CHAPTER XVIII

PLUMBING CODES

The work of plumbing has a direct result on the health of the

occupants of buildings; therefore in order that the plumbing may

not be installed improperly and impair the health of the occupants,

it is necessary to provide a code governing the installation of

plumbing. Naturally these laws at first were under the control of

the health department of cities, but of late years the building

departments have assumed control of the codes with the result that

cooperation with the building codes is now the practice rather than

the exception.

To make certain the carrying out of the plumbing codes, it is

required that a plan indicating the run, size, and length of pipes,

location and number of fixtures of the prospective job be filed in

the building department of the city, before the work is started. If

the plan is approved by the plumbing inspector and acceptance is

sent, then the work can be started. After a job is completed a test

is made and the job is inspected by the plumbing inspector, and if

found to meet requirements a written acceptance of the work is

given by the building department. An effort is being made

throughout the country to have the plumbing codes under State

control rather than have a number of different codes in as many

different cities and towns. The State code can be so arranged that

it will apply to either city or town.

The installation of plumbing varies in different States. In the

northern part of the United States all pipes which pass through the

roof, if less than 4-inch must be increased to 4-inch. A pipe

smaller than 4-inch will be filled with hoar frost during the

winter and render the pipe useless to perform its function as a

vent pipe. Pipes laid under ground in the Northern States must be

at least 4 feet below the surface to protect them from freezing. In

the Southern States the frost does not penetrate the ground to such

a distance and the pipes can be laid on the surface.

Following is a State or City plumbing code insofar as it relates to

the actual installation of plumbing.

SEC. 1. PLANS AND SPECIFICATIONS.--There shall be a separate

plan for each building, public or private, or any addition

thereto, or alterations thereof, accompanied by specifications

showing the location, size and kind of pipe, traps, closets

and fixtures to be used, which plans and specifications shall

be filed with the board or bureau of buildings. The said plans

and specifications shall be furnished by the architect,

plumber or owner, and filed by the plumber. All applications

for change in plans must be made in writing.

SEC. 2. FILING PLANS AND SPECIFICATIONS.--Plumbers before

commencing the construction of plumbing work in any building

(except in case of repairs, which are here defined to relate

to the mending of leaks in soil, vent, or waste pipes,

faucets, valves and water-supply pipes, and shall not be

construed to admit of the replacing of any fixture, such as

water closets, bath tubs, lavatories, sinks, etc., or the

respective traps for such fixtures) shall submit to the bureau

plans and specifications, legibly drawn in ink, on blanks to

be furnished by said board or bureau. Where two or more

buildings are located together and on the same street, and the

plumbing work is identical in each, one plan will be

sufficient. Plans will be approved or rejected within 24 hours

after their receipt.

SEC. 3. MATERIAL OF HOUSE DRAIN AND SEWER.--House drains or

soil pipes laid beneath floor must be extra heavy cast-iron

pipe, with leaded and caulked joints, and carried 5 feet

outside cellar wall. All drains and soil pipes connected with

main drain where it is above the cellar floor shall be extra

heavy cast-iron pipe with leaded joints properly secured or of

heavy wrought-iron pipe with screw joints properly secured

and carried 5 feet outside cellar wall and all arrangements

for soil and waste pipes shall be run as direct as possible.

Changes of direction on pipes shall be made with "Y"-branches,

both above and below the ground, and where such pipes pass

through a new foundation-wall a relieving arch shall be built

over it, with a 2-inch space on either side of the pipe.

SEC. 4.--The size of main house drain shall be determined by

the total area of the buildings and paved surfaces to be

drained, according to the following table, if iron pipe is

used. If the pipe is terra-cotta the pipe shall be one size

larger than for the same amount of area drainage.

