CHAPTER IV

REFRIGERATION EQUIPMENT

AMMONIA MACHINES -- AMMONIA -- COMPRESSOR -- CONDENSER -- RECEIVER --

COOLER -- CONDENSING WATER -- UNIT BASIS -- COMPUTING FROM UNIT BASIS

-- HOW RATED -- FREEZER REQUIREMENTS -- FREEZERS IN SMALL PLANTS --

CYLINDER ARRANGEMENT -- WHY BRINE CIRCULATION -- AIR CIRCULATING

-- FORCE DRAFT -- COIL ROOM SYSTEMS -- BRINE CHILLING -- BRINE

METHODS -- TYPES OF BRINE COOLERS -- BALANCED BRINE SYSTEM -- DIRECT

EXPANSION -- TWO-STAGE COMPRESSORS.

=Mechanical Refrigerating Equipment.=--This agent is of great

consequence in the operation of packing houses, and, therefore, it

is deemed essential to explain the principles briefly; as well as to

describe the uses.

=Ammonia Machines.=--The use of ammonia refrigeration equipment either

absorption or compression has so generally displaced all others for

stationary or land use, and particularly in meat plants and cold

storage houses, that for the present purpose it is unnecessary to

go into a discussion of others. The compression system being so

predominant in its use, a description of same is given.

The diagram indicates a compression system in elementary form

consisting of:

(1) A pump or compressor which withdraws the gas from the cooler or

expansion tank, prepares and passes it to the condenser.

(2) The condenser or liquifier which gives to the water flowing over it

the heat carried to it by the gas from the cooler.

(3) The cooler or expansion tank in which the heat extracted from the

carcasses, the building walls or elsewhere, is passed to the ammonia

gas for conveyance to the condenser.

=Ammonia.=--Leaving for a moment the description of the apparatus to

acquaint the reader with ammonia: In the form used in a compression

refrigerating machine, it bears the name “liquid anhydrous ammonia”

meaning in a “dry liquid” form differentiating from the common

household ammonia which is a water solution containing ammonia gas in

variable quantity. The distinction between these two is that “anhydrous

ammonia” will evaporate to naught; from household ammonia the gas will

evaporate but the water will remain.

[Illustration: FIG. 15.--DIAGRAM SHOWING AMMONIA COMPRESSION SYSTEM.]

Ammonia is a chemical compound made up of one part nitrogen and three

parts hydrogen and is expressed by the chemical symbol NH₃. It has some

peculiar characteristics being analogous to water. It will assume a

solid, liquid and gaseous form, at -115° F. and -28¹⁄₂° F. for solid

and liquid respectively and will modify to a gaseous form at any

temperature above -28¹⁄₂° F. under “atmospheric” or conditions of no

pressure.

Water, as is known, changes from a liquid to a solid at 32° F. and

changes to a vaporous form at 212° F. but here the analogy ceases.

Ammonia has further peculiar advantages for use in refrigerating

production that it becomes a liquid at variable pressures and

temperatures; for example, when the temperature is reduced to 60° F.

under a pressure of 92 pounds, when reduced to 80° under a pressure of

139 pounds and at 100°, under a pressure of 200 pounds; with variables

above, between and below these conditions. Ammonia, as will be seen,

has variable forms and capacities under the conditions imposed upon it.

Substances passing from a liquid to a gaseous form require heat to make

this change and consequently absorb it; the complement to the giving

up of heat when the process is reversed and the substance changed

from a gaseous to a liquid form. The adoption or harnessing of these

principles is the nucleus upon which mechanical refrigerating effect is

built. A pound of water passing to steam will absorb about one thousand

degrees of heat, ammonia has the same characteristic to a different

degree. They both return the heat when the process is reversed.

=Type of Machine Illustrated.=--The diagram illustrates a single acting

pump showing its piston, a liquifier or condenser where the ammonia is

modified in form from a gas as received therein to a liquid; a receiver

to which it flows and a cooler in which it is expanded and where the

heat brought to it by the returning brine is picked up by the ammonia

and carried to the condenser. The arrows indicate the direction of flow.

=Compressor.=--The “Compressor” is a pump, a cylinder fitted with

a piston which withdraws the ammonia from the tank in which it is

expanded. The piston is tightly fitted and when it travels in one

direction, the gas flows in, filling the space, like any ordinary

pump whether it be a water or gas pump. Upon the return stroke, the

gas is compressed in the cylinder until the pressure in the piston is

sufficient to equal or overcome that exerted against it accumulated in

the condenser, when it is discharged thereto. There are spring actuated

valves interposed in the line of gas travel which close and retain in

the condenser that gas which has been discharged, allowing the piston

and compressor to repeat the just described performance many times per

minute.

