CHAPTER LIII

CONVERTERS

The alternating current must change to a direct current in many cases

as in railroad work because the induction motor is not so satisfactory

as the direct current series motor and the alternating current series

motor is slow in coming into general use.

In all kinds of electrolytic work, transformation must be made, and

in many cities where the direct current system was started, it is

still continued for local distribution, but the large main stations

generating alternating currents and frequently located some distance

away from the center of distribution have replaced a number of small

central stations.

Transformation may be made by any of the following methods:

1. Rotary converters;

2. Motor generator sets;

3. [A]Mercury vapor rectifiers;

4. [9]Electrolytic rectifiers.

[9] NOTE.--Rectifiers are explained in detail in Chapter LIV.

Strictly speaking, _a converter is a revolving apparatus for converting

alternating current into direct current or vice versa_; it is usually

called a rotary converter and is to be distinguished from the other

methods mentioned above.

Broadly, however, a converter may be considered as _any species of

apparatus for changing electrical energy from one form into another_.

According to the standardization rules of the A. I. E. E. converters

may be classified as:

1. Direct current converters;

2. Synchronous converters;

3. Motor converters;

4. Frequency converters;

5. Rotary phase converters.

[Illustration: FIGS. 2,032 and 2,033.--Gramme ring dynamo and

alternator armatures illustrating converter operation. The current

generated by the dynamo is assumed to be 100 amperes. Now, suppose, an

armature similar to fig. 2,032 to be revolving in a similar field, but

let its windings be connected at two diametrically opposite points to

two slip rings on the axis, as in fig. 2,032. If driven by power, it

will generate an alternating current. As the maximum voltage between

the points that are connected to the slip rings will be 100 volts, and

the virtual volts (as measured by a voltmeter) between the rings will

be 70.7 (= 100 ÷ √2̅), if the power applied in turning this armature

is to be 10 kilowatts, and if the circuit be non-inductive, the output

in virtual amperes will be 10,000 ÷ 70.7 = 141.4. If the resistances

of each of the armatures be negligibly small, and if there be no

frictional or other losses, the power given out by the armature which

serves as motor will just suffice to drive the armature which serves as

generator. If both armatures be mounted on the same shaft and placed in

equal fields, the combination is a ~motor dynamo~. In actual machines

the various losses are met by an increase of current to the motor.

Since the armatures are identical, and as the similarly placed windings

are passed through identical magnetic fields, one winding with proper

connections to the slip rings and commutator will do for both. In this

case only one field is needed; such a machine is called a ~converter~.]

~A direct current converter~ converts from a direct current to

a direct current.

~A synchronous converter~ (commonly called a _rotary

converter_) converts from an alternating current to a direct

current.

~A motor converter~ is a combination of an induction motor with

a synchronous converter, the secondary of the former feeding

the armature of the latter with current at some frequency other

than the impressed frequency; that is, it is a synchronous

converter in combination with an induction motor.

~A Frequency Converter~ (preferably called a _frequency

changer_) converts alternating current at one frequency into

alternating current of another frequency with or without a

change in the number of phases or voltages.

~A Rotary Phase Converter~ changes alternating current of one

or more phases into alternating current of a different number

of phases, but of the same frequency.

[Illustration: FIG. 2,034.--Diagram of ring wound single phase rotary

converter. It is a combination of a synchronous motor and a dynamo. The

winding is connected to the commutators in the usual way, and divided

into two halves by leads connecting segments 180° apart to collector

rings. A bipolar field is shown for simplicity; in practice the field

is multipolar and energized by direct current.]

~Rotary Converters.~--The synchronous or rotary converter consists of

a synchronous motor and a direct current generator combined in one

machine. It resembles a direct current generator with an unusually

large commutator and an auxiliary set of collector rings.

~Ques. In general, how does a rotary converter operate?~

Ans. On the collector ring side it operates as a synchronous motor,

while on the commutator side, as a dynamo.

Its design in certain respects is a compromise between

alternating current and direct current practice most noticeably

with respect to the number of poles and speed.

~Ques. Upon what does the speed depend?~

Ans. Since the input side consists of a synchronous motor, the speed is

governed by the frequency of the alternating current supplied, and the

number of poles.

[Illustration: FIG. 2,035.--Diagram of two phase rotary converter. This

is identical with the single phase machine with the exception that

another pair of collector rings are added, and connected to points

on the winding at right angles to the first, giving four brushes on

the alternating side for the two phase current. The pressure will be

the same for each phase as in the single phase rotary. Neglecting

losses the current for each phase will be equal to the direct

current × 1 ÷ / √2̅ = direct current × .707.]

Fig. 2,034 is a diagram of a ring wound rotary converter. This

style winding is shown to simplify the explanation. In practice

drum wound armatures are used, the operation, however, is the

same.

With this simple machine the following principles can be

demonstrated:

1. If the coil be rotated, alternating currents can be taken

from the collector rings and it is called an alternator.

2. By connecting up the wires from the commutator segments,

a direct current will flow in the external circuit making a

dynamo.

3. Two separate currents can be taken from the armature, one

supplying alternating current and the other direct current;

such a machine is called a _double current generator_.

4. If a direct current be sent in the armature coil through the

commutator, the coil will begin to rotate as in a motor and an

alternating current can be taken out of the collector rings.

Such an arrangement is called an _inverted rotary converter_.