----------+-----------------------------+---------------------------------

Diameter | Fall 1/4 inch per foot | Fall 1/2 inch per foot

----------+-----------------------------+---------------------------------

4 inches | 1,800 square feet drainage | 2,500 square feet drainage area

5 inches | 3,000 square feet drainage | 4,500 square feet drainage area

6 inches | 5,000 square feet drainage | 7,500 square feet drainage area

8 inches | 9,100 square feet drainage | 13,600 square feet drainage area

10 inches | 14,000 square feet drainage | 20,000 square feet drainage area

----------+-----------------------------+---------------------------------

The main house drains may be decreased in diameter beyond the

rain-water conductor or surface inlet by permission of the

bureau, when the plans show that the conditions are such as to

warrant such decrease, but in no case shall the main house

drain be less than 4 inches in diameter.

SEC. 5. MAIN TRAP.--An iron running trap with two clean-outs

must be placed in the house drain near the front wall of the

house, and on the sewer side of all connections. If placed

outside the house or below the cellar floor the clean-outs

must extend to surface with brass screw cap ferrules caulked

in. If outside the house, it must never be placed less than 4

feet below the surface of the ground.

SEC. 6. FRESH-AIR INLET.--A fresh-air inlet pipe must be

connected with the house drain just inside of the house trap

and extended to the outer air, terminating with a return bend,

or a vent cap or a grating with an open end 1 foot above grade

at the most available point to be determined by the building

department.

The fresh-air inlet pipe must be 4 inches in diameter for

house drains of 6 inches or less and as much larger as the

building department may direct for house drains more than 6

inches in diameter.

SEC. 7. LAYING OF HOUSE SEWERS AND DRAINS.--House sewers and

house drains must, where possible, be given an even grade to

the main sewer of not less than 1/4 inch to the foot.

Full-sized "Y"- and "T"-branch fittings for handhole

clean-outs must be provided where required on house drain and

its branches. No clean-out need be larger than 6 inches.

SEC. 8. FLOOR DRAINS.--Floor or other drains will only be

permitted when it can be shown to the satisfaction of the

department of building that their use is absolutely necessary,

and arrangements made to maintain a permanent water seal, and

be provided with check or back-water valves.

SEC. 9. WEIGHT AND THICKNESS OF CAST-IRON PIPE.--All cast-iron

pipes must be uncoated excepting all laid under ground, which

shall be thoroughly tarred, sound, cylindrical and smooth,

free from cracks, sand holes and other defects, and of uniform

thickness and of grade known to commerce as extra heavy.

Cast-iron pipe including the hub shall weigh not less than the

following weights per linear foot:

2-inch pipe 5-1/2 pounds per foot.

3-inch pipe 9-1/2 pounds per foot.

4-inch pipe 13 pounds per foot.

5-inch pipe 17 pounds per foot.

6-inch pipe 20 pounds per foot.

7-inch pipe 27 pounds per foot.

8-inch pipe 33-1/2 pounds per foot.

10-inch pipe 45 pounds per foot.

12-inch pipe 54 pounds per foot.

All cast-iron pipe must be tested to 50 pounds and marked with

the maker's name.

All joints in cast-iron pipe must be made with picked oakum

and molten lead and caulked gas-tight. Twelve ounces of soft

pig lead must be used at each joint for each inch in the

diameter of the pipe.

SEC. 10. WROUGHT-IRON AND STEEL PIPE.--All wrought-iron and

steel pipe shall be galvanized. Fittings used for drainage

must be galvanized and of recess type known as drainage

fittings. All fittings used for venting shall be galvanized

and of the style known as steam pattern. No plain black pipe

or fittings will be permitted.

SEC. 11. SUB-SOIL DRAINS.--Sub-soil drains must be discharged

into a sump or receiving tank, the contents of which must be

lifted and discharged into the drainage system above the

cellar floor by some approved method. Where directly

sewer-connected, they must be cut off from the rest of the

building and plumbing system by a brass flap valve on the

inlet to the catch basin and the trap on the drain from the

catch basin must be water-supplied.

