CHAPTER LII

TRANSFORMERS

The developments in the field of electrical engineering which have

rendered feasible the transmission of high pressure currents over long

distances, together with the reliability and efficiency of modern

generating units, have resulted in notable economies in the generation

and distribution of electric current.

This has been accomplished largely by the use of distant water power or

the centralization of the generating plants of a large territory in a

single power station.

The transformer is one of the essential factors in effecting the

economical distribution of electric energy, and may be defined as _an

apparatus used for changing the voltage and current of an alternating

circuit_. A transformer consists essentially of:

1. A primary winding;

2. A secondary winding;

3. An iron core.

~Basic Principles.~--If a current be passed through a coil of wire

encircling a bar of soft iron the iron will become a magnet; when the

current is discontinued the bar loses its magnetization.

_Conversely:_ If a bar of iron carrying a coil of wire be magnetized

in a direction at right angles to the plane of the coil a momentary

electric pressure will be induced in the wire; if the current be

reversed, another momentary pressure will be induced in the opposite

direction in the coil.

These actions are fully explained in chaps. X and XI, and as they are

perfectly familiar phenomena, a detailed explanation of the principles

upon which they depend is not necessary here.

From the first two statements given above it is evident that

if a bar of iron be provided with two coils of wire, one of

which is supplied from a source of alternating current, as

shown diagrammatically by fig. 1,916, at each impulse of the

exciting current a pressure will be induced in the secondary

coil, the direction of these impulses alternating like that of

the exciting current.

~Ques. What name is given to the coil through which current from the

source flows?~

Ans. _The primary winding._

[Illustration: Fig. 1,916.--Diagram of elementary transformer with

non-continuous core and connection with single phase alternator. The

three essential parts are: primary winding, secondary winding, and an

iron core.]

~Ques. What name is given to the coil in which a current is induced?~

Ans. _The secondary winding._

Similarly, the current from the source (alternator) is called

the _primary current_ and the induced current, the _secondary

current_.

~Ques. What is the objection to the elementary transformer shown in

fig. 1,916?~

Ans. The non-continuous core. With this type core, the flux emanating

from the north pole of the bar has to return to the south pole through

the surrounding air; and as the reluctance of air is much greater than

that of iron, the magnetism will be weak.

~Ques. How is this overcome?~

Ans. By the use of a continuous core as shown in fig. 1,917.

~Ques. Is this the best arrangement, and why?~

Ans. No. If the windings were put on as in fig. 1,917, the leakage of

magnetic lines of force would be excessive, as indicated by the dotted

lines. In such a case the lines which leak through air have no effect

upon the secondary winding, and are therefore wasted.

[Illustration: Fig. 1,917.--Diagram of elementary transformer with

continuous core and connections with alternator. The dotted lines show

the leakage of magnetic lines. To remedy this the arrangement shown in

fig. 1,918 is used.]

~Ques. How is the magnetic leakage reduced to a minimum in commercial

transformers?~

Ans. In these, and even in ordinary induction coils (the operating

principle of which is the same as that of transformers) the magnetic

leakage is reduced to the lowest possible amount by arranging the coils

one within the other, as shown in cross section in fig. 1,918.

~The Induced Voltage.~--The pressure induced in the secondary winding

will depend on the _ratio_ between the number of turns in the two

windings. For example, a transformer with 500 turns of wire in its

primary winding and 50 turns in its secondary winding would have a

transformation ratio of 10 to 1, and if it were supplied with primary

current at 1,000 volts, the secondary pressure at no load would be 100

volts.

[Illustration: Fig. 1,918.--Cross section showing commercial

arrangement of primary and secondary windings on core. One is

superposed on the other. This arrangement compels practically all of

the magnetic lines created by the primary winding to pass through the

secondary winding.]

EXAMPLE.--If ten amperes flow in the primary winding and the

transformation ratio be 10, then 10 × 10 = 100 amperes will

flow through the secondary winding.

Thus, a direct proportion exists between the pressures and

turns in the two windings and an inverse proportion between the

amperes and turns, that is:

_primary voltage: secondary voltage = primary turns: secondary turns_

_primary current: secondary current = secondary turns: primary turns_

From the above equations it is seen that the watts of the primary

circuit equal the watts of the secondary circuit.

~Ques. Are the above relations strictly true, and why?~

Ans. No, they are only approximate, because of transformer losses.

In the above example, the total wattage in the primary circuit

is 1,000 × 10 = 10 kw., and that in the secondary circuit

is 100 × 100 = 10 kw. Hence, while both volts and amperes

are widely different in the two circuits, the watts for each

are the same in the ideal case, that is, assuming perfect

transformer action or 100% efficiency. Now, the usual loss in

commercial transformers is about 10%, so that the actual watts

delivered in the secondary circuit is (100 × 100) × 90% = 9 kw.

[Illustration: FIG. 1,919.--Wagner transformer coil formed, ready for

taping. These are known as "pan cake" coils. They are wound with flat

cotton covered copper strip. In heavy coils, several strips in parallel

are used per turn in order to facilitate the winding and produce a more

compact coil.]

~The No Load Current.~--When the secondary winding of a transformer is

open or disconnected from the secondary circuit no current will flow in

the winding, but a very small current called the _no load current_ will

flow in the primary circuit.

The reason for this is as follows: The current flowing in

the primary winding causes repeated reversals of magnetic

flux through the iron core. These variations of flux induce

pressures in both coils; that induced in the primary called the

_reverse pressure_ is opposite in direction and very nearly

equal to the impressed pressure, that is, to the pressure

applied to the primary winding. Accordingly the only force

available to cause current to flow through the primary winding

is the difference between the impressed pressure and reverse

pressure, the _effective pressure_.

[Illustration: FIG. 1,920.--Wagner coils with insulation ready for core

assembly. The flat coils, sometimes called pancake coils are wound

of flat, cotton covered, copper strip with ample insulation between

layers. In heavy coils several flat strips in multiple are used per

turn in order to facilitate the winding and produce a more compact

coil. In many cases normal current flow per high tension coil is very

low and could be carried with a very small cross sectional area of

copper; however, flat strip is almost always used on account of the

increased mechanical stability thus obtained.]

~The Magnetizing Current.~--The magnetizing current of a transformer

is sometimes spoken of as that current which the primary winding takes

from the mains when working at normal pressure. The _true magnetizing

current_ is only that component of this total no load current which is

in quadrature with the supply pressure. The remaining component has

to overcome the various iron losses, and is therefore an "in phase"

component. The relation between these two components determines the

power factor of the so called "magnetizing current."

[Illustration: FIGS. 1,921 and 1,922.--Assembled coils of Westinghouse

10 and 15 kva. transformers; views showing ventilating ducts.]

The true magnetizing component is small if the transformer be well

designed, and be worked at low flux density.

~Action of Transformer with Load.~--If the secondary winding of a

transformer be connected to the secondary circuit by closing a switch

so that current flows through the secondary winding, the transformer is

said to be _loaded_.

The action of this secondary current is to oppose the

magnetizing action of the slight current already flowing in the

primary winding, thus decreasing the maximum value reached by

the alternating magnetic flux in the core, thereby decreasing

the induced pressure in each winding.

The amount of this decrease, however, is _very small_,

inasmuch as a very small decrease of the induced pressure in

the primary coil greatly increases the difference between the

pressure applied to the primary coil and the opposing pressure

induced in the primary coil, so that the primary current is

greatly increased. In fact, _the increase of primary current

due to the loading of the transformer is just great enough

(or very nearly) to exactly balance the magnetizing action of

the current in the secondary coil;_ that is, the flux in the

core must be maintained approximately constant by the primary

current whatever value the secondary current may have.

When the load on a transformer is increased, the primary of the

transformer automatically takes additional current and power

from the supply mains in direct proportion to the load on the

secondary.

When the load on the secondary is reduced, for example by

turning off lamps, the power taken from the supply mains by

the primary coil is automatically reduced in proportion to the

decrease in the load. This automatic action of the transformer

is due to the balanced magnetizing action of the primary and

secondary currents.

[Illustration: FIG. 1,923.--Rear view of Fort Wayne distributing

transformer, showing hanger irons for attaching to pole cross arm.]

~Classification of Transformers.~--As in the case of motors, the great

variety of transformer makes it necessary that a classification, to be

comprehensive, must be made from several points of view, as:

1. With respect to the transformation, as

_a._ Step up transformers;

_b._ Step down transformers.

2. With respect to the arrangement of the coils and magnetic circuit, as

_a._ Core transformers;

_b._ Shell transformers;

_c._ Combined core and shell transformers.

3. With respect to the kind of circuit they are to be used on, as

_a._ Single phase transformers;

_b._ Polyphase transformers.

4. With respect to the method employed in cooling, as

_a._ Dry transformers;

_b._ Air cooled transformers {natural draught;

{forced draught, or air blast;

_c._ Oil cooled transformers;

_d._ Water cooled transformers.

5. With respect to the nature of their output, as

_a._ Constant pressure transformers;

_b._ Constant current transformers;

_c._ Current transformers;

_d._ Auto-transformers.

6. With respect to the kind of service, as

_a._ Distributing;

_b._ Power.

7. With respect to the circuit connection that the transformer

is constructed for, as

_a._ Series transformers;

_b._ Shunt transformers.

~Step Up Transformers.~--This form of transformer is used to transform

a low voltage current into a high voltage current. Such transformers

are employed at the generating end of a transmission line to raise the

voltage of the alternators to such value as will enable the electric

power to be economically transmitted to a distant point.

[Illustration: FIG. 1,924.--Diagram of elementary _step up_

transformer. As shown the primary winding has two turns and secondary

10 turns, giving a ratio of voltage transformation of 10 ÷ 2 = 5.

Since only ⅕ as much current flows in the secondary winding as in the

primary, the latter requires heavier wire than the former.]

~Copper Economy with Step Up Transformers.~--To comprehend

fully the bearing of the matter, it must be remembered that the

energy supplied per second is the product of two factors, the

current and the pressure at which that current is supplied;

the magnitudes of the two factors may vary, but the value of

the power supplied depends only on the product of the two; for

example, the energy furnished per second by a current of 10

amperes supplied at a pressure of 2,000 volts is exactly the

same in amount as that furnished per second by a current of 400

amperes supplied at a pressure of 50 volts; in each case, the

product is 20,000 watts.

Now the loss of energy that occurs in transmission through a

well insulated wire depends also on two factors, the current

and the resistance of the wire, and in a given wire is

proportional to the square of the current. In the above example

the current of 400 amperes, if transmitted through the same

wire as the 10 amperes current, would, because it is forty

times as great, waste sixteen hundred times as much energy in

heating the wire. It follows that, for the same loss of energy,

the 10 ampere current at 2,000 volts may be carried by a wire

having only ¹/₁₆₀₀th of the sectional area of the wire used

for the 400 ampere current at 50 volts.

The cost of copper conductors for the distributing lines is

therefore very greatly economized by employing high pressures

for distribution of small currents.