5. If the machine be brought up to synchronous speed by

external means and then supplied with alternating current at

the collector rings, then if the direction of the current

through the armature coil and the pole piece have the proper

magnetic relation, the coil will continue to rotate in

synchronism with the current. A direct current can be taken

from the commutator, and when used thus, the machine is called

simply a _rotary converter_.

[Illustration: FIG. 2,036.--Diagram of three phase rotary converter. In

this type, the winding is tapped at three points 120° distant from each

other, and leads connected with the corresponding commutator segments.]

[Illustration: FIGS. 2,037 to 2,041.--Various rotary converter and

transformer connections. Fig. 2,037 two phase connections; fig. 2,038

three phase delta connections; fig. 2,039 three phase ~Y~ or star

connections; fig. 2,040 six phase delta connections; fig. 2,041 six

phase ~Y~ connections.]

~Ques. What is the relation between the impressed alternating pressure

and the direct pressure at the commutator?~

Ans. The ratio between the impressed alternating pressure and the

direct current pressure given out is theoretically constant, therefore,

the direct pressure will always be as 1 to .707 for single phase

converters or if the pressure of the machine used above indicate 100

volts at the direct current end, it will indicate 70.7 volts at the

alternating current side of the circuit.

~Ques. Name two different classes of converter.~

Ans. Single phase and polyphase.

~Ques. What is the advantage of polyphase converters?~

Ans. In the majority of cases two or three phase converters are used on

account of economy of copper in the transmission line.

~Ques. How is the armature of a polyphase converter connected?~

Ans. Similar to that of an alternator with either delta or ~Y~

connections.

Figs. 2,037 to 2,041 show various converter connections between

the collector rings and commutator.

Fig. 2,037 indicates how the armature is tapped for two phase

connections.

Fig. 2,038 shows three phase delta connections, and fig. 2,039

the three phase ~Y~ or star connections.

Six phase delta and ~Y~ connections are frequently used as

shown in fig. 2,040 and fig. 2,041, both of which require

two secondary coils in the transformer, one set of which is

reversed, so as to supply the current in the proper direction.

~Ques. With respect to the wave, what is the relation between the

direct and alternating pressures?~

Ans. The direct current voltage will be equal to the crest of the

pressure wave while the alternating voltage will depend on the virtual

value of the maximum voltage of the wave according to the connections

employed.

Table of

Alternating Current and Voltage in Terms of Direct Current

(According to Steinmetz)

------------------------------------------------------------------------

| | DIRECT| SINGLE | TWO | THREE |

| |CURRENT| PHASE | PHASE | PHASE |

|-----------------|-------|-------------|-------------|----------------|

|VOLTS BETWEEN | | | | |

|COLLECTOR RING | 1 | | | |

|AND NEUTRAL POINT| |1/(2√2̅)=.354|1/(2√2̅)=.354| 1/(2√2̅)=.354 |

|-----------------|-------|-------------|-------------|----------------|

|VOLTS BETWEEN | | | | |

| ADJACENT | 1 | 1/√2̅=.707 |½=.5 | √3̅/(2√2̅)=.612|

|COLLECTOR RINGS | | | | |

|-----------------|-------|-------------|-------------|----------------|

| | | | | |

| AMPERES | 1 | √2̅=1.414 | 1/√2̅=.707 | (2√2̅)/3=.943 |

| PER LINE | | | | |

|-----------------|-------|-------------|-------------|----------------|

| | | | | |

|AMPERES BETWEEN | 1 | √2̅=1.414 |½=.5 |(2√2̅)/(3√3̅)=.545|

|ADJACENT LINES | | | | |

------------------------------------------------------------------------

-------------------------------------------------------------

| | SIX | TWELVE | n |

| | PHASE | PHASE | PHASE |

|-----------------|-------------|-----------|---------------|

|VOLTS BETWEEN | | | |

|COLLECTOR RING | | | |

|AND NEUTRAL POINT|1/(2√2̅)=.354|1/(2√2̅)=.354|1/(2√2̅)=.354|

|-----------------|-------------|-----------|---------------|

|VOLTS BETWEEN | | | |

| ADJACENT |1/(2√2̅)=.354| .183 | (SIN(π/n))/√2̅|

|COLLECTOR RINGS | | | |

|-----------------|-------------|-----------|---------------|

| | | | |

| AMPERES | √2̅/3=.472 | .236 |(2√2)̅/n |

| PER LINE | | | |

|-----------------|-------------|-----------|---------------|

| | | | |

|AMPERES BETWEEN | √2̅/3=.472 | .455 |(√2̅SIN(π/n))/n|

|ADJACENT LINES | | | |

-------------------------------------------------------------

In a single phase rotary, the value of the direct pressure is 1

to .707, therefore a rotary which must supply 600 volts direct

current must be supplied by 600 × .707 = 424 volts alternating

current. For three phase rotaries the ratio is 1 to .612, or

in order to produce 600 volts direct current, 600 × .612 = 367

volts on the alternating current side of the rotary is required.

[Illustration: FIG. 2,042.--Westinghouse rotary converter armature

coils. These are wound from bar copper and are interchangeable. The

armature coils are heavily insulated to withstand the tests specified

in the standardization rules of the American Institute of Electrical

Engineers.]

Fig. 2,034 shows a complete diagram of the electrical

connections. A single phase rotary is illustrated so as to

simplify the wiring.

The table of Steinmetz on page 1,464 gives the values of the

alternating volts and amperes in units of direct current.

~Ques. How is the voltage of a rotary varied on the direct current

side?~

Ans. Pressure or potential regulators are put in the high tension

alternating current circuit and may be regulated by small motors

operated from the main switchboard or operated by hand.