SEC. 12. YARD AND AREA DRAINS.--All yard, area and court

drains when sewer-connected must have connection not less than

4 inches in diameter. They should be controlled by one

trap--the leader trap if possible. All yards, areas and courts

must be drained. Tenement houses and lodging houses must have

yards, areas and courts drained into sewer.

SEC. 13. USE OF OLD DRAINS AND SEWERS.--Old house drains and

sewers may be used in connection with new buildings or new

plumbing, only when they are found, on examination by the

department of building, to conform in all respects to the

requirements governing new sewers and drains. All extensions

to old house drains must be of extra heavy cast-iron pipe.

SEC. 14. LEADER PIPES.--All building shall be provided with

proper metallic leaders for conducting water from the roofs in

such manner as shall protect the walls and foundations of such

buildings from injury. In no case shall the water from such

leaders be allowed to flow upon the sidewalk but the same

shall be conducted by a pipe or pipes to the sewer. If there

is no sewer in the street upon which such building fronts,

then the water from said leader shall be conducted, by proper

pipes below the surface of the sidewalk, to the street gutter.

Inside leaders shall be constructed of cast iron, wrought iron

or steel, with roof connections made gas-and water-tight by

means of heavy copper drawn tubing slipped into the pipe. The

tubing must slip at least 7 inches into the pipe. Outside

leaders may be of sheet metal, but they must connect with the

house drain by means of cast-iron pipe extending vertically 5

feet above grade level, where the building is located along

public driveways or sidewalks. Where the building is located

off building line, and not liable to be damaged the connection

shall be made with iron pipe extending 1 foot above the grade

level.

All leaders must be trapped with running traps of cast iron,

so placed as to prevent freezing.

Rain leaders must not be used as soil, waste or vent pipes,

nor shall such pipes be used as rain leaders.

SEC. 15.--EXHAUST FROM STEAM PIPES, ETC.--No steam discharge

or exhaust, blow-off or drip pipe shall connect with the sewer

or the house drain, leader, soil pipe, waste or vent pipe.

Such pipes shall discharge into a tank or condenser, from

which suitable outlet to the sewer shall be made. Such

condenser shall be supplied with water, to help condensation

and help protect the sewer, and shall also be supplied with

relief vent to carry off dry steam.

SEC. 16. DIAMETER OF SOIL PIPE.--The smallest diameter of soil

pipe permitted to be used shall be 4 inches. The size of soil

pipes must not be less than those set forth in the following

tables.

Maximum number of fixtures connected to:

-------------+-------------------------+------------------------------

Size of pipe | Waste and soil combined | Soil pipe alone

+------------+------------+---------------+--------------

| Branch | Main | Branch | Main

| fixtures | fixtures | water closets | water closets

-------------+------------+------------+---------------+--------------

4-inch | 48 | 96 | 8 | 16

4.5-inch | 96 | 192 | 16 | 32

6-inch | 268 | 336 | 34 | 68

-------------+------------+------------+---------------+--------------

If the building is six (6) and less than twelve (12) stories

in height, the diameter shall not be less than 5 inches. If

more than twelve (12) it shall be 6 inches, in diameter. A

building six (6) or more stories in height, with fixtures

located below the sixth floor, soil pipe 4 inches in diameter

will be allowed to extend through the roof provided the

number of fixtures does not exceed the number given in the

table. All soil pipes must extend at least 2 feet above the

highest window, and must not be reduced in size. Traps will

not be permitted on main, vertical, soil or waste-pipe lines.

Each house must have a separate line of soil and vent pipes.

No soil or waste line shall be constructed on the outside of a

building.

Fixtures with:

1 to 1-1/4-inch traps count as one fixture.

1 to 1-1/2 " traps count as one fixture.

1 to 2 " traps count as two fixtures.

1 to 2-1/2 " traps count as three fixtures.

1 to 3 " traps (water closets) count as four fixtures.

1 to 4 " traps count as five fixtures.

