CHAPTER LXVII

MANAGEMENT

The term "management," broadly speaking, includes not only the

actual skilled attention necessary for the proper operation of the

machines, after the plant is built, but also other duties which must

be performed from its inception to completion, and which may be

classified as

1. Selection;

2. Location;

3. Erection;

4. Testing;

5. Running;

6. Care;

7. Repair.

That is to say, someone must select the machinery, determine where

each machine is to be located, install them, and then attend to the

running of the machines and make any necessary repairs due to the

ordinary mishaps likely to occur in operation.

These various duties are usually entrusted to more than one

individual; thus, the selection and location of the machinery is done

by the designer of the plant, and requires for its proper execution

the services of an electrical engineer, or one possessing more than

simply a practical knowledge of power plants.

The erection of the machines is best accomplished by those making a

specialty of this line of work, who by the nature of the undertaking

acquire proficiency in methods of precision and an appreciation of

the value of accuracy which is so essential in the work of aligning

the machines, and which if poorly done will prove a constant source

of annoyance afterward.

The attention required for the operation of the machines, embracing

the running care and repair, is left to the "man in charge," who

in most cases of small and medium size plants is the chief steam

engineer. He must therefore, not only understand the steam apparatus,

but possess sufficient knowledge of electrical machinery to operate

and maintain it in proper working order.

The present chapter deals chiefly with alternating current machinery,

the management of direct current machines having been fully explained

in Guide No. 3, however, some of the matter here presented is common

to both classes of apparatus.

* * * * *

=Selection.=--In order to intelligently select a machine so that it

will properly harmonize with the conditions under which it is to

operate, there are several things to be considered.

1. Type;

2. Capacity;

3. Efficiency;

4. Construction.

The general type of machine to be used is, of course, dependent on

the system employed, that is, whether it be direct or alternating,

single or polyphase.

Thus, the voltage in most cases is fixed except on transformer

systems where a choice of voltage may be had by selecting a

transformer to suit.

In alternating current constant pressure transmission circuits, an

average voltage of 2,200 volts with step down transformer ratios of

1/10 and 1/20 is in general use, and is recommended.

For long distance, the following average voltages are

recommended 6,000; 11,000; 22,000; 33,000; 44,000; 66,000; 88,000;

and higher, depending on the length of the line and degree of

economy desired.

In alternating circuits the standard frequencies are 25, and 60

cycles. These frequencies are already in extensive use and it is

recommended to adhere to them as closely as possible.

[Illustration: FIG. 2,784.--Diagram of connections for testing to

obtain the saturation curve of an alternator. The saturation curve

shows the relation between the volts generated in the armature and

the amperes of field current (or ampere turns of the field) for a

constant armature current. The armature current may be zero, in which

case the curve is called _no load saturation curve_, or sometimes the

_open circuit characteristic curve_. A saturation curve may be taken

with full load current in the armature; but this is rarely done,

except in alternators of comparatively small output. If a full load

saturation curve be desired, it can be approximately calculated from

the no load saturation curve. The figure shows the connections. If

the voltage generated is greater than the capacity of the voltmeter,

a multiplying coil or a step down pressure transformer may be used,

as shown. A series of observations of the voltage between the

terminals of one of the phases, is made for different values of the

field current. Eight or nine points along the curve are usually

sufficient, the series extending from zero to about fifty per cent.

above normal rated voltage. The points should be taken more closely

together in the vicinity of normal voltage than at other portions of

the curve. Care must be taken that the alternator is run at its rated

speed, and this speed must be kept constant. Deviations from constant

speed may be most easily detected by the use of a tachometer. If the

machine be two phase or three phase, the voltmeter may be connected

to any one phase throughout a complete series of observations. The

voltage of all the phases should be observed for normal full load

excitation by connecting the voltmeter to each phase successively,

keeping the field current constant at normal voltage. This is done in

order to see how closely the voltage of the different phases agree.]

In fixing the capacity of a machine, _careful consideration

should be given to the conditions of operation both_ =present=

_and_ =future= in order that the resultant efficiency may be

maximum.

Most machines show the best efficiency at or near full load.

If the load be always constant, as for instance, a pump forcing

water to a given head, it would be a simple matter to specify the

proper size of machine, but in nearly all cases, and especially

in electrical plants, the load varies widely, not only the daily

and hourly fluctuations, but the varying demands depending on

the season of the year and growth of the plant's business. All

of these conditions tend to complicate the matter, so that

intelligent selection of capacity of a machine requires not only

calculation but mature judgment, which is only obtained by long

experience.

[Illustration: FIG. 2,785.--Saturation curve taken from a 2,000 kw.,

three phase alternator of the revolving field type, having 16 poles,

and generating 2,000 volts, and 576 amperes per phase when run at 300

R.P.M.]

In selecting a machine, or in fact any item connected with the plant

_its construction should be carefully considered_.

Standard construction should be insisted upon so that in the

event of damage a new part can be obtained with the least possible

delay.

The parts of most machines are _interchangeable_, that is to

say, with the refined methods of machinery a duplicate part

(usually carried in stock) may be obtained at once to replace a

defective or broken part, and made with such precision that little

or no fitting will be required.

The importance of standard construction cannot be better illustrated

than in the matter of steam piping, that is, the kind of fittings

selected for a given installation.

With the exception of the exhaust line from engine to condenser,

where other than standard construction may sometimes be used to

reduce the frictional resistance to the steam, the author would

adhere to standard construction except in very exceptional cases.

Those who have had practical experience in pipe fitting will

appreciate the wisdom of this.

For installations in places remote from large supply houses, the more

usual forms of standard fittings should be employed, such as ordinary

T's, 45° and 90° elbows, etc.

In such locations, where designers specify the less usual forms of

standard fittings such as union fittings, offset reducers, etc.,

or special fittings made to sketch, it simply means, in the first

instance that they usually cannot be obtained of the local dealer,

making it necessary to order from some large supply house and

resulting in vexatious delays.

As a rule, those who specify special fittings have found that their

making requires an unreasonable length of time, and the cost to be

several times that of the equivalent in standard fittings.

An examination of a few installations will usually show numerous

special and odd shape fittings, which are entirely unnecessary.

Moreover, a standard design, in general, is better than a special

design, because the former has been tried out, and any imperfection

or weakness remedied, and where thousands of castings of a kind are

turned out, a better article is usually the result as compared with a

special casting.

In the matter of construction, in addition to the items just

mentioned, it should be considered with respect to

1. Quality;

2. Range;

3. Accessibility;

4. Proportion;

5. Lubrication;

6. Adjustment.

It is poor policy, excepting in very rare instances, to buy a "cheap"

article, as, especially in these days of commercial greed, the best

is none too good.

[Illustration: FIGS. 2,786 and 2,787.--Wheel and roller pipe cutters

illustrating =range=. The illustrations show the comparative

movements necessary with the two types of cutter to perform their

function. The wheel cutter requiring only a small arc of movement

will cut a pipe in an inaccessible place as shown, which with a

roller cutter would be impossible. Accordingly, the wheel cutter is

said to have a greater _range_ than the roller cutter.]

Perhaps next in importance to quality, at least in most cases,

is _range_. This may be defined as _scope of operation_,

_effectiveness_, or _adaptability_. The importance of range is

perhaps most pronounced in the selection of tools, especially for

plants remote from repair shops.