~Ques. What is the advantage of unity power factor for rotary

converters?~

Ans. It prevents overheating when the rotary is delivering its full

load in watts.

~Ques. What greatly influences the power factor of the high tension

line?~

Ans. The strength of the magnetic field.

[Illustration: FIG. 2,043.--Westinghouse rotary converter armature

spider. It is made of cast iron or cast steel. The dovetail grooves

are machined in the feet or ends of the arms and in these slots the

laminations forming the armature coil engage.]

~Ques. Does variation of the field strength materially affect the

voltage?~

Ans. No.

Since variation of the field strength does not materially

affect the voltage, by adjusting the resistance in series with

the magnetic circuit, the strength of the field can be changed

and the power factor kept 1 or nearly 1 as different loads are

thrown on and off the rotary.

~Ques. What is the effect of a field too strong or too weak?~

Ans. If too strong, a leading current is produced, and if too weak,

the current lags, both of which reduce the power factor and are

objectionable.

Usually there is a power factor meter connected up in the main

generating station and one also in the rotary substation, and

it is the duty of the attendant at the substation to maintain

the proper power factor.

~Ques. What is the ordinary range of sizes of rotaries~?

Ans. From 3 kw. to 3,000 kw.

[Illustration: FIG. 2,044.--Equalizer connections of Westinghouse

rotary converter. The armature coils are cross connected at points

of equal voltage and taps are led out from the winding at suitable

points to the slip rings. This construction insures a uniform armature

saturation below each pole piece and eliminates one cause of sparking

at the commutator.]

~Ques. What is the general construction of a rotary converter?~

Ans. It is built similar to a dynamo with the addition of suitable

collector rings connected to the armature windings at points having the

proper phase relations.

Standard rotary converters have been developed for 25 and 60

cycles. The standard railway machines are compound wound, the

series field being designed for a compounding of 600 volts at

no load and full load when supplied from a source of constant

pressure with not more than 10 per cent. resistance drop and

with 20 to 30 per cent. reactance in the circuit. The large

size machines are usually wound for six phase operation.

[Illustration: FIGS. 2,045 and 2,046.--Westinghouse pole construction

for converters. Fig. 2,045, pole without windings; fig 2,046, pole with

windings. Poles are built up of steel laminations held together with

rivets. Projections on the inner ends of the poles form seats for the

field coils and hold them in position. Copper dampers set in slots in

the pole faces insure stable operation. Rotary converters for railway

service are almost invariably compound wound. The series windings are

formed of bare copper strap. The shunt windings are of insulated copper

strap or wire. Spaces between coil turns and sections are provided for

ventilation.]

~Compounding of Rotary Converters.~--Compounding is desirable where the

load is variable, such as is the case with interurban railway systems.

The purpose of the compounding is to compensate automatically for the

drop due to line, transformer, and converter impedance.

On account of the low power factor caused by over compounding, and

the fact that substations are customarily connected to the trolley at

its nearest point without feeder resistance, over compounding is not

recommended. An adjustable shunt to the series field is provided with

each machine.

Shunt wound converters are satisfactory for substations in large

cities and similar installations where due to the larger number of car

units demanding power, the load is more nearly constant.

~Ratio of Conversion.~--The relation between the alternating and

direct current voltages varies slightly in different machines, due to

differences in design. The best operating conditions exist when the

desired direct current voltage is obtained with unity power factor at

the converter terminals when loaded.

[Illustration: FIG. 2,047.--Westinghouse rotary converter brush rigging

showing method of bracing the brushes. The brushes are supported by

a rigid cast iron rocker ring which fits accurately in the frame.

A handwheel worm and screw arrangement for shifting the brushes is

provided. Cast iron arms bolted to, but insulated from the rings, carry

the rods on which the brush holders are mounted. Brush holders are of

brass cast in one piece, of the sliding type and have braided copper

shunts. Brush tension is adjustable.]

[Illustration: FIG. 2,048.--Westinghouse commutating pole rotary

converter. The construction details are substantially the same as for

the railway converter, with exception of the commutating poles. The

application of commutating pole converters is particularly desirable

where special requirements such as great overload capacity or large

capacity and low voltage enable them to show to the greatest advantage.

Commutating poles as applied to rotary converters fulfill the same

functions as in the more familiar applications to dynamos and motors.

That is, the commutating pole insures sparkless commutation from no

load to heavy overloads with a fixed brush position. Brush shifting

devices are not furnished on commutating pole converters. Commutating

pole rotary converters for railway service are normally arranged for

automatic compounding which is effected by the proper combination of

series excitation and inductance between the generator and the rotary

converter. This inductance is normally included in the transformer

but in special cases may be partly in a transformer and partly in a

separate reactance. It is possible to produce by this means a slight

increase in the direct current voltage provided the voltage drop

in the alternating current line be not excessive. Usually it is so

arranged that the compounding that can be obtained is just sufficient

to overcome the alternating current line voltage drop. The standard

Westinghouse method of starting is alternating current self-starting.

With this method of self-starting, the brushes of a commutating pole

rotary converter must be lifted from the commutator during the starting

operation to prevent sparking. A mechanical device, as shown in fig.

2,050, is provided which accomplishes this. With direct current or

motor starting a brush lifting device is not necessary.]

~Ques. Upon what does the ratio of conversion depend?~

Ans. Upon the number of phases and method of connecting the windings.