SEC. 17. CHANGE IN DIRECTION.--All sewer, soil, and waste

pipes must be as direct as possible. Changes in direction must

be made with "Y"- or half "Y"-branches or one-eighth bends.

Offsets in soil or waste pipes will not be permitted when they

can be avoided, nor, in any case unless suitable provision is

made to prevent the accumulation of rust or other obstruction.

Offsets must be made with fourth degree bends or similar

fittings. The use of T "Y"s (sanitary Ts) will be permitted on

upright lines only.

SEC. 18. JOINTS ON SOIL AND WASTE PIPES.--Connection on lead

and cast-iron pipe shall be made with brass sleeve or ferrule,

of the same size as the lead pipe inserted in the hub of the

iron pipe, and caulked with lead. The lead must be attached to

the ferrule by means of a wiped joint. Joints between lead and

wrought-iron pipes must be made with brass nipple, of same

size as lead pipe. The lead pipe must be attached to the brass

nipple by means of a wiped joint. All connections of lead

waste pipes must be made by means of wiped joints.

Short nipples on wrought-iron and steel pipes must be of

thickness and weight known as "extra heavy" or "extra strong."

Brass ferrules must be best quality, extra heavy cast brass,

not less than 4 inches long and 2-1/4, 3-1/2 and 4-1/2 inches

in diameter and not less than the following weights:

Diameters Weights

2-1/4 inches 1 pound 0 ounce.

3-1/2 inches 1 pound 12 ounces.

4-1/2 inches 2 pounds 8 ounces.

SEC. 19. SOLDER NIPPLES.--Solder nipples must be heavy cast

brass or of brass pipe, iron pipe size. When cast they must be

not less than the following weights:

Diameters Weights

1-1/2 inches 0 pound 8 ounces.

2 inches 0 pound 14 ounces.

2-1/2 inches 1 pound 6 ounces.

3 inches 2 pounds 0 ounce.

4 inches 3 pounds 8 ounces.

SEC. 20. BRASS CLEAN-OUTS.--Brass screw caps for clean-outs

must be extra heavy, not less than 1/8 inch thick. The screw

cap must have a solid square or hexagonal nut not less than 1

inch high and a least diameter of 1-1/2 inches. The body of

the clean-out ferrule must be at least equal in weight and

thickness to the caulking ferrule for the same size pipe.

SEC. 21. LEAD WASTE PIPE.--All lead waste, soil vent and flush

pipes must be of the best quality, known in commerce as "_D_,"

and of not less than the following weights per linear foot:

Diameters Weights

1-1/4 inches 2-1/2 pounds.

1-1/2 inches 3 pounds.

2 inches 4 pounds.

3 inches 6 pounds.

4 inches 8 pounds.

All lead traps and bends must be of the same weight and

thicknesses as their corresponding pipe branches.

SEC. 22. ROOF FLASHERS.--Sheet lead for roof flashings must be

6-pound lead and must extend not less than 6 inches from the

pipe and the joint made water-tight.

SEC. 23. TRAPS FOR BATH TUBS, WATER CLOSETS, ETC.--Every sink,

bath tub, basin, water closet, slop hopper, or fixtures having

a waste pipe, must be furnished with a trap, which shall be

placed as close as practicable to the fixture that it serves

and in no case shall it be more than 1 foot. The waste pipe

from the bath tub or other fixtures must not be connected

with a water-closet trap.

SEC. 24. SIZE OF HORIZONTAL AND VERTICAL WASTE PIPES, TRAPS

AND BRANCHES.--

Horizontal and vertical Number of small fixtures

1-1/4-inch 1

1-1/2-inch 2

2 -inch 3 to 8

2-1/2-inch 9 to 20

3 -inch 21 to 44

If building is ten (10) or more stories in height, the

vertical waste pipe shall not be less than 3 inches in

diameter. The use of wrought-iron pipe for waste pipe 2 inches

or less in diameter is prohibited.

