q, as M is along the resistances of the upper line between

P and Q, the pressure will have fallen at N to the same value as it has

fallen to at M; or, in other words, if the ratio of the resistance C to

the resistance D be equal to the ratio between the resistance A and the

resistance B, then M and N will be at equal pressures. To find out if

this condition obtain, a sensitive galvanometer is placed in a branch wire

between M and N which will show _no_ deflection when M and N are at equal

pressure or when the four resistances of the arms "balance" one another

by being in proportion, thus:

(1) A:C = B:D

If, then, the value of A, B, and C be known, D can be calculated. The

proportion (1) is reduced to the following equation before substituting.

D = BC/A

For instance, if A and C be, as in fig. 565, 10 ohms and 100 ohms

respectively, and B be 15 ohms, D will be (15 × 100) ÷ 10 = 150 ohms.

[Illustration: Fig. 566.--Diagram showing usual arrangement of resistances

in arms of Wheatstone's bridge. In practice the bridge is seldom or never

made in the lozenge shape of the diagrams, figs. 564 and 565, these being

given merely for clearness. The resistance box of fig. 554 is, in itself,

a complete "bridge," the appropriate connections being made by screws at

various points. The letters in the above diagram correspond with those in

figs. 564 and 565, and the three figures should be carefully compared.]

As constructed, Wheatstone bridges are provided with some resistance

coils in the arms A and C, as well as with a complete set in the arm

B. The advantage of this arrangement is that by adjusting A and C, the

proportionality between B and D can be determined, and can, in certain

cases, be measured to fractions of an ohm. In fig. 565 resistances of 10,

100, and 1,000 ohms are included in the arms A and C.

[Illustration: Fig. 567.--Standard resistance box and Wheatstone bridge.

This pattern is a modification of the Anthony form of bridge. All the

resistances are wound upon metal spools. The bridge ratio coils are 1, 10,

100, 1,000, 10,000. The rheostat coils are arranged in five rows, of ten

coils each. The ordinary decade plan (explained in fig. 570) is followed.

The coils may be joined in series in multiple, or in any combination of

series and multiple. The coils may thus be checked against each other in

many combinations. For instance, all the ten ohm coils taken in parallel

may be compared with any one ohm coil. The precision of adjustment is said

to be 1/20th of 1% for the coils of the tenth ohm series, and 1/50th of 1%

for the coils of the rheostat. The ratio coils are certified to be like

each other to within 1/100th of 1%. The box is supplied with battery and

galvanometer keys of substantial construction.]

Ques. Describe the method of testing with the bridge.

Ans. Fig. 567 illustrates the general arrangement of resistances to

be found in an ordinary bridge. The connections are made as shown. In

testing, first _depress_ the battery key, then _tap_ the galvanometer key.

This should be repeated adjusting the resistances till no deflection is

obtained. The resistance then in the arm B × (C ÷ A) will give the value

of the unknown resistance.

[Illustration: Fig. 568.--Ratio coils of Wheatstone bridge. Almost every

box intended to serve as a Wheatstone bridge is furnished with a set of

coils which forms the arms of proportion or ratio arms of the bridge.

There is a choice of several different ways of arranging these coils. The

figure shows the simplest arrangement, which is employed in boxes not

intended for the highest accuracy. The required ratio, as for instance

1:100, is obtained by withdrawing a plug from each arm A and B. Ratios

1/1, 1/10, 1/100, 10/100, etc., or 1,000/1, 1,000/10, 1,000/100, 100/100,

etc., are obtainable in this manner. This simple arrangement is open

not only to the objection that the contact resistance of the plugs which

remain in is always included with the resistance unplugged, but also to

all other objections to be urged against the use of many plugs where a few

will do. The method has the limitation that it is not possible to reverse

the arms of the bridge, that is, to transpose the arms A and B.]

Ques. Why should the battery key be depressed before the galvanometer key?

Ans. To avoid the sudden swing of the galvanometer needle, which occurs

on closing circuit in consequence of self-induction.

Ques. How is it known whether too much or too little resistance be

unplugged?

Ans. The galvanometer needle will be deflected to one side for too much

resistance, and to the opposite side for too little resistance.

[Illustration: Fig. 569.--Method of reversing arms of Wheatstone bridge

with reversing blocks. The arrangement shown in the figure is classical,

being that used in the English post office type of Wheatstone bridge. It

is open to the objections which apply to the use of several plugs, one of

which is withdrawn to obtain the desired resistance.]

Ques. What is the meaning of "Inf.," marked on the bridge?

Ans. It stands for "infinity," because the resistance coil at the point

marked infinity is omitted so that adjacent sections of the arm are

disconnected when the plug is taken out.

In fact, the air gap interposed by the removal of the plug by no means

provides an infinitely great resistance, but is usually called such

because it is vastly greater than any of the other resistances of the

bridge.

[Illustration: Fig. 570.]

[Illustration: Figs. 570 and 571.--Diagrams illustrating the decade plan

of combining resistance coils. In this method the coils are connected

in series and the arrangement avoids the disadvantage of the ordinary

Wheatstone bridge in that the latter requires a large number of plugs to

short circuit the resistances not in use, which introduces an element

of uncertainty as to resistance of the plug contacts and the necessity

of adding up the values of all the unplugged resistances in order

to determine the total resistance in circuit. The necessary regular

succession of values in a rheostat built on the decade plan can be

obtained with either nine or ten coils per decade. The chief reason for

using the latter number is found in the facility with which all the coils

of one decade can be compared with one coil of the next higher decade,

thus permitting the coils of a rheostat to be checked among themselves.

Thus, the ten 1 ohm coils can be checked with a 10 ohm, the ten 10's

with a 100, etc. In some sets the ten coils of a decade can be connected

in series or in parallel, and it then becomes an advantage to have ten

coils to a decade, since the coils in one decade in parallel equal one of

the coils of the next lower decade. When these latter advantages are not

required, and especially when dials or sliding switches are used, there is

little or no advantage in using more than nine coils per decade, as shown

in fig. 570. Here all the coils of the set are connected in series so that

the circuit is never open. Thus it is a slight advantage to have permanent

connections _a_, _b_, and _c_, because all the coils of a decade can be

thrown in circuit by simply pulling out a plug, it not being necessary to

insert it again, as would be the case if the _a_, _b_, and _c_ connections

were not used. Moreover, if any plug make bad contact, its effect is

somewhat lessened by having this bad contact shunted by the remaining

coils of the decade. Again, there are occasions where violent deflections

of a galvanometer are prevented by not having the circuit entirely open

when a plug is taken out.]

The Decade Plan.--In this method of combining resistance coils, there are

9 or 10 one ohm coils for the units place, 9 or 10 ten ohm coils for the

tens place, 9 or 10 one hundred ohm coils for the hundreds place and so

on. Each series of coils of the same value is designated a _decade_. The

connections are usually made as shown in figs. 570 and 571.

It is apparent from the figure that any value in any one decade can

be obtained by inserting between a bar and a block, only one plug;

moreover if several decades be in series, any value up to the limit

of the set can be read off directly from the position of the plugs

without having to add up the unplugged resistance as in the ordinary

arrangement.

[Illustration: Fig. 572.--Two plug arrangement of ratio coils. Each of the

ratio coils has one of its terminals connected to a common center which

corresponds to the block marked C in the figure. The other terminal of

each coil is connected to an individual block, there being one block for

each coil. The bar B on one side of these blocks is joined to the rheostat

and the bar A on the other side to an X post. In the ordinary use of this

set of ratio coils two plugs only are used. One plug is inserted between

the bar A and one of the blocks, 1, 1', 10, 10', etc., of the central row

of blocks. The other plug is inserted between the bar B and any one of

the other blocks of the central row. There are two ratio coils of each

value. To obtain an even ratio as 1,000 to 1,000', one plug is inserted

between the block 1,000 and the bar A, and the other plug between the

1,000 block and bar B, the ratio arms are reversed; that is, the 1,000 ohm

coil is connected to the X post and the 1,000 ohm coil to the end of the

rheostat. When uneven ratios are used, the same ratio can be obtained by

four different combinations. To obtain the ratio one to ten, insert a plug

between A and 1, and another between B and 10, or between A and 1', and B

and 10, and get 1:10, or between A and 1, and B and 10', and get 1:10', or

again, between A and 1' and B and 10', and get 1' to 10'. Other ratios are

obtained in a similar manner. By using more than two plugs and connecting

certain of the coils in parallel combinations, a large number of other

ratios may be obtained. This arrangement offers a convenient method of

measuring the sensibility of a bridge and galvanometer combination that is

frequently applicable. If for instance the one ohm coil is used on either

side after a balance has been obtained the one ohm may be shunted with the

1,000 ohm on the same side. This will make a variation of 1/10 of 1% and

the galvanometer deflection may be noted for this variation. Similarly,

the 1 ohm may be shunted with the 100 for a variation of 1%, or with the

10,000 for a variation of 1/100 of 1%. The ten ohm coil may be shunted

with the 1,000 for a variation of 1% and with the 10,000 for a variation

of 1/10 of 1%. In the arrangement of ratio coils, errors due to plug

contacts are negligible because only two plug contacts enter the circuit,

and with an even ratio, it is only the difference in the resistances of

the two plug contacts that can affect the result. In measuring any of the

ratio coils while in the box it is only necessary to connect to the bar

C and to either the bar A or B and plug in the coils to be measured.]

