=Booster Feeding.= Boosters are sometimes used on long feeder lines

where there is a heavy load only a small portion of the time. These

boosters are direct-current dynamos that are connected in series with

the feeder upon which the voltage is to be raised above the regular

power-house voltage. The booster may be driven either by a small

steam engine or by an electric motor. The simplest form of booster

is a series-wound dynamo. A booster armature must, of course, be of

sufficient current capacity to pass all the current that will be

required on its feeder. The voltage yielded by this dynamo, plus the

power-station voltage, is the voltage of the boosted feeder as it

leaves the power house. Supposing that a series-wound booster will give

125 volts at full load; it is obvious that being series-wound it will

give no voltage at no load. The voltage will increase approximately

as the load on the feeder increases; and since the drop in voltage on

the feeder for which the booster is to compensate also varies with the

load, the action of the booster is simply to add sufficient voltage to

its feeder at any instant to compensate for the line loss upon that

feeder and to maintain approximately constant potential at the far end

of the feeder. Boosters raising the power-station voltage of a feeder

more than 250 volts above the normal power-station voltage, are not

common, though cases are on record where a feeder has been boosted as

high as 1,100 volts above the power-station voltage. Since all the

power used in driving a booster is wasted in line loss, this method of

feeding is not economical; but where used only a few days out of the

year it is sometimes to be preferred to a heavy investment in feeders.

The investment in feeders might involve more interest charges than the

cost of power wasted in booster feeding would amount to.

=Alternating-Current Transmission.= High-tension alternating-current

transmission _to_ substations, with direct-current distribution _from_

substations, is extensively used on long interurban roads, and on

large city street-railway systems where power is to be distributed

over a wide area. In such cases the power house is equipped with

alternating-current dynamos supplying high-tension three-phase

alternating current to high-tension transmission lines or feeders.

These high-tension feeders are taken to substations located at

various points on the road, where the voltage is reduced by step-down

transformers; and these transformers supply current to operate rotary

converters, which convert from alternating to direct current for use on

the trolley.

The advantage of this system of high-tension distribution is that,

owing to the high transmission voltage, there is but a small loss

in the high-tension lines, which lines can be made very small, and

will thus involve but little copper investment. The substations can

be located at frequent intervals, so that the distance the 500-volt

direct-current must be conducted to supply the cars is not great.

Current from one power house can thus be distributed over a very

large system in cases where, if the 500-volt direct-current system of

distribution were used, the cost of feeders for distributing such a

low-voltage current would be prohibitive. Were the alternating-current

high-tension scheme of distribution not used, it would be necessary

to have a number of small power houses at various points on the

system instead of one large power house. The cost of operation of

several small power plants per kilowatt output, is likely to be

much greater than that of one large power plant. The first cost of

the alternating-current distributing system, including power house

and substations, is likely to be considerably higher than would

be the cost of a number of small power houses; but in cases where

alternating-current distribution has been installed, it has been

figured that the cost of operation of the central power house with

alternating-current distribution would be sufficiently low as compared

with several small ones to pay more than the interest on this extra

investment.

[Illustration: Fig. 87. Diagram of Distributing System.]

=A System of Distribution for an Interurban Railway.= The typical

features of a high tension system of distribution for an extensive

interurban railway system are shown in Fig. 87, which represents the

electrical transmission and distribution system of the Indiana Union

Traction Company. The central power station at Anderson feeds into

thirteen rotary converter substations from 7 to 65 miles distant from

the power house. The substations east of Indianapolis are fed at 16,000

volts and are placed about 11 miles apart. The substations due north of

Indianapolis are located at intervals of about 17 miles and are fed at

30,000 volts.

The power station at Anderson has a total capacity of 5,000 K. W. The

substations vary in capacity from 250 to 1,500 K. W.

=Efficiency of Transmission Systems.= The average efficiency of a high

tension transmission system for a certain interurban electric railway

system are given below. Current was generated at 380 volts. The step-up

transformers raised it to a potential of 16,000 volts at which pressure

it was transmitted to eight substations at distances from 10 to 40

miles from the power station. It was then stepped down to 380 volts and

converted to direct current by a rotary converter. The tests extended

over a period of three days. The efficiency of the step-up transformers

was 95 per cent; of the high tension line 92.9 per cent; of the

step-down transformers 95 per cent; and of the rotary converters 88 per

cent; giving a total efficiency of the transmission system of 73.5 per

cent.

=Power House Location.= A power house is usually located where coal

and water supply can be cheaply obtained. For this reason it is placed

either on some line of railroad or where coal can be taken to it over

the electric railway.

