CHAPTER XVIII.

POLE LINES FOR POWER TRANSMISSION.

Long transmission lines should follow the most direct routes between

generating and sub-stations as far as practicable. The number of poles,

cross-arms, and insulators increases directly with the length of line,

and the weight of conductors with the square of that length, other

factors remaining equal. Every material deviation from a straight line

must therefore be paid for at a rather high rate.

Distribution lines necessarily follow the public streets in order to

reach consumers, but the saving of the cost of a private right of way

and ease of access are the main considerations which tend to keep

transmission lines on streets and highways. Except in very rough or

swampy country, the difficulty of access to a pole line on a private

right of way is not a serious matter and should be given but little

weight. The cost of a private right of way may be more important, and

should be compared with the additional cost of the pole line and

conductors if erected on the public highway. In this additional cost

should be included any items for paving about the poles, extra pins,

insulators, and guys made necessary by frequent turns in the highway,

and the sums that may be required to secure the necessary franchises.

There is also the possible contingency of future legislation as to the

voltage that may be maintained on wires located over public streets.

These considerations taken together give a strong tendency to the

location of long transmission lines on private rights of way, especially

where the amount of power involved is great and the voltage very high.

A transmission line 80.3 miles in length recently erected between

Rochester and Pelham, N. H., by way of Portsmouth, where the generating

station is located, to feed an electric railway system, operates at

13,200 volts and is mainly located on private rights of way. Deeds

conveying the easements for this right of way provide that all trees or

branches within one rod on either side of the line may be cut away. The

transmission line between Niagara Falls and Buffalo, about twenty-three

miles long and operating at 22,000 volts, is largely on a private way

thirty feet wide.

[Illustration: FIG. 80.--Transmission Line of New Hampshire Traction

Company over Hampton River Bridge, 4,623 Feet Long.]

For the transmission between Cañon Ferry and Butte the line is mainly

located on a private way. Between Colgate and Oakland the transmission

line is mostly on private way, and this is also true of the greater part

of some other high-pressure lines in California. These private rights of

way range from fifty to several hundred feet wide, it being necessary in

forests to cut down all trees that are tall enough to fall onto the

wires.

In some cases of transmission at very high voltage two independent pole

lines are erected and one or more circuits are then run on each set of

poles. This construction has been followed on the transmission line

between Niagara Falls and Buffalo, Cañon Ferry and Butte, Welland Canal

and Hamilton, and between Colgate and Oakland. Such double pole lines

are more usually located on the same right of way, this being true of

the Cañon Ferry and Colgate systems, but this is not always the case. In

the Hamilton system the two lines of poles, one thirty-five miles and

the other thirty-seven miles in length, are located several miles apart.

The two sets of poles on a part of the Buffalo line are less than thirty

feet, on the Colgate line are twenty-five feet, and on the Cañon Ferry

line are forty feet apart.

The main reasons for the use of two pole lines instead of one are the

probability that an arc started on one circuit will be communicated to

another on the same poles, and the greater ease and safety of repairs

when each circuit is on a separate line of poles. On each pole line of

the Cañon Ferry transmission, and also on each pole line of the Colgate

transmission, there is only one three-wire circuit. On the Cañon Ferry

line each wire of the two circuits has a cross-section of only 106,500

circular mils, and on the Colgate line one circuit is of 133,225

circular mils wire and the other circuit is of 211,600 circular mils

cable. In contrast with these figures the line of the Standard Electric

Company between Electra and Mission San José, a distance of ninety-nine

miles, is made up of only three conductors, each being an aluminum cable

of 471,034 circular mils section. Inductance increases with the

frequency of the current in a conductor, and in each of the three

systems just considered the frequency is sixty cycles per second.