[Illustration: Fig. 573.]

[Illustration: Figs. 573 and 574.--The Leeds and Northrup decade. The

object of this arrangement is to reduce the number of coils required. In

fig. 573, the 1, 3', 3 and 2 are connected in series. Let the terminals

of the 1 ohm and 2 ohm coils be numbered (1), (2), (3), (4) and (5) (fig.

573). The current enters at point (1) and leaves the coils at the point

(5), traversing 1, 3', 3, 2 = 9 ohms in all. If this series be multiplied

by any factor _n_, then _n_ (1 + 3' + 3 + 2) = _n_ 9 ohms. It will be

seen that if the points (1) and (5) be connected, all the coils are

short circuited, and the current will traverse zero resistance. If the

points (2) and (5) be connected, the 3', 3 and 2 ohm coils will be short

circuited and the current will traverse 1 ohm. By extending the process so

as to connect two and only two points at a time it is possible to obtain

the regular succession of values n (0, 1, 2, 3, 4, 5, 6, 7, 8, 9), the

last being obtained when no points are connected. Fig. 574 shows Leeds and

Northrup's method of connecting these points two at a time with the use of

a single plug. The circles in the diagram represent two rows of ten brass

blocks each. To the first two blocks at the top of the rows, the points

(5) and (1), fig. 573, are connected; to the second two, the points (2)

and (5) are connected, etc., no points being connected to the last pair

of blocks. Hence, if a plug be inserted between blocks 1 and 5, fig. 575,

the points (1) and (5) of diagram fig. 573 are connected, giving the value

of 0, if between the blocks 2 and 5 the points (2) and (5) are connected,

giving the value 1, and so on. The value 9 is obtainable when the plug is

in the last pair of blocks, which have no connections. Fig. 572 shows a

top view of the blocks of a simple decade constructed upon this plan.]

Ques. What other advantages are gained with the decade arrangement?

Ans. The single plug used with each decade is never out of use, being

either in the zero position or set on some value, and is therefore not

easily lost by being laid aside. The use of only one plug in a decade

makes it easy to ascertain that the plug is making good contact as only

one block in a row is plugged at a time, the other blocks are not kept

under a strain by having plugs forced tightly between them.

This strain on the blocks, which always exists in those sets in which

a resistance is thrown in by removing a plug, tends to separate or

loosen them and often to warp the hard rubber upon which they are

mounted. Another advantage of the decade plan is that it permits

obtaining a succession of values by means of sliding contacts or dial

switches, a method which is becoming deservedly more appreciated.

[Illustration: Fig. 575.--Leeds and Northrup dial Wheatstone bridge.

Rotating switches are used instead of plugs, which permits quicker

adjustment of the resistances, adapting it to rapid working. The ratio

coils are arranged as in fig. 568. There are four dials which form the

rheostat. The units dial contains 9 one ohm coils; the tens dial, 9 ten

ohm coils; the hundreds dial, 9 one hundred ohm coils, and the thousands

dial 9 one thousand ohm coils. The values of the ratio coils are 1, 1,

10, 10, 100, 100, 1,000, 1,000, 10,000, 10,000.]

Ques. What is the difference between "plug out" and "plug in" types of

resistance box?

Ans. In the plug out type, resistance is put in the circuit by removing

plugs, as in fig. 565; in the plug in type, resistance is put in the

circuit by inserting plugs as in figs. 570 and 571.

[Illustration: Fig. 576.--Queen Acme portable testing set. It consists

of a Wheatstone bridge, with reversible arms, battery of four dry cells,

D'Arsonval galvanometer, battery and galvanometer keys. There are sixteen

resistance coils, having a combined resistance of 11,110 ohms. Each

bridge arm is provided with three coils of 1, 10, 100 ohms, and 10, 100,

1,000 ohms respectively. The commutator admits of a ratio of 1 to 1,000

on either bridge arm, giving the set a theoretical range from .001 of an

ohm to 11,110,000 ohms. For resistances above 1,000,000 ohms, the normal

battery power must be increased. The contact keys are located as shown.

The battery key has single contact, but the galvanometer key has double

contact; depressing it closes the galvanometer circuit, and releasing it

short circuits the galvanometer, bringing the latter quickly to rest.]

Testing Sets.--For convenience in testing, a combination of the

instruments used is put up in a neat and substantial case, and known

as a testing set. There are innumerable forms of testing set, a few of

which are shown in the accompanying illustrations. The usual combination

is a Wheatstone bridge, galvanometer, battery and necessary keys and

connections.

[Illustration: Fig. 577.--Connections and circuits of Queen acme portable

testing set. There are three rows of blocks, LL', MM', NN'. LL is

connected to NN' by means of a heavy copper bar, joining L' and N'. LL'

and NN' constitute the rheostat, from which any resistance from 1 ohm

to 11,110 ohms may be obtained by removing the proper plugs. The block

N of the rheostat is connected to the lower line post D. The upper line

post C is connected to the block X of the commutator. The block C has no

other permanent connection, except key G. The block R of the commutator

is connected to the block L of the rheostat, and has no other connection,

excepting by plugs. Each half of MM' constitutes a bridge arm, designated

A and B respectively. Beginning at the lower line post D, the connections

form a continuous circuit through the rheostat, thence through the bridge

arm B, thence through the bridge arm A, thence to the upper line post

C. The commutator serves merely to reverse the bridge arms A and B. The

battery terminals are connected as shown: the positive terminal directly

to the common junction of the two bridge arms, and the negative terminal

through the battery key to the rheostat. The positive terminal of the

galvanometer is connected through the galvanometer key with the block X,

and the negative terminal with the block R of the commutator or what is

equivalent, with the block L of the rheostat. The commutator blocks A, B,

R and X, are connected by plugs as shown. When the commutator plugs are

in the position PQ, the bridge arm B is connected to the rheostat and the

bridge arm A is connected to the line, the ratio between the bridge arms

ratio being A ÷ B = X ÷ R but when the plugs are in the position ST, the

bridge arms are reversed in position A, being connected with the rheostat

and B, with the line, and the bridge arm ratio becomes A ÷ B = R ÷ X. The

connections of the testing set may be more readily understood from the

simplified diagram fig. 578.]

[Illustration: Fig. 578.--Simplified diagram showing connections of Queen

Acme portable testing set.]

Ques. Describe the operation of the Queen Acme testing set figs. 576 and

577, in measuring resistance.

Ans. Connect the terminals of the resistance to be measured to the line

posts C and D. Place the battery connections on the two upper tips 0 and

1, thus throwing one end of the battery into circuit, which is sufficient

until an approximate balance is obtained. Employ the 100 ohm coil in each

bridge arm, and place the commutator plugs in the position PQ, or in the

position ST. Then remove plugs from the rheostat until the value of total

resistance employed, or nearly as may be guessed is equal to that of the

unknown resistance. Now press the battery key Ba, and holding it down

momentarily, press the galvanometer key Ga. If the galvanometer needle

swing to the right toward the symbol + the resistance employed in the

rheostat is too high and must be reduced. If the needle swing to the left

toward -, the resistance employed is too low and must be increased. By

altering the resistance of the rheostat accordingly, a value will soon be

found, which when varied slightly either way, will reverse the deflection

of the galvanometer needle. Now remove the battery connection from tip 1,

and place it on the tip 4, thus throwing the whole battery into circuit.