For instance, in selecting a pipe cutter, there are two general

classes: wheel cutters, and roller cutters. A wheel cutter has

three wheels and a roller cutter one wheel and two rollers, the

object of the rollers being to keep the wheel perpendicular to

the pipe in starting the cut and to reduce burning. It must be

evident that in operation, a roller cutter requires sufficient

room around the pipe to permit making a complete revolution of

the cutter, whereas, with a wheel cutter, the work may be done

by moving the cutter back and forth through a small arc, as

illustrated in figs. 2,786 and 2,787. Thus a wheel cutter has a

_greater range_ than a roll cutter.

Range relates not only to ability to operate in inaccessible

places but to the various operations that may be performed by one

tool.

PROPERTIES OF STANDARD WROUGHT IRON PIPE

--------------------------+------+-----------------+

| | |

| | |

| | |

| | |

Diameter |Thick-| Circumference. |

| ness.| |

--------+--------+--------+ +--------+--------+

Nominal| Actual | Actual | |External|Internal|

internal|external|internal| | | |

--------+--------+--------+------+--------+--------+

Inches | Inches | Inches |Inches| Inches | Inches |

--------+--------+--------+------+--------+--------+

⅛ | .405 | .27 | .068 | 1.272 | .848 |

¼ | .54 | .364 | .088 | 1.696 | 1.144 |

⅜ | .675 | .494 | .91 | 2.121 | 1.552 |

½ | .84 | .623 | .109 | 2.639 | 1.957 |

¾ | 1.05 | .824 | .113 | 3.299 | 2.589 |

1 | 1.315 | 1.048 | .134 | 4.131 | 3.292 |

1¼ | 1.66 | 1.38 | .14 | 5.215 | 4.335 |

1½ | 1.9 | 1.611 | .145 | 5.969 | 5.061 |

2 | 2.375 | 2.067 | .154 | 7.461 | 6.494 |

2½ | 2.875 | 2.468 | .204 | 9.032 | 7.753 |

3 | 3.5 | 3.067 | .217 | 10.996 | 9.636 |

3½ | 4. | 3.548 | .226 | 12.566 | 11.146 |

4 | 4.5 | 4.026 | .237 | 14.137 | 12.648 |

4½ | 5. | 4.508 | .246 | 15.708 | 14.162 |

5 | 5.563 | 5.045 | .259 | 17.477 | 15.849 |

6 | 6.625 | 6.065 | .28 | 20.813 | 19.054 |

7 | 7.625 | 7.023 | .301 | 23.955 | 22.063 |

8 | 8.625 | 7.982 | .322 | 27.096 | 25.076 |

9 | 9.625 | 8.937 | .344 | 30.238 | 28.076 |

10 | 10.75 | 10.019 | .366 | 33.772 | 31.477 |

11 | 12. | 11.25 | .375 | 37.699 | 35.343 |

12 | 12.75 | 12. | .375 | 40.055 | 37.7 |

--------+--------+--------+------+--------+--------+

------+-------------------------+---------------+--------+-------+------

| | | | |

| | | | |

| | | Length | |

| |Length of pipe |of pipe |Nominal|

Diam.| Transverse areas. | per square |contain-|weight |Number

| | foot of |ing one | per | of

------+--------+--------+-------+-------+-------+ cubic | foot. |thread

Nom. |External|Internal| Metal |Ext'nal|Int'nal| foot. | | per

intern| | | |surface|surface| | | inch

------+--------+--------+-------+-------+-------+--------+-------+ of

Inches|Sq. ins.|Sq. ins.|Sq.ins.| Feet | Feet | Feet |Pounds |screw

------+--------+--------+-------+-------+-------+--------+-------+-----

⅛ | .129 | .0573| .0717| 9.44 |14.15 |2513. | .241 | 27

¼ | .229 | .1041| .1249| 7.075 |10.49 |1383.3 | .42 | 18

⅜ | .358 | .1917| .1663| 5.657 | 7.73 | 751.2 | .559 | 18

½ | .554 | .3048| .2492| 4.547 | 6.13 | 472.4 | .837 | 14

¾ | .866 | .5333| .3327| 3.637 | 4.635 | 270. | 1.115 | 14

1 | 1.358 | .8626| .4954| 2.904 | 3.645 | 166.9 | 1.668 | 11½

1¼ | 2.164 | 1.496 | .668 | 2.301 | 2.768 | 96.25 | 2.244 | 11½

1½ | 2.835 | 2.038 | .797 | 2.01 | 2.371 | 70.66 | 2.678 | 11½

2 | 4.43 | 3.356 | 1.074 | 1.608 | 1.848 | 42.91 | 3.609 | 11½

2½ | 6.492 | 4.784 | 1.708 | 1.328 | 1.547 | 30.1 | 5.739 | 8

3 | 9.621 | 7.388 | 2.243 | 1.091 | 1.245 | 19.5 | 7.536 | 8

3½ | 12.566 | 9.887 | 2.679 | .955 | 1.077 | 14.57 | 9.001 | 8

4 | 15.904 | 12.73 | 3.174 | .849 | .949 | 11.31 |10.665 | 8

4½ | 19.635 | 15.961 | 3.674 | .764 | .848 | 9.02 |12.34 | 8

5 | 24.306 | 19.99 | 4.316 | .687 | .757 | 7.2 |14.502 | 8

6 | 34.472 | 28.888 | 5.584 | .577 | .63 | 4.98 |18.762 | 8

7 | 45.664 | 38.738 | 6.926 | .501 | .544 | 3.72 |23.271 | 8

8 | 58.426 | 50.04 | 8.386 | .443 | .478 | 2.88 |28.177 | 8

9 | 72.76 | 62.73 |10.03 | .397 | .427 | 2.29 |33.701 | 8

10 | 90.763 | 78.839 |11.924 | .355 | .382 | 1.82 |40.065 | 8

11 |113.098 | 99.402 |13.696 | .318 | .339 | 1.450|45.95 | 8

12 |127.677 |113.098 |14.579 | .299 | .319 | 1.27 |48.985 | 8

------+--------+--------+-------+-------+-------+--------+-------+----

Open construction should be employed, wherever possible, so that

all parts of a machine that require attention, or that may become

deranged in operation, may be accessible for adjustment or repair.

The design should be such that there is ample strength, and the

bearings for moving parts should be of liberal proportions to

avoid heating with minimum attention.

A comparison of the proportions used by different manufacturers

for a machine of given size might profitably be made before a

selection is made.

The matter of lubrication is important.

Fast running machines, such as generators and motors, should be

provided with ring oilers and oil reservoirs of ample capacity, as

shown in figs. 2,788 to 2,794.

[Illustration: FIG. 2,788.--Sectional view showing a ring oiler or

self oiling bearing. As shown the pedestal or bearing standard is

cored out to form a reservoir for the oil. The rings are in rolling

contact with the shaft, and dip at their lower part into the oil.

In operation, oil is brought up by the rings which revolve because

of the frictional contacts with the shaft. The oil is in this way

brought up to the top of the bearing and distributed along the shaft

gradually descending by gravity to the reservoir, being thus used

over and over. A drain cock, is provided in the base so that the oil

may be periodically removed from the reservoir and strained to remove

the accumulation of foreign matter. This should be frequently done to

minimize the wear of the bearing.]

All bearings subject to appreciable wear should be made adjustable so

that lost motion may be taken up from time to time and thus keep the

vibration and noise of operation within proper limits.

=Selection of Generators.=--This is governed by the class of work

to be done and by certain local conditions which are liable to vary

considerably for different stations.

These variable factors determine whether the generators must be of

the direct or alternating current type, whether they must be wound

to develop a high or a low voltage, and whether their outputs in

amperes must be large or small. Sufficient information has already

been given to cover these various cases; there are, however, certain

general rules that may advantageously be observed in the selection of

generators designed to fill any of the aforementioned conditions, and

it is well to possess certain facts regarding their construction.

