CHAPTER XVI.

VOLTAGE AND LOSSES ON TRANSMISSION LINES.

The voltage on a transmission line may be anything up to at least

60,000, and the weight of conductors varies inversely with the square of

the figures selected, the power, length and loss being constant.

Whatever the total line pressure, the weight of conductors varies

inversely with the percentage of loss therein.

The case of maximum loss and minimum weight of conductors is that in

which all of the transmitted energy is expended in heating the line

wires. Such a case would never occur in practice, because the object of

power transmission is to perform some useful work.

Minimum loss is theoretically zero, and the corresponding weight of

conductors is infinite, but these conditions obviously cannot be

attained in practice. Between these extremes of minimum and of infinite

weights of conductors comes every practical transmission with a line

loss greater than zero and less than 100 per cent.

To determine the weight and allowable cost of conductors, the cost of

the energy that will be annually lost in them enters as one of the

factors. At this point the distinction between the percentage of power

lost at maximum load and the percentage of total energy lost should come

into view.

Line loss ordinarily refers to the percentage of total power consumed in

the conductors at maximum load. This percentage would correspond with

that of total energy lost if the line current and voltage were constant

during all periods of operation, but this is far from the case.

A system of transmission may operate with either constant volts or

constant amperes on the line conductors, but in a practical case

constancy of both these factors is seldom or never to be had. This is

because the product of the line volts and amperes represents accurately

in a continuous-current system, and approximately in an

alternating-current system, the amount of power transmitted. In an

actual transmission system, the load--that is, the demand for power--is

subject to more or less variation at different times of the day, and the

line volts or amperes, or both, must vary with it.

If the transmission system is devoted to the operation of one or more

factories the required power may not vary more than twenty-five per cent

during the hours of daily use; but if a system of general electrical

supply is to be operated, the maximum load will usually be somewhere

between twice and four times as great as the average load for each

twenty-four hours. Such fluctuating loads imply corresponding changes in

the volts or amperes of the transmission line.

A number of rather long transmissions is carried out in Europe with

continuous, constant current, and in such systems the line voltage

varies directly with the load. As the loss of power in an electrical

conductor depends entirely on its ohms of resistance, which are constant

at any given temperature, and on the amperes of current passing through

it, the line loss in a constant-current system does not change during

the period of operation, no matter how great may be its changes of load.

For this reason the percentage of power loss in the line at maximum load

is usually smaller than the percentage of energy loss for an entire day.

If, for example, the constant-current transmission line is designed to

convert into heat 5 per cent of the maximum amount of energy that will

be delivered to it per second--that is, to lose 5 per cent of its power

at maximum load--then, when the power which the line receives drops to

one-half of its maximum, the percentage of loss will rise to 10, because

0.05 ÷ 0.5 = 0.1. So again, when the power sent through the line falls

to one-quarter of the full amount, the line loss will rise to 0.05 ÷

0.25 = 0.2, or 20 per cent.

From these facts it is clear that a fair all-day efficiency for a

constant-current transmission line can be obtained only in conjunction

with a high efficiency at maximum load, if widely varying loads are to

be operated. It does not necessarily follow from these facts as to

losses in constant-current lines that such losses should always be small

at maximum loads, for if a large loss may be permitted at full load a

still greater percentage of loss at partial loads may not imply bad

engineering.

In a large percentage of electric water-power plants some water goes

over the dam during those hours of the day when loads are light, the

storage capacity above the dam not being sufficient to hold all of the

surplus water during most seasons of the year. If, therefore, the line

loss in a constant-current transmission, where all of the daily flow of

water cannot be used, is not great enough to reduce the maximum load

that would otherwise be carried, then the fact that the percentage of

line loss at small loads is still larger is not very important.

Obviously, it makes little difference whether water goes over a dam or

through wheels to make up for a loss in the line. In a case where all

the water can be stored during small loads and used during heavy loads,

it is clearly desirable to keep the loss in a constant-current line down

to a rather low figure, say not more than five per cent, at maximum

load.

Much the greater number of electrical transmissions are carried out with

nearly constant line voltage, mostly alternating, and the line current

in such cases varies directly with the power transmitted, except as to

certain results of inductance on alternating lines. As line resistance

is constant, save for slight variations due to temperature, the rate of

energy loss on a constant-pressure line varies with the square of the

number of amperes flowing, and the percentage of loss with any load

varies directly as the number of amperes.

These relations between line losses and the amperes carried follow from

the law that the power, or rate of work, is represented by the product

of the number of volts by the number of amperes, and the law that the

power actually lost in the line is represented by the product of the

number of ohms of line resistance and the square of the number of

amperes flowing in it. In each of these cases the power delivered to the

line is, of course, measured in watts, each of which is 1/746 of a

horse-power.