Then press the keys again as before, first the battery key, then the

galvanometer key. This will increase the deflection of the galvanometer

needle for the same variation in the rheostat, thus enabling the making

of a more accurate adjustment. The measurement thus made will be the

best result that can be obtained with bridge arms of equal value, but by

selecting more suitable values of the two arms from the following table

of bridge ratios a much higher degree of accuracy may be obtained.

[Illustration: Fig. 579.--Diagram of the Queen dial decade portable

testing set. Its dimensions are 9-1/2" long, 7" wide and 7" deep, and

weighs 11-1/2 pounds. The resistances are arranged upon the dial decade

plan, being placed in circuit by means of a rotating switch contact. The

switches are so constructed that they may be turned in either direction,

thereby permitting them to be turned quickly from the highest resistance

in any dial to the lowest resistance in the same dial. This arrangement

avoids the necessity of turning back through all the remaining resistances

in any particular group of coils and is of value in locating swinging

crosses or conditions of momentary balances. The connections for the

various tests are made by the manipulation of one small knife switch

(W.B.--M.L.) and the switch BA.; these are plainly lettered, thus avoiding

the necessity of referring to a diagram of connections. In construction,

the dial switches are made up of eight laminations of No. 28 B. & S.

phosphor bronze, and the form is such as to prevent wearing grooves on

the top of the contact studs. In this instrument the electrical circuits

are soldered throughout excepting the switch contact whose resistance is

negligible. The resistances are wound with manganin. The battery comprises

six cells sub-divided which are easily replaceable. The galvanometer

is the same as in the Queen acme set, but has the addition of an Ayrton

shunt, which is useful in making insulation measurements. The necessary

keys, binding posts, and switches are provided so as to facilitate the use

of the instrument for the various measurements that can be made with it.]

Table Showing the Best Values of Bridge Arms for Measuring any

Desired Resistance

| | Position of|

| Best Values of| Commutator|

| | Plugs as|

Value of Resistance being measured | | | shown in|

| A = | B = | fig. 582|

--------------------------------------+-------+-------+------------|

Below 1.5 ohms | 1| 1,000| PQ|

Between 1.5 and 11 ohms | 1| 100| PQ|

" 11 and 78 ohms | 10| 100| PQ|

" 78 and 1,100 ohms | 100| 1,000| PQ|

" 1,100 and 6,100 ohms | 100| 100| PQ or ST|

" 6,100 and 110,000 ohms | 1,000| 100| ST|

" 110,000 and 1,110,000 ohms | 1,000| 10| ST|

" 1,110,000 and 11,110,000 ohms | 1,000| 1| ST|

Ques. In testing with the Queen Acme set how should the plugs be placed

in the commutator?

Ans. Always make the arm A the smaller except when the two arms are of

equal value.

Ques. If the resistance being measured is higher than 6,100 ohms, or lower

than 1,100 ohms, how should the commutator plugs be placed?

Ans. If higher than 6,100 ohms, they should be placed in the position ST;

if lower than 1,100 ohms, in position PQ.

When the plugs are placed in the ST position, the unknown resistance

is found by dividing the value of the larger bridge arm by that of the

smaller, and multiplying the total employed resistance in the rheostat

by the quotient. When the plugs are placed in the PQ position, the

employed resistance in the rheostat is divided by the quotient.

[Illustration: Fig. 580.--Queen portable silver chloride testing battery.

The silver chloride cell has the advantage of long life, light weight,

and compactness. The pressure of each cell when new is .8 volt.]

Direct Deflection Method with Queen Acme Set.--To measure for instance,

insulation resistance by direct deflection connect a known high

resistance, say 100,000 ohms between the line post C (fig. 577), and the

positive battery post. Remove all plugs from the commutator, and place all

plugs in the rheostat, as any employed resistance in the rheostat will

be in circuit with the galvanometer and the battery. Place the battery

connection so as to throw only one cell into circuit. Now press the keys

and obtain a deflection of the galvanometer needle. For example: assume

that the needle to be deflected about 8 divisions of the scale. Since

this deflection is due to the current from one cell passing through a

resistance of 100,000 ohms, then 100,000 × 8 = .8 megohms represents

the resistance through which one cell will produce a deflection of

one division on the scale. Hence, .8 megohms is the constant of the

galvanometer.

[Illustration: Fig. 581.--Ohmmeter. It consists essentially of a slide

wire Wheatstone bridge, with the scale divided to read either directly

in ohms, or in per cent. of a fixed resistance value. A galvanometer is

mounted on the containing case of each, and battery and galvanometer keys

are provided. In the direct reading type, the scale is so cut that when

the galvanometer is balanced, the pointer of the instrument indicates the

value of the resistance between the X posts. The scale is calibrated for

any desired range. These ohmmeters being slide wire bridges, the greatest

accuracy is at the center of the scale, hence one should be selected that

will bring the part of the scale likely to be the most used at or near the

center. A convenient type is that in which the scale is cut in per cent.,

100 per cent. being at the center of the scale. Fixed coils of 1, 10, 100,

1,000 and 10,000 ohms are contained in the instrument with a plugging

arrangement allowing any one to be used. When a balance is obtained,

the actual resistance is determined by multiplying the dial reading by

the value of the fixed coil in use. This amounts simply to shifting the

decimal point. For instance, if the 100 ohm coil were being used, and the

pointer were at .875, the resistance would be 87.5 ohms.]

Now, replace the known high resistance (100,000 ohms) by the unknown

resistance (for instance such as a cable) the value of which is to be

determined. Add enough cells to produce as large a deflection of the

needle as possible. Assume that 75 cells give a deflection of 1.5 scale

division. Then, the galvanometer constant multiplied by the number of

cells and the product divided by the deflection will give the insulation

resistance of the cable; or

0.8 megohm × 75 cells = 60.0; and

60.0 ÷ 1.5 = 40 megohms

as the resistance of the cable.

[Illustration: Fig. 582.--Commutator plug setting for comparing

electromotive forces by the fall of potential method with Queen acme set.]

Fall of Potential Method with Queen Acme Set.--To compare electromotive

forces by this method, place the battery connection (fig. 577), so as

to throw into circuit all the cells, taking care not to reverse them by

crossing the battery cords. Plug the commutator as shown in fig. 582, and

remove 1,000 ohms from bridge arm B. Place all plugs in arm A. From the

rheostat unplug 5,000 ohms. Then connect one of the cells being tested,

with its positive terminal to the + battery post and its negative terminal

to the line post C.

When the keys are pressed, the galvanometer needle will swing either to

the right or to the left. If it swing toward +, reduce the resistance

in the rheostat; if it swing toward -, add resistance to the rheostat.

When a value is found wherein a variation of an ohm either way reverses

the deflection, add to this value the resistance unplugged in arm B, and

divide the sum by the resistance in arm B. The result gives the ratio

between the voltages of the testing set battery and cell being tested

respectively. The division is decimal and may be readily accomplished by

merely pointing off as many places as there are ciphers in the resistance

employed from arm B. This operation repeated with any number of different

cells, will give their voltages in terms of the voltage of the testing

set battery, and from these ratios their relative values may be readily

obtained.

[Illustration: Fig. 583.--Diagram of apparatus for measuring low

resistances based on the principle of the Kelvin double bridge. In the

diagram AB represents a heavy piece of resistance metal of uniform cross

section and uniform resistance per unit of length; CD is another piece

of resistance metal of smaller cross section, and the two are joined

together by a heavy copper bar, AC, into which both are silver soldered;

LL are the current terminals and PP are the pressure terminals. The

resistance of AB between the marks 0 and 100 on the scale S is .001 ohm.

From the point 1 on the resistance CD to 0 on AB is also .001 ohm, from 2

to 0 is .002 and so on, and from 9 to 100 is .01 ohm. The slider M moves

along the resistance AB and its position is read on the scale S which is

divided into 100 equal parts and can be read by a vernier to thousandths.

Subdivided in this way the resistance between the tap off points PP may

have any value from .001 to .01 ohms by steps of .000001 ohm.]

If the testing set battery be replaced by a standard cell, the first

measurement gives at once the voltage of the cell tested.

If the voltage of the cell or battery being tested exceed that of the

testing set battery, reverse the position of the two batteries, and the

subsequent operations, as outlined above, will give the desired results.