=Condenser.=--The use of this element is to liquify the ammonia, really

to extract the heat absorbed by the ammonia in the cooler and the heat

generated in the compression. This condensing operation changes the

form of the substance from gaseous to liquid. The most simple style

of condenser is a series of pipes stacked together with ammonia on

the inside of the several pipes, and water flowing over the outside.

The gas on leaving the compressor is hot and at a high temperature,

frequently as high as 250° F. or more, and the pressure from 140 to 220

lbs., depending upon the water supply, its temperature and quantity,

and the area of the surface of the condenser.

The water flowing over the condenser absorbs the heat from within, the

ammonia becoming cooled by contact with the comparatively cool walls

of the pipe while flowing from one end to the other of the condensing

coil, gradually changing from a gaseous to a liquid form.

=Receiver.=--From the condenser the liquid ammonia is collected in the

receiver so as to have a quantity stored for use and in reserve for the

fluctuating requirements.

=Expansion Valve.=--A small but important item in the system is the

expansion valve which is a valve with a controllable opening and

comparatively small. This is interposed in the line between the liquid

receiver and the cooler or expansion tank.

=Cooler or Expansion Tank.=--The next element is the cooler in whatever

form it may exist, whether it be ammonia coils submerged in brine

tank, shell and tube cooler built like a boiler in which the ammonia

surrounds the tube through which the brine solution is pumped, or

ammonia “direct” expansion coils in the air within a room, it matters

not. At this point the heat given off by the substance to be cooled is

absorbed by the ammonia and taken up for discharge to the water flowing

over the condenser.

No substance will change from a liquid to a gaseous form unless heat be

supplied to perform the work of making this change. At the outset it

was stated ammonia will boil or evaporate at 28¹⁄₂° below zero Fahr.

when under no pressure or in the open air. Further, if ammonia be

contained in a vessel and the pressure be reduced below atmosphere,

the boiling point is lowered still further. For example at 10.6 vacuum

gauge pressure the boiling point will be 40° below zero.

Imagine a brine cooler such as a tank with coil submerged and

surrounded by a brine solution: This brine is circulated through

the building and by common knowledge we know it absorbs heat and is

returned warmer than it was sent out. It is supplying the heat for

boiling the ammonia gas.

Reverting to the expansion valves: Assume there is a pressure of 180

pounds in the condenser and a liquid temperature of perhaps 85 to 90

degrees; the same conditions existing in the receiver; also assume

a pressure of 15 pounds on the ammonia coils which will produce a

temperature condition of zero. In the diagram, the coil in the tank

is attached to the expansion valve while on the other end of the coil

is made the connection to the pump or compressor. This by its action

is withdrawing the ammonia gas as rapidly as it is generated, due to

the tightness of the piston, which if it is properly fitted will pump

a vacuum upwards of 22 to 25 inches upon the system attached to it,

unless gas be supplied to fill the space. In operation, the expansion

valve is opened slightly, the liquid is freed into a space where the

pressure is lowered, a condition created for expanding the ammonia to

a gas and the heat contributed by the surrounding brine is absorbed by

the ammonia changing from a liquid to a gaseous form.

=The Cycle.=--The cycle, therefore, is a gas in the expansion tank at

low pressure and temperature, admitted to the pump or compressor under

this condition, compressed to a small volume and increased in pressure,

discharged in this condition to the condenser where it becomes a liquid

and in a condensed form at a lowered temperature and ready to return to

the expansion tank to be used over again.

Ammonia gas is the heat carrier. If it be used in packing house

service, either it absorbs the heat directly from the rooms in which

the animals are suspended or the brine in the tank is circulated

through the rooms to absorb the heat and carry it back to the cooler or

expansion tank.

=Condensing Water.=--In Chapter II reference was made to the condensing

water for refrigerating system. This is important because the lower

its temperature, the less the pressure will be created which means the

less the power must be exerted in the production of the mechanical

refrigerating effect. The water flowing over the condenser carries

the heat to the sewer. Thus the heat from the carcasses, the sun heat

on the walls of the building, the actinic rays through the windows,

the heat from the men employed within, that from the electric lights

within, and that absorbed from the earth upon which the building stands

must all be collected and eventually passed into the sewer.

=Absorption Equipment.=--Absorption refrigeration equipment is used to

some extent in packing house work, but its complexity makes unnecessary

an attempt of its description in this work.

=Unit Basis.=--The unit basis of refrigeration commonly used in

expressing quantity is tons of refrigeration, meaning the tons of

refrigerating duty that can be performed per day of twenty-four hours.