As it is always desirable to operate the engines in connection with

condensers, on account of the saving in fuel, which is approximately

20 per cent with condensers, power stations are located, when

possible, near rivers and ponds from which a large supply of cold

water for condensation of exhaust steam can be obtained. Where no

such natural water supply is available, it has become customary to

provide means for artificially cooling a sufficiently large supply of

water for condensation. One method is to erect a number of towers, so

constructed that the water when pumped to the top will fall through a

structure that breaks the water up into fine spray as it falls, thus

allowing it to cool by evaporation so that it can be used again for the

condensers when it arrives at the bottom of the tower. Where more room

is available, ponds are sometimes excavated near the power house, and

the water is made to flow back and forth through a series of troughs

located above the pond, and it is thus cooled.

Where a power station is of the direct-current type, operating at

500 to 600 volts, it is desirable to have it as near the center of

electrical distribution as possible, in order to keep down the amount

of investment in the feed wire; but it is more important to have it

located near a cheap coal and water supply than exactly at the center

of distribution.

It is also desirable to have the station located where there is room

for coal storage, on account of the chances for interruption of the

coal supply by strikes, railroad blockades, and other causes beyond the

company’s control. The continuity of the coal supply is also another

argument against placing the station where dependence must be placed

upon wagons or inadequate railroad facilities.

Coal handling, after the coal has reached the station, is done by hand

in the smaller power stations; but in larger power stations it has come

to be the general practice to do as much of the handling as possible by

means of automatic coal conveyors. The most elaborate power stations

have means for dumping coal from cars into hoppers, from which it is

conveyed by an endless chain provided with buckets, called a _coal

conveyor_, to storage bins. Coal conveyors also take the coal from the

storage bins, and deposit it in the hoppers of mechanical stokers in

front of the boilers. Ashes are conveyed from under the boilers by the

same kind of conveyors, and are dumped into hoppers, whence they are

drawn into cars or wagons to be hauled away. The coal, having been

deposited in hoppers at the boiler front, is automatically fed into the

furnaces by automatic stokers. One type of automatic stoker in common

use is of the chain-grate or link-belt type, which is constructed like

an endless sprocket chain, with links composed of heavy cast-iron

blocks that serve as grate bars. This link belt or chain is kept in

constant, slow motion by a small stoker engine or motor which operates

all the stokers of a line of boilers. The coal is fed from the hopper

on to the chain grate, and the chain is slowly moved under the boilers.

As the coal on that part of the grate under the boilers is on fire, the

fresh coal as it enters the furnaces is soon ignited. The grate is run

at such a rate, and the thickness of the coal is so adjusted, that the

coal is burned to an ash by the time it has traveled to the back of

the furnace. There the grate turns down over a sprocket wheel, and the

ashes are dumped into the ash pit as the grate revolves.

The boilers in most common use in large American electric-railway power

houses are of the water-tube type, in which water is contained inside

of a bank of tubes, the ends of these tubes being connected to drums or

headers. The horizontal return-tubular type of boiler is used in many

of the smaller power stations, and vertical boilers are also in use.

The engines in the larger and more economical stations are generally

of the Corliss compound-condensing type, running at speeds of from

60 to 120 revolutions per minute, according to the size of the unit.

The smaller the unit, the higher the speed. In the smaller and older

stations, simple Corliss engines belted to generators are frequently

found, and high-speed engines also are used. It is the almost universal

custom now, to place the generator directly on the engine shaft, making

a direct-connected unit.

Steam turbines, in which the steam acts in jets against the blades of

a turbine wheel, are beginning to come into use at the present time.

These turbines rotate at very high speed, the largest and slowest

speed-units running 600 r.p.m., and others at higher rates. As the

output of any generator varies directly according to its speed, a

very much smaller generator can be used when coupled to a high-speed

steam turbine, to obtain a given output, than if the generator must be

coupled to a Corliss steam engine which revolves at very low speed.

The economy of the steam turbine at full load is about that of a

compound-condensing Corliss engine, but is better on light loads than

the engine. The turbine requires less building space and a much less

expensive foundation.

[Illustration: Fig. 88. Plan of Power House.]

Railway generators or dynamos for direct current are usually built

with compound-wound fields, so that, as the load increases, they will

automatically raise the voltage at their terminals to compensate for

the drop in the feeders and to maintain a constant potential at the

cars. Thus, if the line loss on a system is 10 per cent, or 50 volts

at full load, the generators will be provided with shunt fields of

sufficient strength to give 500 volts at no load, and with series

field coils which will add to the field strength enough to give 550

volts at full load. The amount of “compounding”—which is the term

applied to this method of increasing voltage—may be any amount within

reasonable limits. The pressure maintained at different companies’

electric-railway power houses varies, but is usually between 500 and

600 volts.