How to check a Voltmeter with the Queen Acme Set.--In using a set as

in fig. 576, first remove about 10,000 ohms from the rheostat, plug the

commutator as shown in fig. 582, remove 100 ohms from the arm B, of the

bridge, and connect a standard cell with the positive terminal to the +

battery post and the negative terminal to the line post C. Then, connect

the circuit to the battery posts of the testing set the positive lead to

the + post and the negative lead to the - post. Now, press both keys and

note the direction of the deflection of the galvanometer needle. If it

move toward +, the rheostat resistance is too high; if toward -, too low.

[Illustration: Fig. 584.--Kelvin bridge. This includes a low resistance

standard of .1 ohm variable by steps of .00001 ohm, a set of ratio coils,

and a holder for rods or wires to be measured, with a scale to measure

their length. It is also provided with heavy flexibles to be used in

measuring the resistances of irregularly shaped pieces. The connections

are clearly shown in the diagram. The range of measurements of this bridge

is: 1 ohm to .1 ohm by steps of .001 ohm readily estimated to .0001; .1

to .01 ohm by steps of .0001 ohm readily estimated to .00001; .01 ohm to

.001 ohm by steps of .00001 ohm, readily estimated to .000001; .001 ohm

down by steps of .00001 ohm, readily estimated to .000001 ohm.]

Change the rheostat resistance accordingly until the balance attained is

such that a very slight variation of the rheostat resistance one way or

the other will reverse the galvanometer deflection. To find the pressure

on the circuit, add 100 to rheostat resistance and point off two places.

Multiply this value by the voltage and the product will be the desired

voltage.

If the voltage of the standard cell be exactly one volt, the total

employed resistance represents the voltage on the circuit.

[Illustration: Fig. 585.--Queen slide wire bridge. It consists of a

portable slide wire, Wheatstone bridge arranged to read directly in ohms

in addition to its use for locating crosses and grounds. It is complete

with battery, galvanometer and telephone receiver. The bridge is balanced

by moving the hand stylus until the galvanometer shows no deflection or

until there is no sound in the telephone receiver. In order to provide a

wide range of measurement and maximum accuracy, ratio coils or multipliers

having values of 1, 10, 100, 1,000 and 10,000 are provided. The scale of

the instrument is arranged in two parts, one of which indicates ohms and

the other is divided into uniform divisions for use when locating crosses

and grounds by the Murray and Varley loop methods. A small induction

coil is included so as to furnish an alternating current when using the

telephone receiver.]

For instance, in making a measurement on a 110 volt circuit, assume

that the employing of 7,840 ohms rheostat resistance produces balance,

and that increasing or decreasing this resistance by two ohms,

reverses the galvanometer deflection. This indication that the setting

7,840 is uncertain, about 1/40 of 1 per cent. Since the rheostat coils

are adjusted to an accuracy of only 1/5 of 1 per cent., that will be

about the accuracy of the measurement.

If the pressure of the standard cell be 1.018 volts, then 7,840 + 100

= 7,940. Pointing off two places, gives 79.40, which multiplied by

1.018 gives 80.82 for the voltage on the circuit.

To Measure Internal Resistance of Cell with Queen Acme Set.--First compare

its voltage on open circuit with the pressure of the testing set battery.

Then, shunt the cell with a known resistance, about 100 ohms, and again

measure its terminal voltage. The difference between the two values thus

obtained, divided by the value of the shunt resistance, will give the

value of the current. To find the internal resistance, multiply the value

of the shunt resistance by the ratio between the first and second measured

values.

[Illustration: Fig. 586.--Evershed portable ohmmeter set. This testing set

consists of a direct reading ohmmeter which indicates by direct reading

the value of the resistance being tested, also a portable hand dynamo

which provides at any required pressure the current necessary to make the

test. It is adapted to the needs of supply stations, wiring contractors

and dynamo builders. It is also useful in testing the insulation of

underground and aerial cables, and is designed so that it can be used by

ordinary workmen who are not experienced in handling delicate instruments

and who, by its use, are able to obtain accurate results. The dynamo is

wound for 100, 200, 500, or 1,000 volts, and is fitted with spring drum

inside the case on which is coiled a twin flexible cord provided with a

connector adapted for clamping under the ohmmeter terminals.]

For instance, assume that the open circuit voltage of the cell being

tested as compared with the voltage of the testing set battery is .212

of the latter, and that when it is shunted with a resistance of 1,000

ohms, its terminal voltage is .179. Then, the total resistance is to

the 1,000 ohms shunt resistance as .212 is to .179 or (.212/.179) ×

1,000 = 1,184, from which deducting the 1,000 ohms shunt resistance,

gives 184 ohms as the internal resistance of the cell.

[Illustration: Fig. 587.--Leeds and Northrup fault finder. A lineman's

instrument for the location of faults, crosses, grounds, and opens in

telephone and telegraph circuits, and for the measurement of conductor

and insulation resistance.]

[Illustration: Fig. 588.--Diagram showing arrangement and connections

of Leeds and Northrup fault finder. It is used to measure conductor

resistance, fault resistance, to locate faults by four different tests,

and when used with a buzzer and telephone, to locate opens. The essential

feature of the instrument is the uniform resistance AB, which lies in a

circle and which has a value of about 100 ohms. By a special construction,

it is so arranged that the contact can be made at any point along it, and

it is therefore equivalent to a very high resistance slide wire. It has

a moving contact C and a uniform scale of 1,000 divisions. In series with

this, there are the two resistances E and R which may be short circuited

by the switches U and V. E has exactly the same resistance as the wire AB.

R has a resistance of 100 ohms, and is the fixed resistance of the bridge

arrangement for resistance measurements. The resistances of 1,000 ohms

and 9,000 ohms connected to the battery post are to protect the battery

and the apparatus from excessive current. The 9,000 ohms may be short

circuited by the switch W.]

Ammeter Test with Queen Acme Set.--Connect a low resistance in series with

the ammeter and run leads from it to the testing set, the positive lead to

the + battery post and the negative lead to the line post C (fig. 577).

Insert a standard cell between the battery posts, with positive terminal to

+ battery post, and negative terminal to - battery post. Plug commutator

as shown in fig. 582. Remove 10,000 ohms from rheostat, and 100 ohms from

bridge arm B. Determine a balance in the usual way by changing the value

of the resistance in the rheostat. This operation will balance the

difference of pressure at the terminals of the shunt resistance against

the standard cell, and its value is equal to

(1.40 × 100) / (R + 100) = 140 / (R + 100)

To determine the current flowing, divide the value of the difference of

pressure thus obtained by the value of the shunt resistance.

[Illustration: Fig. 589.--Resistance measurement with Leeds and Northrup

fault finder. The diagram shows the proper connections and switch settings

for measuring conductor resistance. As in the ordinary slide wire bridge,

the resistance X between the two posts 1 and 2 is obtained from the

formula X = A ÷ (1,000 - A) × R. To avoid the necessity of solving in

each case the fraction A ÷ (1,000 - A), a table is furnished with the

instrument, giving the value of this fraction for each value of A. _The

resistance is accordingly determined in each case by simply setting the

contact C for a balance and reading from the table the resistance opposite

the number corresponding to the scale reading and multiplying by 100,

the value of R._ To use an outside battery, remove the inside battery and

connect the outside battery between the posts Gr and Ba. The pressure of

this battery should not exceed 110 volts. _If it exceed 25 volts, open

switch W._

EXAMPLE--With an unknown resistance connected between the posts 1 and 2,

the galvanometer showed a balance for a dial reading of 387. The number

opposite 387 in the table is .6313; hence, X = .6313 × 100 = 63.13 ohms.]

[Illustration: Fig. 590.--Diagram of the Queen standard potentiometer. The

circuit arrangement is a method of sub-dividing the main potentiometer

wire, MNOPQ, so as to provide for very accurate reading. The secondary

voltage, or that used to supply current to the main potentiometer circuit,

is adjusted by regulating rheostats, "Fast," "Medium," and "Slow" so that

the current flow is exactly .0001 ampere. It is noted that this instrument

requires a very small current for its operation. The instrument is

direct reading for voltage measurements, not exceeding 1.4+. In order to

determine if the current flow through the potentiometer be exactly .0001

ampere, the terminals of the standard cell binding posts are connected

in circuit so that the drop over points between which they are connected

are exactly equal to the voltage of the standard cell used. Binding posts

are provided for connection with various standard cells. The unknown

voltage to be measured is placed in opposition to the current flow in the

potentiometer circuit by connecting to the binding post "XEMF." Observe

that polarity is connected as required. The galvanometer with its shunt

is placed in the standard cell circuit, or X circuit, by means of a

double pole, double throw switch. The switch at T provides for standard

cells of different values and the setting at U allows for temperature

correction. The range of the instrument in volts can be increased by means

of multipliers or volt boxes.]