The standard measurement per ton as adopted by the American Society of

Refrigerating Engineers, is a cooling effect equal to 288,000 B.t.u.,

being equivalent to the extraction of this quantity of heat from any

substance.

It has been established by the Bureau of Standards that in freezing one

pound of water at 32° F., to ice at 32° F., 143.5 British thermal units

of heat must be withdrawn from the water. For convenience in practice

the fractional part is ignored, and 144 B.t.u. per pound of water is

accepted as standard in calculations.

=Computing From Unit Basis.=--If 144 B.t.u. are withdrawn from each

pound of water at 32° F. to convert the water into ice at the same

temperature, the melting of the pound of ice at the same temperature

must re-absorb an equal heat in the process of freezing, consequently

the melting of one ton (2,000 pounds) of ice to water at the same

temperature would absorb 2,000 × 144 B.t.u., or 288,000 B.t.u., the

accepted standard for computing the heat absorbed in the performance of

one ton of refrigeration duty. In ice melting this absorption of heat

is _latent_, not sensible to the thermometer, as no change is apparent

by thermometer test in the temperature of the ice and the water,

nevertheless an appreciable _cooling_ of surrounding is measurable

by thermometer wherever ice melting takes place; for example, in an

air-tight room, or in contact with solid substances, or with liquids,

having a higher temperature than 32° F.

=How Rated.=--The rating of refrigerating compressors as usually stated

by manufacturers is expressed in tons. This refers to the tons of duty

that a machine will develop in a period of twenty-four hours continuous

operation under assumed conditions of about fifteen pounds gauge, back

or suction pressure, and 185 pounds head pressure. To perform this

duty the compressor should be of sufficient size to displace or pump

a volume of gas equal to 4¹⁄₄ cubic feet per minute. This rating of

the machine is proper when you are producing temperatures of about

32° F. or over, and presupposes the plant to be properly balanced as

to condensers, and to be properly provided with liquid receivers, oil

extractors and other complementary equipment.

=Freezer-Requirement.=--The growing demand for freezer space in and

about packing houses, however, is so important that special means and

methods must be provided to meet the conditions. It is impossible

to produce freezer temperatures and conditions under the same back

pressure as described above; the back pressures must be lowered and

in doing so the capacity of the compressor is reduced very rapidly.

The same compressor producing one hundred tons refrigeration duty at

fifteen pounds back pressure and 185 pounds head pressure will only

perform half the work when operating under a back pressure of five

pounds, the head pressure remaining the same.

The purchaser must never lose sight of the fact that in cooling freezer

spaces the compressor capacity is reduced practically by half and that

this is applicable to all portions of the system working under these

conditions.

=System to Adopt.=--No hard and fast rule can be adopted regarding

the system of refrigeration to be adopted, whether by use of brine

circulation or direct expansion. The case in hand and the nature of the

business to be done seems to govern. For example, if the plant in which

the business is mixed, wherein hogs, cattle and sheep are killed,

curing performed, and lard made, with a limited amount of freezing,

brine circulation for general use would seem the better. The excellent

results obtained by the use of spray coolers, later described, seem to

point to its use in chilling coolers, with brine circulated through

ceiling or wall coils for cooling storage rooms.

=Freezers in Small Plants.=--If the plant be quite moderate in size

and only sufficient to justify the installation of one compressor the

amount of space required for freezing purposes is thus limited, and if

commercial freezer space is available it is a question as to whether

the operator can afford to deplete his small equipment capacity by

installing freezers.

[Illustration: FIG. 16.--SUCTION CONNECTION FOR DUO-PURPOSE COMPRESSOR.]

=Cylinder Arrangements.=--If the plant be sufficiently large so that

the machine equipment can be afforded in two units then it would be

proper to install freezers. Supposing then that the plant justifies

this arrangement the compressors would be connected to the brine

tank for chilling purposes, and to the closed cooler for circulating

purposes. The gland end of the compressors would be arranged so that

they could be operated independently upon the freezer space at will.

=Why Brine Circulation.=--The chief reason for using brine in the

moderate sized plant is that with a reasonably large brine capacity

there is a reserve cold (so to speak) stored in the brine which will

permit of stopping the compressor, the brine continuing in circulation

by pumping, and there is less likelihood of changes in temperature.

Direct expansion chilling requires an almost constant machine operation.

=Air Circulating.=--The chilling of packing houses and methods involved

are various, each with its advocates. In Europe and where English

methods are followed the system is chiefly forced draft. This system

has been used to some extent in the United States, but the majority of

the coolers are handled with lofts, and circulation therefrom is of

natural sequence. The cellars and freezers are handled by pipes hung in

the rooms.