[Illustration: FIG. 1,925.--Diagram of elementary step down

transformer. As shown the primary winding has 10 turns and the

secondary 2, giving a ratio of voltage transformation of 2 ÷ 10 = .2.

The current in the secondary being 5 times greater than in the primary

will require a proportionately heavier wire.]

~Step Down Transformers.~--When current is supplied to consumers

for lighting purposes, and for the operation of motors, etc.,

considerations of safety as well as those of suitability, require the

delivery of the current at comparatively low pressures ranging from 100

to 250 volts for lamps, and from 100 to 600 volts for motors.

This involves that the high pressure current in the transmission

lines must be transformed to low pressure current at the receiving

or distributing points by _step down transformers_, an elementary

transformer being shown in fig. 1,925.

[Illustration: FIGS. 1,926 and 1,927.--Core type transformer. It

consists of a central core of laminated iron, around which the coils

are wound. A usual form of core type transformer consists of a

rectangular core, around the two long limbs of which the primary and

secondary coils are wound, the low tension coil being placed next the

core.]

Transformers of this type have a large number of turns in the primary

winding and a small number in the secondary, in ratio depending on the

amount of pressure reduction required.

~Core Transformers.~--This type of transformer may be defined as one

having an iron core, upon which the wire is wound in such a manner that

the iron is enveloped within the coils, the outer surface of the coils

being exposed to the air as shown in figs. 1,926 and 1,927.

~Shell Transformers.~--In the shell type of transformer, as shown in

fig. 1,928, the core is in the form of a shell, being built around and

through the coils. A shell transformer has, as a rule, fewer turns and

a higher voltage per turn than the core type.

~Ques. What is the comparison between core and shell transformers?~

Ans. The relative advantages of the two types has been the subject of

considerable discussion among manufacturers; the companies who formerly

built only shell type transformers, now build core types, while with

other builders the opposite practice obtains.

[Illustration: FIG. 1,928.--Shell type transformer. In construction

the laminated core is built around and through the coils as shown. For

large ratings this type has some advantages with respect to insulation,

while for small ratings the core type is to be preferred in this

respect. The shell arrangement of the core gives better cooling; with

this arrangement minimum magnetic leakage is easily obtained.]

~Ques. Upon what does the choice between the two types chiefly depend?~

Ans. Upon manufacturing convenience rather than operating

characteristics.

The major insulation in a core type transformer consists of

several large pieces of great mechanical strength, while in

the shell type, there are required an extremely large number

of relatively small pieces of insulating material, which

necessitates careful workmanship to prevent defects in the

finished transformer, when thin or fragile material is used.

Both core and shell transformers are built for all ratings; for

small ratings the core type possesses certain advantages with

reference to insulation, while for large ratings, the shell

type possesses better cooling properties, and has less magnetic

leakage than the core type.

[Illustration: FIG. 1,929.--View illustrating the construction of cores

and coils of Maloney transformers.]

[Illustration: FIG. 1,930.--Maloney mica shield between primary and

secondary coils, showing lapping feature which prevents the wrinkling

and cracking of the mica.]

~Combined Core and Shell Transformers.~--An improved type of

transformer has been introduced which can be considered either as two

superposed shell transformers with coils in common, or as a single core

type transformer with divided magnetic circuit and having coils on only

one leg. It is best considered however, as a combined core and shell

transformer, and for small sizes it possesses most of the advantages

of both types. It can be constructed at less cost than can either a

core or a shell transformer having the same operating characteristics

and temperature limits.

[Illustration: FIGS. 1,931 and 1,932.--The Berry combined core and

shell transformer. It consists of a number of inner and outer vertical

and radial laminated iron blocks built up of the usual thin sheet iron,

with the coils between. The magnetic circuit is completed at the top

and bottom by other laminated blocks placed horizontally, and the whole

is held together between top and bottom cast iron frame plates by a

bolt passing right down the center. Fig. 1,931 gives a general view,

W being the winding, and B, B, B, etc., the outer laminated blocks.

The construction will be better understood from fig. 1,932, where it

may be supposed that the top cap and laminated cross pieces have been

removed. Here I, I, I and O, O, O are respectively the inner and outer

radial vertical blocks, P the primary, and S, S the secondary; the

latter being in two sections with the primary sandwiched between, as an

extra precaution against shock. It will be evident that this form of

transformer possesses excellent ventilation; and this is still further

enhanced by opening out the winding at intervals to leave ventilating

apertures, as at A, A, A. Fig. 1,932 shows only 6 sets of radial

blocks, but the usual plan is to provide 24 or 36, according to the

size of the transformer.]

Fig. 1,932 shows a cross section of the first transformer of this type

to be developed commercially, and known as an "iron clad" transformer;

this construction has been used in England for some time. Fig. 1,933

shows the American practice.

[Illustration: FIG. 1,933.--Plan of core of General Electric combined

core and shell transformer. The core used contains four magnetic

circuits of equal reluctance, in multiple; each circuit consisting of a

separate core. In this construction one leg of each circuit is built up

of two different widths of punchings forming such a cross section that

when the four circuits are assembled together they interlock to form

a central leg, upon which the winding is placed. The four remaining

legs consist of punchings of equal width. These occupy a position

surrounding the coil at equal distances from the center, on the four

sides; forming a channel between each leg and coil, thereby presenting

large surfaces to the oil and allowing its free access to all parts

of the winding. The punchings of each size transformer are all of the

same length, assembled alternately, and forming two lap joints equally

distributed in the four corners of the core, thereby giving a magnetic

circuit of low reluctance.]

~Ques. How is economy of construction obtained in designing combined

core and shell transformers?~

Ans. The cross section of iron in the central leg of the core is made

somewhat less than that external to the coils, in order to reduce the

amount of copper used in the coils.

~Single and Polyphase Transformers.~--A single phase transformer may be

defined as _one having only one set of primary and secondary terminals,

and in which the fluxes in the one or more magnetic circuits are all in

phase_, as distinguished from a polyphase transformer, or combination

in one unit of several one phase transformers with separate electric

circuits but having certain magnetic circuits in common. In polyphase

transformers there are two or more magnetic circuits through the core,

and the fluxes in the various circuits are displaced in phase.

~Ques. Is it necessary to use a polyphase transformer to transform a

polyphase current?~

Ans. No, a separate single phase transformer may be used for each phase.

[Illustration: FIGS. 1,934 and 1,935.--Top view showing core and

coils in place, and view of coils of Westinghouse distributing

transformer. The coils are wound from round wire in the smaller sizes

of transformers and from strap copper in the larger sizes. Strap wound

coils allow a greater current carrying conductor section than coils

wound from large round wire, as there is little waste space between the

different turns of the conductor. The coils are arranged concentrically

with the high tension winding between the two low tension coils, this

arrangement giving the fine regulation found in these transformers. The

low tension coils are wound in layers which extend across the whole

length of the coil opening in the iron, while the high tension coils

are wound in two parts and placed end to end. This construction reduces

the normal voltage strains to a value which will not give trouble

under any condition of service. The magnetic circuit is built up of

laminated, alloy steel punchings, each layer of laminæ being reversed

with reference to the preceding layer and all joints butted. This gives

a continuous magnetic circuit of low reluctance, low iron loss and low

exciting current. When assembled, the magnetic circuit consists of four

separate parallel circuits encircling the coils and protecting the

windings from mechanical injury. Separate high and low tension terminal

blocks of glazed porcelain are mounted upon extensions of the upper

end frames. All danger of confusing the leads or inadvertently making

an electrical connection between the high and low tension sides of the

transformer is thus averted. The high tension winding has four leads

brought to the studs in the terminal block. Adjustable brass connectors

or links between the studs provide for series or multiple connections

between two points of the high tension winding. The position of the

studs and the length of the links are so proportioned that wrong

connections on the block are impossible. Barriers on the porcelain

block separate the studs and prevent danger of arcing. Leads with means

of preventing creeping of oil by capillary action are attached to these

studs and brought out of the core through porcelain bushings.]

~Ques. Is there any choice between a polyphase transformer and separate

single phase transformers for transforming a polyphase current?~

Ans. Yes, the polyphase transformer is preferable, because less iron

is required than would be with the several single phase transformers.

The polyphase transformer therefore is somewhat lighter and also more

efficient.

[Illustration: FIGS. 1,936 and 1,937.--Core and shell types of three

phase transformer. In the core type, fig. 1,936, there are three cores

A, B, and C, joined by the yokes D and D'. This forms a three phase

magnetic circuit, since the instantaneous sum of the fluxes is zero.

Each core is wound with a primary coil P, and a secondary coil S. As

shown, the primary winding of each phase is divided into three coils

to ensure better insulation. The primaries and secondaries may be

connected _star_ or _mesh_. The core B has a shorter return path than

A and C, which causes the magnetizing current in that phase to be less

than in the A and C phases. This has sometimes been obviated by placing

the three cores at the corners of an equilateral triangle (as in figs.

1,939 and 1,940), but the extra trouble involved is not justified, as

the unbalancing is a no load condition, and practically disappears

when the transformer is loaded. The shell type, fig. 1,937, consists

practically of three separate transformers in one unit. The flux paths

are here separate, each pair of coils being threaded by its own flux,

which does not, as in the core type, return through the other coils.

This gives the shell type an advantage over the core type, for should

one phase burn out, the other two may still be used, especially if the

faulty coils be short circuited. The effect of such short circuiting is

to prevent all but a very small flux from threading the faulty coil.]

~Ques. Name two varieties of polyphase transformer?~

Ans. The core, and the shell types as shown in figs. 1,936 and 1,937.

~Ques. How should a three phase transformer be operated with one phase

damaged?~

Ans. The damaged windings should be separated electrically from the

other coils.

The pressure winding of the damaged phase should be short

circuited upon itself and the corresponding low pressure

winding should also be short circuited upon itself. The winding

thus short circuited will choke down the flux passing through

the portion of the core surrounded by them without producing

in any portion of the winding a current greater than a small

fraction of the current which would normally exist in such

portion at full load.

~Transformer Losses.~--As previously mentioned, the ratio between

the applied primary voltage and the secondary terminal voltage of a

transformer is not always equal to the ratio of primary to secondary

turns of wire around the core.

The commercial transformer is not a perfect converter of energy, that

is, the ~input~, or watts applied to the primary circuit is always more

than the ~output~ or watts delivered from the secondary winding.

[Illustration: FIG. 1,938.--Interior of General Electric oil cooled 500

kva. 33,000 volt outdoor transformer showing lifting arrangement.]

This is due to the various losses which take place, and the difference

between the input and the output is equal to the sum of these losses.

They are divided into two classes:

1. The ~iron~ or ~core~ losses;

2. The ~copper~ losses.

The iron or core losses are due to

1. Hysteresis;

2. Eddy currents;

3. Magnetic leakage (negligibly small).

[Illustration: FIGS. 1,939 and 1,940.--Triangular arrangements of cores

of three phase transformer. Fig. 1,939, form with three cornered yokes

at bottom and top of cores; fig. 1,940, form with circular yokes. While

these designs give perfect symmetry for the three phases, there is some

trouble in the mechanical arrangement of the yokes. If these be stamped

out triangularly and inserted horizontally between the three cores, it

is necessary to interpose a layer of insulation, otherwise there would

be objectionable eddy currents formed in the stampings.]