The size of traps and waste branches, for a given fixture,

shall be as follows:

---------------------------------------------+------------------

| Size in inches

Kind of fixtures +-------+----------

| Trap | Branch

---------------------------------------------+-------+----------

Water closet | 3 | 4

Slop sink with trap combined | 3 | 3

Slop sink ordinary | 2 | 2

Pedestal urinal | 3 | 3

Floor drain or wash | 4 | 4

Yard drain or catch basin | 4 | 4

Urinal trough | 2 | 2

Laundry trays, two or five | 2 | 2

Combination sink and tray (for each fixture) | 1-1/2 | 2

Kitchen sinks, small | 1-1/2 | 1-1/2

Kitchen sinks, large hotel, etc. | |

Kitchen sinks, grease trap | | 2

Pantry sinks | 1-1/2 | 1-1/2

Wash basin, one only | 1-1/4 | 1-1/4

Bath tub | 2 | 2

Shower baths | 1-1/2 | 1-1/2

Shower baths, floor | 2 | 2

Sitz bath | 1-1/2 | 1-1/2

Drinking fountains | 1-1/4 | 1-1/4

---------------------------------------------+-------+----------

SEC. 25. OVERFLOW PIPES.--Overflow pipes from fixtures must in

all cases be connected on the inlet side of the traps.

SEC. 26. SETTING OF TRAPS WITHOUT RE-VENT.--All traps must be

substantially supported and set true with respect to their

water levels. No pot, bottle or "D" trap will be permitted nor

any form of trap that is not self-cleaning, nor that has

interior chambers or mechanism nor any trap except earthenware

ones that depend upon interior partitions for a seal. In case

there is an additional fixture required in building and it is

impossible to re-vent pipe for the trap, the building

department may designate the kind of trap to be used. This

shall not be construed to allow traps without re-vents in new

buildings.

SEC. 27. SAFE AND REFRIGERATOR PIPES.--Safe-waste pipes must

not connect directly with any part of the plumbing system.

Safe-waste pipes must discharge over an open, water-supplied,

publicly-placed, ordinary-used sink, placed not more than

3-1/2 feet above the cellar floor. The safe waste from a

refrigerator must be trapped at the bottom of the line only

and must not discharge upon the ground floor, but over an

ordinary open pan, or some properly-trapped, water-supplied

sink, as above. In no case shall the refrigerator waste pipe

discharge into a sink located in a living room.

The branches on vertical lines must be made by means of "Y"

fittings and be carried to the safe with as much pitch as

possible. Where there is an offset on the refrigerator waste

pipe in the cellar, there must be clean-outs placed. These

clean-outs must be of brass.

In tenement and lodging houses the refrigerator waste pipe

must extend above the roof, and not be larger than 1-1/2

inches and the branches not smaller than 1-1/4 inches.

Refrigerator waste pipes, except in tenement houses, and all

safe-waste pipes, must have brass flap valve on the lower

ends. Lead safes must be graded and neatly turned over beveled

strips at their edges.

SEC. 28. VENT-PIPE MATERIAL.--Material for vent pipes shall be

of lead, brass, enameled iron or galvanized iron.

SEC. 29. VENTILATION OF TRAPS AND SOIL LINES.--Traps shall be

protected from siphonage or air pressure by special vent pipes

of a size of not less than the following tables:

-----------------+----------------+-----------------------------

| Maximum | Number of traps vented

| length in feet |

Size of pipe +----------------+------------+----------------

| Mains | Branch | Main vertical

-----------------+----------------+------------+----------------

1-1/4-inch vent | 20 feet | 1 |

1-1/2-inch vent | 40 feet | 2 or less |

2-inch vent | 65 feet | 10 or less | 20 or less

2-1/2-inch vent | 100 feet | 20 or less | 40 or less

3-inch vent | 10 or more | 60 or less | 100 or less

| stories | |

-----------------+----------------+------------+----------------

The branch vent shall not be less than the following sizes:

1-1/4 inches in diameter for 1-1/4 inch trap.