Applying these laws, it appears that if the loss of a certain

constant-pressure transmission line is 10 per cent of the power

delivered to it at full load, then, when the power, and consequently the

amperes, on the line is reduced one-half, the watts lost in the line as

heat will be (1/2)² = 1/4 of the watts lost at full load, because the

number of amperes flowing has been divided by 2.

But the amount of power delivered to the line at full load having been

reduced by 50 per cent, while the power lost on the line dropped to

one-fourth of 10 per cent, or to 2.5 per cent of the full line load, it

follows that the power lost on the line at half-load is represented by

0.025 ÷ 0.5 = 0.05, or 5 per cent of the power then delivered to it.

This rise in the efficiency of a constant-pressure transmission line as

the power delivered to it decreases, together with the fact that maximum

loads on such lines continue during hardly more than one to two hours

daily, tends to raise the allowable percentage of line loss at maximum

loads.

This is so because a loss of fifteen per cent at maximum load may easily

drop to an average loss of somewhere between five and ten per cent for

the entire amount of energy delivered to a line during each day under

ordinary conditions in electrical supply. In the practical design of

transmission lines, therefore, the sizes of conductors are influenced by

the relation of the largest load to be operated to the greatest amount

of power available for its operation, and by questions of regulation, as

well as by considerations of all-day efficiency.

If the maximum load that must be carried by a transmission system during

a single hour per day requires nearly as much power as can be delivered

to the line conductors, either because of lack of water storage or of

water itself, even if it is stored, it may be desirable to design these

conductors for a small loss at maximum load, rather than to install a

steam plant.

So again, as the fluctuation in voltage at the delivery end of a

transmission line between no load and full load will amount to the

entire drop of volts in the line at full load, if the pressure at the

generating end is constant, the requirements of pressure regulation on

distribution circuits limit the drop of pressure in the transmission

conductors. For good lighting service with incandescent lamps at about

110 volts, the usual pressure, it is necessary that variations be held

within one volt either way of the pressure of the lamps--that is,

between 109 and 111 volts.

Every long-transmission system for general electrical supply necessarily

includes one or more sub-stations where the distribution lines join the

transmission circuits, and where the voltage for lighting service is

regulated. As the limits of voltage variations on lighting circuits are

so narrow, it is necessary to keep the changes of pressure on the

transmission lines themselves within moderate limits, or such as can be

compensated for at sub-stations.

This is particularly true in cases where energy transmitted over a

single circuit is distributed for both incandescent lamps and large

electric motors, because the starting and operation of such motors

causes large fluctuations of amperes and terminal voltage on the

transmission circuits. To hold such fluctuations within limits which a

sub-station can readily compensate for, it is necessary that the loss in

the transmission line be moderate, say often within ten per cent of the

total voltage delivered to it at maximum load.

Capacity and cost of equipment at generating stations go up with the

percentage of line loss, and thus serve to limit its economical amount.

For every horse-power delivered to a transmission line at a water-power

station there must be somewhat more than one horse-power of capacity in

water-wheels, at least one horse-power in generators, and frequently a

further capacity of one horse-power in step-up transformers. Every

additional horse-power lost in the line at maximum load, if the

generating plant is to be worked up to its full capacity, implies an

addition of somewhat more than one horse-power capacity in water-wheels,

one horse-power in generators, and one horse-power in transformers.

Since the cost of a generating station is thus increased as the maximum

line loss is raised, a point may be reached where any further saving in

the cost of the line is more than offset by the corresponding addition

to the cost of the station and of its operation. Just where this point,

as indicated by a percentage of line loss, is to be found depends on the

factors of each case, important among which is the length of the

transmission line.

Much effort has been made to fix some exact relation for maximum economy

between the first cost of conductors for a transmission line and the

amount of energy annually lost as heat therein. The best-known statement

applying to this case is that of Lord Kelvin, made in a paper read

before the British Association in 1881. According to the rule there laid

down, the most economical size for the conductors of a transmission line

is that for which the annual interest on first cost equals the cost of

the energy annually wasted in them.

If transmission systems were designed for the sole purpose of wasting

energy in their line conductors this rule would exactly apply, for it

simply shows how the cost of energy wasted, plus the interest on the

cost of the conductor in which it is wasted, may be brought to a

minimum. As a matter of fact, transmission systems are primarily

intended to deliver energy rather than to waste it; but of the

proportions of the entire energy to be delivered and wasted (which is

exactly what we want to know), the rule of Kelvin takes no account.

According to his rule, the cheaper the cost of power where it is

developed, the less should be paid for conductors to bring it to market.

The obvious truth is that the less the cost of power development at a

particular point, the more may be invested in a line to bring it to

market. If power cost nothing whatever at its source it would not be

worth while to build any transmission line at all if this rule is

correct.

A modification of Lord Kelvin’s rule has been proposed by which it is

said that the interest on the cost of the conductors and the annual

value of the energy lost in them should be equal, value here meaning

what the energy can be sold for. This rule would make an investment in

line conductors too large.