=Alternating-Current Generators.= Alternating-current generators used

for generating alternating current to be distributed at high tension,

are generally constructed to give a three-phase current at 25 cycles

per second. The voltage of these alternating-current generators

is sometimes the voltage at which the power is to be transmitted,

if the distances are not too great. A number of stations have

alternating-current generators giving 6,600 volts at their terminals,

which is a voltage well adapted to high-tension distribution within

the limits of a large city. However, generators giving 11,000 volts

at their terminals are now becoming common. For higher voltages than

this, it is considered necessary to use step-up transformers, in order

to raise the voltage to the proper pressure for transmission over long

distances. In such cases there is no object in having a high generator

voltage. At such stations the voltage of the generators adopted may

be anything desired, and it varies according to the ideas of the

constructing engineer. Voltages of 400, 1,000, and 2,300 are among

those in most common use.

=Double-Current Generators.= Double-current generators are sometimes

used, which generators will give direct current at a commutator at one

end of the armature for use on a 500-volt direct-current distribution

system supplying the trolley direct. The other end of the armature

has collector rings from which the three-phase alternating current is

obtained, which can be taken to step-up transformers and raised to a

sufficient pressure, for high-tension transmission to substations at

distant parts of the road. The same generator can therefore be used

on both the direct-current and the high-tension alternating-current

distribution.

=General Plan of Power Stations.= The general plan of an

electric-railway power station is usually such that the building can

be extended and more boilers, engines and generators added without

disturbing the symmetrical design of the station. Thus, the boilers

and engines are placed as in Fig. 88, in parallel rows, although

almost invariably in different rooms separated by a fire wall. By

adding to the row of engines and to the row of boilers, the station

capacity can be increased. Other arrangements are sometimes required

by circumstances; but this is the most common arrangement and gives

the greatest capacity with the minimum amount of steam piping. Large

stations are sometimes constructed with a boiler room of several floors

and with boilers on each floor, in order to save ground space and bring

the boilers near to the large engine units so that there will not be an

excessive amount of steam piping.

[Illustration: Fig. 89_a_. G. E. Circuit Breaker.]

=Switchboards.= Direct-current stations have switchboards, which may

be considered under two general classes—_generator boards_ and _feeder

boards_. Each board consists of panels.

=Generator D. C. Panels.= The generator panel usually contains an

automatic circuit breaker which will open the main circuit to the

generator in case of an overload due to a short circuit. These circuit

breakers consist of a coil in the main circuit, which acts upon a

solenoid. When the current in the coil exceeds a certain amount, the

solenoid is drawn in, and a trigger is tripped which allows the circuit

breaker to fly open under the pressure of a spring. In the General

Electric circuit breaker, the main contact is made by heavy copper

jaws, but the last breaking of the contact is made between points

which are under the influence of a magnetic field. This magnetic field

blows out the heavy arc that would otherwise be established. On the

I-T-E, the Westinghouse and most other types of circuit breaker, the

breaking of the contact takes place between carbon points, which are

not so readily destroyed by an arc as are copper contacts, and which

are more cheaply renewed. The main contact through the circuit breaker,

in either type, is made between copper jaws of sufficient cross-section

for carrying the current without heating. These jaws open before the

current is finally broken by the smaller contacts which take the final

arc.

In Fig. 89_a_ is seen a General Electric circuit breaker with the

magnetic blow-out coils at the top, the solenoid at the left, and the

handle for resetting the circuit breaker at the bottom. The small

handle for tripping the circuit breaker, when it is desired to open the

circuit by hand, is shown just under the solenoid.

An I-T-E circuit breaker is shown in Fig. 89_b_. This is of the type

previously mentioned, in which the break occurs between carbon contacts

and there is no magnetic blow-out.

[Illustration: Fig. 89_b_. I-T-E Circuit Breaker.]

In addition to the circuit breaker there is usually an ammeter, to

indicate the current passing from the generator; and a rheostat handle,

geared to a rheostat back of the board, for cutting in and out more

or less resistance in the shunt field coils of the generator so as to

reduce or raise the voltage. There is a small switch for opening and

closing the circuit through the shunt field coils.

The main leads from the generator pass through two single-pole

quick-break knife switches. The most recent practice is to have the

switches on the switchboard in only the positive and negative leads

from the generator, leaving connection to the equalizer to be made by a

switch located on or near the generator. However, all three leads may

be taken to the switchboard, and a three-pole knife switch may be used

instead of the positive and negative switches spoken of.

In Fig. 90 is given a simple diagram of the general relative connection

of generators and feeders in a direct-current railway power station.

It is seen that the generators are connected in parallel across the

positive and negative bus bar. There is a third bus bar—called an

“equalizing bus”—which connects in parallel the series coils of all

the generator fields. The object of this equalizer is to prevent the

weakening of the series field of any one generator, so as to allow it

to take current and to act as a motor instead of as a generator.