[Illustration: Fig. 591.]

[Illustration: Fig. 592.]

[Illustration: Fig. 593.]

[Illustration: Figs. 591 to 594.--Diagrams illustrating loop testing. To

properly understand the Murray or Varley loop tests, consider a Wheatstone

bridge (fig. 591) the arms of which are equal. In loop testing, the

rheostat is replaced by a length of cable and the unknown resistance also

by a length of cable, as in fig. 592, both being similar in resistance per

foot. If both lengths be the same, their resistances are the same and the

bridge balances. Now shorten one cable and add resistance in series with

it until the bridge again balances as in fig. 593. The added resistance

equals that of the piece cut off. Hence, if the resistance per foot be

known, the length of the shorter piece can be easily calculated. In the

Murray and Varley tests, the battery circuit is by ground connections

instead of by wire. In the Murray loop the arrangement is similar to fig.

592, the battery circuit being completed by ground connection through

fault in defective cable. Fig. 594 shows the general arrangement of the

Varley loop.]

Loop Test.--This is a method of locating a fault in a telegraph or

telephone circuit when there is a good wire running parallel with the

defective one. In the process, the good and bad wires are joined at their

distant ends and one terminal of the battery is connected to a Wheatstone

bridge, while the other terminal is grounded. There are different ways of

making loop tests as by:

1. The Murray loop;

2. The Varley loop;

3. Special loop.

[Illustration: Fig. 595.--The Murray loop test. The apparatus is connected

as in the figure. The rheostat of the bridge is used in place of the

second arm to permit large adjustment. X and Y are the resistances of the

cable between the fault and the points 1 and 2 respectively.]

The Murray Loop.--In this test only one of the two regular bridge arms

is used, the other being replaced by the rheostat giving an arm of large

adjustment.

The connections are shown in fig. 595. In making the test, close key

and note the deflection of the needle due to pressure of chemical

action at fault, if any. This is called the _false zero_.

Now apply the positive or negative pole of the battery by depressing

the battery key, and balance to the false zero previously obtained

by varying the resistance in arms A or B. Then by Wheatstone bridge

formula: RX=AY, and L=X+Y; Y=L-X, whence

X = A/(R+A)

Y = L(R/(B+A))

[Illustration: Fig. 596.--Murray loop method of fault location with Leeds

and Northrup fault finder. Case I where there are two wires having equal

resistance, in one of which there is a fault. Connect and set switches

as shown; join the good wire to post 1 and the faulty wire to post 2.

The resistance of E is equal to that of AB. From the symmetry of the

arrangement, it is evident that, if the fault were exactly at the junction

between the good and bad wires, the contact point C would rest for a

balance at 1,000 on the scale, or at 500 if the fault were half-way along

the bad wire; hence, at whatever point it comes to rest, the reading

divided by 1,000 and multiplied by the length of the bad wire is the

distance from the instrument to the fault.

EXAMPLE--In a pair of equal wires, 5.8 miles long, one is grounded. With

the connections made as above, and the galvanometer balanced for the

dial reading 124, the distance to the fault is (124 × 58) ÷ 1,000 = .7192

miles.]

[Illustration: Fig. 597.--Murray loop method of fault location with Leeds

and Northrup fault finder: Case II, where the good and bad wires are

_unequal_. The figure shows the connections. It is the ordinary Murray

loop and it is evident that the resistance _a_, to the fault will be

obtained from the formula _a_ = (A ÷ 1,000) × r, where r is the resistance

of the loop, and A is the reading of the contact C on its scale. The

distance d, to the fault is obtained from the formula d = Ar ÷ (1,000 ×

M), where M is the resistance per mile of the faulty wire.

EXAMPLE--A wire having a resistance M of 16.46 ohms per mile is grounded.

This wire was looped with a wire of unknown resistance and the total

resistance of the loop r was measured and found to be 54.07 ohms.

Connections were made as in the figure, and the reading A was found to be

332. Substituting these values in the above formula: d = (332 × 54.07) ÷

(1,000 × 16.46) = 1.09 miles.]

Ques. How may the distance from 2 to the fault be determined in knots or

miles.

Ans. Divide Y by resistance per knot or mile.

The Varley Loop.--This is a method of locating a cross or ground in a

telephone or telegraph line or other cable by using a Wheatstone bridge in

a loop formed of a good wire and the faulty wire joined at their distance

ends. One terminal of the battery is grounded and the other connected

to a point on the bridge at the junction of the ratio arms. The rheostat

arm then includes the resistance of the rheostat plus the resistance of

the fault, while the unknown arm includes the resistance of the good wire

plus the resistance of the bad wire beyond the fault. When the bridge is

balanced, the unknown resistances may be readily determined by a simple

equation.

[Illustration: Fig. 598.--The Varley loop test. The diagram shows the

various connections. X and Y are the resistances of the cable between the

fault and the points 1 and 2 respectively. L is the resistance of the good

and bad cable or X + Y.]

In making the Varley loop test, the resistance of looped cable or

conductors is measured, and then connected as in fig. 598. Close the

battery key and adjust R for balance.

When earth current is present, the best results are obtained when the

fault is cleared by the negative pole, and just before it begins to

polarize. If X be the resistance from 2 to the fault, then

X = (L - R) / 2

also, X divided by the resistance of the cable or conductor per knot

or mile gives the distance of fault in knot or miles.

When the resistance of the good wire used to form a loop with the

defective wire, together with that portion of the defective wire from

the joint to the fault is less than the resistance of the defective

wire from the testing station to the fault, the resistance R must be

inserted between point 1 and the good conductor, the defective wire

being connected directly to point. The formula in this case is

X = (L + R) / 2

[Illustration: Figs. 599 and 600.--Varley loop method of fault location

with Leeds and Northrup fault finder. This method may be used as a check

on the Murray methods. Connect the faulty wire to 1, and measure the

resistance of the loop. Then throw switches as shown in the fig. 600.

Let: a = resistance to fault, d = distance to the fault in miles, M =

resistance of the faulty wire per mile, r = resistance of the loop, R =

resistance of the coil R, or 100 ohms, T = A ÷ (1,000 - A) to be read from

the table. From the Wheatstone bridge relation: a = (r - 100T) ÷ (T + 1),

and d = (r - 100T) ÷ (T + 1)M.

EXAMPLE--A wire having a resistance of 16.46 ohms per mile is grounded.

This was looped with a wire of unknown resistance and the resistance

of the loop was found to be 54.07 ohms. Connections were made as in the

figure, and the reading A was found to be 234. From the table T = .3055,

and substituting: d = (54.07 - 30.55) ÷ (1.3055 × 16.46) = 1.094 + miles.]

Special Loop.--This method may be used to advantage where the length

of the cable or faulty wire only is known and where there are two other

wires which may be used to complete the loop. It is not necessary that

the resistance of the faulty wire and the length and resistance of the

other wires be known. Figs. 601 to 604 show the connections and method of

testing.

EXAMPLE.--All the wires in a cable 10,852 ft. long were found to

be grounded so that none of them could be used as good wires. Two

wires were selected out of another cable going to the same place by

a different route and securely joined to one of the grounded wires

at the distant end. This grounded wire and one of the good ones were

connected as shown in figs. 601 and 602 and the reading A was found

to be 307. Connections were then made as shown in figs. 603 and 604

and A was found to be 610. What is the value of d?

According to formula

d = AL/A = (307 × 10,853)/610 = 5,461 ft.

[Illustration: Figs. 601 and 602.--Special loop test with Leeds and

Northrup fault finder. For the first measurement connect the faulty wire

to 2, either of the good wires, as Z, to 1, the post Gr to ground, and

short circuit the coils R and E by closing switches U and V as in the

figures. Balance in the usual way and call the dial reading A. For the

second measurement, connect the post Gr. (disconnected from ground),

to the other good wire y as shown in figs. 603 and 604, and get another

balance; call this reading A'. The distance d, to the fault is determined

from the simple formula d = AL ÷ A' where L is the length of the cable or

faulty wire.]