1-1/2 inches in diameter for 1-1/2 inch to 2-1/2 inch trap.

2 inches in diameter for 3 inch to 4 inch trap.

One-half their diameter, for traps 3 inches and over.

Where two or more closets are placed side by side, on a

horizontal branch, the branch line shall have a relief

extended as a loop. A pipe 2 inches in diameter shall be

sufficient as a loop vent for two closets. A pipe 3 inches in

diameter shall be sufficient as a relief for three or four

closets; and where more than four closets are located on the

same branch the relief shall not be less than 4 inches in

diameter. All house drains and soil lines on which a water

closet is located must have a 4-inch main vent line. Where an

additional closet is located in the cellar or basement, and

within 10 feet of main soil or vent line, no relief vent will

be required for said closet; but where it is more than 10

feet, a 2-inch vent line will be required. Relief vent pipes

for water closets must not be less than 2 inches in diameter,

for a length of 40 feet, and not less than 3 inches in

diameter, for more than 40 feet.

No re-vent from traps under bell traps will be required.

In any building having a sewer connection with a private or

public sewer used for bell-trap connections or floor drainage

only, a 2-inch relief line must be extended to the roof of the

building from rear end of main. House drains, constructed for

roof drainage only, will not require a relief vent.

A floor trap for a shower shall be vented, unless located in

the cellar or ground floor the paving of which renders the

trap inaccessible.

SEC. 30. HORIZONTAL VENT PIPES.--Where rows of fixtures are

placed in a line, fitting of not less than 45 deg. to the

horizontal must be used on vent lines to prevent filling with

rust or condensation; except on brick or tile walls, where it

is necessary to channel same for pipes, 90 deg. fittings will be

allowed. Trapped vent pipes are strictly prohibited. No vent

pipe from the house side of any trap shall connect with the

ventilation pipe or with sewer, soil or waste pipe.

SEC. 31. OFFSET ON VENT LINES.--All offsets on vent lines must

be made at an angle of not less than 45 deg. to the horizontal,

and all lines must be connected at the bottom with a soil or

waste pipe, or the drain, in such manner as to prevent the

accumulation of rust, scale or condensation.

No sheet metal, brick, or other flue shall be used as a vent

pipe.

SEC. 32. SETTING OF FIXTURES.--All fixtures must be set open

and free from all enclosing woodwork. Water closets and

urinals must not be connected directly or flushed from the

water-supply pipes except when flushometer valves are used.

Each water closet must be flushed from a separate cistern, the

water from which is used for no other purpose, or may be

flushed through flushometer valves.

Rubber connection and elbows are not permitted.

Pan, plunger, or hopper closets will not be permitted in any

building. No range closet either wet or dry, nor any

evaporating system of closets shall be constructed or allowed

inside of any building.

A separate building constructed especially for the purpose,

must be provided in which such range closets shall be set.

All earthenware traps must have heavy brass floor flange

plates, soldered to the lead bends and bolted to the trap

flange, and the joint made permanently secure and gas-tight.

In all buildings sewer-connected there must be at least one

water closet in each building. There must be a sufficient

number of water closets so that there will never be more than

15 people to each water closet.

Separate water closets and toilet rooms must be provided for

each sex in buildings used as workshops, office buildings,

factories, hotels and all places of public assembly.

In all buildings the water closet and urinal apartments must

be ventilated into the outer air by windows opening on the

same lot as the building is situated on or by a ventilating

skylight placed over each room or apartment where such

fixtures are located.

In all buildings the outside partition of any water closet or

urinal apartment must be air-tight and extend to the ceiling

or be independently ceiled over. When necessary to light such

apartments properly the upper part of the partition must be

provided with translucent glass. The interior partitions of

such apartments must be dwarfed partitions.

In alteration work where it is not practicable to ventilate a

closet or urinal apartment by windows or skylight to the outer

air, there must be provided a sheet-iron duct extending to the

outer air, the area of the duct must be at least 144 square

inches for one water closet or urinal, and an additional 72

square inches for each addition closet or urinal added

therein.