[Illustration: FIGS. 2,789 to 2,794.--Self oiling self aligning

bearing open. Views showing oil grooves, rings, bolts etc.]

=Ques. Name an important point to be considered in selecting a

generator.=

Ans. Its efficiency.

=Ques. What are the important points with respect to efficiency?=

Ans. A generator possessing a high efficiency at the average load is

more desirable than a generator showing a high efficiency at full

load.

=Ques. Why?=

Ans. The reason is that in station practice the full load limit is

seldom reached, the usual load carried by a generator ordinarily

lying between the one-half and three-quarter load points.

=Ques. How do the efficiencies of large and small generators compare?=

Ans. There is little difference.

[Illustration: FIG. 2,795.--Rotor of Westinghouse type T turbine

dynamo set. The dynamo is of the commutating pole type either shunt

or compound wound. The turbine is of the single wheel impulse type.

The wheel is mounted directly on the end of the shaft as shown. Steam

is used two or more times on the wheel to secure efficiency. A fly

ball governor is provided with weights hung on hardened steel knife

edges. In case of over speeding, an automatic safety stop throttle

valve is tapped shutting off the steam supply. This type of turbine

dynamo set is especially applicable for exciter service in modern,

superheated steam generating stations where the steam pressure

exceeds 125 pounds. Westinghouse Type T turbines operate directly

(that is, without a reducing valve) on pressures up to 200 pounds per

square inch with steam superheated to 150 degrees Fahrenheit.]

=Ques. How are the sizes and number of generator determined?=

Ans. The sizes and number of generator to be installed should be

such as to permit the engines operating them being worked at nearly

full load, because the efficiencies of the latter machines decrease

rapidly when carrying less than this amount.

=Ques. What is understood by regulation?=

Ans. The accuracy and reliability with which the pressure or current

developed in a machine may be controlled.

It is generally possible if purchasing of a reputable concern,

to obtain access to record sheets on which may be found results

of tests conducted on the generator in question, and as these are

really the only means of ascertaining the values of efficiency and

regulation, the purchaser has a right to inspect them. If, for

some reason or other, he has not been afforded this privilege, he

should order the machine installed in the station on approval, and

test its efficiency and regulation before making the purchase.

[Illustration: FIG. 2,796.--Cross section of electrical station

showing small traveling crane.]

=Installation.=--The installation of machines and apparatus in an

electrical station is a task which increases in difficulty with

the size of the plant. When the parts are small and comparatively

light they may readily be placed in position, either by hand, by

erecting temporary supports which may be moved from place to place

as desired, or by rolling the parts along on the floor upon pieces

of iron pipe. If, however, the parts be large and heavy, a traveling

crane such as shown in fig. 2,797, becomes necessary.

=Ques. What precaution should be taken in moving the parts of

machines?=

Ans. Care should be taken not to injure the bearings and shafts, the

joints in magnetic circuits such as those between frame and pole

pieces, and the windings on the field and armature.

[Illustration: FIG. 2,797.--Cross section of electrical station

showing a traveling crane for the installation or removal of large

and heavy machine parts. A traveling crane consists of an iron beam

which, being supplied with wheels at the ends, can be made to move

either mechanically or electrically upon a track running the entire

length of the station. This track is not supported by the walls

of the building, but rests upon beams specially provided for the

purpose. In addition to the horizontal motion thus obtained, another

horizontal motion at right angles to the former is afforded by means

of the carriage which, being also mounted on wheels, runs upon a

track on the top of the beam. Electrical power is generally used to

move the carriage and also the revolving drums contained thereon,

the latter of which give a vertical motion to the main hoist or the

auxiliary hoist, these hoists being used respectively for raising

or lowering heavy or light loads. In the larger sizes of electric

traveling crane, a cage is attached to the beam for the operator,

who, by means of three controllers mounted in the cage, can move a

load on either the main or auxiliary hoist in any direction.]

The insulations of the windings are perhaps the most vital parts

of a generator, and the most readily injured. The prick of a pin

or tack, a bruise, or a bending of the wires by resting their

weight upon them or by their coming in contact with some hard

substance, will often render a field coil or an armature useless.

Owing to its costly construction, it is advisable when

transporting armatures by means of cranes to use a wooden

spreader, as shown in fig. 2,798 to prevent the supporting rope

bruising the winding.

[Illustration: FIG. 2,798.--View of armature in transit showing use

of a wooden spreader as a protection. If a chain be used in place of

the rope, a padding of cloth should be placed around the armature

shaft and special care taken that the chain does not scratch the

commutator.]

=Ques. If an armature cannot be placed at once in its final position

what should be done?=

Ans. It may be laid temporarily upon the floor, if a sheet of

cardboard or cloth be placed underneath the armature as a protection

for the windings; in case the armature is not to be used for some

time, it is better practice to place it in a horizontal position on

two wooden supports near the shaft ends.

=Ques. What kind of base should be used with a belt driven generator

or motor?=

Ans. The base should be provided with V ways and adjusting screws

for moving the machine horizontally to take up slack in the belt, as

shown in fig. 2,799.

Owing to the normal tension on the belt, there is a moment

exerted equal in amount to the distance from the center of gravity

of the machine to the center of the belt, multiplied by the

effective pull on the belt. This force tends to turn the machine

about its center of gravity. By placing the screws as shown, any

turning moment, as just mentioned, is prevented.

[Illustration: FIG. 2,799.--Plan of belt drive machine showing V ways

and adjusting screws for moving the machine forward from the engine

or counter shaft to take up slack in the belt.]

=Ques. How should a machine be assembled?=

Ans. The assembling should progress by the aid of a blue print, or by

the information obtained from a photograph of the complete machine

as it appears when ready for service. Each part should be perfectly

clean when placed in position, especially those parts between which

there is friction when the machine is in operation, or across which

pass lines of magnetic force; in both cases the surfaces in contact

must be true and slightly oiled before placing in position.

Contact surfaces forming part of electrical circuits must also

be clean and tightly screwed together. An important point to bear

in mind when assembling a machine is, to so place the parts that

it will not be necessary to remove any one of them in order to get

some other part in its proper position. By remembering this simple

rule much time will be saved, and in the majority of instances the

parts will finally be better fitted together than if the task has

to be repeated a number of times.

When there are two or more parts of the machine similarly

shaped, it is often difficult to properly locate them, but in such

cases notice should be taken of the factory marks usually stamped

upon such pieces and their proper places determined from the

instructions sent with the machine.

[Illustration: FIGS. 2,800 to 2,802.--Starrett's improved speed

indicator. In construction, the working parts are enclosed like a

watch. The graduations show every revolution, and with two rows of

figures read both right and left as the shaft may run. While looking

at the watch, each hundred revolutions may be counted by allowing

the oval headed pin on the revolving disc to pass under the thumb as

the instrument is pressed to its work. A late improvement in this

indicator consists in the rotating disc, which, being carried by

friction may be moved to the starting point where the raised knobs

coincide. When the spindle is placed in connection with the revolving

shaft, pressing the raised knob with the thumb will prevent the disc

rotating, while the hand of the watch gets to the right position to

take the time. By releasing the pressure the disc is liberated for

counting the revolutions of the shaft when every 100 may be noted by

feeling the knob pass under the thumb lightly pressed against it,

thus relieving the eye, which has only to look on the watch to note

the time.]

=Ques. What should be noted with respect to speed of generator?=

Ans. Each generator is designed to be run at a certain speed in

order to develop the voltage at which the machine is rated. The

speed, in revolutions per minute, the pressure in volts, and the

capacity or output in watts (volts × amperes) or in kilowatts

(thousands of watts) are generally stamped on a nameplate screwed to

the machine.