The entire cost of production and transmission for the delivered energy

should not be greater than the cost of a like amount of energy

developed at the point where the delivery is made. In this entire cost

of production and transmission, interest on the investment in line

conductors is only one item.

It is perhaps impossible to state any exact rule for the most economical

relation between the cost of conductors and the loss of energy therein

that will apply to every transmission. A maximum limit to the weight of

conductors may, however, be set for most cases. This limit should not

allow the annual interest and depreciation charges on the investment in

line conductors, plus all other costs of development and transmission,

to raise the total cost of the transmitted energy above the cost of

development for an equal amount of energy at the point where the

transmitted energy is delivered.

While the maximum investment in transmission conductors may be properly

limited in the way just stated, it by no means follows that this maximum

limit should be reached in every case. In the varying requirements of

actual cases, the problem may be to deliver a fixed amount of power at

the least possible cost, or to deliver the largest possible amount of

power at a cost per unit under that of development at the point of use.

Frequently a transmission system has a possible capacity in excess of

present requirements, and a line that would not be too heavy for future

business might put an unreasonable burden of interest charges on present

earnings.

The foregoing considerations apply to the design of conductors for a

transmission line after the voltage at which it is to operate has been

decided on. Quite a different set of facts should influence the

selection of this voltage. A transmission that would be entirely

impracticable with any percentage of line loss that might be selected,

if carried out at some one voltage, might represent a paying business at

some higher voltage and any one of several sizes of line conductors. The

power that could be delivered by a line of practicable cost, operated at

one voltage, might be too small for the purpose in hand, while the

available power at a higher voltage might be ample.

If any given power is to be transmitted with a given percentage of

maximum loss in line conductors, the weight of these conductors will

increase as the square of their length, and decrease as the square of

the full voltage of operation in every case.

Thus, if the length of this transmission is doubled, the weight of the

conductors must be multiplied by four, the voltage remaining the same;

but if the voltage is doubled and the line length remains unchanged, the

weight of conductors must be divided by four. With the length of line

and the voltage of transmission either lowered or raised together, the

weight of the conductors remains fixed, for constant power and loss.

An illustration of this last rule may be drawn from the case of lines

designed to transmit any given power a distance of ten miles at 10,000

volts, and a distance of fifty miles at 50,000 volts, in which the total

weight of conductors would be the same for each line if the percentage

of loss was constant.

This statement of the rule as to proportionate increase of voltage and

distance presents the advantages of high voltages in their most

favorable light. Though a uniform ratio between the voltage of operation

and the length of line allows a constant weight of conductors to be

employed for the transmission of a given power with unchanging

efficiency of conductors, yet other considerations soon limit the

advantage thus obtained.

Important among these considerations may be mentioned the mechanical

strength of line conductors, difficulties of line insulation, losses

between conductors through the air, limits of generator voltages, and

the cost of transformers.

If the ten-mile transmission at 10,000 volts, above mentioned, requires

a circuit of two No. 1/0 copper wires, the total weight of these wires

will be represented by (5,500 × 10 × 2 × 320) ÷ 1,000 = 35,200 pounds,

allowing 5,500 feet of wire per mile of single conductor to provide

something for sag between poles, and 320 pounds being the weight of bare

No. 1/0 copper wire per 1,000 feet.

When the length of line is raised to 50 miles, the two-wire circuit will

contain 5,500 × 50 × 2 = 550,000 feet of single conductor, and since the

voltage is raised to 50,000 at the same time, the total weight of

conductors will be 35,200 pounds as before. The weight of single

conductor per 1,000 feet is therefore only 64 pounds in the 50-mile

line.

A No. 7 copper wire, B. & S. gauge, has a weight of 63 pounds per 1,000

feet, and is the nearest regular size to that required for the 50-mile

line as just found. It would be poor policy to string a wire of this

size for a transmission line, because it is so weak mechanically that

breaks would probably be frequent in stormy weather. The element of

unreliability introduced by the use of this small wire on a 50-mile line

would cost far more in the end than a larger conductor.

As a rule, No. 4 B. & S. gauge wire is the smallest that should be used

on a long transmission line in order to give fair mechanical strength,

and this size has just twice the weight of a No. 7 wire of equal

length. Here, then, is one of the practical limits to the advantages

that may be gained by increasing the voltage with the length of line.

As line voltage goes up, the strain on line insulation increases

rapidly, and the insulators for a circuit operated at 50,000 volts must

be larger and of a much more expensive character than those for a

10,000-volt circuit. In this way a part of the saving in conductors

effected by the use of very high voltages on long lines is offset by the

increased cost of insulation.