For single phase or two phase machines it is 1 to .7; for three

phase, 1 to .612, or six phase, 1 to .7 or 1 to .613 depending

upon the kind of connection used for the transformer.

For example, a two phase rotary receiving alternating current

at 426 volts will deliver direct current at 600 volts, while a

three phase rotary receiving alternating current at 367 volts

will deliver direct current at 600 volts.

[Illustration: FIG. 2,049.--Commutating pole of Westinghouse

commutating pole rotary converter. The commutating poles are similar in

general construction to the main poles. The coils are of bare copper

strap wound on edge. Ventilating spaces are provided between the pole

and coil and between turns. The copper winding is bare except for a few

turns at each end. Insulating bolts retain the turns in their proper

position.]

~Ques. What difficulty would be encountered if other ratios of

conversion than those given above were required?~

Ans. An armature with a single winding could not be used.

It would be necessary to use a machine with two distinct

armature windings or else a motor generator set.

~Ques. What change in voltage is necessary between a converter and the

alternator which furnishes the current?~

Ans. The voltage must be reduced to the proper value by a step down

transformer.

~Voltage Regulation.~--As the ratio of the alternating to the direct

current voltage of a converter is practically constant, means must be

provided to compensate for voltage variation due to changes of load in

order to maintain the direct current pressure constant.

[Illustration: FIG. 2,050.--Westinghouse brush lifting device for

commutating pole rotary converter. A rack is attached to each brush as

shown. Into this rack the spring hinged lifting hook of the raising

device engages only when the lifting lever is shifted toward the

raised position. The lifting arrangement is independent of the brushes

during normal running, so it can in no way affect the operation of the

machine. Each brush is merely raised and lowered within its own holder

so the brush position or commutation is not altered.]

There are several methods of doing this, as by:

1. Shifting the brushes (objectionable);

2. Split pole method;

3. Regulating pole method;

4. Reactance method;

5. "Multi-tap" transformer method;

6. Synchronous regulator.

~Shifting the Brushes.~--Were it not for the difficulties encountered,

this would be a most convenient method of voltage regulation, since by

this procedure the direct current voltage may be varied from maximum to

zero. It is, however, not practical because of the excessive sparking

produced when the brushes are shifted out of the neutral plane.

[Illustration: FIGS. 2,051 to 2,053.--Woodbridge split pole rotary

converter. Each pole is split into three sections and provided with

windings as indicated in fig. 2,051. When excited as in fig. 2,052, the

commutator voltage is at its highest value; when excited as in fig.

2,053, the commutator voltage is low. The change in commutator voltage

for constant collector ring voltage is in virtue of the property of

rotary converters that the ratio of these two voltages is a function of

the width of the pole arc.]

~Split Pole Method.~--In order to overcome the difficulty encountered

in shifting the brushes the split pole method was devised by Woodbridge

in which each field pole is split into two or three parts.

The effect of this is the same as shifting the brushes except that no

sparking results.

The other part is arranged so that its excitation may be varied, thus

shifting the resultant plane of the field with respect to the direct

current brushes.

One of these parts is permanently excited and it produces near its edge

the fringe of field necessary for sparkless commutation.

~Regulating Pole Method.~--As applied to the rotary converter

regulating poles fulfill the same functions as commutating or

interpoles (see page 385) on motors and dynamos, that is, they insure

sparkless commutation from no load to heavy overloads with a fixed

brush position.

[Illustration: FIG. 2,054.--General Electric regulating pole rotary

converter. The field structure is divided into two parts, a main pole

and a regulating pole. The ratio between the voltages on the direct

current and alternating current sides may be readily varied by varying

the excitation of the regulating poles, the only auxiliary apparatus

required being a field rheostat for controlling the exciting current.

Where automatic regulation is required, machines may be provided with

compound windings, or automatic field regulators may be used responsive

to either voltage or current. These converters are adapted for a

variety of purposes where a variable conversion ratio is required,

either to maintain constant D. C. voltage with varying A. C. voltage

or to vary the D. C. voltage as required. Converters may be operated

inverted where it is required to furnish constant or variable A. C.

voltage from a D. C. source. Where converter and inverted converter

operation are desired, an opposite direction of rotation is required

for the inverted operation. Converters of this type are built in

capacities from 300 kw. up to 3,000 kw., and constructed to give a

voltage range between 240 and 300 volts, to cover the usual lighting

circuit requirements. In design, they are similar to standard rotary

converters, with the exception that the regulating poles are located

next to the main pole pieces and a slightly different form of pole

piece bridge is used for the main poles, in order to allow the

auxiliary poles to be readily removed or assembled.]

The regulating poles are used in order to vary the ratio between the

alternating current collector rings and the direct current side without

the use of auxiliary apparatus such as induction regulators or dial

switches which involve complicated connections and many additional

wires. The regulating poles are arranged with suitable connection so

that the current through them can be raised, lowered or reversed.

[Illustration: FIG. 2,055.--Detail of Westinghouse commutating pole

rotary converter brush, showing rack. The brush lifting mechanism and

its operation is explained in fig. 2,050.]

The characteristics of the regulating pole converter being novel, a

detailed explanation of the principles involved is given to facilitate

a clear understanding of its operation.

Consider a machine with a field structure as shown in fig.

2,056 resembling in appearance a machine with commutating

poles, but with the brushes so set that one of the regulating

poles adds its flux to that of one main pole, cutting the

inductors between two direct current brushes. The regulating

pole is shown with a width equal to 20 per cent. of that of the

main pole.