This requirement frequently requires calculations to be made by

the erectors to determine the proper size pulleys to employ to

obtain the desired speed.

[Illustration: FIG. 2,803.--Home made belt clamp. It is made with

four pieces of oak of ample size to firmly grip the belt ends where

the bolts are tightened. The figure shows the clamp complete and

in position on the belt and clearly illustrates the details of

construction. In making the long bolts the thread should be cut about

three-quarter length of bolt and deep enough so that the nuts will

easily screw on.]

=Example.=--What diameter of engine pulley is required to run

a dynamo at a speed of 1,450 revolutions per minute the dynamo

pulley being 10 inches in diameter and the speed of engine, 275

revolutions per minute?

The diameter of pulley required on engine is 10 × (1,450 ÷ 275) = 53

inches, nearly.

=Rule.=--To find the diameter of the driving pulley, _multiply

the speed of the driven pulley by its diameter, divide the product

by the speed of the driver and the answer will be the size of the

driver required_.

_Example._--If the speed of an engine be 325 revolutions per

minute, diameter of engine pulley 42 inches, and the speed of

the dynamo 1,400 revolutions per minute, how large a pulley is

required on dynamo?

The size of the dynamo pulley is

42 × (325 ÷ 1,400) = 9¾ inches.

=Rule.=--To find the size of dynamo pulley, _multiply the speed

of engine by the diameter of engine wheel and divide the product

by the speed of the dynamo_.

[Illustration: FIGS. 2,804 and 2,805.--A good method of lacing a

belt. The view at the left shows outer side of belt, and at the

right, inner or pulley side.]

_Example._--If a steam engine, running 300 revolutions per

minute, have a belt wheel 48 inches in diameter, and be belted

to a dynamo having a pulley 12 inches in diameter, how many

revolutions per minute will the dynamo make?

The speed of dynamo will be 300 × (48 ÷ 12) = 1,200 rev. per min.

=Rule.=--When the speed of the driving pulley and its diameter

are known, and the diameter of the driven pulley is known, the

speed of the driven pulley is found by _multiplying the speed of

the driver by its diameter in inches and dividing the product by

the diameter of the driven pulley_.

=Example.=--What will be the required speed of an engine

having a belt wheel 46 inches in diameter to run a dynamo 1,500

revolutions per minute, the dynamo pulley being 11 inches in

diameter?

The speed of the engine is 1,500 × (11 ÷ 46) = 359 rev. per min.

nearly.

[Illustration: FIG. 2,806.--Wiring diagram and directions for

operating Holzer-Cabot single phase self-starting motor. =Location:=

The motor should be placed in as clear and dry a location as

possible, away from acid or other fumes which would attack the

metal parts or insulation, and should be located where it is easily

accessible for cleaning and oiling. =Erection:= The motor should be

set so that the shaft is level and parallel with the shaft it is

to drive so that the belt will run in the middle of the pulleys.

Do not use a belt which is too heavy or too tight for the work it

has to do, as it will materially reduce the output of the motor.

The belt should be from one-half to one inch narrower than the

pulley. =Rotation:= In order to reverse the direction of rotation,

interchange leads A and B. =Suspended Motors:= Motors with ring oil

bearings may be used on the wall or ceiling by taking off end caps

and revolving 90 or 180 degrees until the oil wells come directly

below the bearings. =Starting:= Motors are provided with link across

two terminals on the upper right hand bracket at the front of the

motor and with this connection should start considerable overloads.

If the starting current be too great with this connection, it may be

reduced by removing the link. =Temperatures:= At full load the motor

will feel hot to the hand, but this is far below the danger point. If

too hot for touch, measure temperature with a thermometer by placing

bulb against field winding for 10 minutes, covering thermometer

with cloth or waste. The temperature should not exceed 75 degrees

Fahr. above the surrounding air. =Oiling:= Fill the oil wells to the

overflow before starting and keep them full. See that the oil rings

turn freely with shaft. =Care:= The motor must be kept clean. Smooth

collector rings with sandpaper and see that the brushes make good

contact. When brushes become worn they may be reversed. When fitting

new brushes or changing them always sandpaper them down until they

make good contact with the collector rings, by passing a strip of

sandpaper beneath the brush.]

=Rule.=--To find the speed of engine when diameter of both

pulleys, and speed of dynamo are given, _multiply the dynamo speed

by the diameter of its pulley and divide by the diameter of engine

pulley_.

=Ques. How are the diameters and speeds of gear wheels figured?=

Ans. The same as belted wheels, using either the pitch circle

diameters or number of teeth in each gear wheel.

[Illustration: FIGS. 2,807 to 2,809.--Wiring diagrams and directions

for operating Holzer-Cabot slow speed alternating current motors.

=Erecting:= In installing the motor, be sure the transformer and

wiring to the motor are large enough to permit the proper voltage

at the terminals. If too small, the voltage will drop and reduce

the capacity of the motor. =Oiling:= Maintain oil in wells to the

overflow. =Starting: Single phase= motors are started by first

throwing the starting switch down into the starting position, and

when the motor is up to speed, throwing it up into the running

position. _Do not hold the switch in starting position over 10

seconds._ Starter for single phase motors above ½ H.P. are arranged

with an adjusting link at the bottom of the panel. The link is shown

in the position of least starting torque and current. Connect from

W to 2 or W to 3 for starting heavier loads. _Two or three phase_

motors are started simply by closing the switch. These motors start

full load without starters. The motor should start promptly on

closing the switch. It should be started the first time without

being coupled to the line shaft. If the motor start free, but will

not start loaded, it shows either that the load upon the motor is

too great, the line voltage too low, or the frequency too high. The

voltage and frequency with the motor running should be within 5% of

the name plate rating and the voltage with 10 to 15% while starting.

If the motor do not start free, either it is getting no current or

something is wrong with the motor. In either case an electrician

should be consulted. =Solution:= To reverse the direction of rotation

interchange the leads marked "XX" in the diagrams. =Temperature:= At

full load the motor should not heat over 75 degrees Fahr. above the

temperature of the surrounding air; if run in a small enclosed space

with no ventilation, the temperature will be somewhat higher.]

=Ques. What should be noted with respect to generator pulleys?=

Ans. A pulley of certain size is usually supplied with each generator

by its manufacturer, and it is not generally advisable to depart much

from the dimensions of this pulley. Accordingly, the solution of the

pulley problem usually consists in finding the necessary diameter of

the driving pulley relative to that of the pulley on the generator in

order to furnish the required speed.

=Ques. What is the chief objection to belt drive?=

Ans. The large amount of floor space required.

[Illustration: FIG. 2,810.--Tandem drive for economizing floor space

with belt transmission. Belts of different lengths are used, as

shown, each of which passes over the driving wheel _d_ of the engine,

and then over the pulley wheel of one of the generators. In such

an arrangement the belts would be run lengthwise through the room

in which the machines are placed, and it is obvious that since the

width of the room would be governed by the width of the machines thus

installed, this method is a very efficient one for accomplishing the

end in view.]

=Ques. How may the amount of space that would ordinarily be required

for belt drive, be reduced?=

Ans. By driving machines in tandem as in fig. 2,810, or by the double

pulley drive as in fig. 2,811.

=Ques. What is the objection to the tandem method?=

Ans. The most economical distance between centers cannot be employed

for all machines.

