TURBIDIMETRIC METHOD.

Several forms of turbidimeter or diaphanometer[73] have been suggested

for use. The simplest and most satisfactory form is the candle

turbidimeter.[116] This consists of a graduated glass tube with a flat

polished bottom, enclosed in a metal case. This is supported over an

English standard candle and so arranged that one may look vertically

down through the tube at the flame of the candle. The observation is

made by pouring the sample of water into the tube until the image of the

flame of the candle just disappears from view. Care shall be taken not

to allow soot or moisture to accumulate on the lower side of the glass

bottom of the tube so as to interfere with the accuracy of the

observations. The graduations on the tube correspond to turbidities

produced in distilled water by certain numbers of parts per million of

silica standard. In order to insure uniform results it is necessary to

have the distance between the top rim of the candle and the bottom of

the tube constant, and this distance shall be 7.6 cm. or 3 inches. The

observations shall be made in a darkened room or with a black cloth over

the head.

It is allowable to substitute for the candle an electric light.

Calibrate the apparatus to correspond with the United States Geological

Survey scale. The figures in Table 2 on page 8 are believed to be

approximately correct for the candle turbidimeter but should be checked

by the experimenter. It is allowable to calibrate the tube of the

instrument with waters of known turbidity prepared by making a series of

dilutions of the silica standard with distilled water. From the figures

obtained in calibrating plot a curve from which the turbidity of a

sample may be read when the depth of water in the tube has been

obtained.

Table 2.—GRADUATION OF CANDLE TURBIDIMETER.

───────────────────────────────────┬───────────────────────────────────

Depth of liquid │ Turbidity

(cm.). │ (parts per million of silica).

───────────────────────────────────┼───────────────────────────────────

2.3│ 1000

2.6│ 900

2.9│ 800

3.2│ 700

3.5│ 650

3.8│ 600

4.1│ 550

4.5│ 500

4.9│ 450

5.5│ 400

5.6│ 390

5.8│ 380

5.9│ 370

6.1│ 360

6.3│ 350

6.4│ 340

6.6│ 330

6.8│ 320

7.0│ 310

7.3│ 300

7.5│ 290

7.8│ 280

8.1│ 270

8.4│ 260

8.7│ 250

9.1│ 240

9.5│ 230

9.9│ 220

10.3│ 210

10.9│ 200

11.4│ 190

12.0│ 180

12.7│ 170

13.5│ 160

14.4│ 150

15.4│ 140

16.6│ 130

18.0│ 120

19.6│ 110

21.5│ 100

───────────────────────────────────┴───────────────────────────────────

The results of turbidity observations shall be expressed in whole

numbers which correspond to parts per million of silica and recorded as

follows:

Turbidity between │ 1│and│ 50│recorded to nearest│unit

" " │ 51│ " │ 100│ " " " │ 5

" " │ 101│ " │ 500│ " " " │ 10

" " │ 501│ " │ 1000│ " " " │ 50

" " │1001│ " │greater│ " " " │ 100

Standard methods for the examination of water and sewage · 第 16 / 249 题