=Force Draft.=--The force draft or indirect cooling system consists of

forcing chilled air, cooled by passing through batteries of expansion

coils operated dry, or over which brine is passed, through a series

of ducts, and withdrawing it; thence passing it through the coils and

repeating. It is not favored among American packers owing to a belief

that it increases shrinkage, and tends to darken beef; that large

quantities of cold air are lost through open doors; because of the

expense of operating fans, as well as the room taken up by ducts and

the interference occasioned with meat rails.

=Coil Room Systems.=--The overhead bunker system as described under

“_Construction_” in this work details the application of the United

States practice.

Accepting the use of the coil room system and of still storage the

question arises as to the application. A visit of inspection to the

various packing plants throughout America will impress one with the

fact of the existence of a wide variation of opinion and practice with

regard to the methods of applying refrigeration for packing house

purposes. There are two principal applications--direct expansion,

wherein the ammonia gas is circulated through the coils throughout the

premises, and brine circulation, open or closed, where chilled brine is

circulated throughout the works.

=Brine Chilling.=--The two types of brine chilling, open and closed,

produce the same result, except as to the actual brine cooler, of which

there are several, namely:

(1) Brine tank in which are submerged ammonia expansion coils.

(2) Double or triple pipe coolers in which brine and ammonia are

circulated in annular spaces between pipes.

(3) Shell type coolers in which the brine is passed through tubes

within a shell similar to an ordinary flue boiler.

For a close brine system, which is the term applied to a system where

brine is circulated through pipes and not exposed to the atmosphere

so as to absorb moisture, the shell type cooler is a convenient and

economical means of chilling brine. It is so readily applicable to the

use of a balanced system, thereby lessening the power requirement for

pumping.

Double pipe coolers can be used in the same method, but are not quite

so favorably considered owing to the aggregate quantity of joints.

Either the shell type cooler or the double pipe cooler can be safely

used with an open system. The open type brine system is any system used

wherein the cooling effect is produced by bringing the cold brine in

direct contact with the air to be chilled, as in the spray system, the

“Gardner” sheet system, or an open pan system.

=Brine Methods--Recommendation.=--Where it would seem best for other

reasons to use a brine system, and the plant would justify the

expenditure, it would appear well to use a double brine system--open

brine in the hog chill rooms, and a closed system on the freezers, beef

chill rooms, storage rooms.

=Types of Brine Coolers.=--Open tanks with submerged coils are used on

some plants. The investment is greater, but the risk is slightly less

than in the use of closed type brine coolers, commonly called shell and

tube type. Unless the engineering force of the plant is fully qualified

and alert, there is danger of diluted brine and freezing the solution

in shell type coolers, which is likely to split the tubes, causing

leaks and the possibility of brine finding its way to the ammonia

compressors, rendering them liable to damage of a serious nature.

Whereas, with the open type tank and submerged coils, weakened brine

might cause ice to form on the expansion pipes and render them inert,

but no comparable damage could arise. However, we advocate an alert

engineering force and the closed system.

[Illustration: FIG. 17.--DIAGRAM SHOWING BALANCED BRINE SYSTEM.]

=Balanced Brine System.=--The balanced brine system as referred to in

the preceding, is indicated by diagram and has the advantage of keeping

the pipes full at all times, also of reducing the power requirement to

the actual friction through the pipes in the shell type cooler, and a

slight increase for passing through the coils. In practice twenty to

twenty-five pounds friction represents the total head to pump against

in a building nine stories high. The two types of the balanced brine

system are as follows:

_Open System._--Beginning at shell and tube coolers the brine passes

into supply pipes which decrease in size as they approach the ends. The

return line tapers in opposite direction. The pressure carried is only

sufficient to make a sufficiently rapid circulation.

A small pump is inserted in the line so that the pressure can be

increased on that portion through the spray nozzles. This lessens the

power over carrying the entire system at a high pressure.

The balance tank is located at such point as will best serve to collect

the brine from closed coils and the return from the spray coolers. A

vacuum valve is put on the closed line to prevent siphon.

A return connection to the main pumps is made, and also connections to

the concentrator from balance tank so that a portion of the brine can

be concentrated.

This system requires more concentration than the closed system. It has

the advantage that coolers can be used as sharp freezers if insulation

be proper.

_Closed System._--Beginning at shell and tube coolers the discharge

mains and piping are the same as for the open system. Return mains as

indicated. Balance tank is located elevated above upper coils.