The use of one circuit of larger wire instead of two circuits of smaller

wire has the obvious advantage of greater mechanical strength in each

conductor, saves the cost of one pole line and of the erection of the

second circuit. With voltages above 40,000 to 50,000 on long

transmission lines there is a large loss of energy by leakage directly

through the air from wire to wire. To keep this loss within desirable

limits it may be necessary to give each wire of a circuit a greater

distance from the others of the same circuit than can readily be had if

all the wires of each circuit are mounted on one line of poles. If there

is only one three-wire circuit to be provided for, three lines of poles

or two lines with a long crosspiece between them may be set with any

desired distance between the lines so that the leakage through the air

with one wire on each pole will be reduced to a small quantity. On a

line built in this way it would be practically impossible for an arc to

start between the wires by any of the usual means.

Distances from pole to pole in the same line vary somewhat with the

number, size, and material of the conductors to be carried. On ordinary

construction in a straight line poles are often spaced from 100 to 110

feet apart--that is, about fifty poles per mile. On curves and near

corners the spacing of poles should be shorter. Poles for the 80.3

miles, mentioned in New Hampshire, are regularly located 100 feet apart.

Of the two pole lines between Niagara Falls and Buffalo, the older was

designed to carry twelve copper cables of 350,000 circular mils each,

and its poles were spaced only 70 feet apart. The newer line is designed

to carry six aluminum cables of 500,000 circular mils each and its poles

are 140 feet apart. Poles in each of the lines between Cañon Ferry and

Butte are regularly spaced 110 feet apart and each pole carries three

copper cables of 106,500 circular mils.

[Illustration: FIG. 81.--Chambly-Montreal Line Crossing the Chambly

Canal.]

[Illustration: FIG. 82.--Special Wooden Structures on Line Between Spier

Falls and Schenectady.]

The two 142-mile lines between Colgate and Oakland are each made up of

poles 132 feet apart, and one line of poles carries the three copper

conductors and the other line of poles the aluminum conductors already

named. As aluminum wire has only one-half the weight of copper wire of

equal conductivity, the length of span between poles carrying aluminum

wire may be greater than that where copper is used. Only a part of the

strain on poles is due to the weight of wires carried, however. Where a

body of water must be crossed, a very long span, with special supports

for the wires at each side, may be necessary. A case of this sort was

met where the Colgate and Oakland line crosses the Carquinez Straits at

a point where the waterway is 3,200 feet wide. It was necessary to have

the lowest part of the cables across these straits at least 200 feet

above the surface of the water so that vessels with the tallest masts

could pass underneath. To secure the necessary elevation for the cables

a steel tower was built on each bank of the straits at such a point that

the distance between the points for cable support on the two towers is

4,427 feet apart. As the banks rise rapidly from the water level, one

steel tower was given a height of only 65 feet, while the height of the

other was made 225 feet. Between these two towers four steel cables were

suspended, each cable being made up of nineteen strands of galvanized

steel wire, having an outside diameter of seven-eighths inch and

weighing 7,080 pounds for the span. The breaking strain of each cable is

98,000 pounds, and it has the electrical conductivity of a No. 2 copper

wire. The cables are simply supported on the towers by steel rollers,

and the pull of each cable, amounting to twelve tons, is taken by an

anchorage some distance behind each tower, where the cable terminates.

Each anchorage consists of a large block of cement deeply embedded in

the ground, and with anchor bolts running through it. Each cable is

secured to its anchorage through a series of strain insulators, and the

regular line cables of copper and aluminum are connected with the steel

cables just outside of the shelter built over the strain insulators of

each anchor. Steel cables were used for the long span across the straits

because of the great tensile strength that could be had in that metal.

This span is, no doubt, the longest and highest that has ever been

erected for electrical transmission at high voltage.

[Illustration: FIG. 83.--Special Structure on Line Between Spier Falls

and Schenectady.]

It has been suggested in one instance that steel towers ninety feet high

and 1,000 feet apart be substituted for pole lines and the wires strung

from tower to tower. Such construction would increase the difficulty of

insulation and would cost more at the start than a line of wooden poles.

The question is whether a lower maintenance and depreciation rate for

the steel towers would offset their disadvantages compared with poles.