Those which are classed as copper losses are due to

1. Heating the conductors (the I²R loss);

2. Eddy currents in conductors.

~Hysteresis.~--In the operation of a transformer the alternating

current causes the core to undergo rapid reversals of magnetism. This

requires an expenditure of energy which is converted into heat.

[Illustration: FIG. 1,941.--View showing mechanical construction of

coil and core of Moloney pole type ½ to 50 kw. transformer. Moloney

standard transformers of these sizes are regularly wound for 1,100 to

2,200 primary volts. For 1,100 volts the primary coils are connected

in parallel by means of connecting links; for 2,200 volts, they are

connected in series. The porcelain primary terminal board is provided

with two connecting links so that connections can be made for either

1,100 or 2,200 volts.]

This loss of energy as before explained is due to the work required

to change the position of the molecules of the iron, in reversing the

magnetization. Extra power then must be taken from the line to make up

for this loss, thus reducing the efficiency of the transformer.

~Ques. Upon what does the hysteresis loss depend?~

Ans. Upon the quality of the iron in the core, the magnetic density at

which it is worked and the frequency.

~Ques. With a given quality of iron how does the hysteresis loss vary?~

Ans. It varies as the 1.6 power of the voltage with constant frequency.

~Ques. In construction, what is done to obtain minimum hysteresis loss?~

Ans. The softest iron obtainable is used for the core, and a low degree

of magnetization is employed.

[Illustration: FIG. 1,942.--Fort Wayne transformer coils and core

complete.]

[Illustration: FIG. 1,943.--Top view of Fort Wayne (type A) transformer

cover removed, showing assembly of coils and core and disposition of

leads.]

~Eddy Currents.~--The iron core of a transformer acts as a closed

conductor in which small pressures of different values are induced in

different parts by the alternating field, giving rise to eddy currents.

Energy is thus consumed by these currents which is wasted in heating

the iron, thus reducing the efficiency of the transformer.

~Ques. How is the loss reduced to a minimum?~

Ans. By the usual method of laminating the core.

The iron core is built up of very thin sheet iron or steel

stampings, and these are insulated from each other by varnish

and are laid face to face at right angles to the path that the

eddy currents tend to follow, so that the currents would have

to pass from sheet to sheet, through the insulation.

~Ques. In practice, upon what does the thickness of the laminæ or

stampings depend?~

Ans. Upon the frequency.

The laminæ vary in thickness from about .014 to .025 inch,

according as the frequency is respectively high or low.

[Illustration: FIG. 1,944.--General Electric 10 kva., (type H)

transformer removed from tank. That part of the steel core composing

the magnetic circuit outside of the winding is divided into four

equal sections. Each section is located a sufficient distance from

the winding so that all portions of the winding and core are equally

exposed to the cooling action of the oil. On all except the very

smallest sizes the winding is divided by channels and ducts through

which a continual circulation of oil is maintained. The result is

uniform temperature throughout the transformer, thus eliminating the

detrimental effects of unequal expansion in the coils with consequent

rubbing and abrasion of the insulation.]

~Ques. Does a transformer take any current when the secondary circuit

is open?~

Ans. Yes, a "no load" current passes through the primary.

~Ques. Why?~

Ans. The energy thus supplied balances the core losses.

[Illustration: FIG. 1,945.--Cover construction of Wagner 350 kva., oil

filled 1,100-2,200 volt transformer. In transformers with corrugated

cases, the base and top ring are cast to the corrugated iron sheets.]

~Ques. Are the iron or copper losses the more important, and why?~

Ans. The iron losses, because these are going on as long as the primary

pressure is maintained, and the copper losses take place only while

energy is being delivered from the secondary.

Strictly speaking, on _no load_ (that is when the secondary

circuit is open) a slight copper loss takes place in the

primary coil but because of its smallness is not mentioned.

It is, to be exact, included in the expression "iron losses,"

as the precise meaning of this term signifies _not only the

hysteresis and eddy current losses but the copper loss in the

primary coil when the secondary is open_.

The importance of the iron losses is apparent in noting that in

electric lighting the lights are in use only a small fraction

of the 24 hours, but the iron losses continue all the time,

thus the greater part of each day energy must be supplied to

each transformer by the power company to meet the losses,

during which time no money is received from the customers.

Some companies make a minimum charge per month whether any

current is used or not to offset the no load transformer losses

and rent of meter.

[Illustration: FIGS. 1,946 to 1,948.--Methods of connecting the low

tension sides of Westinghouse transformers using the connectors

illustrated in figs. 1,949 to 1,953.]

~Ques. How may the iron losses be reduced to a minimum?~

Ans. By having short magnetic paths of large area and using iron or

steel of high permeability. The design and construction must keep the

eddy currents as low as possible.

As before stated the iron losses take place continually, and

since most transformers are loaded only a small fraction of a

day it is very important that the iron losses should be reduced

to a minimum.

With a large number of transformers on a line, the magnetizing

current that is wasted, is considerable.

During May, 1910, the U. S. Bureau of Standards issued a

circular showing that each watt saving in core losses was a

saving of 88 cents, which is evident economy in the use of high

grade transformers.

~Copper Losses.~--Since the primary and secondary windings of a

transformer have resistance, some of the energy supplied will be lost

by heating the copper. The amount of this loss is proportional to

square of the current, and is usually spoken of as the I²R loss.

[Illustration: FIGS. 1,949 to 1,953.--Westinghouse low tension

transformer connectors for connecting the low tension leads to the

feeder wires. The transformers of the smaller capacities have knuckle

joint connectors and those of the larger sizes have interleaved

connectors. These connectors form a mechanically strong joint of high

current carrying capacity. Since the high tension leads are connected

directly to the cut out or fuse blocks, connectors are not required on

these leads. The use of these connectors allows a transformer to be

removed and another of the same or a different capacity substituted

usually without soldering or unsoldering a joint. The connectors also

facilitate changes in the low tension connections.]

~Ques. Define the copper losses.~

Ans. The copper losses are the sum of the I²R losses of both the

primary and secondary windings, and the eddy current loss in the

conductors.

~Ques. Is the eddy current loss in the conductors large?~

Ans. No, it is very small and may be disregarded, so that the sum of

the I²R losses of primary and secondary can be taken as the total

copper loss for practical purposes.

~Ques. What effect has the power factor on the copper losses?~

Ans. Since the copper loss depends upon the current in the primary and

secondary windings, it requires a larger current when the power factor

is low than when high, hence the copper losses increase with a lowering

of the power factor.

[Illustration: FIG. 1,954.--Method of bringing out the secondary leads

in Wagner central station transformers. Each primary lead is brought

into the case through a similar bushing. Observe the elimination of all

possibility of grounding the cable on the case or core.]

~Ques. What effect other than heating has resistance in the windings?~

Ans. It causes poor regulation.

This is objectionable, especially when incandescent lights are

in use, because the voltage fluctuates inversely with load

changes, that is, it drops as lamps are turned on and rises

as they are turned off, producing disagreeable changes in the

brilliancy of the lamps.

~Cooling of Transformers.~--Owing to the fact that a transformer is a

stationary piece of apparatus, not receiving ventilation from moving

parts, its efficient cooling becomes a very strong feature of the

design, especially in the case of large high pressure transformers. The

effective cooling is rendered more difficult because transformers are

invariably enclosed in more or less air tight cases, except in very dry

situations, where a perforated metal covering may be permitted.

[Illustration: FIGS. 1,955 and 1,956.--Westinghouse transformer

terminal blocks for high and low tension conductors.]

The final degree to which the temperature rises after continuous

working for some hours, depends on the total losses in iron and copper,

on the total radiating surface, and on the facilities afforded for

cooling.

There are various methods of cooling transformers, the cooling mediums

employed being

1. Air;

2. Oil;

3. Water.

The means adopted for getting rid of the heat which is inevitably

developed in a transformer by the waste energy is one of the important

considerations with respect to its design.

~Ques. What is the behaviour of a transformer with respect to heating

when operated continuously at full load?~

Ans. The temperature gradually rises until at the end of some hours it

becomes constant.

The difference between the constant temperature and that of the

secondary atmosphere is called the temperature rise at full

load. _Its amount constitutes a most important feature in the

commercial value of the transformer._

[Illustration: FIGS. 1,957 to 1,960.--Porcelain bushing for

Westinghouse transformers.]

~Ques. Why is a high rise of temperature objectionable?~

Ans. It causes rapid deterioration of the insulation, increased

hysteresis losses, and greater fire risk.

~Dry Transformers.~--This classification is used to distinguish

transformers using air as a cooling medium from those which employ a

liquid such as water or oil to effect the cooling.

~Air Cooled Transformers.~--This name is given to all transformers

which are cooled by currents of air without regard to the manner in

which the air is circulated. There are two methods of circulating the

air, as by

1. Natural draught;

2. Forced draught, or blast.

~Ques. Describe a natural draught air cooled transformer.~

Ans. In this type, the case containing the windings is open at the top

and bottom. The column of air in the case expands as its temperature

rises, becoming lighter than the cold air on the outside and is

consequently displaced by the latter, resulting in a circulation of air

through the case. The process is identical with furnace draught.

[Illustration: FIGS. 1,961 to 1,963.--Fuse blocks for Westinghouse

transformers. The fuses furnished with the transformers are mounted in

a weather proof porcelain fuse box of special design. The stationary

contacts are deeply recessed in the porcelain and are well separated

from each other. The contacts are so constructed that the plug is held

securely in place by giving it a partial turn after inserting it. When

the plug is in position, the fuse is in sight and its condition can be

noted which eliminates all danger of pulling the fuse while same is

still intact and the transformer is under load.]

~Ques. Describe a forced draught or air blast transformer.~

Ans. The case is closed at the bottom and open at the top. A current of

air is forced through from bottom to top as shown in fig. 1,964 by a

fan.

~Ques. How are the coils best adapted to air cooling?~

Ans. They are built up high and thin, and assembled with spaces between

them, for the circulation of the air.

~Ques. What are the requirements with respect to the air supply in

forced draught transformers?~

Ans. Air blast transformers require a large volume of air at a

comparatively low pressure. This varies from one-half to one ounce

per square inch. The larger transformers require greater pressure to

overcome the resistance of longer air ducts.

[Illustration: FIG. 1,964.--Forced draught or "air blast" transformer.

As is indicated by the classification, this type of transformer is

cooled by forcing a current of air through ducts, provided between the

coils and between sectionalized portions of the core. The cold air

is forced through the interior of the core containing the coils by a

blower, the air passing vertically through the coils and out through

the top. Part of the air is sometimes diverted horizontally through

the ventilating ducts provided in the core, passing off at one side of

the transformer. The amount of air going through the coils, or through

the core, may be controlled independently by providing dampers in the

passages.]

~Ques. How much air is used ordinarily for cooling per kw. of load?~

Ans. About 150 cu. ft. of air per minute.