To obtain definite figures, it will be assumed that the machine

at normal speed, with the main poles excited to normal density,

but with no excitation on the regulating poles, gives 250 volts

direct current pressure. Then with each regulating pole excited

to the same density as the main poles, and with a polarity

corresponding to that of the main pole in the same section

between brushes, the direct current pressure will rise to 300

volts at the same speed, since the total flux cutting the

inductors in one direction between brushes has been increased

20 per cent.

If, on the other hand, the excitation of the regulating poles

be reversed and increased to the same density as that of the

main poles, the direct current pressure will fall to 200

volts, since in this case the regulating poles give a reverse

pressure, that is, a pressure opposing that generated by the

main poles.

[Illustration: FIG. 2,056.--Diagram of field of regulating pole

converter illustrating principles explained in the accompanying text.]

Now, if the machine be equipped with collector rings, that is,

if it be a converter, this method of varying the direct current

voltage from 200 to 300 volts does not give nearly as great

a variation of the alternating current voltage; in fact, the

latter voltage will be the same when delivering 200 volts as

when delivering 300 volts direct current pressure, if the field

excitation be the same.

This may be seen by reference to fig. 2,057, which is a diagram

of the alternating current voltage developed in the armature

windings by the two sets of poles.[10]

[10] NOTE.--In the Burnham split pole rotary converter, each pole is

divided into only two sections, one larger than the other. A main shunt

winding is arranged on the large sections, and a winding for providing

the voltage regulation is placed on the other section. When the current

is sent through this latter winding in one direction the voltage is

raised, when in the other direction the voltage is lowered.

The horizontal line OA represents the alternating current

voltage generated by the main poles, alone, with the

regulating poles unexcited, that is, when delivering 250 volts

direct current pressure.

For a six phase converter OA measures about 180 volts

diametrically, that is, between electrically opposite collector

rings.

If now the regulating poles be excited to full strength,

to bring the direct current pressure up to 300 volts, the

alternating current voltage generated by the regulating poles

will be 90 degrees out of phase with that generated by the main

poles (since they are placed midway between the main poles),

and will be about 40 volts as shown by the line AB.

The resultant alternating current volts across the collector

rings will be represented by the line OB with a value equal to

184.

[Illustration: FIG. 2,057.--Voltage diagram for regulating pole

converter illustrating principles explained in the accompanying text.]

Again, if the regulating poles be reversed at full strength,

to cut the direct current pressure down to 200 volts, the

alternating current voltage of the main and regulating poles

will be OA and AC respectively, giving the resultant OC equal

to OB with a value of 184 volts. Accordingly, the direct

current pressure may be either 200 or 300 volts with the same

alternating current pressure, and if the main field be kept

constant, the direct current pressure may range between 200 or

300 volts, while the alternating current pressure varies only

between 180 and 184 volts.

The alternating current pressure can be kept constant through

the full range of direct current voltage by changing the main

field so as always to give an equal and opposite flux change to

that of the regulating field. A constant total flux may thus

be obtained equal to the radius of the arc BC, fig. 2,057. In

this case the line OA, representing the main field strength,

will equal OB when the regulating field is not excited, and 250

volts can only be obtained at this adjustment.

This method of operation gives unity power factor with a

constant impressed pressure of 184 volts alternating current

with a range of direct current voltage from 200 to 300 volts.

[Illustration: FIGS. 2,058 and 2,059.--Diagrams illustrating the effect

on the alternating current voltage due to varying the regulating field

strength (of a machine proportioned according to fig. 2,060), from a

density equal to that in the main poles to the same density reversed,

the main field strength remaining constant. The D. C. voltage in this

case varies from 30 per cent. above that produced by the main field

alone to 30 per cent. below, or from 325 to 175 volts, while the A. C.

voltage varies only from 200 to 175 volts. To keep the A. C. voltage

constant with such a machine the main field must be strengthened as the

regulating field is weakened or reversed to reduce the D. C. voltage.

This strengthening increases the core loss particularly on low direct

current voltages, which however, are rarely required, hence a machine

proportioned as in fig. 2,060, would not be operated through so wide a

range as 175 to 325 volts. Assume that the range is 240 to 300 volts,

and that at the highest voltage, both main and regulating fields have

the same density, presenting to the armature practically one continuous

pole face of uniform flux intensity. The diagram of A. C. component

voltages to give constant A. C. resultant voltage across the rings for

the case, is shown in fig. 2,059. At 300 volts D. C., the main field

produces an A. C. voltage OA, and the regulating field, a voltage AB,

with a resultant OB, equal to about 200 volts A. C. At 270 volts D. C.,

the main field produces an A. C. voltage OA, and a regulating field

voltage AB, giving a resultant A. C. voltage OB, equal to 200 volts.

Similarly, at 240 volts D. C., the main field produces an A. C. voltage

OA, and the regulating field (now reversed) produces the reverse

voltage AB, giving the resultant OB again equal to 200 volts. It will

be noted that, theoretically the main field strength must be increased

about 15 per cent. above its value at 300 volts D. C. in order to keep

the D. C. voltage at 250 volts.]

~Ques. Where should the regulating poles be located for best results?~

Ans. A better construction is obtained by placing them closer to the

corresponding main pole, as in fig. 2,060, than when spaced midway

between the main poles as in fig. 2,056.