Pole lines should be staked out with a transit, and the same instrument

can be used to give a perpendicular position to each pole and bring it

into line. Wooden poles are used in most cases of high-voltage

transmission lines. Iron poles would make it unsafe to work on any

circuit carried by them when it was transmitting current at high

voltage. With iron poles a defective insulator might lead to the

destruction of the conductors at that point through continuous arcing on

to the iron.

[Illustration: FIG. 84.--Crossing of Delaware and Hudson Railway Tracks

by 30,000-volt Line at Saratoga, N. Y.]

The kinds of wood used for poles vary in different sections of the

country. In New England, chestnut poles are a favorite and were used on

the 80.3 miles of transmission line mentioned in New Hampshire. Cedar

poles are used to some extent in nearly all parts of the country,

including Canada. Spruce and pine poles are employed to some extent,

especially in lengths of more than fifty feet. In the Rocky Mountain

region and in California round cedar poles from the forests of Oregon,

Washington, and Idaho are much used. Sawed redwood poles from the trunks

of large trees were erected on the 147-mile line between Electra

power-house and San Francisco. For the Colgate and Oakland line Oregon

cedar poles were selected, and the transmission between Cañon Ferry and

Butte was carried out with cedar poles from Idaho. For transmission

circuits it is far more important at most points to have poles very

strong rather than very long. Where wires or obstructions must be

crossed by the high-voltage circuits the poles should be long enough to

carry these circuits well above everything else. In the open country,

where no obstructions are to be avoided, it does not pay to use poles

with a length greater than thirty-five feet.

[Illustration: FIG. 85.--Pole Line from Spier Falls over Mount

McGregor.]

Short poles offer less surface to the wind, the length of the lever

through which wind pressure acts to break the pole at the ground

decreases with the length of pole, and the shorter the poles the smaller

is the strain on struts and guy wires. If poles are only thirty or

thirty-five feet long, they may be large in diameter without excessive

cost. As a rule, no pole should be used with a top less than seven

inches in diameter, and a pole with this top should not be required to

carry more than three wires. A pole with seven- or eight-inch top and

thirty feet long should measure not less than twelve inches in diameter

at the butt. For longer poles the diameters at the butt should increase

up to at least eighteen inches for a round pole sixty feet long.

In the New Hampshire transmission above named the standard length of

poles is thirty-five feet. On the line between Cañon Ferry and Butte the

poles range from thirty-five to ninety feet in length. The round cedar

poles used in the Colgate and Oakland line range from twenty-five to

sixty feet in length, from eight to twelve inches diameter at the top,

and from twelve to eighteen inches diameter at the butt. On the line

between Electra and San Francisco the square-sawed redwood poles are

reported to have the following dimensions, in a paper read at the annual

convention of Edison Illuminating Companies in 1902.

+-------+-------+---------------+----------+

|Height,| Top, | Butt, | Depth |

| Feet. |Inches.| Inches. |in Ground.|

+-------+-------+---------------+----------+

| | | | |

| 35 | 7 × 7 |12 × 12 | 5.5 |

| 40 | 8 × 8 |13-1/2 × 13-1/2| 6 |

| 45 | 9 × 9 |15 × 15 | 6.5 |

| 50 |10 × 10|16 × 16 | 7 |

| 60 |11 × 11|17 × 17 | 8 |

+-------+-------+---------------+----------+

The relative dimensions of these poles are of interest because, being

sawed from the trunks of large trees, they could have any desired

measurements at the tops and butts. These poles, over the greater part

of the line, carried the three aluminum cables of 471,034 circular mils

each, previously mentioned. Depth to which poles are set in the ground

ranges from about five feet for twenty-five- or thirty-foot poles to

eight feet for poles sixty feet long. In locations where the soil is

very soft or where poles must resist heavy strains the stability of each

pole may be much increased by digging the hole two feet or more larger

in diameter than the butt of the pole, and then filling in cement

concrete--one part, by measure, of Portland cement, three of sand and

five of broken stone--all around the butt of the pole after it is in the

hole. The butts of poles up to a point one foot or more above the ground

line are frequently treated with hot tar, pitch, asphalt, or carbolineum

before the poles are erected, and in Salt Lake City salt is said to be

used around pole butts after they are in the hole.