=Ques. What is the objectionable tendency in resorting to floor

economy methods with belt transmission?=

Ans. The tendency to place the machines too closely together. This is

poor economy as it makes the cleaning of the machines a difficult and

dangerous task; it is therefore advisable to allow sufficient room

for this purpose regardless of the method of belting employed.

[Illustration: FIG. 2,811.--Double pulley drive for economizing floor

space with belt transmission. Where a center crank engine is used

both pulleys may be employed by belting a machine to each as shown.

Although considerable floor space would be saved by the use of this

scheme if the generators thus belted were placed at M and G yet still

more floor space would be saved by having them occupy the positions

indicated at M and S.]

=Ques. What is the approved location for an alternator exciter?=

Ans. To economize floor space the exciter may be placed between the

alternator and engine at S in fig. 2,811.

=Belts.=--In the selection of a belt, the quality of the leather

should be first under consideration. The leather must be firm, yet

pliable, free from wrinkles on the grain or hair side, and of an even

thickness throughout.

[Illustration: FIG. 2,812.--Separately excited belt driven alternator

showing approved location of exciter. In an electrical station where

alternating current is generated, the alternators for producing

the current generally require separate excitation for their field

windings; that is, it is usually necessary to install in conjunction

with an alternator a small dynamo for supplying current to the

alternator field. The exciter is a comparatively small machine; in

fact, it requires only about 1 per cent. of the capacity of the

alternator which it excites, and so being small is often belted to

an auxiliary pulley mounted on the alternator shaft. Considerable

floor space would be occupied by an installation of this nature if

the exciter be placed at M, and belted to the alternator as indicated

by the dotted lines. By locating the exciter at S, between the

alternator and the engine, much floor space will be saved and the

general appearance of the installation improved.]

If the belt be well selected and properly handled, it should do

service for twenty years, and even then if the worn part be cut off,

the remaining portion may be remade and used again as a narrower and

shorter belt.

Besides leather belts, there are those made of rubber which

withstand moisture much better than leather belts, and which also

possess an excellent grip on the pulley; they are, however, more

costly and much less durable under normal conditions.

In addition to leather and rubber belts, there are belts

composed of cotton, of a combination of cotton and leather, and

of rope. The leather belt, however, is the standard and is to be

recommended.

Equally important with the quality of a belt is its size in order to

transmit the necessary power.

The average strain under which leather will break has been found

by many experiments to be 3,200 pounds per square inch of cross

section. A good quality of leather will sustain a somewhat greater

strain. In use on the pulleys, belts should not be subjected to a

greater strain than one eleventh their tensile strength, or about

290 pounds to the square inch or cross section. This will be about

55 pounds average strain for every inch in width of single belt

three-sixteenths inch thick. The strain allowed for all widths

of belting--single, light double, and heavy double--is in direct

proportion to the thickness of the belt.

=Ques. How much horse power will a belt transmit?=

Ans. The capacity of a belt depends on, its width, speed, and

thickness. _A single belt one inch wide and travelling 1,000 feet per

minute will transmit one horse power; a double belt under the same

conditions, will transmit two horse power._

[Illustration: FIG. 2,813.--One horse power transmitted by belt to

illustrate the rule given above. A pulley is driven by a belt by

means of the friction between the surfaces in contact. Let T be the

tension on the driving side of the belt, and T', the tension on the

loose side; then the driving force = T-T'. In the figure T is taken

at 34 lbs. and T' at 1 lb.; hence driving force = 34-1 = 33 lbs.

Since the belt is travelling at a velocity of 1,000 feet per minute

the power transmitted = 33 lbs. × 1,000 ft. = 33,000 ft. lbs. per

minute = 1 horse power.]

This corresponds to a working pull of 33 and 66 lbs. per inch of

width respectively.

=Example.=--What width double belt will be required to transmit

50 horse power travelling at a speed of 3,000 feet per minute?

The horse power transmitted by each inch width of double belt

travelling at the stated speed is

3,000

1 × ----- × 2 = 6,

1,000

hence the width of belt required to transmit 50 horse power is

50 ÷ 6 = 8.33, say 8 inches.

=Ques. At what velocity should a belt be run?=

Ans. At from 3,000 to 5,000 feet per minute.

=Ques. How may the greatest amount of power transmitting capacity be

obtained from belts?=

Ans. By covering the pulleys with leather.

=Ques. How should belts be run?=

Ans. With the tight side underneath as in fig. 2,814.

[Illustration: FIGS. 2,814 and 2,815.--Right and wrong way to run a

belt. The tight side should be underneath so as to increase the arc

of contact and consequently the adhesion, that is to say, a _better

grip_, is in this way obtained.]

=Ques. What is a good indication of the capacity of a belt in

operation?=

Ans. Its appearance after a few days' run.

If the side of the belt coming in contact with the pulley assume

a mottled appearance, it is an indication that the capacity of

the belt is considerably in excess of the power which it is

transmitting, inasmuch as the spotted portions of the belt do not

touch the pulley; and in consequence of this there is liable to be

more or less slipping.

Small quantities of a mixture of tallow and fish oil which

have previously been melted together in the proportion of two of

the former to one of the latter, will, if applied to the belt

at frequent intervals, do much toward softening it, and thus

by permitting its entire surface to come in contact with the

pulley, prevent any tendency toward slipping. The best results

are obtained when the smooth side of the belt is used next to the

pulley, since tests conducted in the past prove that more power is

thus transmitted, and that the belt lasts longer when used in this

way.

[Illustration: FIG. 2,816.--The Hill friction clutch pulley for power

control. The clutch mechanism will start a load equivalent to the

double belt capacity of the pulley to which the clutch is attached.]

=Ques. What is the comparison between the so called endless belts and

laced belts?=

Ans. With an endless belt there is no uneven or noisy action as with

laced belts, when the laced joint passes over the pulleys, and the

former is free from the liability of breakage at the joint.

=Ques. How should a belt be placed on the pulleys?=

Ans. The belt should first be placed on the pulley at rest, and then

run on the other pulley while the latter is in motion.

The best results are obtained, and the strain on the belt is

less, when the speed at which the moving pulley revolves is

comparatively low. With heavy belts, particular care should be

taken to prevent any portion of the clothing being caught either

by the moving belt or pulleys, as many serious accidents have

resulted in the past from carelessness in regard to this important

detail. The person handling the belt should, therefore, be sure of

a firm footing, and when it is impossible to secure this, it is

advisable to stop the engine and fit the belt around the engine

pulley as well as possible by the aid of a rope looped around the

belt.

[Illustration: FIG. 2,817--Sectional view of Hill clutch mechanism.

In every case the mechanism hub A, and in a clutch coupling the

ring W, is permanently and rigidly secured to the shaft and need

not be disturbed when removing the wearing parts. When erected, the

adjustment should be verified, and always with the clutch and ring

engaged and at rest. If the jaws do not press equally on the ring, or

if the pressure required on the cone be abnormal, loosen the upper

adjusting nuts T´ on eye bolts and set up the lower adjusting nuts

T´´ until each set of jaws is under the same pressure. Should the

clutch then slip when started it is evident that the jaw pressure is

insufficient and a further adjustment will be necessary. All clutches

are equipped throughout with split lock washers. Vibration or shock

will not loosen the nuts if properly set up. The jaws can be removed

parallel to the shaft as follows: Remove the gibs V, and withdraw the

jaw pins P, then pull out the levers D. Do not disturb the eye bolt

nuts T´ and T´´. The outside jaws B can now be taken out. Remove the

bolt nuts I allowing the fulcrum plates R to be taken off. On the

separable hub pattern the clamping bolts must be taken out before

fulcrum plate is removed. The inside jaws C may now be withdrawn.