Another disadvantage that attends the operation of transmission lines at

very high voltages is the continuous loss of energy by the silent

passage of current through the air between wires of a circuit. This loss

increases at a rapid rate after a pressure between 40,000 and 50,000

volts is reached with ordinary distances between the wires of each

circuit. To keep losses of this sort within moderate limits, and also to

lessen the probability of arcs on a circuit at very high voltage, the

distance of eighteen inches or two feet between conductors that carry

current at 10,000 volts should be increased to six feet or more on

circuits that operate at 50,000 volts.

Such an increase in the distance between conductors makes the cost of

poles and cross-arms greater, either by requiring them to be larger than

would otherwise be necessary or by limiting the number of wires to two

or three per pole and thus increasing the number of pole lines. These

added expenses form another part of the penalty that must be paid for

the use of very high voltages and the attendant saving in the cost of

conductors.

Apparatus grows more expensive as the voltage at which it is to operate

increases, because of the cost of insulating materials and the room

which they take up, thereby adding to the size and weight of the iron

parts.

Generators for alternating current can be had that develop as much as

13,500 volts, but such generators cost more than others of equal power

that operate at between 2,000 and 2,500 volts. These latter voltages are

as high as it is usually thought desirable to operate distribution

circuits and service transformers in cities and towns, so that if more

than 2,500 volts are employed on the transmission line, step-down

transformers are required at a sub-station. For a transmission of more

than ten miles the saving in line conductors by operation at 10,000 to

12,000 volts will usually more than offset the additional cost of

generators designed for this pressure and of step-down transformers. If

the voltage of transmission is to exceed that of distribution, it will

generally be found desirable to carry the former voltage up to 10,000

or 12,000, at least.

As the cost of generators designed for the voltage last named is less

than that of lower voltage generators plus transformers, step-up

transformers should usually be omitted in systems where these pressures

are not exceeded. For alternating pressures above 13,000 to 15,000

volts, step-up transformers must generally be employed. In order that

the saving in the weight of line conductors may more than offset the

additional cost of transformers when the voltage of transmission is

carried above 15,000, this voltage should be pushed on up to as much as

25,000 in most cases.

Power transmission with continuous current has the advantage that the

cost of generators remains nearly the same whatever the line voltage,

and that no transformers are required. Such transmissions are common in

Europe, but have hardly a footing as yet in the United States. The

reason for the uniform cost of continuous-current generators is found in

the fact that they are connected in series to give the desired line

voltage, and the voltage of each machine is kept under 3,000 or 4,000.

As a partial offset to the low cost of the continuous-current generators

and to the absence of transformers, there is the necessity for

motor-generators in a sub-station when current for lighting as well as

power is to be distributed.

In spite of the various additions to the cost of transmission systems

made necessary by the adoption of very high voltages, these additions

are much more than offset by the saving in the cost of conductors on

lines 30, 50, or 100 miles in length. In fact, it is only by means of

voltages ranging from 25,000 to 50,000 that the greatest of these

distances, and others up to more than 140 miles, have been successfully

covered by transmission lines. Above 60,000 volts there has been but

slight practical experience in the operation of transmission lines.

Calculations to determine the sizes of conductors for electric

transmission lines are all based on the fundamental law discovered by

Ohm, which is that the electric current flowing in a circuit at any

instant equals the electric pressure that causes the current divided by

the electric resistance of the circuit itself, or current = pressure ÷

resistance.

Substituting in this formula the units that have been selected because

of their convenient sizes for practical use, it becomes, amperes = volts

÷ ohms, in which the ohm is simply the electrical resistance, taken as

unity, of a certain standard copper bar with fixed dimensions.

The ampere is the unit flow of current that is maintained with the unit

pressure of one volt between the terminals of a one-ohm conductor. When

this formula is applied to the computation of transmission lines the

volts represent the electrical pressure that is required to force the

desired amperes of current through the ohms of resistance in any

particular line, and these volts have no necessary or fixed relation to

the total voltage at which the line may operate. Thus, if the total

voltage of a transmission system is 10,000, it may be desirable to use

500, 1,000, or even 2,000 volts to force current through the line, so

that one of these numbers will represent the actual drop or loss of

volts in the line conductors when the number of amperes that represent

full load is flowing. As it is a law of every electric circuit that the

rate of transformation of electric energy to heat or work in each of its

several parts is directly proportional to the drop of voltage therein,

it follows that a drop of 500 or 1,000 or 2,000 volts in the conductors

of a 10,000-volt transmission line at full load would correspond to a

power loss of five to ten or twenty per cent respectively. Any other

part of 10,000 volts might be selected in this case as the pressure to

be lost in the line. Evidently no formula can give the number of volts

that should be lost in line conductors at full load for a given power

transmission, but this number must be decided on by consideration of the

items of line efficiency, regulation, and the ratio of the available

power to the required load.