A localized defrosting system is installed with individual pump

circulating brine over coils, continuously as required. The collecting

tank is located as near as convenient to lessen pumping head. The brine

flowing over coils in the lofts is concentrated to a strength equal to

circulating brine and introduce into circulation replenishing brine for

defrosting from mains. Concentrator is located where suitable.

In using closed coils the arrangement is different for beef and hogs so

as to assist in the circulation for hog cooler with a view to producing

uniform temperatures.

[Illustration: FIG. 18.--CONCENTRATING ARRANGEMENT, BALANCE BRINE

SYSTEM, CLOSED TYPE.]

In any system using open brine, there is a quite appreciable gain in

the quantity of brine in the system, and a weakening of its strength

lowering the freezing point. This necessitates vigilance as if the

brine weaken too much there is a possibility of it freezing solidly and

insulating submerged coils in an open brine tank rendering them inert

or splitting the pipes in a shell type cooler with disastrous results.

It is consequently necessary to evaporate the brine which can be done

with a concentrator as provided for in Figs. 17 and 18.

The concentrator apparatus consists of a balance or storage tank in

elevated position according to whether the closed or open system is

used; one or more stands of pipe coils; a catch pan for concentrated

brine; a reservoir and a small pump for passing brine into system.

The brine flows from storage tank, entering the bottom pipe of the

coils and passes upward through seventeen pipes, from which point it

is delivered to the trough at the top of the coil and allowed to flow

down over the entire battery of pipes, steam being circulated through

the top six pipes, thus heating the brine and concentrating it by

evaporation. The hot concentrated brine is cooled as it passes over the

lower seventeen pipes through which it originally entered as cold weak

brine.

=Direct Expansion.=--Many plants are equipped completely with direct

expansion systems. This is quite satisfactory provided means are

arranged to dispose of the accumulating ice and snow on the coils.

This is particularly applicable to coils in pipe lofts where moisture

rapidly accumulates, and is accomplished by some arrangement of

defrosting such as circulating a brine over coils by permitting it to

drip over the coils, pumping over and over again.

=Two-Stage Compressors.=--The revising editor brought into prominence

the two-stage compression system by building a successfully operating

plant which functioned with quite astounding results. The system

consists of a large low temperature gas compressor and a smaller second

stage compressor, arranged the reverse to a compound steam engine.

Ammonia gas which at the low temperatures resulting when low

back-pressures are required, becomes highly attenuated (light), it

is necessary to handle a very large volume per ton of refrigeration

developed. To provide for this, the low pressure cylinder is made about

double the volume of the high pressure cylinder.

In the low pressure cylinder the gas is compressed to a pre-determined

pressure and passed at a relatively high pressure, making for a very

high efficiency. The gas is chilled by the introduction of expanded

ammonia to take up the superheat.

The use of this compressor arrangement with its refinement makes an

economical cold producing unit. A record of one year’s run follows:

TWO-STAGE COMPRESSION SYSTEM.

Per Per

year. ton.

Tons received 60,000

Cu. ft. space cooled 2,930,000

Coal cost $17,309.11 .288

Labor 15,156.73 .252

Oil and waste 1,030.82 .017

Water and chemicals 2,103.21 .035

Repairs and changes 1,698.38 .028

---------- ----

Total cost $37,298.25 .62

Expense per cu. ft. space per year .013

=Ample Capacity.=--All of the above factors must be considered in the

calculations for refrigerating requirements, and it is best to make

allowances for a considerable factor of safety over and above the

actual maximum, as well as for the economical operation of the plant.

It never pays to crowd a plant to its limit or capacity. Guard against

emergencies and possible abnormal demand for refrigeration by providing

ample equipment. The plant should be constructed as far as possible in

duplicate, not only as regards the machinery but also in the apparatus,

as a safeguard against accidents and total cessation of refrigeration.

With two machines and duplicate apparatus one-half the maximum

refrigeration is always available, and the preservation of the product

in storage is assured, even if it be found necessary to stop killing

for a sufficient period to make the repairs on the broken machinery or

apparatus, while with one machine only available, a breakdown might

result in a very serious loss and considerable damage to the stored

products.

With regard to insulation, it may be said that the best is the

most economical in the long run. There is no such thing as absolute

insulation, some heat leakage must occur through the very best

insulation, and the reduction of this heat leakage to the minimum

should be the chief object or factor for consideration. First-class

insulation costs more in original investment, but it creates a

continuous saving and economy in refrigeration, resulting oftentimes in

a less investment also in refrigerating, pumping and steam equipment.

The modern packing house · 第 4 / 29 章