In some cases the poles of transmission lines are painted over their

entire length. Pole tops should always be pointed or wedge-shaped, to

shed water, and paint or tar should be applied to these tops. In some

cases poles are filled with crude petroleum or other preservative

compound in iron retorts, where moisture is withdrawn from the pole by

exhausting the air, and then, after treatment with dry steam, the poles

have the compound forced into them by hydraulic pressure.

In favorable soils cedar poles may remain fairly sound for twenty years,

chestnut poles more than one-half of that time, and spruce and pine

about five years. Poles up to forty feet in length may be readily set

with pike poles, but when they are much longer than this a derrick will

save time and labor. A derrick should have a little more than one-half

the length of the poles to be set.

[Illustration: FIG. 86.--Chambly-Montreal Line Crossing the Richelieu

River.]

Poles should be guyed or braced at all points where there are material

changes in the direction of the line, and on long straight stretches

about every fifth pole should be guyed or braced in both directions to

prevent the poles setting back when the line wire is cut or broken at

any point. Where there is room for wooden struts, as on a private right

of way, they should be used instead of guys because of their more

substantial character and the higher security of insulation thus

obtained. Ordinary strain insulators cannot be relied on with lines that

operate at very high voltages, and where guys must be used a timber four

by six inches and ten to twenty feet long may have the guy twisted

about each end of it and be used as a strain insulator. A guy or strut

should come well up under the lower cross-arm on a pole to avoid

breaking of the pole at the point of attachment.

Where poles have heavy circuits and several cross-arms each it is

sometimes desirable to attach a guy or strut beneath the lowest arm and

also a guy close to the pole top. Galvanized iron or steel wire is the

material best suited for guys, and the cable form has greater strength

and is more flexible than solid wire.

[Illustration: FIG. 87.--Cross-arms and Insulators on the Line Between

the Chambly Plant and Montreal.]

On the transmission line between Electra and San Francisco, which is

intended to operate at 60,000 volts, the use of guys has been mostly

avoided and struts employed instead. Where a guy had to be used, a

strain insulator of wood six by six inches and twenty feet long was

inserted in it.

The number and spacing of cross-arms on the poles of transmission lines

are regulated by the number of circuits that each pole must carry and by

the desired distance apart of the wires. Formerly it was common to carry

two or more circuits on a single line of poles, but now a frequent

practice is to give each pole line only one circuit and each pole only

one cross-arm, except that a small cross-arm for a telephone circuit is

placed some feet below the power wires. With only one transmission

circuit per pole line, one wire is usually placed at the top of the pole

and the other two wires at opposite ends of the single cross-arm. The

older pole line for the transmission between Niagara Falls and Buffalo

carried two cross-arms per pole for the power wires, these cross-arms

being two feet apart. Each cross-arm was of yellow pine, twelve feet

long, four by six inches in section, and intended to carry four

three-wire circuits, but only two circuits have been erected on these

two cross-arms. On the later pole line for this same transmission each

pole carries two cross-arms, the upper intended for four and the lower

cross-arm for two wires, so that one three-wire circuit may be strung on

each side of the poles, two wires on the upper and one on the lower arm

in the form of an equilateral triangle. The pole lines between Cañon

Ferry and Butte, Colgate and Oakland, and Electra and San Francisco all

have only one cross-arm for power wires per pole, and the third wire of

the circuit in each case is mounted at the top of the pole so that the

three conductors are at the corners of an equilateral triangle.

This relative position of the conductors makes it easy to transpose them

as often as desired. On the line from Cañon Ferry to Butte the

cross-arms are each eight feet long with two holes for pins

seventy-eight inches apart, and are attached to the pole five feet ten

and one-half inches from the top. Gains for cross-arms should be cut

from one to two inches deep in poles before they are raised, and one

hole for three-quarters or seven-eighths-inch bolt should be bored

through the centre of the cross-arm and of the pole at the gain. Each

cross-arm should be attached to the pole by a single bolt passing

entirely through the pole and cross-arm with a washer about three inches

in diameter next to the cross-arm. One large through bolt weakens the

pole and arm less than two smaller bolts or lag-screws, and the arm can

be more easily replaced if there is only one bolt to remove. Alternate

poles in a line should have their cross-arms bolted on opposite sides,

and at corners double arms should be used.