In forced draught transformers, the air pressure maintained

by the blower varies from ½ to 1½ oz. per square inch. Forced

draught or air blast transformers are seldom built in small

sizes or for voltages higher than about 35,000 volts.

~Oil Cooled Transformers.~--In this type of transformer the coils and

core are immersed in oil and provided with ducts to allow the oil to

circulate by convection and thus serve as a medium to transmit the heat

to the case, from which it passes by radiation.

[Illustration: FIG. 1965.--Looking down into a Wagner central station

transformer, showing the connection board, which provides facility for

varying the ratio of transformation and also for interchanging the

primaries.]

~Ques. Explain in detail the circulation of the oil.~

Ans. The oil, heated by contact with the exposed surfaces of the core

and coils, rises to the surface, flows outward and descends along the

sides of the transformer case, from the outer surface of which the heat

is radiated into the air.

~Ques. How may the efficiency of this method of cooling be increased?~

Ans. By providing the case with external ribs or fins, or by "fluting"

so as to increase the external cooling surface.

[Illustration: FIG. 1966.--Section through Westinghouse ½ kilovolt

ampere type S transformer. FIG. 1967.--Section through Westinghouse 50

kilovolt ampere type S transformer showing large oil ducts.]

~Ques. In what types of transformer is this mode of oil cooling used?~

Ans. Lighting transformers.

In such transformers, the large volume of oil absorbs

considerable heat, so that the rise of temperature is retarded.

Hence, for moderate periods of operation, say 3 or 4 hours,

the average lighting period, the maximum temperature would not

be reached.

~Ques. In what other capacities except that of cooling agent, does the

oil act?~

Ans. It is a good insulator, preserves the insulation from oxidation,

increasing the breakdown resistance of the insulation, and generally

restores the insulation in case of puncture.

[Illustration: FIG. 1,968.--Wagner 300 kva, 4,400 volt three phase oil

cooled transformer. In this type of transformer the case is filled with

oil and fluted so as to increase the cooling surface, an oil drain

valve is screwed to a wrought iron nipple cast into the base, the duct

to which is in such a position as to make it possible not only to drain

all of the oil from the transformer, but when desirable, to draw off a

small quantity from the bottom. Should any moisture be in the oil it is

therefore drawn off first.]

~Ques. What is the special objection to oil?~

Ans. Danger of fire.

~Ques. What kind of oil is used in transformers?~

Ans. Mineral oil.

~Ques. What are the requirements of a good grade of transformer oil?~

Ans. It should show very little evaporation at 212° Fahr., and should

not give off gases at such a rate as to produce an explosive mixture

with the air at a temperate below 356°. It should not contain moisture,

acid, alkali or sulphur compounds.

[Illustration: FIG. 1,969.--Section through Fort Wayne (type A)

transformer showing interior of case, core conductors, and insulation,

also division of laminæ.]

The presence of moisture can be detected by thrusting a red

hot nail in the oil; if the oil "crackle," water is present.

Moisture may be removed by raising the temperature slightly

above the boiling point, 212° Fahr., but the time consumed

(several days) is excessive.

~Water Cooled Transformers.~--A water cooled transformer is one in

which water is the cooling agent, and, in most cases, oil is the

medium by which heat is transferred from the coils to the water. In

construction, pipes or a jacketed casing is provided through which the

cooling water is passed by forced circulation, as shown in figs. 1,970

and 1,971.

[Illustration: FIG. 1,970.--Water cooled transformer with internal

cooling coil, that is, with cooling coil within the transformer case.

In this type, the cooling coil, through which the circulating water

passes, is placed in the top of the case or tank, the latter is

filled with oil so that the coil is submerged. The oil acts simply

as a medium to transfer the heat generated by the transformer to the

water circulating through the cooling coil. In operation a continual

circulation of the oil takes place, as indicated by the arrows, due

to the alternate heating and cooling it receives as it flows past the

transformer coils and cooling coil respectively.]

In some cases tubular conductors are provided for the circulation of

the water.

Water cooled transformers may be divided into two classes, as those

having:

1. Internal cooling coils;

2. External cooling coils.

~Ques. Describe the first named type.~

Ans. Inside the transformer case near the top is placed a coil of

wrought iron pipe, through which the cooling water is pumped. The case

is filled with oil, which by _thermo-circulation_ flows upward through

the coils, transferring the heat absorbed from the coils to the water;

on cooling it becomes more dense (heavier) and descends along the

inside surface of the casing.

[Illustration: FIG. 1,971.--Water cooled transformer with external

cooling coil. In this arrangement the cooling coil is placed in a

separate tank as shown. Here forced circulation is employed for both

the heat transfer medium (oil) and the cooling agent (water), two

pumps being necessary. The cool oil enters the transformer case at

the lowest point and absorbing heat from the transformer coils it

passes off through the top connection leading to the cooling coil and

expansion tank. Since the transformer tank is closed, an expansion tank

is provided to allow for expansion of the oil due to heating. The water

circulation is arranged as illustrated.]

~Ques. How much circulating water is required?~

Ans. It depends upon the difference between the initial and discharge

temperatures of the circulating water.

[Illustration: FIG. 1,972.--Interior of General Electric water cooled

140,000 volt transformer showing cooling coil.]

~Ques. In water cooled transformers how much cooling surface is

required for an internal cooling coil?~

Ans. The surface of the cooling coil should be from .5 to 1.3 sq. in.

per watt of total transformer loss, depending upon the amount of heat

which the external surface of the transformer case will dissipate.

For a water temperature rise of 43° Fahr., 1.32 lbs. of water

per minute is required per kw. of load.

~Transformer Insulation.~--This subject has not, until the last few

years, been given the same special attention that many other electrical

problems have received, although the development of the transformer

from its original form, consisting of an iron core enclosed by coils of

wire, to its present degree of refinement and economy of material, has

been comparatively rapid.

In transformer construction it is obviously very important that

the insulation be of the best quality to prevent burn outs and

interruptions of service.

~Ques. What is the "major" insulation?~

Ans. The insulation placed between the core and secondary (low

pressure) coils, and between the primary and secondary coils.

[Illustration: FIG. 1,973.--Assembled coils of General Electric water

cooled 500 kva., 66,000 volt transformer.]

It consists usually of mica tubes, sometimes applied as sheets

held in place by the windings, when no ventilating ducts are

provided, or moulded to correct form and held between sheets of

tough insulating material where ducts are provided for air or

oil circulation.

~Ques. Describe the "minor" insulation.~

Ans. It is the insulation placed between adjacent turns of the coils.

Since the difference of pressure is small between the adjacent

turns the insulation need not be very thick. It usually

consists of a double thickness of cotton wrapped around each

conductor. For round conductors, the ordinary double covered

magnet wire is satisfactory.

~Ques. What is the most efficient insulating material for transformers?~

Ans. Mica.

It has a high dielective strength, is fireproof, and is the

most desirable insulator where there are no sharp corners.

[Illustration: FIG. 1,974.--Three Westinghouse 20 kva, outdoor

transformers, for irrigation service. These are mounted on a drag

so that they may be readily transported from place to place. 33,000

volts high tension; 2,200 and 440 volts low tension, 50 cycles. These

outdoor transformers are of the oil immersed, self-cooling type and

have been developed to meet the requirements for transformers of

capacities greater or of voltages higher than are usually found in

distribution work. They are in reality distributing transformers for

high voltage, outdoor installations, single or three phase service,

for voltages up to 110,000. Where the magnitude of the load does not

warrant an expensive installation, transformers of the outdoor type are

particularly applicable. The cost of a building and outlet bushings

which is often the item of greatest expense is eliminated where outdoor

type transformers are installed.]

~Oil Insulated Transformers.~--High voltage transformers are insulated

with oil, as it is very important to maintain careful insulation not

only between the coils, but also between the coils and the core. In the

case of high voltage transformers, any accidental static discharge,

such as that due to lightning, which might destroy one of the air

insulated type, might be successfully withstood by one insulated with

oil, for if the oil insulation be damaged it will mend itself at once.

By providing good circulation for the oil, the transformer can get rid

of the heat produced in it readily and operate at a low temperature,

which not only increases its life but cuts down the electric resistance

of the copper conductors and therefore the I²R loss.

~Efficiency of Transformers.~--The efficiency of transformers is _the

ratio of the electric power delivered at the secondary terminals to the

electric power absorbed at the primary terminals_.

Accordingly, the output must equal the input minus the losses. If the

iron and copper losses at a given load be known, their values and

consequently the efficiency at other loads may be readily calculated.

EXAMPLE.--If a 10 kilowatt constant pressure transformer at full load

and temperature have a copper loss of .16 kilowatt, or 1.6 per cent.,

and the iron loss be the same, then its

output 10

efficiency = ------ = -------------- × 100 = 96.9 per cent.

input   10 + .16 + .16

At three-quarters load the output will be 7.5 kilowatts; and as the

iron loss is practically constant at all loads and the copper loss is

proportional to the square of the load, the

output 7.5

efficiency = ------ = --------------- × 100 = 96.8 per cent.

input  7.5 + .16 + .09

The matter of efficiency is important, especially in the case of large

transformers, as a low efficiency not only means a large waste of power

in the form of heat, but also a great increase in the difficulties

encountered in keeping the apparatus cool. The efficiency curve shown

in fig. 1,975, serves to indicate, however, how slight a margin

actually remains for improvement in this particular in the design and

construction of large transformers.

[Illustration: FIG. 1,975.--Efficiency curve of Westinghouse 375 kw.,

transformer. Pressure 500 to 15,000 volts; frequency 60. Efficiencies

at different loads: full load efficiency, 98%; ¾ full load efficiency,

98%; ½ full load efficiency, 97.6%; ¼ full load efficiency, 96.1%;

regulation non-inductive load, 1.4%; load having .9 power factor, 3.3%.]

The efficiency of transformers is, in general, higher than that

of other electrical machines; even in quite small sizes it

reaches over 90 per cent., and in the largest, is frequently as

high as 98.5 per cent.

To measure the efficiency of a transformer directly, by

measuring input and output, does not constitute a satisfactory

method when the efficiency is so high. A very accurate

result can be obtained, however, by measuring separately, by

wattmeter, the core and copper losses.

The core loss is measured by placing a wattmeter in circuit

when the transformer is on circuit at no load and normal

frequency.

The copper loss is measured by placing a wattmeter in circuit

with the primary when the secondary is short circuited, and

when enough pressure is applied to cause full load current to

flow.

If it be desired to separate the load losses from the true

I²R loss, the resistances can be measured, and the I²R loss

calculated and subtracted from the wattmeter reading. The

losses being known, the efficiency at any load is readily found

by taking the core loss as constant and the copper loss as

varying proportionally to the square of the load. Thus,

output

efficiency = --------------- × 100

output + losses

~All Day Efficiency of Transformers.~--This denotes the ratio of the

total watt hour output of a transformer to the total watt hour input

taken over a working day. To compute this efficiency it is necessary to

know the load curve of the transformer over a day. Suppose that this is

equivalent to 5 hours at full load, and 19 hours at no load. Then, if

W₁ be the core loss in watts, W₂ the copper loss at rated load, and W

the rated output,

output = 5 × W,

losses = 5 (W₁ + W₂) + 19 W₁,

input  = 5 (W + W₁ + W₂) + 19 W₁,

and the all day efficiency is equal to

5W × 100

--------------------- per cent.