Having decided on the maximum loss of volts in the line conductors, and

knowing the full voltage of operation, the power and consequently the

number of amperes delivered to the line at maximum load, the resistance

of the conductors may then be calculated by the formula, amperes = volts

÷ ohms. Thus, if the proposition is to deliver 2,000,000 watts or 2,000

kilowatts to a two-wire transmission line with a voltage of 20,000, the

amperes in each wire must be represented by 2,000,000 ÷ 20,000 = 100.

With a drop of ten per cent or 2,000 volts in the two line conductors,

their combined resistance must be found from 100 = 2,000 ÷ ohms, and the

ohms are therefore twenty. If the combined length of the two conductors

is 200,000 feet, corresponding to a transmission line of a little under

twenty miles, the resistance of these conductors must be 20 ÷ 200 = 0.1

ohm per 1,000 feet. From a wire table it may be seen that a No. 1/0 wire

of copper, B. & S. gauge, with a diameter of 0.3249 inch, has a

resistance of 0.1001 ohm per 1,000 feet at the temperature of 90°

Fahrenheit, a little less at lower temperatures, and is thus the

required size. Obviously, the resistance of twenty ohms is entirely

independent of the length of the line, all the other factors being

constant, and wires of various sizes will be required for other

distances of transmission.

It is often convenient to find the area of cross section for the desired

transmission conductor instead of finding its resistance. This can be

done by substituting in the formula, amperes = volts ÷ ohms, the

expression for the number of ohms in any conductor, and then solving as

before.

Electrical resistance in every conductor varies directly with its

length, inversely with its area of cross section, and also has a

constant factor that depends on the material of which the conductor is

composed. This constant factor is always the same for any given

material, as pure iron, copper, or aluminum, and is usually taken as the

resistance in ohms of a round wire one foot long and 0.001 inch in

diameter, of the material to be used for conductors. Such a wire is said

to have an area in cross section of one circular mil, because the square

of its diameter taken as unity is still unity, that is, 1 × 1 = 1. In

like manner, for the convenient designation of wires by their areas of

cross-section, each round wire of any size is said to have an area in

circular mils equal to the square of its diameter measured in units of

0.001 inch each. Thus, a round wire of 0.1 inch diameter has an area of

100 × 100 = 10,000 circular mils, and a round wire one inch in diameter

has an area of 1,000 × 1000 = 1,000,000 circular mils. The circular mils

of a wire do not express its area of cross section in terms of square

inches, but this is not necessary since the resistance of a wire of one

circular mil is taken as unity. Obviously, the areas of all round wires

are to each other as are their circular mils.

From the foregoing it may be seen that the resistance of any round

conductor is represented by the formula, ohms = _l_ × _s_ ÷ circular

mils, in which _l_ represents the length of the conductor in feet, _s_

is the resistance in ohms of a wire of the same material as the

conductor but with an area of one circular mil and a length of one foot,

and the circular mils are those of the required conductor. Substituting

the quantity, _l_ × _s_ ÷ circular mils, for ohms in the formula,

amperes = volts ÷ ohms, the equation, amperes = volts ÷ (_l_ × _s_ ÷

circular mils), is obtained, and this reduces to circular mils = amperes

× _l_ × _s_ ÷ volts. For any proposed transmission all of the quantities

in this formula are known, except the desired circular mils of the line

conductors. The constant quantity s is about 10.8 for copper, but is

conveniently used as eleven in calculation, and this allows a trifle for

the effects of impurities that may exist in the line wire.

The case above mentioned, where 2,000 kilowatts were to be delivered to

a transmission line at 20,000 volts, and a loss of 2,000 volts at full

load was allowed in the line conductors, may now be solved by the

formula for circular mils. Taking the resistance of a round copper wire

0.001 inch in diameter and one foot long as eleven ohms, and

substituting the 100 amperes, 2,000 volts, and 200,000 feet of the

present case in the formula, gives circular mils = (100 × 200,000 × 11)

÷ 2,000 = 110,000. The square root of this 110,000 will give the

diameter of a copper wire that will exactly meet the conditions of the

case, or the more practical course of consulting a table of standard

sizes of wire will show that a No. 1-0 B. & S. gauge, with a diameter of

0.3249 inch, has a cross section of 105,500 circular mils, or about five

per cent less than the calculated number, and is the size nearest to

that wanted. As this No. 1-0 wire will give a line loss at full load of

about 10.5 per cent, or only one-half of one per cent more than the loss

at first selected, it should be adopted for the line in this case.

The formula just made use of is perfectly general in its application,

and may be applied to the calculation of lines of aluminum or iron or

any other metal just as well as to lines of copper. In order to use the

formula for any desired metal, it is necessary that the resistance in

ohms of a round wire of that metal one foot long and 0.001 inch in

diameter be known and substituted for _s_ in the formula. This

resistance of a wire one foot long and 0.001 inch in diameter is called

the specific resistance of the substance of which the wire is composed.