[Illustration: Figs. 603 and 604.--Special loop test as made with the

Leeds and Northrup fault finder. Diagram showing connections for the

second measurement. The special loop test may be used to advantage where

the length of the cable or faulty wire only is known, and where there are

two other wires which may be used to complete the loop. To use an outside

battery, connect one pole to Ba, and ground the other. The pressure of

this battery must never exceed 110 volts; if it be over 25 volts, see that

switch W is open.]

The Potentiometer.--For the rapid and accurate measurement of voltage,

current, and resistance, the potentiometer can be recommended. Those in

charge of electric light and power companies, and also those who purchase

large amounts of electrical energy are realizing, more and more, the

necessity of having satisfactory primary standards with which to check

their volt-, ampere-, and watt-meters.

When it is realized that an error of one per cent. in a commercial

instrument means an error of one dollar one way or the other in every

one hundred dollars charged, the need of such standardization apparatus

becomes at once apparent.

The potentiometer, it should be noted, relies for its accuracy, only upon

the constancy and accuracy of resistances and upon standard cells.

With the materials now available, and the skill which has been acquired

in their manufacture, both the resistances and the standard cells are

obtainable which are remarkably constant, and both can be readily checked

for accuracy.

Location of Opens.--These measurements are based on the fact that the

capacity of wires in a cable is ordinarily a measurable quantity, which,

in wire of uniform diameter, is proportionate to length. In making these

tests, a fault finder is used together with a buzzer, dry cells to operate

it, small induction coil, and telephone receiver. These instruments are

to be found in any telephone exchange. It is best to locate the buzzer at

some distance from the fault finder in order that it cannot be heard by

the operator.

[Illustration: Fig. 605.--To use galvanometer of Leeds and Northrup fault

finder in series with the battery: Set switches as shown, and connect

between posts Gr. and 2 (see figs. 587 and 588). The galvanometer will

have the maximum sensibility with the pointer at 1,000 and the minimum at

zero.]

[Illustration: Fig. 606.--To measure high resistances, such as the

resistances of faults with Leeds and Northrup fault finder. _First

Method._--Arrange the switches as shown in the figure. Connect posts Gr.

and 2, turn the handle until the galvanometer needle comes to rest at

an even deflection of ten divisions. Call the reading A. Connect in the

unknown resistance between Gr. and 2. Now close the switch W, so that the

figure 1 appears on the top of the block, and again bring the galvanometer

to a deflection of ten divisions and call the reading B. Then X = (10,000

B ÷ A) - 1,000. In case X be a high resistance, it will be found that

the galvanometer will not deflect ten divisions for any position of the

pointer. In such case, choose a number of divisions which is a factor of

ten, such as 5, 2, or 1, and multiply (10,000 B ÷ A) by ten divided by

the number chosen, as 10/5, 10/2, 10/1. For example, for a deflection

of two divisions: X = (10/2)(10,000 B ÷ A) - 1,000. The satisfactory

range of the set for high resistance measurement may be increased by

using an outside battery of higher voltage. With the contained battery,

satisfactory measurements can be made up to 1 or 2 megohms. When outside

battery is used, connect one terminal to the post Ba, and the other to 2

for the reading A. Connect the battery and unknown resistance in series

between these posts for the reading B. When an outside pressure of 25

volts or over is used, the switch W should not be closed unless there be

a resistance in series with the battery of 10,000 ohms or over. _Second

Method._--For use as a voltmeter to measure high resistances. (More

convenient but not quite as accurate as first method.) Set the switches to

RV, M and 10. Turn the knurled nut on the galvanometer so as to set the

needle to the extreme right hand side of the scale. Connect the posts 2

and Gr. with a short piece of wire. Turn the rotating pointer on the scale

until the galvanometer needle moves over about 20 scale divisions when

the battery key is closed. Remove the connection between 2 and Gr. as the

voltmeter terminals. This makes a simple way of testing for various kinds

and amounts of trouble. On a wet cable a deflection of 10 to 15 divisions

indicates heavy enough trouble to locate with the fault finder. With a

little care, trouble showing only 5 or 6 divisions can be located.]

Before attempting locations for opens it is well to make the following

measurements:

1. The insulation of the broken wire and the insulation of the good wire

with which it is to be compared.

This may be done as shown in fig. 606. It is best that the insulation

resistance be fairly good, but experiments indicate that good results

can be obtained by the methods which follow, even when the insulation

is as low as 100,000 ohms, and fair results when as low as 50,000 to

100,000 ohms.

[Illustration: Fig. 607.--Diagram of connections in testing for opens with

Leeds and Northrup fault finder. The apparatus required consists of fault

finder, buzzer, dry cell to operate buzzer, small induction coil, and

telephone receiver. Connect the battery to the primary of the induction

coil, one terminal of the secondary to the post Ba, and the other to the

connected wires as shown. Set switches U and V so as to short circuit the

two resistance coils.]

2. The resistance between the two sections of the broken wire should be

measured.

This may be done by joining the broken wire and a good wire at the

distant end of the cable and measuring the resistance of the loop. To

ensure close locations, this resistance should be over 100,000 ohms.

Fair locations can be made when the resistance is much lower and it is

worth while to attempt it even if the resistance be as low as 10,000

ohms. The difficulty of determining the balance point increases as

the resistance decreases.

Ques. Describe the method of locating an open with a fault finder.

Ans. (_Case I_) The broken wire will be one of a pair. Select another pair

in the cable that will have the same capacity per mile and join together

the mate of the broken wire and one wire of the other pair. Make the

connections as shown in fig. 607, then depress the battery key and move

the contact to the point of minimum sound in the telephone. The distance

to the break is equal to LA ÷ (1,000 - A), where L is the length of the

good wire.

EXAMPLE: A cable 1.45 miles long contained a broken wire. It was found

that the insulation resistance of the end of this wire was over 10

megohms, as was that of the good pair selected to test against it. The

resistance between the two pieces of the good wire was also over 10

megohms. Connections were made as in fig. 607, and it was found that

the balance point was 476. Accordingly from the table

A / (1,000 - A) = 0.9084

and

d = 1.45 × .9084 = 1.317 + miles.

[Illustration: Fig. 608.--Diagram of connections in testing with Leeds

and Northrup fault finder for open wire in telegraph and other cables

in which the wires are not grouped in pairs. Connect the broken wire to

1. Select a good wire and join to 2. Connect all other wires and ground

them, by connecting to the cable sheath. Connect the distant end of the

broken wire to the others. Ground the end of the induction coil that is

not connected to the post Ba.]

Location of Opens.--(_Case II_) Open wire in telegraph or other cables in

which the wires are not grouped in pairs. The connections are made as in

fig. 608, and the measurement and calculation exactly as in the preceding

case.

The accuracy of the location of both of the above methods depends on

the good and broken pair, or the good and broken wires having equal

and uniform capacity per unit length. It is not always possible to

select wires that are alike in this respect. In such cases, as for

instance, where there is no good wire in the cable containing the

broken wire, and a good wire has to be selected from another cable,

the method of _Case III_ may be used.

[Illustration: Fig. 609.--Diagram of connections for reading in testing

for opens with Leeds and Northrup fault finder, when broken wire and good

wire are not in the same cable.]

[Illustration: Fig. 610.--Leeds and Northrup potentiometer. It is direct

reading from .000001 volt to 16 volts, and with accessories the range

may be extended to 1600 volts, and currents may be measured up to 3000

amperes. The instrument has fifteen coils of 5 ohms each, which are in

series with an extended wire about 190" long of equal resistance. The

electrical circuits are shown in the diagram fig. 611. It is well for

the user to open up the potentiometer and make himself familiar with

its interior construction, in order to fully understand the operation

of the rheostat and other parts. There are no contact resistances in

the potentiometer circuit proper. The potentiometer has low internal

resistance which gives it the maximum sensibility. Compared with high

resistance potentiometer, this is especially advantageous in measuring

the electromotive force of thermocouples, and the fall of potential

across standard low resistances. As constructed, the last one-tenth volt

is covered by the extended wire and the handle which carries the contact

point on the wire may be manipulated rapidly so that a fluctuating

voltage may be accurately followed. When used with any cadmium cell,

the potentiometer is direct reading. The accuracy of the potentiometer

resistances can be verified with the facilities of the ordinary

laboratory.]