5(W + W₁ + W₂) + 19W₁

Commercial or all day efficiency is a most important point in a good

transformer. The principal factor in securing a high all day efficiency

is to keep the core loss as low as possible. The core loss is

constant--it continues while current is supplied to the primary, while

copper loss takes place only when the secondary is delivering energy.

In general, if a transformer is to be operated at light loads the

greater part of the day, it is much more economical to use one designed

for a small iron loss than for a small full load copper loss.

[Illustration: FIGS. 1,976 and 1,977.--Westinghouse double pole fuse

box; views showing box open with tubes in place, and with tubes

removed.]

~Transformer Fuse Blocks.~--These may be of either the single pole or

double pole type. Fig. 1,976 shows a double pole fuse box opened, and

fig. 1,977, the fuse box opened and the tubes removed. Of the four

wires, W, W, W, W, entering the box from beneath, two are from the

primary mains, and two lead to the primary coil of the transformer.

These wires terminate in metallic receptacles R, R, R, R, in the

porcelain plate P, fig. 1,977, which are bridged over in pairs by fuse

wires placed inside porcelain tubes T, T, as shown in fig. 1,976. These

tubes are air tight except for a small outlet O in each, which fit into

the receptacles B, B, in the porcelain plate and open out at the back

of the block, as shown in fig. 1,977.

The fuse wires are connected between metallic spring tubes S, S, S, S,

which fit into the receptacles R, R, R, R.

If a sudden load or a short circuit occur in the transformer, the

intense heat, accompanying the melting or blowing of the fuse,

causes a rapid expansion of the air inside the tube, so that a strong

blast of air rushes through the outlet O of the tube and immediately

extinguishes the arc.

By this arrangement, sustained arcing is prevented, as the

action of the tube causes the arc to extinguish itself

automatically when the current is interrupted.

The porcelain tubes are held in position by the spring K, and

the primary of the transformer becomes entirely disconnected

from the circuit when the tubes are lifted out.

This form of construction enables the lineman to detach

the tubes from the fuse box, and insert the fuse at his

convenience. Furthermore, when inserting a fuse in a short

circuited line, he does not run the risk of being hurt, as

the heated vapor of the exploding fuse can escape through

the outlet provided for that purpose, and in a predetermined

direction.

The method of attaching the lid not only permits of quick

access to the interior of the box, but enables the lineman to

tighten the joints by means of the thumb screws L, L, so as to

keep the box waterproof.

[Illustration: FIG. 1,978.--Diagram illustrating connections and

principles of auto-transformers as explained in the accompanying text.]

~Auto-transformers.~--In this class of transformer, there is only one

winding which serves for both primary and secondary. On account of its

simplicity it is made cheaply.

Auto-transformers are used where the ratio of transformation

is small, as a considerable saving in copper and iron can be

effected, and the whole transformer reduced in size as compared

with one having separate windings.

Fig. 1,978 illustrates the electrical connections and the

relations between the volts and number of turns.

By using the end wire and tapping in on turn No. 20 a current

at 20 volts pressure is readily obtained which may be used for

starting up motors requiring a large starting current and yet

not draw heavily on the line.

Since the primary is connected directly to the secondary it

would be dangerous to use an auto-transformer on high pressure

circuits. This type of transformer has only a limited use,

usually as compensator for motor starting boxes.

[Illustration: FIGS. 1,979 and 1,980.--Two winding transformer and

single winding or auto-transformer. Fig. 1,979 shows a 200:100 volt

transformer having a 10 amp. primary and a 20 amp. secondary, the

currents being in opposite directions. If these currents be superposed

by using one winding only, the auto-transformer shown in fig. 1,980

is obtained where the winding carries 10 amp. only and requires only

one-half the copper (assuming the same mean length of turn). If R be

the ratio of an auto-transformer, the relative size of it compared

with a transformer of the same ratio and output is ((R - 1) / R):1.

For example, a 10 kw. transformer of 400 volts primary and 300 volts

secondary could be replaced by an auto-transformer of

10 × (1.33 - 1) / 1.33 = 2.5 kw.; or, in other words, the amount

of material used in a 2½ kw. transformer could be used to wind an

auto-transformer of 400:300 ratio and 10 kw. output.]

~Constant Current Transformers for Series Arc Lighting.~--The

principle of the constant current transformer as used for series arc

lighting is readily understood by reference to the elementary diagram

shown in fig. 1,981. A constant alternating current is supplied to

the stationary primary coil which induces a current in the movable

secondary coil. The pressure induced in the coil will depend on the

number of lines of flux which pass through it and by changing its

position in the magnetic field over the primary a variable e.m.f. can

be produced and a constant current maintained in the lighting circuit

when the lamps are turned on or off, or if the resistance of the

circuit be lowered by the consumption of the carbons.

[Illustration: FIG. 1,981.--Elementary diagram illustrating the

principles of constant current transformer as used for series arc

lighting.]

Since the induced currents in the secondary are repelled by the primary

there is a tendency for the secondary coil to jump out of the primary

field, and in case of a very large current due to a short circuit in

the lamp circuit, the secondary current is quickly reduced to normal by

the rapid movement of the coil upward.

By adjusting the counterweight for a given number of amperes required

by the arc, the current will be maintained constant by the movement of

the secondary coil.

The magnetic field produced by the primary must be kept the same by a

constant current from the alternator, therefore, when the lamp load is

increased the primary voltage increases similar to that of an ordinary

series wound direct current dynamo. In other words the alternator and

regulating transformer supply a constant current and variable voltage.

[Illustration: FIG. 1,982.--Mechanism of General Electric air cooled

constant current transformer. It operates on the principle explained in

the accompanying text and is built to supply 25 to 100 arc lamps at 6.6

to 7.5 amperes. The transformers are interchangeable and will operate

on 60 or 125 cycles. The relative positions of the two coils may be

changed in order to regulate the strength of the current more closely,

by shifting the position of the arc carrying the counterbalance by

means of the adjusting screw on it. A dash pot filled with special oil

prevents sudden movements of the secondary coil and keeps the current

through the lamps nearly constant, when they are being cut in or out

of the circuit. In starting up a constant current transformer, it is

necessary to separate the two coils as far as possible and then close

the primary circuit switch and allow the two coils to come together.

If the primary circuit be thrown directly on the generator the heavy

rush of current which will follow due to the two coils being too close

together might injure the lamps.]

Constant current incandescent lighting systems for use in small towns

also use this method for automatically regulating the current.

~Regulation.~--This term applies to the means adopted either to obtain

constancy of pressure or current. In the transformer, regulation is

_inherent_, that is, the apparatus automatically effects its own

regulation. The regulation of a transformer means, _the change of

voltage due to change of load on the secondary_; it may be defined more

precisely as: _the percentage increase in the secondary voltage as the

load is decreased from its normal value to zero_. Thus, observation

should be made of the secondary voltage, at full load and at no load,

the primary pressure being held constant at the normal value.

[Illustration: FIG. 1,983.--General Electric air cooled constant

current transformer. View showing external appearance with case on.]

The regulation is said to be "good" or "close," when this

change is small. In the design of a transformer, good

regulation and low iron losses are in opposition to one another

when the best results are desired in both. A well designed

transformer, however, should give good results, both as to

regulation and iron losses, the relative value depending upon

the class of work it has to do, and size.

~Transformer Connections.~--The alternating current has the advantage

over direct current, in the ease with which the pressure and current

can be changed by different connections of transformers.

On single phase circuits the transformer connections can be varied to

change current and pressure, and in addition on polyphase circuits the

phases can also be changed to almost any form.

~Single Phase Connections.~--The method of connecting ordinary

distributing transformers to constant pressure mains is shown by the

elementary diagram, fig. 1,984, where a transformer of 10 to 1 ratio is

indicated with its primary winding connected to a 1,000 volt main, and

a secondary winding to deliver 100 volts.

[Illustration: FIG. 1,984.--Single phase transformer connection with

constant pressure main.]

[Illustration: FIG. 1,985.--Usual method of single phase transformer

connections for residence lighting with three wire secondaries. A

balancing transformer is connected to the three wire circuit near the

center of distribution as shown.]

Fig. 1,986 shows a transformer with each winding divided into two

sections. Each primary section is wound for 1,000 volts, and each

secondary section for 50 volts. By connecting the entire primary

winding in series, the transformer may be supplied from a 2,000 volt

main, as indicated, and if the secondary winding be also connected

all in series, as shown, the no load voltage will be 100 between the

secondary terminals.

[Illustration: FIG. 1,986.--Diagram of single phase transformer having

primary and secondary windings in two sections, showing voltages per

section with series connections.]

The sections of the primary winding may be connected in parallel to

a 1,000 volt main, and 100 volts obtained from the secondary, or the

primary and secondary windings may be connected each with its two

sections in parallel, and transformations made from 1,000 to 50 volts

as represented in fig. 1,987.

This is a very common method of construction for small

transformers, which are provided with convenient terminal

blocks for combining the sections of each winding to suit the

requirements of the case. When the two sections of either

winding are connected in parallel as shown in fig. 1,987, _care

must be taken to connect_ ~corresponding ends~ _of the two

sections together_.

~Combining Transformers.~--Two or more transformers built to operate

at the same pressure and frequency may be connected together in a

variety of ways; in fact, the primary and secondary terminals may each

be considered exactly as the terminals of direct current dynamos, with

certain restrictions.

[Illustration: FIG. 1,987.--Diagram of single phase transformer with

primary and secondary windings of two sections each, showing voltages

per section with parallel connection.]

~Ques. What are the two principal precautions which must be observed in

combining transformer terminals?~

Ans. The terminals must have the same polarity at a given instant, and

the transformers should have practically identical characteristics.

The latter condition is not absolutely essential, but it

is emphatically preferable. For example, if a transformer,

which has 2 per cent. regulation, be connected in parallel,

as indicated in fig. 1,988, with one which has 3 per cent.

regulation, at no load the transformers will give exactly the

same voltage at the secondary terminals, but at full load one

will have a secondary pressure of, say, 98 volts, while the

other has 97 volts. The result is that the transformer giving

only 97 volts will be subject to a reverse pressure of one

volt from its mate. This will not cause excessive current to

flow backward through the secondary winding of the low voltage

transformer, but it will disturb the phase relations and lower

the power factor and efficiency of the combination. In such a

case it is much better to work the secondary circuits of the

two transformers separately.

In case the transformers have practically the same

characteristics it is necessary, as stated above, to make sure

that the secondary terminals connected together have the same

polarity at a given instant; it is not necessary to find out

definitely what the polarity is, merely that it is the same for

both terminals. This can be easily done as shown in fig. 1,989.

[Illustration: FIG. 1,988.--Diagram showing unlike single phase

transformers in parallel.]