For pure aluminum this specific resistance is about 17.7, for soft iron

about sixty, and for hard steel about eighty ohms. The use of these

values for _s_ in the formula will therefore give the areas in circular

mils for wires of these three substances, respectively, for any proposed

transmission line. In the same way the specific resistance of any other

metal or alloy, when known, may be applied in the formula.

The foregoing calculations apply accurately to all two-wire circuits

that carry continuous currents, whether these circuits operate with

constant current, constant pressure, or with pressure and current both

variable. Where circuits are to carry alternating currents, certain

other factors may require consideration. Almost all transmissions with

alternating currents are carried out with three-phase three-wire, or

two-phase four-wire, or single-phase two-wire circuits. Of the entire

number of such transmissions, those with the three-phase three-wire

circuits are in the majority, next in point of number come the two-phase

transmissions, and lastly a few transmissions are carried out with

single-phase currents. The voltage of a continuous-current circuit, by

which the power of the transmission is computed and on which the

percentage of line loss is based, is the maximum voltage operating

there; but this is not true for circuits carrying alternating currents.

Both the volts and amperes in an alternating circuit are constantly

varying between maximum values in opposite directions along the wires.

It follows from this fact that both the volts and amperes drop to zero

as often as they rise to a maximum. It is fully demonstrated in books on

the theory of alternating currents, that with certain ideal

constructions in alternating generators, and certain conditions in the

circuits to which they are connected, the equivalent or, as they are

called, the virtual values of the constantly changing volts and amperes

in these circuits are 0.707 of their respective maximum values. Or, to

state the reverse of this proposition, the maximum volts and amperes

respectively in these circuits rise to 1.414 times their equivalent or

virtual values. These relations between maximum and virtual volts and

amperes are subject to some variations with actual circuits and

generators, but the virtual values of these factors, as measured by

suitable volt- and amperemeters, are important in the design of

transmission circuits, rather than their maximum values. When the volts

or amperes of an alternating circuit are mentioned, the virtual values

of these factors are usually meant unless some other value is specified.

Thus, as commonly stated, the voltage of a single-phase circuit is the

number of virtual volts between its two conductors, the voltage of a

two-phase circuit is the number of virtual volts between each pair of

its four conductors, and the voltage of a three-phase circuit is the

number of virtual volts between either two of its three conductors.

Several factors not present with continuous currents tend to affect the

losses in conductors where alternating currents are flowing, and the

importance of such effects will be noted later. In spite of such

effects, the formula above discussed should be applied to the

calculation of transmission lines for alternating currents, and then the

proper corrections of the results, if any are necessary, should be made.

With this proviso as to corrections, the virtual volts and amperes of

circuits carrying alternating currents may be used in the formula in the

same way as the actual volts and amperes of continuous current circuits.

Thus, reverting to the above example, where 2,000 kilowatts was to be

delivered at 20,000 volts to a transmission line in which the loss was

to be 2,000 volts, the kilowatts should be taken as the actual rate of

work represented by the alternating current, and the volts named as the

virtual volts on the line. The virtual amperes will now be 100, as were

the actual amperes of continuous current, and the size of line conductor

for a single-phase alternating transmission will therefore be 1-0, the

same as for the continuous-current line. If the transmission is to be

carried out on the two-phase four-wire system, the virtual amperes in

each of these wires will be fifty instead of 100, as the power will be

divided equally between the two pairs of conductors, and each of these

four wires should have a cross-section in circular mils just one-half as

great as that of the No. 1-0 wire. The required wire will thus be a No.

3 B. & S. gauge, of 52,630 circular mils, this being the nearest

standard size. In weight the two No. 1-0 wires and the four No. 3 wires

are almost equal, and they should be exactly equal to give the same loss

in the single-phase and the two-phase lines. For a three-phase circuit

to make the transmission above considered, each of the three conductors

should have an area just one-half as great as that of each of the two

conductors for a single phase circuit, the loss remaining as before, and

the nearest standard size of wire is again No. 3, as it was for the

two-phase line. This is not a self-evident proposition, but the proof

can be found in books devoted to the theory of the subject. From the

foregoing it is evident that while the single-phase and two-phase lines

require equal weights of conductors, all other factors being the same,

the weight of conductors in the three-phase line is only seventy-five

per cent of that in either of the other two. Neglecting the special

factors that tend to raise the size and weight of alternating-current

circuits, the single-phase and two-phase lines require the same weight

of conductors as does a continuous-current transmission of equal power,

voltage, and line loss. It should be noted that in each of these cases

the factor _l_ in the formula for circular mils denotes the entire

length of the pair of conductors for a continuous-current line, or

double the distance of the transmission with either of the

alternating-current lines.