Always set the clutch operating lever in the position as shown in

fig. 2,816 to avoid interference with mechanism parts. Oil the moving

parts of the clutch. Keep it clean. Examine at regular intervals.]

=Ques. Under what conditions does a belt drive give the best results?=

Ans. When the two pulleys are at the same level.

If the belt must occupy an inclined position it should not form

a greater angle than 45 degrees with the horizontal.

=Ques. What is a characteristic feature in the operation of belts,

and why?=

Ans. Belts in motion will always run to the highest side of a

pulley; this is due partially to the greater speed in feet per minute

developed at that point owing to the greater circumference of the

pulley, and also to the effects of centrifugal force.

If, therefore, the highest sides of both pulleys be in line with

each other, and the shafts of the respective pulleys be parallel

to each other, there will be no tendency for the belt to leave

the pulleys when once in its proper position. In order that these

conditions be maintained, the belt should be no more than tight

enough to prevent slipping, and the distance between the centers

of the pulleys should be approximately 3.5 times the diameter of

the larger one.

[Illustration: FIG. 2,818.--Hill clutch mechanism Smith type. The

friction surfaces are wood to iron, the wood shoes being made from

maple. All parts of the toggle gear are of steel and forgings with

the exception of the connection lever which is of cast iron.]

=Ques. What minor appurtenances should be provided in a station?=

Ans. Apparatus should be installed as a prevention against accidents,

such as fire, and protection of attendants from danger.

In every electrical station there should be a pump, pipes

and hose; the pump may be either directly connected to a small

electric motor or belted to a countershaft, while the pipes

and hose should be so placed that no water can accidentally

reach the generators and electrical circuits. A number of fire

bucket filled with water should be placed on brackets around the

station, and with these there should be an equal number of bucket

containing dry sand, the water being used for extinguishing fire

occurring at a distance from the machines and conductors, and the

sand for extinguishing fire in current carrying circuits where

water would cause more harm than benefit. To prevent the sand

being blown about the station, each sand bucket, when not in use,

should be provided with a cover.

Neat cans and boxes should be mounted in convenient places for

greasy rags, waste, nuts, screws, etc., which are used continually

and which therefore cannot be kept in the storeroom.

While it is important to guard against fire in the station,

it is equally necessary to provide for personal safety. All

passages and dark pits should therefore be thoroughly lighted

both day and night, and obstacles of any nature that are not

absolutely necessary in the operation of the station, should be

removed. Moving belts, and especially those passing through the

floor, should be enclosed in iron railings. If high voltages be

generated, it is well to place a railing about the switchboard to

prevent accidental contact with current carrying circuits, and in

such cases it is also advisable to construct an insulated platform

on the floor in front of the switchboard.

[Illustration: FIG. 2,819.--Method of joining adjacent switchboard

panels.]

=Switchboards.=--The plan of switchboard wiring for alternating

current work depends upon the system in use and this latter may be

either of the single phase, two phase, three phase, or monocyclic

types. The general principles in all these cases, however, are

practically identical.

Fig. 2,820 shows the switchboard wiring for a single phase

alternator. As an aid in reading the diagram, the conductors

carrying alternating current are represented by solid lines, and

those carrying direct current, by dotted lines.

[Illustration: FIG. 2,820.--Switchboard wiring for a single phase

separately excited alternator. The direct current circuits are

represented by dotted lines, and the alternating current circuit, by

solid lines.]

The exciter shown at the right is a shunt wound machine. By

means of the exciter rheostat, the voltage for exciting the field

winding of the alternator is varied; this, in turn, varies the

voltage developed in the alternator since the main leads of the

exciter are connected through a double pole switch G to the field

winding of the alternator.

[Illustration: FIGS. 2,821 to 2,825.--General Electric diagrams of

connections. A, ammeter; C.B, circuit breaker; C.P, candle power;

C.T, current transformer; D.R, discharge resistance; F, fuse; F.S,

field switch; L, lamp; O.C, overload coil; P.P, pressure plug;

P.R, pressure receptacle; R.C, reactance; rheo, rheostat; R.P,

synchronizing plug, running; R.S, resistance; S, switch; S.I,

synchronism indicator; S.P, synchronizing plug, starting; S.R,

synchronizing receptacle; V, voltmeter.]

A rheostat is also introduced in the alternator field winding

circuit to adjust the alternator pressure. It may seem unnecessary

to employ a rheostat in each of two separate field circuits to

regulate the voltage of the alternator, but these rheostats are

not both used to produce the same result. When a considerable

variation of pressure is required, the exciter rheostat is

manipulated, whereas for a fine adjustment of voltage the

alternator rheostat is preferably employed.

Sometimes a direct current ammeter is introduced in the

alternator's field circuit to aid in the adjustment.

The main circuit of alternator after being protected on both

sides by fuses, runs to the double pole switch K. These fuses

serve as a protection to the alternator in case of a short circuit

at the main switch. It will be noticed the fuses are of the single

pole type and are mounted a considerable distance apart; this is

to prevent any liability of a short circuit between them in case

of action. Enclosed fuses are now used entirely for such work,

since in these there is no danger of heated metal being thrown

about and causing damage when the fuse wire is melted. Enclosed

fuses are also more readily and quickly replaced than open fuses,

the containing tube of each being easy to adjust in circuit, and

when the fuse wire within is once melted the tube is discarded for

a new one.

The main circuit after passing through the main switch is

further protected on both sides by circuit breakers. Leaving these

protective devices, the left hand side of the circuit includes

the alternating current ammeter, and then connects with one of

the bus bars. The right hand side of the circuit runs from the

circuit breaker to the other bus bar. As many feeder circuits

may be connected to the bus bars and supplied with current by

the alternator as the capacity of this machine will permit. If,

however, there be more than one feeder circuit, each must be wired

through a double pole switch.

In alternating current work the pressures dealt with are much

greater than those in direct current installations, so that

proportionate care must be taken in the wiring to remove all

possibility of grounds.

To locate such troubles, however, should they occur, a ground

detector is provided. For this class of work the ground detector

must be an instrument especially designed for high pressure

circuits. Two of its terminals should be connected to the line

wires and the third, to ground; in case of a leak on the line, a

current will then flow through the detector and by the position of

the pointer the location and seriousness of the leak may be judged.

A step down transformer is also rendered necessary for the

voltmeter and the pilot lamps, owing to the high voltage in use.

The primary winding of the transformer is connected across the

main circuit of the alternator. This connection should never be

made so that it will be cut out of circuit when the main switch is

open, for it is always advisable to consult the voltmeter before

throwing on the load by closing this switch.

[Illustration: FIGS. 2,826 to 2,829.--General Electric diagrams of

connections. A, ammeter; C.B, circuit breaker; C.P, candle power;

C.T, current transformer; D.R, discharge resistance; F, fuse; F.S,

field switch; L, lamp; O.C, overload coil; P.P, pressure plug;

P.R, pressure receptacle; R.C, reactance; rheo, rheostat; R.P,

synchronizing plug, running; R.S, resistance; S, switch; S.I,

synchronous indicator: S.P, synchronizing plug, starting; S.R,

synchronizing receptacle: V, voltmeter.]

=Ques. How does the switchboard wiring for a two phase system differ

from the single phase arrangement shown in fig. 2,820?=

Ans. It is practically the same, except for the introduction of an

extra ammeter and a compensator in each of the outside wires, and in

the use of a four pole switch in place of the two pole main switch.

The ammeters, of course, are for measuring the alternating

currents in each of the two phases or legs of the system, and the

compensators are two transformers with their primary coils in

series with the outside wires and their secondary coils in series

with each other across the outside wires. The transformers thus

connected are known as compensators or pressure regulators, and

as such compensate for the drop in pressure on either side of the

system.