~Ques. What may be said with respect to operating transformer

secondaries in parallel?~

Ans. It is seldom advantageous. Occasionally it may be necessary as a

temporary expedient, but where the load is such as to require a greater

capacity than that of a transformer already installed, it is much

better to replace it by a large transformer than to supplement it by an

additional transformer of its own size.

~Ques. How are the secondaries arranged in modern transformers and why?~

Ans. The secondary windings are divided into at least two sections so

that they may be connected either in series or parallel.

~Ques. Explain how secondary connections are made for different

voltages.~

Ans. If, for instance, the secondary pressure of a transformer having

two sections be 100 volts with the terminals in parallel, as in fig.

1,990, then connecting them in series will give 200 volts at the free

secondary terminals, as indicated in fig. 1,991.

~Ques. What precaution should be taken in connecting secondary sections

in parallel in core type if the two sections be wound on different

limbs of the cores?~

[Illustration: FIG. 1,989.--Method of comparing instantaneous polarity.

Two of the terminals are connected as shown by a small strip of fuse

wire, and then touching the other two terminals together. If the fuse

blows, then the connections must be reversed; if it does not, then they

may be made permanent.]

Ans. It will be advisable to make the connections ample and permanent,

so that there will not be any liability to a difference between the

current flowing in one secondary winding and that flowing through the

other.

~Two Phase Connections.~--In the case of two phase distribution each

circuit may be treated as entirely independent of the other so far as

the transformers are concerned. Two transformers are used, one being

connected to one primary phase and supplying one secondary phase, the

other being connected to the other primary phase and supplying the

other secondary phase as indicated in fig. 1,996, exactly as though

each primary and secondary phase were an ordinary single phase system,

independent of the other phase.

[Illustration: FIGS. 1,990 and 1,991.--Methods of altering the

secondary connections of a transformer having two sections in the

secondary to obtain a different voltage. Fig. 1,990 shows the two

sections in parallel giving say 100 volts; fig. 1,991 shows the two

sections in series giving 200 volts.]

~Ques. Is the above method usually employed?~

Ans. No, the method shown in fig. 1,997 is generally used.

~Three Phase Connections.~--There is not so much freedom in making

three phase transformer connections, as with single or two phase,

because the three phases are inseparably interlinked. However, the

system gives rise to several methods of transformer connection, which

are known as:

1. Star;

2. Delta;

3. Star-delta;

4. Delta-star.

[Illustration: FIGS. 1,992 to 1,995.--Three phase transformer

connections. Fig. 1,992 ~delta~ connection; fig. 1,993 ~star~

connection; fig. 1,994 ~delta star~ connection; fig. 1,995 ~star-delta~

connection.] /#

~Delta Connection.~--In the delta connection both primaries and

secondaries are connected in delta grouping, as in fig. 1,992.

~Star Connection.~--This method consists in connecting both the

primaries and secondaries in star grouping, as in fig. 1,993.

~Delta-star Connection.~--In this method the primaries are connected in

delta grouping and the secondaries in star grouping, as in fig. 1,994.

~Star-delta Connection.~--This consists in connecting the primaries in

star grouping, and the secondaries in delta grouping, as in fig. 1,995.

[Illustration: FIG. 1,996.--Two phase transformer connections. Two

single phase transformers are used and connections made just as though

each phase were an ordinary single phase system.]

~Ques. What advantage has the star connection over the delta

connection?~

Ans. Each star transformer is wound for only 58% of the line voltage.

In high voltage transmission, this admits of much smaller transformers

being built for high pressure than possible with the delta connection.

~Ques. What advantages are obtained with the delta connection?~

Ans. When three transformers are delta connected, one may be removed

without interrupting the performance of the circuit, the two remaining

transformers in a manner acting in series to carry the load of the

missing transformer.

[Illustration: FIG. 1,997.--Two phase transformer connections, with

secondaries arranged for three wire distribution, the primaries

being independently connected to the two phases. In the three wire

circuit, the middle or neutral wire is made about one-half larger than

each of the two outer wires. In fig. 1,996 it makes no difference

which secondary terminal of a transformer is connected to a given

secondary wire, so long as no transformers are used in parallel. For

example, referring to the diagram, the left hand secondary terminal

of transformer, A, could just as well be connected to the lower wire

of the secondary phase, A, and its right hand terminal connected to

the upper wire, the only requirement being that the two pairs of mains

shall not be "mixed;" that is, transformer, A, must not be connected

with one secondary terminal to phase, A and the other to phase, B. In

the case shown by fig. 1,997, there is not quite so much freedom in

making connections. One secondary terminal of each transformer must be

connected to one of the outer wires and the other two terminals must be

both connected to the larger middle wire of the secondary system. It

makes no difference, however, which two secondary terminals are joined

and connected to the middle wire so long as the other terminal of each

transformer is connected to an outer wire of the secondary system.]

The desire to guard against a shut down due to the disabling

of one transformer has led to the extensive use of the delta

connection, especially for the secondaries or low pressure

side.

It should be noted that if one transformer be disabled, the

efficiency of the other two will be greatly reduced. To operate

a damaged three phase transformer, the damaged windings must

be separated electrically from the other coils, the damaged

primary and secondary being respectively short circuited upon

themselves.

~Ques. What kinds of transformers are used for three phase current?~

Ans. Either a three phase transformer, or a separate single phase

transformer for each phase.

[Illustration: FIG. 1,998.--Three wire connections for transformer

having two secondary sections on different legs of the core. If the

secondary terminals be connected up to a three wire distribution, as

here shown diagrammatically, it is advisable to make the fuse, 2,

in the middle wire, considerably smaller than necessary to pass the

normal load in either side of the circuit, because, should the fuse,

1, be blown, the secondary circuit through the section, Sa, will be

open, and the corresponding half of the primary winding, Pa, will

have a much higher impedance than the half of the primary winding,

Pb, the inductance of which is so nearly neutralized by the load on

the secondary winding, Sb. The result will be that the voltage of

the primary section, Pa, will be very much greater than that of the

section, Pb, and as the sections are in series the current must be the

same through both halves of the winding; the drop or difference of

pressure, therefore, between the terminals of Pa will be much higher

than that between the terminals of Pb, consequently, the secondary

voltage of Sb will be greatly lowered and the service impaired. As the

primary winding, Pa, is designed to take only one-half of the total

voltage, the unbalancing referred to will subject it to a considerably

higher pressure than the normal value; consequently, the magnetic

density in that leg of the transformer core will be much higher than

normal, and the transformer will heat disastrously. If the fuse, 2,

in the middle wire be made, say, one-half the capacity of each of the

other fuses, this condition will be relieved by the blowing of this

fuse, and as the lamps in the live circuit would not be anywhere near

candle power if the circuit remained intact, the blowing of the middle

fuse will not be any disadvantage to the user of the lamps. Some makers

avoid the contingency just described by dividing each secondary coil

into two sections and connecting a section on one leg in series with a

section on the other leg of the core, so that current applied to either

pair of the secondary terminals will circulate about both legs of the

core.]

[Illustration: FIGS. 1,999 to 2,002.--Three phase delta, and star

connections using three transformers. There are two ways of connecting

up the primaries and secondaries, one known as the "delta" connection,

and illustrated diagrammatically by fig. 1,999, and the other known

as the "star" connection, and illustrated by fig. 2,001. In both

diagrams the line wires are lettered, A, B and C. Fig. 2,000 shows the

primaries and secondaries connected up delta fashion, corresponding

to fig. 1,999, and fig. 2,002 shows them connected up star fashion,

corresponding to fig. 2,001. In both of the latter sketches the

secondary wires are lettered to correspond with the respective primary

wires. When the primaries are connected up delta fashion, the voltage

between the terminals of each primary winding is the same as the

voltage between the corresponding two wires of the primary circuit,

and the same is true of the secondary transformer terminals and

circuit wires. The current, however, flowing through the transformer

winding is less than the current in the line wire, for the reason

that the current from any one line wire divides between the windings

of two transformers. For example, in figs. 1,999 and 2,000, part of

the current from the line wire, A, will flow from A to B through the

left hand transformer, and part from A to C through the right hand

transformer; if the current in the line wire, A, be 100 amperes, the

current in each transformer winding will be 57.735 amperes. When

transformers are connected up star fashion, as in figs. 2,001 and

2,002, the current in each transformer winding is the same as that

in the line wire to which it is connected, but the voltage between

the terminals of each transformer winding is 57.735 per cent. of the

voltage from wire to wire on the circuit. For example, if the primary

voltage from A to B is 1,000 volts, the voltage at the terminals of

the left hand transformer (from A to J) will be only 577.35 volts,

and the same is true of each of the other transformers if the system

is balanced. These statements apply, of course, to both primary and

secondary windings, from which it will become evident that if the

three transformers of a three phase circuit be connected up star

fashion at the primaries, and delta fashion at the secondaries, the

secondary voltage will be lower than if both sides are connected up

star fashion. For example, if the transformers be wound for a ratio

of 10 to 1, and are connected up with both primaries and secondaries

alike, no matter whether it be delta fashion or star fashion, the

secondary voltage will be one-tenth of the primary voltage; but if the

primaries be connected up star fashion on a 1,000 volt circuit, and

the secondaries be connected up delta fashion, the secondary voltage

will be only 57.735 volts, instead of 100 volts. The explanation of the

difference between the voltage per coil in a delta system and that in

a star system is that in the former each winding is connected directly

across from wire to wire; whereas in the star system, two windings are

in series between each pair of line wires. The voltage of each winding

is not reduced to one-half, however, because the pressures are out of

phase with each other, being 120°, or one-third of a cycle, apart;

consequently, instead of having 500 volts at the terminals of each coil

in fig. 2,001 the voltage is 577.35. The same explanation applies to

the current values in a delta system. The current phase between A and

B, in fig. 1,999, is 120° removed from that in the winding between A

and C; consequently the sum of the two currents, in the wire, A, is

1.732 times the current in each wire; or, to state it the opposite way,

the current in each winding is 57.735% of the current in the wire, A.

It will be well for the reader to remember that in all cases pressures

differing in phase when connected in series, combine according to the

well-known law of the parallelogram of forces; currents differing in

phase, and connected in parallel, combine according to the same law.]

~Ques. What points are to be considered in choosing between three

phase and single phase transformers for the three phase current

transformation?~

Ans. No specific rule can be given regarding the selection of single

phase or three phase transformers since both designs are equally

reliable; local conditions will generally determine which type is

preferable.

The following general remarks may, however, be helpful:

Single phase transformers are preferable where only one

transformer group is installed and where the expense of a spare

transformer would not be warranted. In such installations

the burn out of one phase of a three phase unit would cause

considerable inconvenience for the reason that the whole

transformer would have to be disconnected from the circuit

before repairs could be made.

If single phase transformers be used and connected in delta

on both primary and secondary, the damaged transformer can

be cut out with a minimum amount of trouble and the other two

transformers can be operated at normal temperature open delta

at 58 per cent. of the normal capacity of the group of three

transformers, until the third unit can be replaced.