~Ques. When the regulating poles are spaced as in fig. 2,060, what is

the effect on the direct current voltage?~

Ans. The effect is the same as for the midway position (fig. 2,056)

except for magnetic leakage from the main poles to the regulating poles

when the latter is opposed to the former, that is, when the direct

current voltage is being depressed.

[Illustration: FIG. 2,060.--Diagram illustrating placement of

regulating poles. In practice machines are not built as indicated

diagrammatically in fig. 2,056, that is, with regulating poles spaced

midway between the main poles, because a better construction is

obtained by placing the regulating pole closer to the corresponding

main pole, as shown above.]

~Ques. What is the effect on the alternating current voltage?~

Ans. It is somewhat altered as explained in figs. 2,058 and 2,059.

~Reactance Method.~--This consists in inserting inductance in the

supply circuit and running the load current through a few turns around

the field cores. This method is sometimes called _compounding_, and

as it is automatic it is generally used where there is a rapidly

fluctuating load.

[Illustration: FIG. 2,061.--Westinghouse 300 kw., 1,500 volt, three

phase, 25 cycle, commutating pole rotary converter. The illustration

shows clearly the commutating, and main poles and the relative sizes,

also arrangement of the terminal connections.]

If a lagging current be passed through an inductance, the collector

ring voltage will be lowered, but will be raised in case of a leading

current. The degree of excitation governs the change in the phase of

the current to the converter, the excitation, in turn, being regulated

by the load current. Accordingly with series inductance, the effect of

the series coils on the field of the converter is quite similar to that

of the compounding of the ordinary railway dynamo.

~Multi-tap Transformer Method.~--The employment of a variable ratio

step down transformer for voltage regulation is a non-automatic method

of control and, accordingly, is not desirable except in cases where the

load is fairly constant over considerable periods of time. It requires

no special explanation.

[Illustration: FIG. 2,062.--Mechanical oscillator and speed limit

device of Westinghouse commutating pole rotary converter. It

automatically prevents the armature of the converter remaining in

one position and thus not allowing brushes to wear grooves in both

commutator and collector rings. The oscillator is a self-contained

device carried at one end of the shaft. The operating parts consist

of a hardened steel ball and a steel plate with a circular ball

race, backed by a spring. The machine is so installed with a slight

inclination toward the end carrying the oscillator. As the armature

revolves the ball is carried upward and owing to the convergence of

the steel race and shaft face, the spring is compressed. The reaction

of the spring forces the armature away from its natural position and

allows the ball to drop back to the lowest point of the race.]

~Synchronous Booster Method.~--This consists of combining with the

converter a revolving armature alternator having the same number of

poles.

~Ques. How is the winding of the booster alternator armature connected?~

Ans. It is connected in series with the input circuits on the converter.

[Illustration: FIG. 2,063.--Westinghouse 2,000 kw., 270 volt, direct

current, 6 phase, 167 R.P.M., synchronous booster rotary converter,

having a voltage range from 230 to 310 volts. It consists of a standard

rotary converter in combination with a revolving armature alternator

mounted on the same shaft with the rotary converter and having the same

number of poles. By varying the field excitation of the alternator,

the alternating current voltage impressed on the rotary converter

can be increased or decreased as desired. The direct current voltage

delivered by the converter is thereby varied accordingly. The principle

of operation of the booster converter is therefore very simple and

easily understood. It is simply a combination of two standard pieces

of electrical apparatus, accordingly there are incorporated in it no

details of construction essentially different from those encountered

in standard rotary converters and alternators. The only novelty is in

their combination. The frames may be supported either from the rotary

converter frame, as in the small units, or from the bed plate, as in

the larger ones. A synchronous booster converter can be built, if

necessary, with a vertical shaft to satisfy special floor space and

head room requirements.]

~Ques. How are the field windings connected?~

Ans. They are either fed with current regulated by means of a motor

operated field circuit rheostat, or joined in series with the

commutator leads of the converter.

[Illustration: FIG. 2,064.--Armature of Westinghouse synchronous

booster converter. Heavy cast yokes form the frames. They are

proportioned to rigidly support the laminated steel field poles. The

poles are fastened to the frame with through bolts. A lifting hook is

provided on all frames. The bed plates are in one piece for the smaller

machines but two piece bed plates are used for the larger ones. The

bearings are ring oiling and have babbitt wearing surfaces that are

renewable.]

[Illustration: FIG. 2,065.--Westinghouse field frames and bearings for

synchronous booster rotary converter. The frames consist of heavy cast

yokes. The poles are fastened to the frames with through bolts. The bed

plate is in one piece for the small machines and in two pieces for the

large ones.]

~Ques. For what service is the synchronous booster method desirable?~

Ans. For any application where a relatively wide variation in direct

current voltage is necessary.

It is particularly desirable for serving incandescent lighting

systems where considerable voltage variation is required for

the compensation of drop in long feeders, for operation in

parallel with storage batteries and for electrolytic work where

extreme variations in voltage are required by changes in the

resistance of the electrolytic cells.

[Illustration: FIG. 2,066.--General Electric motor generator set

consisting of 2,300 volt synchronous motor and 550 volt dynamo.]

~Motor Generator Sets.~--The ordinary rotary converter is the most

economical machine for converting alternating currents into direct

currents, and where slight variations in the direct current voltage is

necessary, they are mostly used on account of their high efficiency,

and because they are compact.

[Illustration: FIG. 2,067.--General Electric motor generator set

consisting of 230 volt induction motor and 125 volt dynamo.]

In many central stations where they supply a great variety of

apparatus, the motor generator sets are employed as the generator is

independent of the alternating current line voltage and any degree of

voltage regulation can be performed.