Location of Opens.--_Case III_, in which the broken wire and good wire

are not in the same cable. Connect the good wire and broken wire in the

same way as shown in fig. 607, and set the pointer for a balance. Call the

reading A. Then connect the good wire and the broken wire at the distant

end and set the pointer for a new balance. Call this A'. The connections

for this reading are shown in fig. 609. The distance to the break will be

d = (A A' L) / (1,000(A - A') + A A')

where L is the total length of the broken wire.

[Illustration: Fig. 611.--Diagram showing connections of Leeds and

Northrup potentiometer. The coils in the series AD are each 5 ohms, and

between each two there is a brass block with a reamed hole. A pair of

flexible cords with taper plug terminals to fit these holes is furnished.

These coils can be measured with an ordinary Wheatstone bridge and thus

compared with each other to a high degree of accuracy, even if the bridge

be not accurate. For potentiometer work, the essential point is that

they should be like each other, not that they should be accurately any

particular value. In the same way the resistance of the extended wire

can be compared with the resistance of the coils in AD. Its resistance

should be 1.1 times the value of any coil between A and D. Outside

connection with the extended wire may be made by using the posts marked

BR and -BA. This adjustment for balancing an unknown electromotive force

is accomplished by the manipulation of the two contact points M and M'.

The coils AD are arranged in a circle, a revolving switch moving M. A

checking device enables the operator to set this switch without taking his

eye from the galvanometer. The resistance S is of such value that when

it shunts the wire OB, the total resistance between O and B is 1/10 of

the same unshunted. When the shunt is applied, provided the total current

remain the same, the drop between any two points on AB will be 1/10 of

its previous value. The total current will remain the same provided the

total resistance in the circuit remain the same. This is accomplished

by making the coil K such that it exactly compensates for the reduction

in resistance caused by plugging in the shunt coil S. The low scale is

applied by moving the plug from the position 1 to the position .1. With

this change the potentiometer reads from .16 volt down by indicated

steps of .000005 volt. The reading is very simple. For instance, if M

stand at 1.2 and M' at 1.35 revolutions, the reading is 1.2135 volts.

The resistances of the instrument are wound upon metal spools, and are

therefore able to dissipate a comparatively large amount of energy. This

allows the potentiometer to be used for pressure measurements up to 16

volts without the use of a volt box.]

[Illustration: Fig. 612.--Diagram showing actual connections in the

rheostat of Leeds and Northrup potentiometer. The figure corresponds to

R of fig. 611. The rheostat is mounted in the end of the potentiometer

as shown in fig. 610. Rough adjustment of the potentiometer current is

made by means of the variable resistance R. Fine adjustment is made by

means of the variable resistance R'. It will be noted that the 23 ohm

resistance of this latter rheostat is shunted by a resistance of 6.1 ohms,

making possible a very fine regulation. Further, there is in series with

the moving contact a resistance of 400 ohms, which makes the effect of

variable contact resistance negligible. Only one cell of storage battery

should be used. When this battery is fresh, the plug shown in the figure

at 2R should be inserted at R. This gives the greatest resistance in the

rheostat circuit. As the cell runs down, the plug should be changed to

2R. When both plugs are in, the rheostat slide wires are in series with

the potentiometer circuit.]

EXAMPLE: A pair of wires containing one broken wire was connected with

a good pair in a different cable as shown in fig. 607. The reading A

was found to be 180. The good and bad wires were then joined at the

distant end as in fig. 609, and the reading A was found to be 88. The

total length of the bad wire MN was 1.44 miles. Required, the distance

to the break. Substituting the values in the formula:

d = 180 × 88 × 1.44 / 1,000(180 - 88) + 180 × 88 = .211 + mile.

To Pick Out Faulty Wires in a Cable.--Short circuit the coils E and R with

switches U and V. Set the pointer at 1,000. Connect the post Gr. to ground

or the cable sheath and apply the wires one after another to the binding

post 2. The galvanometer will deflect for a faulty wire.

[Illustration: Fig. 613.--Diagram of the Crompton potentiometer. In this

instrument the resistance consists of fourteen coils, each of 10 ohms,

in series with a straight wire, also 10 ohms resistance, thus forming a

system of fifteen equal steps. Across the whole a pressure of 1.5 volt

is applied from a secondary cell, thus providing .10 volt per step. Any

fraction is then tapped off by means of a radial switch on the resistance

coils and a sliding contact on the wire. The standardization is performed

by adjusting a resistance in series with the whole until the standard cell

employed indicates, by means of the galvanometer G, a balance at the point

which represents its electromotive force on the basis given above.]

Ques. What is a potentiometer?

Ans. An arrangement of carefully standardized resistances for measuring

voltages in comparison with a standard cell. It is used for accurate

measurement of voltages, currents, and resistances.

In place of a series of standardized resistances, a slide wire may be

used as in fig. 614.

Ques. Describe one form of potentiometer.

Ans. As shown in fig. 614, it consists of a fine German silver wire about

3 feet long stretched between the binding posts A, B, which are attached

to a wooden base carrying a scale divided into 1,000 equal parts. There

are three circuits, the terminal A being included in each, one including

the battery, and the other two the galvanometer. A three point switch

connects the galvanometer in series with the standard cell SC, or the cell

to be tested C, the circuits being completed by leads terminating in the

sliding contacts M and S.

[Illustration: Fig. 614.--Diagram of potentiometer showing method of

measuring the voltage of a cell. The potentiometer is simply a high

resistance wire of uniform diameter stretched between two binding posts,

A and B, in such a way that contact can be made at its ends and along

its length. Necessary circuits are plainly shown in the figure; SC, is

a _standard cell_ and C, the cell to be tested. M, and S are sliding

contacts, connecting with the "slide wire."]

Ques. Describe the method of measuring the voltage of a cell with a

potentiometer.

Ans. Fig. 614 shows a method of comparing a pressure with that of a

standard cell and is applicable whether the pressure of the cell to

be tested be greater or less than that of the standard cell. In making

the test the switch F is first closed, then the other switch is moved

to D, and M adjusted till galvanometer shows no deflection; similarly,

the switch is moved to G, and S adjusted till galvanometer shows no

deflection. Then, C:SC = AS:AM. from which C = SC × AS ÷ AM.

EXAMPLE.--Let 1.016 volts be the known voltage of the standard cell

SC, and the scale reading of AS be 657, and of AM, 225 as in the

figure, then

C = (1.016 × 657) / 225 = 2.966 volts

The arrangement may, however, be made direct reading, that is,

the slide wire may have a scale of volts instead of lengths or

resistances, as follows: Suppose the standard cell to have a pressure

of 1.434 volts, the sliding contact M is placed at the reading 1.434,

and the adjustable resistance varied till the galvanometer shows no

current. This means that the pressure between A and M is 1.434, and

consequently the pressures all along the slide can be read off the

scale _in volts_. Hence, when S has been adjusted to balance, the

pressure of C is read off the scale in volts.

[Illustration: Fig. 615.--To measure a pressure greater than 1.6 volts

with Leeds and Northrup potentiometer by using a volt box or multiplier.

To measure high voltages it is necessary to connect the voltage across

high resistance and to measure on the potentiometer a definite fraction

of the total drop. In the figure, AB is a high resistance of which CB is

.1th, DB .01th, and EB .001th of the total resistance. The potentiometer

reading is accordingly multiplied by 10, 100, or 1,000, depending upon

whether the switch M is set on C, D, or E. Resistance boxes for this

purpose are called _volt boxes_, and are constructed to multiply the

potentiometer readings by 10, 100, and 1,000. In using them, it is only

necessary to connect the unknown E.M.F. at the posts so marked, and the

potentiometer to the posts marked P. The potentiometer reading is taken

as above and multiplied by a factor depending upon the position of the

switch M, which factor is indicated upon the box. _It is essential in

making these connections that the polarity be carefully observed._]

How to Use a Potentiometer.--All connections must be made as indicated by

the stamping on the instrument. Particular attention must be given to the

polarity of the standard cell, of the battery, and of the voltage, the

corresponding + and - signs being marked. If used with a wall galvanometer

having a telescope and scale, it will be found convenient to place the

potentiometer so that the telescope is directly over the glass index of

the extended wire, thus permitting the observer to read the galvanometer

deflections and potentiometer settings without changing his position.