With a three phase shell type transformer, if both the primary

and secondary be delta connected, trouble in one phase will not

prevent the use of the other two phases in open delta. By short

circuiting both primary and secondary of the defective phase,

and cutting it out of circuit the magnetic flux in that section

is entirely neutralized. This cannot be done, however, with any

but delta connected shell type transformers.

[Illustration: FIG. 2,003.--Diagram showing three wire secondary

connections General Electric (type H) transformer. As will be seen,

the method adopted consists of distributing equally, on each side of

the primary coil, both halves of the secondary winding, so that each

secondary throughout its length is closely adjacent to the entire

primary winding. In order to insure the exact equality of resistance

and reactance in the two secondary windings necessary to obtain perfect

regulation of the two halves, the inside portion of the secondary

winding on one side of the primary coil is connected in series with the

outside portion of that on the other side. As a result, the drop of

voltage in either side of the secondary under any ordinary conditions

of unbalanced load, does not exceed the listed regulation drop. This

particular arrangement is used because it is the simplest and best

method for this construction.]

Where a large number of three phase transformers can be used,

it is generally advisable to install three phase units, the

following advantages being in their favor as compared with

single phase units:

1. Require less floor space than three single phase units;

2. Weigh less than the single phase units;

3. Simpler connections, as only three primary and three

secondary leads are generally brought out;

4. Transformer presents a symmetrical and compact appearance.

~Ques. What is the character of the construction of three phase

transformers?~

Ans. The three phase transformer is practically similar to that of

the single phase, except that somewhat heavier and larger parts are

required for the core structure.

~COMPARISON OF AIR BLAST, WATER COOLED, AND OIL COOLED

TRANSFORMERS~

======================+=======================+=======================

~Air blast type~ | ~Water cooled type~ | ~Oil cooled type~

----------------------+-----------------------+-----------------------

~1. COST~

----------------------+-----------------------+-----------------------

~A. First cost~ | |

Necessarily more |Least expensive of all |Necessarily more

expensive than the |types. |expensive than the air

water cooled type of | |blast and water cooled

similar rating. | |type of similar rating.

| |

~B.~ | |

The installation is |Being heavier than the |Being heavier than the

extremely simple. |air blast type, these |air blast and water

|transformers, as a |cooled type, these

Moisture that may |rule, require heavier |transformers require

have collected on the |apparatus for |heavier apparatus for

surfaces during |installing. Both |installing. Both

transportation |transformer and tank |transformer and tank

or storage should be |should be thoroughly |should be thoroughly

thoroughly dried out. |dried out before being |dried out before being

|filled with oil. |filled with oil.

| |

|The oil is usually |

|supplied in 50 gal. |

|hermetically sealed |

|steel barrels to |

|minimize possibility of|

|moisture during |

|transportation. |

----------------------+-----------------------+-----------------------

~C. Auxiliary | |

apparatus~| |

A duct, or chamber, |In most cases, cooling |Do not require cooling

of considerable size |water may be obtained |water or blower.

is required under the |with sufficient natural|

transformers in order |head. However, there |

to conduct the cooling|are frequent cases in |

air to them. |which it can be |

|obtained only by the |

A blower outfit for |use of pumps. |

supplying air is | |

required. |A system of piping for |

|the cooling water and |

|oil drainage is |

|required, the cost of |

|which depends, of |

|course, on the station |

|layout. |

~D. Maintenance~ | |

An occasional |A water pumping outfit |No air or water

cleaning, for which a |would possibly require |circulation to demand

supply of compressed |a trifle more attention|attention.

air at about 20 lb. |than a blower outfit in|

pressure is |which there are no |

recommended. |valves or piping. |

| |

The blower outfit | |

requires no more care | |

than any other similar| |

apparatus. | |

======================+=======================+=======================

~2. FLOOR SPACE~

----------------------+-----------------------+-----------------------

Always requires space |Extra space only |Only require space for

for cooling apparatus.|required when auxiliary|the transformer as no

|pumping apparatus is |extra apparatus is

|necessary. |necessary

======================+=======================+=======================

~3. LOCATION~

----------------------+-----------------------+-----------------------

As the transformers |Transformers are |Transformers are

are open at the top |completely enclosed but|completely enclosed but

they should not be |location should be such|location should be such

located where there is|that no water will fall|that no water will fall

much dust or dirt nor |on leads or bushings. |on leads or bushings.

where water from any | |

source is liable to | |The building should be

fall on them. | |well ventilated.

| |

| |There is no auxiliary

| |apparatus.

The blower should be |Location of auxiliary |

so situated as to |apparatus will depend |

obtain clean dry air |on the station layout. |

of a temperature not | |

greater than 77° Fahr.| |

======================+=======================+=======================

~4. GENERAL APPEARANCE~

----------------------+-----------------------+-----------------------

Terminal leads may |Leads are brought out |Leads are brought out

be located in the |of the top of the |of the top of the

base and the air |transformers. |transformers.

chamber may be used | |

for conducting and |Water cooling pipes |

distributing the |are connected at the |

connecting wiring. |top in most cases. |

| |

The absence of | |

overhead wiring aids | |

in simplifying the | |

appearance of the | |

station. | |

======================+=======================+=======================

~5. OPERATION~

----------------------------------------------------------------------

Equal reliability in all three types.

While full load efficiencies are practically equal in the three

designs, it is necessary to change the proportion of iron and copper

losses somewhat as the copper loss of the air blast transformer is a

smaller part of its total loss than of the water cooled and oil cooled

types. As a result, the regulation of the air blast transformer is a

trifle better.

======================================================================

~6. GENERAL~

----------------------------------------------------------------------

The above information regarding selection of type is not applicable

to air blast transformers for circuits materially in excess of 33,000

volts.

On account of the great thickness of the solid insulation needed and

the consequent difficulty in radiating heat from the copper, it is

impracticable to design the air blast type for more than this voltage.

The oil immersed designs are therefore recommended for transformers

above 33,000 volts.

Both oil cooled and water cooled types are available for all

voltages, being restricted in this respect only by the limitations of

transmission facilities.[8]

======================================================================

[8] NOTE.--No special foundations are necessary for any type of

transformer other than a good, even floor, having sufficient strength

to support the weight.

[Illustration: FIGS. 2,004 to 2,011.--Connections of standard

transformers. All stock transformers are wound for some standard

transformation ratio, such as 10 to 1, but various leads are brought

out by means of which ratios of 5, 10 and 20 to 1 may be obtained for

one transformer. The figures show the voltage combinations possible

with a standard transformer.]

~Ques. How are transformers connected for four wire three phase

distribution?~

Ans. When the secondaries of three transformers are star connected, a

fourth wire may be run from the neutral point, thus obtaining the four

wire system.

[Illustration: FIG. 2,012.--Method of determining core loss. Connect

voltmeter and wattmeter as shown in the illustration to the low tension

side of the transformer. By means of a variable voltage transformer

bring the applied voltage to the point for which the transformer

is designed. The wattmeter indicates directly the core loss, which

includes a very small loss due to the current in the copper.

~Cautions.~--1. Make sure of the voltage and frequency. The

manufacturers' tabulated statements refer to a definite voltage and

frequency and these have a decided influence upon the core loss. 2. The

high tension circuit must remain open during the test.]

The voltage between any main wire and the neutral will be

57 per cent. of the voltage between any two main wires. For

general distribution this system is desirable, requiring less

copper and greater flexibility than other systems.

Three phase 200 volt motors may be supplied from the main wires

and 115 volt lamps connected between each of the three main

wires and the neutral; if the lamp load be very nearly balanced

the current flowing in the neutral wire will be very small, as

in the case of the ordinary three wire direct current system.

~How to Test Transformers.--~The troubles incident to gas or water

service have their parallels in electric power distribution.

[Illustration: FIG. 2,013.--Method of determining copper loss. Connect

ammeter and wattmeter to high tension side of transformer short circuit

secondary leads, as shown in the illustration, and by means of a

variable voltage, adjust current to the full load value for which the

transformer is intended. The wattmeter reading shows the copper loss at

full load. The full load primary current of any transformer is found

from the following equation.

_full load current = full load watts ÷ primary volts_

EXAMPLE: To find proper full load current on a five kw. 2,200 volt

transformer, divide 5,000 watts by 2,200 volts, the full load current

will then be 2.27 amperes. A slight variation in primary current

greatly increases or decreases the copper loss.

~Remarks.~--Copper loss increases with temperature because the

resistance of the metal rises. Do not overload the current coil of the

wattmeter. For greater accuracy the I²R drop of potential method should

be used.]

Companies engaged in the former, credit a large percentage of their

losses to leaky valves and defective mains. The remedy may involve

heavy expense and the loss is often tolerated as the lesser of two

evils.

In electric power distribution the transformer takes in part the place

of the valve and pipe system. An inferior or defective transformer

usually treats both the central station and its customers badly, being

in this respect more impartial than the gas or water pipe which may

annoy but one of the interested parties at a time.

Like a neglected or defective gas fixture a transformer can

menace life, failing, however, to give the warning the former

gives, and with a more hidden threat on account of its location.

[Illustration: FIG. 2,014.--Diagram of connections for regulation

test. Connect transformer under test to high tension supply circuit.

A second transformer with same or other known change ratio is also

to be connected up, as illustrated. By means of a double pole double

throw switch, the voltmeter can be made to read the pressure on the

secondary of either transformer. Supposing the same change ratio it

is evident that if both remain unloaded the voltmeter will indicate

the same pressure. A gradually increasing lamp load up to the limit

of the transformer capacity, will be attended by a drop in pressure

at the terminals. This drop can be read as the difference of the

voltmeter indications, and when expressed in per cent. of secondary

voltage stands for "regulation." ~Remarks:~ The auxiliary transformer

is necessary in order to make sure of the high tension line voltage. A

large transformer under test may cause primary drop in taking power.

This must be set down against it in testing regulation. The second

transformer gives notice of such drop, whatever be the cause. Figs.

2,012 to 2,014 used by courtesy of the Moloney Electric Co.]

Apart from this, corresponding to an exasperated customer who

complains at home and to his friends of dim lamps, blackened

lamps, you will find in the power station the manager,

who, also worried and in no better humor, contemplates the

difference in meter readings at the end of the line.

His business does not increase and would not increase even if

he could lower the rates, which he cannot do because of these

meter readings.

He may be confident of his engines and generators, and that

his line is up and all right, but he very seldom knows what

the transformers are doing on top of the poles. Perhaps he

feels that this waste is so slight that it makes no material

difference. This can be readily ascertained by means of a set

of testing instruments.

Perhaps the transformers were purchased because of their attractive

prices and never tested.

Water, plumbing, gas and steam fittings are subjected to test. Why not

transformers? Even more so because transformers take constant toll from

the company installing them, while gas and water fittings, once passed,

are off the contractor's hands.

The busy manager has little time for complicated treatises and

monographs on electrical measurements and even handbooks confront

him with forbidding formulæ. Accordingly the methods of transformer

testing, which are very simple, are illustrated in the accompanying

cuts. Managers of electric power and lighting companies should study

them carefully.

