SYSTEM OF DISTRIBUTION.

The mains from the Kensington Court Station are laid underground in

a culvert 18 in. by 12 in., which is built with brickwork and cement

under the pavement. A double conductor of flat copper, 0·25 square

inches section, is stretched from shackle insulators attached to iron

bars, which are firmly built into the culvert; the continuity of the

circuit is provided by means of stranded wire, which connects each

section; the flat copper rests on the top of porcelain insulators,

fixed on vertical iron pieces, which are built into the floor.

Connections with the sewers are left for drainage, and six surface

boxes are provided for every hundred yards. Where house connections

have to be made, the branch wires are united by soldering to the bare

copper mains. For crossing under the streets a heavily insulated cable

is employed, and is led through cast-iron pipes.

[Illustration: FIG. 26.]

Until a larger amount of mileage is actually at work, it is difficult

to express an opinion as to which is the cheapest and most efficient

method of laying conductors in the streets. The relative cost of two

plans tried at Kensington Court—the insulated and the bare cable in a

culvert—was given by Mr. Crompton in the following Tables, No. 1 and

No. 2, which are taken from a paper read before the Society of

Telegraph Engineers and Electricians on April 12th, 1888.

Table No. 1 refers more particularly to what is known as the

Callender-Webber system of using bitumen concrete, which is compressed

into blocks or cases usually about 6 ft. long, 8 in. by 5½ in. section,

having two-inch holes through which the insulated copper cable is led.

The estimates given in Table No. 2 were criticised by Mr. Kapp, who

thought that “a more reliable conductor could be obtained by using a

high-class lead-covered cable, which might be laid in the ground with

the simple protection of a rough tarred plank to cover it.” The cost of

digging the trench and running in the cable from the drum was quoted at

3_s._ a yard, and the total cost, inclusive of £10 for surface boxes,

at £155 per 100 yards, instead of £187, as shown by the Table.

Central-Station Electric Lighting With Notes on the Methods Used for the Distribution of Electricity · 第 26 / 83 题