SEC. 33. URINALS.--All urinals must be constructed of

materials impervious to moisture and that will not corrode

under the action of urine. The floors and walls of urinal

apartments must be lined with similar non-absorbent and

non-corrosive material.

The platforms and treads of urinal stalls must be connected

independently of the plumbing system, nor can they be

connected with any safe-waste pipe.

The copper lining of water closet and urinal cisterns must not

be lighter than 12 ounces copper, and must be stamped on

lining with maker's name. Where lead is used it must not weigh

less than 4 pounds to the square foot. All other materials are

prohibited.

SEC. 34. FIXTURES PROHIBITED.--Wooden wash trays, sinks, or

bath tubs are prohibited inside buildings. Such fixtures must

be constructed of non-absorbent materials. Cement or

artificial stone tubs will not be permitted, unless approved

by the plumbing inspector and building department.

Yard water closets will not be permitted except as approved by

the plumbing inspector and then passed by the building

department.

SEC. 35. PRIVY VAULTS AND CESSPOOLS.--No privy vault or

cesspool for sewage, shall be constructed in any part of the

city where a sewer is at all accessible. In parts of the city

where no sewer exists privy vaults and cesspools shall not be

located within 2 feet of party or street line nor within 20

feet of any building. Before these are constructed application

for permission therefore shall be made to the building

department.

SEC. 36. MATERIAL AND WORKMANSHIP.--All material used in the

work of plumbing and drainage must be of good quality and free

from defects. The work must be executed in a thorough and

workmanlike manner.