~Motor Generator Combinations.~--The following combinations of motor

generators are made and used to suit local conditions:

Synchronous motor dynamo

Induction motor dynamo

Direct current motor dynamo

Direct current motor alternator

Synchronous motor alternator

Induction motor alternator

[Illustration: FIG. 2,068.--General Electric generator set, as

installed for the Cleveland Electric Illuminating Company, Cleveland,

Ohio. It consists of 11,431 volt motor and 275 volt generator. Speed,

360 revolutions per minute.]

Standard practice has adopted high tension alternating current for

transmission systems, but direct current distribution is very

frequently used. This is particularly true where alternating current

apparatus has been introduced in old direct current lighting systems.

The synchronous motor or the induction motor connected to a generator

stands next in importance to the rotary converter because it is easy

to operate and the pressure may be changed by a rheostat placed in the

field circuit of the generator.

The line wires carrying full voltage can usually be connected direct

to the motor and thus do away with the necessary step-down transformer

required by the rotary.

~Ques. What is the behavior of a rotary converter when hunting?~

Ans. It is liable to flash over at the direct current brushes, which is

common in high frequency converters where there are a great number of

poles and the brushes are necessarily spaced close together around the

commutator.

~Ques. Is this fault so pronounced with motor generator sets?~

Ans. The motor generator operating on a high frequency circuit, the

generator can be designed with a few poles and the brushes set far

apart which will greatly reduce the chance of flashing over.

A synchronous motor will drive a generator at a constant speed

during changes in load on it, and by having a field regulating

resistance it can be used to improve the power factor of the

system.

When an induction motor is used its speed drops off slowly

as the load comes on the generator, and it is necessary to

regulate the voltage of the generator by means of a field

rheostat, or compound wound machines may be used.

While an induction motor requires no separate excitation of the

field magnets like the synchronous motor, its effect on the

power factor of the system is undesirable.

Although it is seldom necessary to convert direct current to

alternating, such an arrangement of a direct current motor

driving an alternator is often justified in place of an

inverted rotary converter, as in this case the alternating

current voltage can be changed independent of the direct

current voltage.

The racing of an inverted rotary under a heavy inductive load

or short circuit does not take place in motor generator set

mentioned above.

[Illustration: FIG. 2,069.--General Electric frequency changer set,

consisting of a 11,000 volt synchronous motor with direct connected

exciter and a 2,300 volt alternator.]

~Frequency Changing Sets.~--A frequency of 25 cycles is generally used

on railway work and in large cities using the Edison three wire system,

and as a 25 cycle current is not desirable for electric lighting it is

necessary to change it to 60 cycles by means of a frequency changer

shown in fig. 2,069 for distribution in the outlying districts.

The two machines in this combination are of the same construction, only

the synchronous motor would have eight poles and have the 25 cycle

current passing through it, while the generator would have 20 poles

and produce 62½ cycles per second at 300 revolutions per minute. By

supplying the motor with 24 cycles, the generator would produce 60

cycles.

[Illustration: FIG. 2,070.--General Electric four unit frequency

changer set consisting of a 11,000 volt synchronous motor, 13,200 volt

alternator, 250 volt exciter, and 440 volt starting induction motor.

Where parallel operation is required between synchronous motor driven

frequency changers, a mechanical adjustment is necessary between

the fields or armatures of the alternator and motor to obtain equal

division of the load. The adjustment can be obtained by shifting the

keyway, or by special cradle construction. In the latter method, one

machine is bolted to a cradle fastened to the base. By taking out the

bolts, the frame can be turned around through a small angle relative to

the cradle and therefore to the armature frame of the other machine,

when the bolts can be replaced.]

It will be seen from the figure that the separate exciter is fastened

on the base plate and has its armature directly connected to the shaft.

~Parallel Operation of Frequency Changers.~--It is very difficult to

construct two or more frequency changers and join them to synchronous

motors so that the current wave of one machine will be in phase with

the other, since the speed of the motor will depend on the frequency of

the line and be independent of the load thrown on it.

When alternators are run in parallel, if one machine lag behind, the

other carries the load with the result that the lightly loaded machine

will speed up and get in step with the other, or in other words a

synchronizing current will flow between the two alternators and tend to

keep them in proper relation with respect to phase and load.

[Illustration: FIG. 2,071.--Diagram of "Cascade" motor generator

set or motor converter, as it is called in England where it is used

extensively for electric railway work. In the diagram of motor armature

winding, some of the connections are omitted for simplicity. The

windings are ~Y~ connected, and as they are fed by wires joined to the

slip rings at the right and center, the rest of the power passes to the

converter windings back to rotor winding and out to the slip rings so

that part of the power enters the rotor and part through the converter.]

~Cascade Converter.~--This piece of apparatus was introduced by Arnold

and La Cour. Briefly, it consists of a combination of an induction

motor having a wound armature and a dynamo, the armatures being placed

on the same shaft. The windings are joined in cascade, that is, in

series with those of the armature of the induction motor. The line

supplies three phase currents at high voltage direct to the field of

the induction motor and drives it, generating in it currents at a lower

voltage depending on the ratio of the windings.

[Illustration: FIG. 2,072.--General Electric shunt wound booster set.