Yellow pine is a favorite wood for cross-arms, though other varieties

are also used. The large, long pins necessary on high voltage lines tend

to increase the sectional area of cross-arms, and a section less than

five and one-half by four and one-half inches is seldom desirable. On

the line between Electra and San Francisco, which carries the three

aluminum cables of 471,034 circular mils each, the cross-arms of Oregon

pine have a section of six by six inches each. Standard dimensions of

some smaller cross-arms are four and three-quarters by three and

three-quarters inches, but it may be doubted whether these arms are

strong enough for long transmission work. Cross-arms should be surfaced

all over and crowned one-quarter to one-half inch on top so as to shed

water. After being kiln dried, cross-arms should be boiled in asphaltum

or linseed oil to preserve the wood and give it higher insulating

properties. Cross-arms longer than five feet should be secured by braces

starting at the pole some distance below each arm and extending to

points on the arm about half-way between the pole and each end of the

arm.

[Illustration: FIG. 88.--Tail Race and Pole Line at Chambly, Quebec

Power-station.]

Each brace may be of flat bar iron about one and one-half by one-quarter

inch in section, or the brace for both ends of an arm may be made of a

single piece of angle-iron bent into the proper shape. For high-voltage

lines it is undesirable to employ iron braces of any sort, since these

braces form a path of low resistance that comes much too close to the

pins on which the insulators and wires are mounted. Braces formed of

hard wood are much better as to insulation, and such braces of maple are

in use on the line between Butte and Cañon Ferry where the voltage is

50,000. Each brace on that line is thirty-six inches long and three

inches wide, with one end bolted to the centre of its pole and the other

end to the cross-arm twenty-three inches from the pole centre.

The line from Electra has hard-wood braces secured with wood pins.

Wood is the most common material for pins on which to mount the

insulators of high-voltage transmission circuits. Iron has been used for

pins to some extent, and its use is on the increase. Oak and locust pins

are generally used, the latter being stronger and more lasting. In

California, pins of eucalyptus wood are much used and are said to be

stronger than locust. All wooden pins should be boiled several hours in

linseed oil after being well dried. This increases the insulating and

lasting properties of the pins.

High-voltage lines require long pins to hold the lower edges of

insulators well above the cross-arms, and these pins must be much

stronger than those used on ordinary lines, because of the increased

leverage of each wire.

A pin twelve inches long over all and having a diameter of one and

one-half inches in the part that enters the cross-arm has been much used

for transmission circuits, but is much too short and weak for high

voltages. On the 50,000-volt line between Cañon Ferry and Butte the pins

are seasoned oak boiled in paraffin. Each of these pins is seventeen and

one-half inches long, two and one-half inches in diameter for a length

of four and one-half inches in the middle part, two inches in diameter

for a length of five and one-half inches that fits into the cross-arm or

pole top, and one and one-half inches in diameter at the top of the

thread inside of the insulator. These pins hold the outside edges of the

insulators nine inches above the tops of cross-arms. Each of these pins

is held in its socket by a three-eighths-inch bolt that passes entirely

through the pin and the cross-arm or pole top.

On the line between Electra and San Francisco the pins are each sixteen

and seven-eighths inches long, two and three-quarters inches in diameter

at the largest central part, and two and one-quarter inches in diameter

in the lower part, five inches long, that fits into the cross-arm or

pole top. One of these pins broke at the shoulder with a pull of 2,200

pounds at the threaded part. Carriage bolts one-half inch in diameter

pass through the cross-arm and pin two inches from the top of the arm,

and one bolt three inches from the pin on each side. Without these bolts

the arms split on test with a pull of 1,200 pounds on the pin, but with

the bolts the pin broke as above.