=Starting Up a Generator.= Suppose that a new generator is to be

started up and connected to the bus bars in addition to others

already in operation. The engine of that generator is first brought

up to speed. The switch controlling the shunt field circuit is then

closed, causing current to flow through the shunt fields; and the

generator begins to “build up,” its voltage gradually rising until it

approximates that upon the bus bars. Before the generator is thrown

in parallel with the others by connecting it with the bus bars, it is

important that its voltage be nearly the same as that of the bus bars.

Otherwise, when connected to the bus bars, it might take more than its

share of the load; while, on the other hand, if its voltage were too

low, it might act as a motor, taking current from the bus bars. The

voltage of the bus bars in a railway station is constantly fluctuating,

owing to the varying load and to the fact that generators are often

compounded, as before mentioned, in order to compensate for the line

loss.

[Illustration: Fig. 90. Connection of Generators and Feeders.]

In order that the voltage of the generator to be thrown in shall vary

in accordance with the bus bar voltage, the next step in the operation

is to close the positive switch, assuming that the equalizer switch on

the generator has already been closed. This throws the series field

of the new generator in parallel with the series fields of the other

generators. The voltage of the new generator will therefore vary just

as the voltage on the bus bars; and, by adjusting the resistance of the

shunt field, this voltage can be adjusted so as to be the same as that

on the bus bars. The voltages on the bus bars and on the new generator

are measured usually by a large voltmeter on a bracket at the end of

the generator switchboard. By means of a voltmeter plug or of a push

button on the generator panel, the voltmeter can be connected either

to the bus bars or to the new generator. When the two voltages are the

same, the negative switch of the new generator can be closed, and it

will operate in parallel with the other generators, taking its share of

the load. If the attendant sees that any generator is not taking its

share, he can raise its voltage by cutting out some of the resistance

in series with its shunt field, and this makes that generator take more

load.

[Illustration: Fig. 91. Railway Switchboard.]

=Feeder Panel.= The feeder panel is simpler than the generator panel,

since it usually handles only the positive side of the circuit.

Frequently two feeders are run on a single panel side by side.

The feeder panel has an automatic circuit breaker, an ammeter for

indicating the current on that feeder, and a single-pole switch for

connecting the feeder to the bus bar. All generators feed into a common

set of bus bars; and the positive bus bar continues back of the feeder

panels so that all feeders can draw current from the bus bars. Fig.

91 shows a railway switchboard with 7 feeder panels at the right; 4

generator panels at the left; and, in the middle, a panel with an

ammeter and recording wattmeter for measuring total output.

In some stations two and even three sets of bus bars are used, as it

may be desired to operate different parts of the system at different

voltages or to feed a higher voltage to the longer lines than to those

near the station. In such a case double-throw switches are provided for

connecting feeders and generators to either set of bus bars.

=Alternating-Current Switchboards.= In an alternating-current station,

generator switchboards are radically different from those in a

direct-current station. Practice in alternating-current generator

switchboards has not yet been so fully standardized and is not so

uniform as in direct-current railway switchboards. There is always,

however, a three-pole main switch for opening and closing the main

three wires from the three-phase generator. Automatic circuit breakers

are usually provided, as well as indicating ammeters and wattmeters to

show the output.

Indicating wattmeters, recording the number of watt hours passing

through them, are frequently used both on alternating and

direct-current generator panels.

A station usually has what is called a “total load” panel, which has

a recording wattmeter measuring the total output of the station in

kilowatt hours. This panel also has an ammeter indicating the total

station load.

=High-Tension Oil Switches.= Alternating-current generators for high

voltages usually have oil switches to interrupt the main circuit, that

is, switches in which the contact is made and broken under oil. These

switches have been found very efficient in preventing the formation

of a destructive arc upon the opening of a high-voltage circuit, on

circuits up to 60,000 volts. Some of the larger oil switches are

operated by electric motors or solenoids. The machine-type oil switch

of the General Electric Company has the motive power for operating the

switches, stored up in a spring. The spring is wound up by a small

electric motor. This motor operates every time the switch is opened or

closed, and winds up the spring enough to compensate for the amount it

was unwound in operating the switch. Each circuit is broken under oil

in a long tube, and these tubes are mounted in individual cells, each

cell being separated from the next by a masonry wall so that there can

be no flashing across from one leg of the circuit to another in case

of any defect in the switch. All the high-tension wiring to and from

such switches, is taken either in lead-covered cables, or on bus bars

separated from each other by masonry walls to prevent the spread of

short circuits. These precautions are necessary because of the great

length of arc that may be established between adjacent high-tension

conductors.

Where alternating-current generators of low voltage are used in

connection with step-up transformers, one practice is to have the

switches for each generator directly in the generator leads, between

the generators and the step-up transformers, in the low-voltage circuit.