[Illustration: FIG. 2,015.--Wagner central station core type

transformer repair unit consisting of one half set of primary and

secondary windings together with the section of the iron core upon

which the coils are wound.]

An ammeter, voltmeter and wattmeter are required to make the tests.

Losses are small in ~good~ transformers and hence the instruments

~should be accurate~. For the same reason instruments should be chosen

of the proper capacity to give their best readings. If there be any

doubt about the testing instruments being correct, they should be

calibrated before being used. The testing circuits should be properly

fused for the protection of the instruments. It is hardly logical, but

a very common practice is to mistrust meters and to watch them closely,

while the transformers are guilty of theft unchallenged, and keep

busily at it on a large scale.

[Illustration: FIG. 2,016.--Moloney tubular air draft oil filled

transformer. The case is made of cast iron, with large steel tubes

passing from the bottom through the top. In operation the air in the

tubes becomes hot and expands; a draft is thus produced which carries

away considerable heat.]

~Transformer Operation with Grounded Secondary.~--The operation of a

transformer with a grounded secondary has been approved by the American

Institute of Electrical Engineers, and by the National Board of Fire

Underwriters.

This method of operation effectually prevents a high voltage occurring

upon the low tension wires in case of a breakdown or other electrical

connections occurring between the primary and secondary windings.

[Illustration: FIG. 2,017.--Moloney pressure transformer adapted for

switchboard work in connection with voltmeters, wattmeters the, etc.,

in sizes from 25 to 500 watts.]

In case of a breakdown without the secondary grounded, any one touching

a part of the low tension system, such as a lamp socket, might receive

the full high pressure voltage. With the low tension grounded, the fuse

in the high tension circuit will blow and the fault be discovered upon

replacing it.

~Transformer Capacity for Motors.~--The voltage regulation of a well

designed transformer is within 3 per cent. of its rated voltage on a

non-inductive load such as incandescent lamps, but when motors are

connected to the circuit their self-induction causes a loss of 5 per

cent. or more, and if the load be fluctuating, it is better to use

independent transformers for the motor, which will prevent considerable

fluctuations in the incandescent lamps. Arc lamps do not show slight

voltage changes as much as incandescent lamps. The proper rating of

transformers for two phase and three phase induction motors is given in

table on the next page.

[Illustration: FIG. 2,018.--Moloney current transformer switchboard or

indoor type. It is used ordinarily for insulating an ammeter, a current

relay, the current coil of a watt meter or watt hour meter from a high

tension circuit, for reducing the line current to a value suitable for

these instruments.]

A three phase induction motor may be operated from three single phase

transformers or one three phase transformer. While the one three phase

transformer greatly reduces the space and simplifies the wiring, the

use of three single phase transformers is more flexible and, in case

one transformer burns out, the connection can be readily changed so

that two transformers will operate the motor at reduced load until the

burned out transformer is replaced or repaired.

[Illustration: FIG. 2,019.--Diagram showing a method of operating a

three phase motor on a two phase circuit, using a transformer having

a tap made in the middle of the secondary winding, so as to get the

necessary additional phase. While this does not give a true balanced

three phase secondary, it is close enough for motor work. In the above

arrangement, the main transformer supplies 54 per cent. of the current

and the other with the split winding 46 per cent.]

It is well to allow one kilowatt per horse power of the motor in

selecting the size for the transformers, excepting in the small sizes

when a little larger kilowatt rating is found to be the most desirable.

~Transformers for Two and Three Phase Motors~

-----------+-------------------------------------------------

| Single phase transformer voltages

Delivered +------------------------+------------------------

voltage of | 110 volt motor | 220 volt motor

circuit +-----------+------------+----------+-------------

| Primary | Secondary | Primary | Secondary

-----------+-----------+------------+----------+-------------

1,100 | 1,100 | 122 | 1,100 | 244

2,200 | 2,200 | 122 | 2,200 | 244

-----------+-----------+------------+----------+-------------

Very small transformers should not be used, even when the motor is

large compared to the work it has to do, as the heavy starting current

may burn them out.

The following tables give the proper sizes of transformer for three

types of induction motor and the approximate current taken by three

phase induction motors at 220 volts.

-----------------------------------------------------------

~Capacities of Transformers for Induction Motors~

---------------+-------------------------------------------

| Kilowatts per transformer

Size of motor +--------------+--------------+-------------

horse power | Two single | Three single | One three

| phase | phase | phase

| transformers | transformers | transformer

---------------+--------------+--------------+-------------

1 | 0.6 | 0.6 |

2 | 1.5 | 1.0 | 2.0

3 | 2.0 | 1.5 | 3.0

5 | 3.0 | 2.0 | 5.0

7 | 4.0 | 3.0 | 7.5

10 | 5.0 | 4.0 | 10.0

15 | 7.5 | 5.0 | 15.0

20 | 10.0 | 7.5 | 20.0

30 | 15.0 | 10.0 | 30.0

50 | 25.0 | 15.0 | 50.0

75 | 40.0 | 25.0 | 75.0

100 | 50.0 | 30.0 | 100.0

---------------+--------------+--------------+-------------

~Current taken by Three Phase Induction Motors at 220 Volts~

-------------+-----------------+------------+----------------

Horse power |Approximate full |Horse power |Approximate full

of motor | load current | of motor |load current

-------------+-----------------+------------+----------------

1 | 3.2 | 20 | 50.

2 | 6.0 | 30 | 75.

3 | 9.0 | 50 | 125.

5 | 14.0 | 75 | 185.

10 | 27.0 | 100 | 250.

15 | 40.0 | 150 | 370.

-------------+-----------------+------------+----------------

~Transformer Connections for Motors.~--Fig. 2,020 shows the connection

of a three phase so called delta connected transformer with the three

primaries connected to the lines leading from the alternator and the

three secondaries leading to the motor.

The connections for a three phase motor using two transformers is shown

in fig. 2,021 and is identical with the previous arrangement, except

that one transformer is left out and the other two made correspondingly

larger.

The copper required in any three wire three phase circuit for a given

power and loss is 75 per cent. that necessary with the two wire single

phase or four wire two phase system having the same voltage between

lines.

[Illustration: FIG. 2,020.--Three phase motor transformer connections;

the so-called Delta connected transformers.]

The connections of three transformers for a low tension system of

distribution by the four wire three phase system are shown in fig.

2,022. The three transformers have their primaries joined in delta

connection and the secondaries in "~Y~" connection. The three upper

lines of the secondary are the three main three phase lines, and the

lowest line is the common neutral.

[Illustration: FIG. 2,021.--Three phase motor connections using two

transformers.]

The voltage across the main conductors is 200 volts, while

that between either of them and the neutral is 115 volts; 200

volt motors should be joined to the mains while 115 volt lamps

are connected between the mains and neutral. The arrangement

is similar to the Edison three wire system and the neutral

carries current only when the lamp load is unbalanced.

The voltage between the mains should be used in calculating the

size of wires, and the size of the neutral wire should be made

in proportion to each of the main conductors that the lighting

load is to the total load.

[Illustration: FIG. 2,022.--Delta-star connection of three transformers

for low pressure, three phase, four wire system.]

When lights only are used the neutral should be the same as the

main conductors. The copper required in such a system for a

given power and loss is about 33.3 per cent. as compared with

a two wire single phase system or a four wire two phase system

using the same voltage.

[Illustration: FIG. 2,023.--Diagram of transformer connections for

motors on the monocyclic system.]

~Monocyclic Motor System.~--Motors on the monocyclic system are

operated from two transformers connected as shown in fig. 2,023. In

the monocyclic system the single phase current is used to supply the

lighting load and two wires only are necessary, but if a self-starting

induction motor be required, a third or _teaser wire_ is brought to the

motor and two transformers used.

The teaser wire supplies the quarter phase current required to start

the motor, which afterwards runs as a single phase synchronous motor

and little or no current flows through the teaser circuit as long as

the motor keeps in synchronism; in case it fall behind, the teaser

current tends to bring it up to speed instead of the motor stopping, as

would be the case of a single phase motor.

[Illustration: FIG. 2,024.--Moloney flaming auto type arc lamp

transformer for 110 volts primary to 55 volts secondary. A hook in

bottom of case provides means for suspension of lamp. The transformer

may be operated on circuits from 100 to 120 volts primary, 50 to 60

volts secondary. The secondary capacity is 8 to 12 amperes.]

The voltage of the transformers should be tested by means of a

voltmeter or two incandescent lamps joined in series, before starting

up the motor, to see if the proper transformer connections have been

made and prevent an excessive flow of current.

If one of the transformers be reversed the voltage will be

almost doubled; in fact, it is a good plan to check up all the

transformer connections with the voltmeter or lamps which will

often save a burn out.

+------------------+-----------+-----------+-----------------------+

| | | |Ratio of transformation|

| | | | at no load |

| | | +-----------+-----------+

| Arrangement of | Primary | For | with | with |

| links on the | coils | circuit | secondary | secondary |

| connecting board | will be | voltage | coils in | coils in |

| | connected | normal at | multiple | series. |

| | in | | | |

|------------------+-----------+-----------+-----------+-----------+

| [ILLUSTRATION] | Multiple | 1,100 | 10:1 | 5:1 |

|------------------+-----------+-----------+-----------+-----------+

| [ILLUSTRATION] | Multiple | 1,100 | 9.05:1 | 4.52:1 |

|------------------+-----------+-----------+-----------+-----------+

| [ILLUSTRATION] | Series | 2,200 | 20:1 | 10:1 |

|------------------+-----------+-----------+-----------+-----------+

| [ILLUSTRATION] | Series | 2,200 | 19.05:1 | 9.5:1 |

|------------------+-----------+-----------+-----------+-----------+

| [ILLUSTRATION] | Series | 2,200 | 18.1:1 | 9.05:1 |

|------------------+-----------+-----------+-----------+-----------+

FIGS. 2,025 to 2,029.--Diagrams of Wagner transformer connection

board, and table showing various arrangements of the terminal links,

corresponding transformation ratios, and suitable primary voltages. */

[Illustration: FIG. 2,030.--Installation of a transformer on pole;

view showing method of attachment and disposition of the primary and

secondary leads, cutouts, etc.]

[Illustration: FIG. 2,031.--Diagram of static booster or regulating

transformer. It is used for regulating the pressure on feeders. In

the figure, B are the station bus bars, R the regulable transformer,

F the two wire feeders, and T a distant transformer feeding into the

low pressure three wire distributing network N. The two ends of the

primary, and one end of the secondary of R, are connected to the bus

bars as shown. The other end of the secondary, as well as a number of

intermediate points, are joined up to a multiple way switch S, to which

one of the feeder conductors is attached, the other feeder main being

connected to the opposite bus bar. As will be evident from the figure,

by manipulating S extra volts may be added to the bus bar pressure at

will, and the drop along F compensated for. R is a step transformer,

the total secondary difference of pressure being comparatively small.

The above device possesses rather serious drawbacks, in that the switch

S has to carry the main current, and that the supply would be stopped

if the switch got out of order. Kapp improved on the arrangement by

putting the switch in the primary circuit.]

Hawkins Electrical Guide v. 06 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 3 / 5 章