=Ques. How is the four pole main switch wired?=

Ans. Its two central terminals which connect directly with the line

wires, are joined together by a conductor, and from this point one

wire is led off. This wire, together with the two outside wires, form

the feeders of the system.

=Ques. How many voltmeters are required for the two phase system?=

Ans. One voltmeter is sufficient on the board if a proper switching

device be employed to shift its connections across either of the two

circuits; otherwise, two voltmeters will be necessary, one bridged

across each of these respective circuits.

The same reasoning holds true in regard to ground detectors,

so that one or two of these will be required, depending upon the

aforementioned conditions.

=Ques. What are the essential points of difference between the single

phase switchboard wiring as shown in fig. 2,820, and that required

for a three wire three phase system?=

Ans. The three phase system requires the use of a three pole switch

in place of the two pole switch; the insertion of an ammeter, a

circuit breaker, and a compensator in each of the three wires of the

system; the presence of two ground detectors instead of one, and the

addition of a voltmeter switch if but one voltmeter be provided, or

else the installation of two voltmeters, connected the one between

the middle wire and outer right hand wire, and the other between the

middle wire and outer left hand wire.

[Illustration: FIG. 2,830.--Diagram of switchboard connections for

General Electric automatic voltage regulator with two exciters and

two alternators.]

=Ques. Mention a few points relating to lightning arresters.=

Ans. In most cases where direct current is used they are mounted

on the walls of the station near the place at which the line wires

enter. If they be mounted outside the station at this point, special

precautions should be taken to keep them free from moisture by

enclosing them in iron cases, but no matter where they are located it

is necessary that they be dry in order to work properly.

[Illustration: FIGS. 2,831 and 2,832.--Garton-Daniels alternating

current lightning arrester; diagram showing connections. A lightning

discharge takes the path indicated by the dotted line, across the

upper air gap A, through resistance rod B, C, D, across copper strip

R on the base, thence flowing to ground through the movable plunger

M, lower on gap N, and ground binding post L. The discharge path is

practically straight, contains an air gap, distance of but 3/32 inch,

a series resistance averaging but 225 ohms. The lightning discharge

does not flow through the flexible lead connecting band D on the

lower end of the resistance rod with the top of the movable plunger.

These two points are electrically connected by the heavy copper

strip R, and lightning discharges generally, if not always, take the

path across this copper strip in preference to flowing through the

inductance of the one turn of flexible cable. When a discharge occurs

from line to ground through any lightning arrester, the air gaps arc

over, and so there is offered a path from line to ground for the line

current. This flow of line current following the lightning discharge

to ground may vary anywhere from a small capacity current where

the arrester is installed on an ungrounded circuit, a moderately

heavy flow on a partially grounded circuit, to a very heavy flow on

a grounded circuit--either a circuit operated as a dead grounded

circuit, or a circuit which has become accidentally grounded during

a storm. The path taken by this flow of line current from line to

ground may be traced by following the path shown by the dashed line.

It, as seen, crosses upper air gap A, flows through section B of the

resistance rod to band C. Leaving band C it flows through the magnet

winding H, thence to band D on the resistance rod, through flexible

lead to upper end of movable plunger, through movable plunger, across

lower air gap N, to ground binding post L, thence to ground. The

function of the short length of resistance rod CD is as follows: It

has an ohmic resistance of about 30 ohms but is _non-inductive_.

Magnet winding H, connected to bands C and D on the ends of this

short length of rod has an ohmic resistance of 3 ohms, but is _highly

inductive_. Lightning discharges being of _high frequency_ take the

higher resistance _but non-inductive_ path CD in their passage from

line to ground. The flow of normal current from line to ground being

of a very low frequency, 25 or 60 cycles in ordinary alternating

current circuits, zero in direct current circuits--takes the _low

resistance_ path through coil H in its path to ground. Section CD of

the rod is used therefore simply to shunt the inductance of winding

H to high frequency lightning discharges, leaving the lightning

discharge path in the arrester a _non-inductive_ highly efficient

path. In all Garton-Daniels A. C. lightning arresters operating on

non-grounded or partially grounded circuits, the action of the air

gaps and series resistance are together sufficient to extinguish the

flow of normal current to ground at the zero point of the generator

voltage wave. If, however, as frequently happens, the line grounds

accidentally during a storm, then the arrester does not have to

depend for its proper operation on the arc extinguishing properties

of the air gaps and resistance, but the heavier flow of line current

through the arrester energizes the movable plunger, which raises

upward in the coil, opening the circuit between the discharge point M

and the lower end of the plunger. To limit the flow of line current

to ground the resistance rod B is provided, there being approximately

225 ohms between the discharge point A and clamp C in the 2,500 volt

arrester. This feature is particularly effective where the circuit is

temporarily or accidentally grounded. The series resistance prevents

a heavy short circuit through the arrester and limits the current to

a value that is readily broken by the cut out and is not enough to

impede the passage of the discharge.]

[Illustration: FIG. 2,833.--Diagram of switchboard connections for

General Electric automatic voltage regulator with three exciters and

three alternators.]

If possible, one place should be set aside for them and a marble

or slate panel provided on which they may be mounted.

Wooden supports are undesirable for lightning arresters on

account of the fire risk incurred; this, however, may be reduced

to a minimum by employing skeleton boards and using sheets of

asbestos between the arresters and the wood.

In parts of the country where lightning is of common occurrence

and where overhead circuits are installed which carry high

pressures, heavy currents, and extend over considerable territory,

it is advisable to have the station well equipped with lightning

arresters of the most improved types.

In each side of the main circuit, between the lightning arrester

connections and the switchboard apparatus there should be

connected a choke coil or else each of the main conductors at this

point should be tightly coiled up part of its length to answer the

same purpose.

A quick and effective way of coiling up a wire consists in

wrapping around a cylindrical piece of iron or wood that part

of the conductor in which it is desired to have the coils, the

desired number of times, and then withdrawing the cylindrical

piece. The coils, each of which may contain 50 or 200 turns,

thus inserted in the main circuit introduce a high resistance or

reluctance to a lightning current, and thus prevent it passing

to the generator; there will, however, be an easy path to earth

afforded it through the lightning arrester, and so no damage will

be done. Coils of the nature just mentioned may advantageously be

introduced between the generator and switchboard to take up the

reactive current developed upon the opening of the circuit, and in

the case of suspended conductors, the coils may be used to take up

the slack by the spring-like effect produced by them.

The safety of the operator should be especially considered in

the design of high pressure alternating current switchboards.

Such protection may be secured by screening all the exposed

terminals, or preferably by mounting all the switch mechanism on

the back of the board with simply the switch handle projecting

through to the front; by pushing or pulling the switch handle, the

connections can thus be shifted either to one side of the system

or to the other.

=Ques. Upon what does the work of assembling a switchboard depend?=

Ans. It depends almost entirely upon the size of the plant, varying

from the simple task of mounting a single panel in the case of an

isolated plant, to the more difficult problem of supporting a large

number of panels in a central station.

=Ques. When the material chosen for a switchboard must be shipped a

considerable distance, what form of board should be used?=

Ans. The board units or "slabs" should be of small dimensions, to

avoid the liability of breakage and expense of renewal when a unit

becomes cracked or machine injured.

[Illustration: FIGS. 2,834 and 2,835.--Front and rear views showing

General Electric automatic voltage regulator mounted on switchboard

panel.]

Ordinarily, switchboards vary from five to eight feet in

height and the widths of the panels vary from five to six feet.