Having found the circular mils of any desired conductor, its weight per

1,000 feet can be found readily in a wire table. In some cases it is

desirable to calculate the weight of the conductors for a transmission

line without finding the circular mils of each, and this can be done by

a modification of the above formula. A copper wire of 1,000,000 circular

mils weighs nearly 3.03 pounds per foot of its length, and the weight of

any copper wire may therefore be found from the formula, pounds =

(circular mils × 3.03 × _l_) ÷ 1,000,000, in which pounds indicates the

total weight of the conductor, _l_, its total length, and the circular

mils are those of its cross-section. This formula reduces to the form,

circular mils = (1,000,000 × pounds) ÷ (3.03 × _l_) and if this value

for circular mils is substituted in the formula above given for the

cross-section of any wire, the result is (1,000,000 × pounds) ÷ (3.03 ×

_l_) = (_l_ × amperes × 11) ÷ volts. Transposition of the factors in

this last equation brings it to the form, pounds = (3.03 × _l_² ×

amperes × 11) ÷ (1,000,000 × volts), which is the general formula for

the total weight of copper conductors when _l_, the length of one pair,

the total amperes flowing, and the volts lost in the conductors are

known for either a continuous-current, a single-phase, or a two-phase

four-wire line.

If the value of _l_, 200,000, of amperes, 100, and of volts, 2,000, for

the transmission above considered are substituted in the formula for

total weight, just found, the result is pounds = (3.03 (200,000)² × 100

× 11) ÷ (1,000,000 × 2,000), which reduced to pounds = 66,660, the

weight of copper wire necessary for the transmission with either

continuous, single-phase or two-phase current. With three-phase current

the weight of copper in the line for this transmission will be 75 per

cent of the 66,660 pounds just found. One or more two-wire circuits may

be employed for the continuous current or for the single-phase

transmission, and if one such circuit is used the weight for each of the

two wires is obviously 33,660 pounds. For a two-phase transmission two

or more circuits of two wires each will be used, and in the case of two

circuits, if all four of the wires are of equal cross section, as would

usually be the case, the total weight of each is 16,830 pounds. If the

transmission is made with one three-phase circuit, the weight of each of

the three wires is 16,830 pounds, and their combined weight, 50,490

pounds of copper. In each of these transmission lines the length of a

single conductor in one direction is 100,000 feet, or one-half of the

length of the wires in a single two-wire circuit. For the two-wire line

the calculated weight of each conductor amounts to 66,660 ÷ 200 = 333.3

pounds per 1,000 feet. For a two-phase four-wire line and also for a

three-phase three-wire line, the weight of each conductor is 16,830 ÷

100 = 168.3 pounds per 1,000 feet. On inspection of a table of weights

for bare copper wires it may be seen that a No. 1-0 B. & S. gauge wire

has a weight of 320 pounds per 1,000 feet, and being much the nearest

size to the calculated weight of 333 pounds should be selected for the

two-wire circuit. It may also be seen that a No. 3 wire, with a weight

of 159 pounds per 1,000 feet, is the size that comes nearest to the

calculated weight of 168 pounds, and should therefore be employed in the

three-wire and the four-wire circuits, for two- and three-phase

transmissions. Either a continuous-current, single-phase, two-phase, or

three-phase transmission line may of course be split up into as many

circuits as desired, and these circuits may or may not be designed to

carry equal portions of the entire power. In either case the combined

weights of the several circuits should equal those above found, the

conditions as to power, loss, and length of line remaining constant. It

will be noted that the formulæ for the calculation of the circular mils

and for the weight of the conductors in the transmission line lead to

the selection of the same sizes of wires, as they obviously should do.

Several laws governing the relations of volts lost, length and weight of

line conductors, may be readily deduced from the above formulæ.

Evidently the circular mils and weight of line conductors vary inversely

with the number of volts lost in them when carrying a given current, so

that doubling this number of volts reduces the circular mils and weight

of conductors by one-half. If the length of the line changes, the

circular mils of the required conductors change directly with it, but

the weight of these conductors varies as the square of their length.

Thus, if the length of the line conductors is doubled, the cross-section

in circular mils of each conductor is also doubled, and each conductor

is therefore four times as heavy as before for the same current and loss

in volts. Should the length of the conductors and also the number of

volts lost in them be varied at the same rate, the circular mils of each

conductor remain constant, and its weight increases directly with the

distance of transmission. Thus, with the same size of line wire, both

the number of volts lost and the total weight are twice as great for a

100- as for a fifty-mile transmission. If the total weight of conductors

is to be held constant, then the number of volts lost therein must vary

as the square of their length, and their circular mils must vary

inversely as the length. So that if the length of a transmission line is

doubled, the circular mils for conductors of constant weight are divided

by two, and the volts lost are four times as great as before. Each of

these rules assumes that the watts and percentage of loss in the line

are constant.