Potentiometer Current.--A medium sized storage cell will be found

desirable, producing a steady current. Errors in measurements are

frequently made by using an unsteady current.

Setting for Standard Cell.--Set the standard cell to correspond

with the certified pressure of the standard cell as given in its

certificate. In using the potentiometer shown in fig. 610, place

the plug in hole 1, and see that it is always in this position when

checking against the standard cell. Place the double throw switch at

STD. CELL.

Adjust the regulating rheostat until the galvanometer shows no

deflection. In making the first adjustment use the key marked R_{1};

when a balance is almost attained, use key R_{2}, and for the final

adjustment use key marked R_{0}. This cuts out the resistance in

series with the galvanometer and gives the maximum sensibility.

Measurement of Unknown Pressure.--The potentiometer (fig. 610),

as ordinarily used, gives direct readings for voltages up to and

including 1.6 volts. For pressures higher than 1.6 volts, a volt

box or multiplier should be used. After obtaining the standard cell

balance, as previously described, place the double throw switch in

the position marked E.M.F. The balance for the unknown E.M.F. is

obtained by manipulating the tenths switch and rotating the contact

on the extended potentiometer wire. The final position of the two

contacts in conjunction with the position of the plug at the left of

the instrument indicates the voltage under test.

As directed above, use key R_{1} for rough adjustment, R_{2} for

intermediate adjustment, and key R_{0} for final adjustment.

Plug at 1 gives readings for voltage directly from settings of tenths

switch and extended wire contact.

Plug at .1 shunts the potentiometer circuit so that the voltage

measured is .1 of the reading taken directly from the scale. Hence,

the readings taken from the setting of the tenths switch and the slide

wire contact must be divided by 10.

To Balance Galvanometer for Unknown Voltage.--Place plug in hole 1

(fig. 610) for voltages up to 1.6, and in hole .1 for voltages up

to .16. Rotate the tenths switch until a condition of balance is

obtained exactly or approximately. To secure an exact balance, rotate

the contact on the extended wire. The unknown voltage can now be read

directly from the position of the tenths switch and the extended wire

contact if plug be at 1, or by dividing by 10 if plug be at .1.

EXAMPLE.--A balance was obtained with the tenths switch at 1.3, the

extended wire contact at 176 and the plug at 1. The voltage under

test, therefore, is 1.3176. If the plug at .1 had been used, the same

reading would have indicated .13176.

To ascertain if the current in the potentiometer circuit has altered

during a measurement, it is only necessary to plug in at 1, place

the double throw switch on STD. CELL and close the galvanometer key.

No deflection indicates that the current has not changed. If the

galvanometer deflect, the regulating rheostat must again be adjusted

until the galvanometer shows no deflection.

To Measure Voltages from 1.6 to 16.--Pressures up to 16 volts may

be measured by using a greater voltage across the BA posts (fig.

615). For this purpose a battery of about 20 volts should be used.

Insert the large plug at .1 and throw the switch to STD. CELL, then

balance the galvanometer by means of the regulating rheostat. When the

rheostat has been set to secure a balance, insert the large plug at

1, set the switch on E.M.F. and read the voltage in the usual manner.

Multiply the reading by 10.

[Illustration: Fig. 616.--Measurement of current with potentiometer. This

is done by measuring the drop in volts across a known low resistance.

In the figure S is the standard resistance, and on it are the pressure

terminals pp, and the current terminals CC. The potentiometer is connected

to the shunt through the posts marked P. The resistance between the

points pp is adjusted to an even fraction of an ohm. These resistances

are so chosen that in order to determine the current passing through

the shunt, after having obtained a potentiometer balance it is only

necessary to multiply the potentiometer reading by a simple factor. For

instance, in using a .01 ohm standard. It is only necessary to multiply

the potentiometer reading by 100, which gives the current reading in

amperes; similarly, a .1 ohm requires multiplication by 10, and a .001

ohm by 1,000.]

Care of Potentiometer.--The slide wire, although protected to a great

extent by the hood, in time accumulates dust and dirt with a thin film

of oxide. This will tend to increase the resistance in this part of the

circuit owing to poor contact. This wire should, therefore, be cleaned

occasionally.

To do this, unscrew the stop against which the hood strikes when

turned to read zero; then remove the hood and rub the entire slide

wire vigorously with a soft cloth dipped in vaseline. _Do not use

emery or sand paper as this will destroy the uniformity of the slide

wire._ Clean also the steel contact which rubs on the wire, as this

becomes glazed after much use. When the potentiometer is not in use,

the hood should be screwed all the way down, and the lid put in place

to exclude dust.

If it be used in a chemical factory, laboratory, or any place where

acid fumes are prevalent, this latter precaution is important, because

the fumes may attack the slide wire.

It is also well to keep the contact surfaces of the switch studs clean

and bright by wiping them occasionally with a soft cloth dipped in

vaseline.

[Illustration: _Res. of leads on each end is equal to 10 divisions of

slide wire. The slide wire is divided into 1000 parts--20 for the leads,

or 980 divisions. Calibrated scale on Galvanometer:_

Fig. 617.--Diagram of Leeds and Northrup bridge for locating faults in

power circuits, showing arrangement of the connections including the lead

cables and galvanometer contacts. Make connections as shown. The clamps

must be so fastened at A and C that the contact resistances will be very

small. This contact resistance will figure as an error in the measurement.

If, for instance, the contact resistance were equal to .001 of an ohm,

and the wire were of such a size that .001 of an ohm were equal to the

resistance of 20 feet of the cable, there would be an error of 20 feet

in the location of the fault. For this reason all contact resistances

throughout the loop from A to C must be extremely small. The battery is

to be connected to the posts marked Ba., and the post marked Gr. is to

be grounded. It will very frequently happen that the ground is to the

cable sheath or some other conductor. In this case, the binding post Gr.

should be grounded to this conductor. Sufficient battery should be used

to give a readable deflection on the galvanometer for a small movement of

the contact on the bridge wire. The fault is located by the usual Murray

formula. If, for instance, the galvanometer show no deflection when the

contact is at 300 on the scale, it would indicate that the fault is at a

distance from A equal to .003 of the total length of the loop from A to C.

A testing current of five amperes may be used with this bridge. In cases

of necessity, this current may be increased to eight amperes, but when

this current is used it should not be allowed to pass through the bridge

for a longer time than is necessary. It frequently happens that small

faults which have a very high resistance develop in high pressure cables.

Such faults are likely to break down and result in damage and should be

located. It is usually impossible to locate these faults until they have

been partially carbonized. This must be done by applying a sufficiently

high voltage between the cable and the sheath (or whatever it is grounded

on) to break down the fault. In order to prevent the breaking down process

from resulting in a serious burn out a high resistance must be placed in

the circuit which will prevent an excessive current, or the circuit must

be carefully fused. The former procedure is the better.]

Location of Faults where the Loop is Composed of Cables of Different Cross

Sections.--Faults in loops of this character may be located with the same

degree of accuracy as those in loops of a uniform cross section, provided

the length and cross section of each length of cable are known. An example

will illustrate the method:

In the diagram, fig. 617, assume the length of the cable AE to be

550 yards of 25,000 cir. mil., EF, 500 yards of 40,000 cir. mil., and

FC, 1,050 yards of 30,000 cir. mil. These lengths must be reduced by

calculation to equivalent lengths of one size, and for this purpose it is

best to select the largest size. The results of this calculation are as

follows:

550 yds. of 25,000 cir. mil. = 880 yds. of 40,000 cir. mil.

500 " " 40,000 " " = 500 " " 40,000 " "

1,050 " " 30,000 " " = 1,400 " " 40,000 " "

This makes the total resistance of the loop equivalent to 2,780 yards

of 40,000 cir. mil. If the contact show a balance for a reading of

372.5, this indicates that the fault is at a distance of 372.5/1,000 of

2,780 = 1,035.5 equivalent yards. Of this, 880 are in the stretch A E.

Consequently the fault is:

1,035.5 - 880 = 155.5 yards from E.

[Illustration: Fig. 618.--The Fischer portable cable testing set, designed

for locating crosses, grounds and breaks in cables, also for conductor

and liquid resistance measure. The distinguishing feature of the set is

the _master switch_. By means of this switch, connections can be made for

the various tests by a single movement, thus avoiding the labor and time

which have to be expended in interchanging the connections and memorizing

the rather complicated scheme of connections.]