Sets of this class are used in railway stations to raise the pressure

of the feeders extending to distant points of the system, for storage

battery charging and regulation, and in connection with the Edison

three wire lighting system. The design of the various sets is closely

dependent upon their application. Booster sets are constructed in

either series or shunt wound types and they may be arranged for either

automatic or hand regulation, depending on the nature of the service

required. Where there are a number of lighting feeders connected and

run at full load for only a short time each day it will generally be

economical to install boosters rather than to invest in additional

feeder copper. It is important, however, to consider each case where

the question of installing a booster arises, as a separate problem, and

to determine if the value of the power lost represents an amount lower

than the interest charge on the extra copper necessary to deliver the

same voltage without the use of a booster.]

Part of the current thus generated in the armature passes into the

armature of the dynamo and is _converted_ by the commutator into

direct current as in a rotary converter, but is also increased by the

current induced in the winding of the dynamo armature.

[Illustration: FIG. 2,073.--General Electric 9.5 kw. 1,000 R.P.M.

balancer set. This is a form of direct current compensator, the units

of which it is composed may be alternately motor or generator, and the

secondary circuit is interconnected with the primary. Balancer sets

are widely used to provide the neutral of Edison three wire lighting

systems. They are also installed for power service in connection with

the use of 250 volt motors on a 500 volt service or 125 volt motors

on a 250 volt service. Although the balancer set may be manufactured

for more than one intermediate voltage, the General Electric Company

recommends the three wire system as it is simpler. The motors may

be more equally divided and the reserve margin of the motor is more

conservative for that class of work requiring increase in torque

with decrease in speed. The voltage of the system being given, the

capacity of a three wire balancer set is fixed by the maximum current

the neutral wire is required to carry. This figure is a more definite

specification of capacity than a statement in per cent. of unbalanced

load. As designed for power work and generally for lighting service,

the brushes of each machine are set at the neutral point in order to

get the best results for operating alternately either as a generator or

motor. Where the changes of balance are so gradual as to permit of hand

adjustment if desired, a considerable increase in output is obtainable.]

~Ques. At what speed does the machine run?~

Ans. Assuming equal numbers of pole, the armatures rotate at a speed

corresponding to one half the circuit frequency.

[Illustration: FIGS. 2,074 and 2,075.--General Electric charging sets.

Fig. 2,074 set consists of dynamo and direct current motor; fig. 2,075

set consists of a dynamo and alternating current motor. Fig. 2,074 set

is equipped with 125 volt, shunt wound dynamo and 230 or 550 volt motor

and range in capacity from .125 kw. to 13 kw., the speed varying from

2,250 R.P.M. in the .125 kw. set to 925 R.P.M. in the 13 kw. set with

230 volt motor. Both motor and dynamo have the same type and size of

frame; these are bolted together and form a compact and symmetrical

outfit, no base being necessary. Sets of the type shown in fig. 2,075

range in capacity from .2 kw. to 10 kw. and are equipped with 125 volt

shunt wound dynamo and 110, 220, 440 or 550 volt two or three phase

motors. If desired they can be furnished with single phase motors

wound for 110 or 220 volts. The speed of this type is 1,800 R.P.M.

When a motor generator set is used to charge only one battery, the

insertion of a resistance between the charging dynamo and the battery

is not necessary, inasmuch as all adjustments of voltage can be made

by varying the field strength of the dynamo, and, therefore, there are

no large losses due to resistance since the loss in the dynamo field

rheostat is very small. When a motor generator set is used to charge

two or more batteries of different capacities, or voltages, or which

are in different conditions of charge, it is necessary to insert a

resistance in series with each battery, in order that the current may

be properly adjusted for each particular battery.]

Thus if the motor have six poles and the frequency be 50, the

rotary field revolves at 50 × 60 ÷ 3 = 1,000 R.P.M. and the

motor will revolve at one-half that speed or 1,000 ÷ 2 = 500

R.P.M.

Since the connections are so arranged that these currents

tend to set up in the armature a revolving field, rotating at

half speed in a sense opposite to that in which the shaft is

rotating at half speed, it follows that by the super-position

of this revolving field upon the revolutions of the machine,

the magnetic effect is equivalent to a rotation of the armature

at whole speed, so that it operates in synchronism, as does the

armature of a rotary converter.

Half the electric input into the motor part is, therefore,

turned into mechanical energy to drive the shaft, the other

half acts inductively on the armature winding, generating

currents therein.

As to the dynamo part it is half generator, receiving

mechanical power by transmission along the shaft to furnish

half its output, and it is half converter, turning the currents

received from the armature into direct current delivered at the

brushes.

~Ques. What action takes place in the motor armature winding?~

Ans. Since it runs at one-half synchronous speed, it generates

alternating current of half the supply current frequency, delivering

these to the armature of the dynamo.

~Ques. What claim is made for this type of apparatus?~

Ans. The cost is said to be less than a motor generator set, and it is

claimed to be self-synchronizing and to require no special starting

gear, also to be 2.5 per cent. more efficient than a motor generator.

~Ques. How is the machine started from the high pressure side?~

Ans. The field winding is connected directly to the high pressure

leads. The three slip ring brushes are connected with external

resistances which are used while starting, the external resistances

being gradually cut out of the circuit as the machine comes up to speed

(the same as with an ordinary slip ring motor).

~Ques. How does a cascade converter compare with a synchronous

converter?~

Ans. It is about equally expensive as the synchronous converter with

its necessary bank of transformers, but is about one per cent. less

efficient. It is claimed to be more desirable for frequencies above 40

on account of the improved commutation at the low frequency used in

the dynamo member. For lower frequencies the synchronous converter is

preferable.