The above principles and formulæ apply to the design of transmission

lines for either continuous or alternating currents, but where the

alternating current is employed certain additional factors should be

considered. One of these factors is inductance, by which is meant the

counter-electromotive force that is always present and opposed to the

regular voltage in an alternating current circuit. One effect of

inductance is to cut down the voltage at that end of the line where the

power is delivered to a sub-station, just as is also done by the ohmic

resistance of the line conductors. Between the loss of voltage due to

line resistance and the loss due to inductance there is the very

important difference that the former represents an actual conversion of

electrical energy into heat, while the latter is simply the loss of

pressure without any material decrease in the amount of energy. While

the loss of energy in a transmission line depends directly on its

resistance, the loss of pressure due to inductance depends on the

diameter of conductors without regard to their resistance, on the length

of the circuit, the distance between the conductors, and on the

frequency or number of cycles per second through which the current

passes. As a result of these facts, it is not desirable or even

practicable to use inductance as a factor in the calculation of the

resistance or weight of a transmission line. On transmission lines, as

ordinarily constructed, the loss of voltage due to inductance generally

ranges between 25 and 100 per cent of the number of volts lost at full

load because of the resistance of the conductors. This loss through

inductance may be lowered by reducing the diameter of individual wires,

though the resistance of all the circuits concerned in the transmission

remains the same, by bringing the wires nearer together and by adopting

smaller frequencies. In practice the volts lost through inductance are

compensated for by operating generators or transformers in the

power-plant at a voltage that insures the delivery of energy in the

receiving-station at the required pressure. Thus, in a certain case, it

may be desirable to transmit energy with a maximum loss of ten per cent

in the line at full load, due to the resistance of the conductors, when

the effective voltage at the generator end of the line is 10,000, so

that the pressure at the receiving-station will be 9,000 volts. If it

appears that the loss of pressure due to inductance on this line will be

1,000 volts, then the generators should be operated at 11,000 volts,

which will provide for the loss of 1,000 volts by inductance, leave an

effective voltage of 10,000 on the line, and allow the delivery of

energy at the sub-station with a pressure of 9,000 volts, when there is

a ten-percent loss of power due to the line resistance.

Inductance not only sets up a counter-electromotive force in the line,

which reduces the voltage delivered to it by generators or transformers,

but also causes a larger current to flow in the line than is indicated

by the division of the number of watts delivered to it by the virtual

voltage of delivery. The amount of current increase depends on both the

inductance of the line itself and also on the character of its connected

apparatus. In a system with a mixed load of lamps and motors there is

quite certain to be some inductance, but it is very hard to predetermine

its exact amount. Experience with such systems shows, however, that the

increase of line current due to inductance is often not above five and

usually less than ten per cent of the current that would flow if there

were no inductance. To provide for the flow of this additional current,

due to inductance, without an increase of the loss in volts because of

ohmic resistance, the cross section of the line conductors must be

enlarged by a percentage equal to that of the additional current. This

means that in an ordinary case of a transmission with either single,

two, or three-phase alternating current, the circular mils of each line

wire, as computed with the formulæ above given, should be increased by

five to ten per cent. Such increase in the cross section of wires of

course carries with it a like rise in the total weight of the conductors

for the transmission. If wire of the cross section computed with the

formulæ is employed for the alternating current transmission, inductance

in an ordinary case will raise the assumed line loss of power by five to

ten per cent of what it would be if no inductance existed. Thus, with

conductors calculated by the formulæ for a power loss of ten per cent at

full load, inductance in an ordinary case would raise this loss to

somewhere between 10.5 and eleven per cent. As a rule it may therefore

be said that inductance will seldom increase the weight of line

conductors, or the loss of power therein, by more than ten per cent.

When an alternating current flows along a conductor its density is not

uniform in all parts of each cross section, but the current density is

least at the centre of the conductor and increases toward the outside

surface. This unequal distribution of the alternating current over each

cross section of a conductor through which it is passing increases with

the diameter or thickness of the conductor and with the frequency of the

alternating current. By reason of this action the ohmic resistance of

any conductor is somewhat greater for an alternating than for a

continuous current, because the full cross section of the conductor

cannot be utilized with the former current. Fortunately, the practical

importance of this unequal distribution of alternating current over each

cross section of its conductor is usually slight, so far as the sizes of

wires for transmission lines are concerned, because the usual

frequencies of current and diameters of conductors concerned are not

great enough to give the effect mentioned a large numerical value. Thus,

sixty cycles per second is the highest frequency commonly employed for

the current on transmission lines. With a 4-0 wire, and the current

frequency named, the increase in the ohmic resistance for alternating

over that for continuous current does not reach one-half of one per

cent.

Having calculated the circular mils of weight of a transmission line by

the foregoing formulæ, it appears that the only material increase of

this weight required by the use of alternating current is that due to

inductance. This increase cannot be calculated exactly beforehand

because of the uncertain elements in future loads, but experience shows

that it is seldom more than ten per cent of the calculated size or

weight of conductors.