INDEX

A

Acid, muriatic, 12

B

Banjo, 120

Bath-tub, 5-6-7

size waste, 99

Bending irons, 15, 48, 59

Bib, wiping, 59, 68

Bowls, closet, 4, 5

C

Caulking joints, 89, 90

Cellar drainer, 84

Cement, pipe joint, 122

Cementing, 72, 73

Circulation, hot water, 124, 129

Closets, 3, 4, 5

Cocks, stop and waste, 120

Code-plumbing, 153

brass clean-outs, 160

change in direction, 159

diameter of soil pipes, 158

exhaust from steam pipes, 158

filing plans, 154

floor drains, 156

fresh-air inlet, 155

joints, 159

laying of drains, 156

lead waste pipe, 160

leader pipes, 157

main trap, 155

materials of drains, 154

old drains and sewers, 157

over-flow pipes, 162

plans and specification, 154

roof flashers, 160

safe and refrigerator pipes, 162

size of drains, 155

of waste pipes, 161

solder nipples, 160

traps, 160

without vents, 162

yard and area drains, 157

Code, fixtures prohibited, 165

horizontal vents, 164

material and workmanship, 166

offsets, 164

privy vaults and cesspools, 166

setting of fixtures, 164

urinals, 165

vent, pipe material, 162

ventilation of traps, 162

Connecting, sewers, 74

Connections, of fixtures, 139

Corporation cock and tap, 76-77

Coupling, right and left, 116

Covering, pipe, 131

Cup joint, 14-66

Curb cock, 77-81

box, 78-81

Cutters, pipe, 113

Cutting, terra-cotta pipe, 72

cast-iron pipe, 93

D

Dies, 112

Drainage, 2

Drains, 82, 83, 84, 87, 92

Drift plugs, 18

Drum trap, 61, 65, 68, 107

Durham work, 134

E

Earthenware, 3-5

Expansion joints, 129

F

Ferrule, brass, 37-43

File, 15

Fittings, drainage, 136

gas, 143

screw pipe, 98

soil pipe, 96

Fixtures, 3

Flushing, 3

Flux, 12

Fresh-air inlet, 105

G

Gas pipe and fittings, 143

piping, 141, 144

Goose neck, 81

H

Half and half solder, 21

Hammer, 15

Hangers, 121, 137

Heaters, flue connection, 130

gas coil, 126

instantaneous, 127

Hot water supply, 124

House drains, 86

traps, 87, 104

I

Inserting, terra-cotta pipe, 74

Intercepting trap, 92, 93

Iron enamelled ware, 3

J

Joints, amount of lead and oakum, 97

caulk, 87, 89

cup, 14

expansion, 129

of sub-soil, 84

overcast, 17

runner, 90

rust, 97

seams, 19

solder, 14

K

Kitchen sinks, 99

L

Lavatories, 8, 99

Lead connection, 78

used in caulked joints, 89, 97

Lead pipe, for water mains, 80

preparing for wiping, 45

use of, 27

Leaders, pipes and traps, 93

Long screws, 115

M

Main sewer, 81

Mason trap, 104

Measurements of piping, 146

Melting point of metals, 21

Metal, wiping, 31

Meter, reading gas, 142

N

Nipples, cutting and threading, 114

holders, 114

O

Oakum, use of, 89, 97

Overcast joint, 17, 67

P

Paste, 13

Pipe, brass, 80

covering, 131

cutting, 93

kinds of, 122

service, 81

soil, location, 95

steel, 97

tell-tale, 100

terra-cotta, 69

threading, 110

wrought iron, 97

Pipe laying, sewer, 71

water, 78

in tunnel, 73

Piping, water, 120

drainage, 135

Planking, 70, 71

Pressure, water, 119

R

Rain leaders, 86

Reaming, 135

Receptors, showers, 99

Refill, trench, 75, 79

tunnels, 79

Right and left couplings, 116

S

Sanitary drains, 91, 92

Screw-pipe work, 134

Seams, 19, 67

Sewerage, system of, 86

Sewers, 69, 81

Shoe, use of, 75

Shower stall, 150

Sinks, 2

Soil pipe, 95, 96

Soils, 13

Soldering iron, 11, 15, 66

Solders, 21

Stopcock, 45, 68, 81, 120

Sulphur, 97

Swab, 73, 81

T

Tables, angle measurements, 138, 139

brass ferrules, 160

fixtures and traps, 161

lead waste pipe, 160

measurements, 116

roof drainage, 155

screw-pipe, 134

size of vent pipes, 163

of waste pipe, 99

soil and waste pipe, 158

standard, threads, 110

terra-cotta pipe, 75

waste pipe, 161

weight of cast-iron pipe, 156

of solder nipples, 160

Tallow, 13

Tank, storage connections of, 125

Tell-tale pipe, 100

Terra-cotta pipe, 69, 75, 83

cutting, 72

Testing, gas pipe, 148

Thermostat, 124, 126

Tinning, brass, 38, 42, 45

bib, 59

Tools, bending iron, 15

caulking iron, 89

cold chisel, 89, 93

file, 15

hammer, 15

joint runner, 90

ladle, 29

pipe cutters, 113

rasp, 15

saw, 15

shave hook, 15

soldering iron, 15

tap-borer, 15, 47, 59

turn pin, 15

vise, 111

yarning iron, 89

Traps, bag, 109

centrifugal, 109

cleansweep, 108

drum, 107

flask, 108

house, 104

intercepting, 92

mechanical, 109

non-syphoning, 107

"S," 109

sure-seal, 109

Trenches, digging, 70, 81, 87

refilling, 75

water service, 76

Tubs, bath, 6

Tunnels, 73

U

Urinals, 99

V

Valves, check, 128

closet, 4

safety, 128

Ventilation pipe, 101

Vents, 100-103

W

Wash trays, 86, 99

Water connection, 76

supply, 118

rivers and lakes, 119

streams and brooks, 118

under pressure, 119

underground, 118

Wiping, 29

bib, 59

branch joints, 49

cloths, 67

drum trap, 61

2-inch brass ferrule, 40

4-inch brass ferrule, 43

round joint, 31

solder, 21

stopcock, 45