In some boards the seams between the slabs run vertically, and

in others horizontally. In order to render the assembling of

the switchboard as simple as possible, and its appearance when

finished the most artistic, these seams should run horizontally

rather than vertically. The edges of each of the slabs should also

be chamfered so that there will be less danger of their breaking

out when being mounted on the framework.

=Ques. In assembling a switchboard, how should the lower slabs be

placed, and why?=

Ans. They should be suspended a little distance from the floor to

prevent contact with any oil, dirt, water or rubbish that might be on

the floor.

=Ques. How are the slabs or panels supported?=

Ans. They are carried on an iron or wooden framework with braces to

give stability.

The braces should be securely fastened at one end to the wall of

the station, and at the other end to the framework of the board,

as shown in fig. 2,836.

To fasten the switchboard end of the brace directly to the

slate, marble or other material composing the board is poor

practice and should never be attempted.

If the station be constructed of iron, these switchboard braces

must be such that they will thoroughly insulate the board and its

contents from the adjoining wall.

[Illustration: FIG. 2,836.--Method of supporting the framework of a

switchboard.]

=Ques. What is the usual equipment of a switchboard?=

Ans. It comprises switching devices, current or pressure limiting

devices, indicating devices, and fuses for protecting the apparatus

and circuits.

[Illustration: FIG. 2,837.--Diagram showing elementary connections of

General Electric automatic regulator for direct current. It consists

essentially of a main control magnet with two independent windings

and a differentially wound relay magnet. One winding, known as the

pressure winding, of the main control magnet is connected across the

dynamo terminals, the other across a shunt in one of the load mains.

The latter is the "compensating winding" and it opposes the action

of the pressure winding so that as the load increases, a higher

pressure at the dynamo is necessary to "over compound" for line drop.

In ordinary practice, the voltage terminals are connected to the bus

bars, and the compensating shunt inserted in one of the principal

feeders of the system. In operation the shunt circuit across the

dynamo field rheostat is first opened by means of a switch provided

for that purpose on the base of the regulator and the rheostat turned

to a point that will reduce the generator voltage 35 per cent below

normal. The main control magnet is at once weakened and allows the

spring to pull out the movable core until the main contacts are

closed. This closes the second circuit of the differential relay,

thus neutralizing its windings. The relay spring then lifts the

armature and closes the relay contacts. The switch in the shunt

circuit across the dynamo field rheostat is now closed, practically

short circuiting the rheostat, and the dynamo voltage at once rises.

As soon as it reaches the point for which the regulator has been

adjusted, the main control magnet is strengthened, which causes the

main contacts to open, which in turn open the relay contacts across

the rheostat. The rheostat is now in the field circuit, the voltage

at once falls off, the main contacts are closed, and relay armature

released, and shunt circuit across the rheostat again completed. The

voltage then starts to rise and this cycle of operation is continued

at a high rate of vibration, maintaining not a constant but a steady

voltage at the bus bars. When neither the compensating winding nor

pressure wires are used, there will be no "over compounding" effect

due to increase of load and a constant voltage will be maintained at

the bus bars. The compensating winding on the control magnet, which

opposes the pressure winding is connected across an adjustable shunt

in the principal feeder circuit. As the load increases the voltage

drop across the shunt increases and the effect of the compensating

winding becomes greater. This will require a higher voltage on the

pressure winding to open the main contacts and the regulator will

therefore cause the dynamo to compensate for line drop, maintaining

at the bus bars a steady voltage without fluctuations, which rises

and falls with a load on the feeders, giving a constant voltage at

the lamps or center of distribution. The compensating shunt may be

adjusted so as to compensate for any desired line drop up to 15 per

cent; it is preferably placed in the principal lighting feeder, but

may be connected to the bus bars so that the total current will pass

through it. The latter method, however, is sometimes desirable, as

large fluctuating power loads on separate feeders might disturb the

regulation of the lighting feeders. Adjustment is made by sliding

the movable contact at the center of the shunt. This contact may be

clamped at any desired point and determines the pressure across the

compensating winding of the regulator's main control magnet. Where

pressure wires are run back to the central station from the center

of distribution they may be connected directly to the pressure

winding of the main control magnet, and it is unnecessary to use the

compensating shunt. The pressure wires take the place of the leads

from the control magnet to the bus bars and maintain a constant

voltage at the center of distribution.]

On some switchboards are also mounted small transformers for

raising or lowering the voltages, and lightning arresters as a

protection from lightning. In addition to the apparatus previously

mentioned nearly all switchboards carry at or near their top two

or more incandescent lamps provided with shades or reflectors, for

lighting the board.

=Ques. What should be done before wiring a switchboard?=

Ans. The electrical connections between the various apparatus

mounted on the face or front of the board, are made on the back of

the board. It is necessary that these connections be properly made

else considerable electrical power will be wasted at this point. The

wiring on the back of the board should therefore be planned out on

paper before commencing the work.

[Illustration: FIG. 2,838.--Diagram showing connections of General

Electric automatic voltage regulator for direct current as connected

for maintaining balanced voltage on both sides of a three wire system

using a balancer set. In operation, should the voltage on the upper

bus bars become greater than that on the lower ones, the middle and

upper contacts on the regulator will close, thus opening the relay

contacts to the left and closing those to the right. This inserts all

the resistance in the field of balancer A, and short circuits the

resistance in the field of balancer B. A will then be running as a

motor, and B as a dynamo, thereby equalizing the two voltages until

that on the lower bus bars becomes greater than that of the upper

ones; then the regulator contacts operate in the opposite direction

and balancer A is run as a dynamo, and balancer B as a motor. This

cycle of operation is repeated at the rate of from three to four

hundred times per minute, thus maintaining a balanced voltage on the

system.]

In laying out the plan of wiring care must be taken to allow

sufficient contact surface at each connection; there should be not

less than one square inch of contact surface allowed for each 160

amperes of current transmitted.

[Illustration: FIG. 2,839.--Diagram of connections of General

Electric voltage regulators for one or more alternators using one

exciter.]

For the bus bars, which, by the way are always of copper, one

square inch per 1,000 amperes is the usual allowance; this is

equal to 1,000 circular mils of cross sectional area per ampere.

Every effort should be made to give the bus bars the greatest

amount of radiation consistent with other conditions, in order

that their resistances may not become excessive owing to the heat

developed by the large currents they are forced to carry. Suppose,

for instance, the number of amperes to be generated is such as

to require bus bars having each a cross sectional area of one

square inch. If the end dimensions of these bars were each 1 inch

by 1 inch, there would be less radiating surface than if their

dimensions were each 2 inches by ½ inch.

=Operation of Alternators.=--The operation of an alternator when run

singly differs but little from that for a dynamo.

As to the preliminaries, the exciter must first be started.

This is done in the same way as for any shunt dynamo. At first

only a small current should be sent through the field winding of

the alternator; then, if the exciter operates satisfactorily and

the field magnetism of the operator show up well, the load may

gradually be thrown on until the normal current is carried, the

same method of procedure being followed as in the similar case of

a dynamo.

[Illustration: FIGS. 2,840 and 2,841.--General Electric equalizer

regulator designed to equalize the load on two machines, and diagram

of connections.]

On loading an alternator, a noticeable drop in voltage occurs

across its terminals. This drop in voltage is caused in part by the

demagnetization of the field magnets due to the armature current,

and so depends in a measure upon the position and form of the pole

pieces as well as upon those of the teeth in the armature core. The

resistance of the armature winding also causes a drop in voltage

under an increase of load.

Another cause which may be mentioned is the inductance of the

armature winding, which is in turn due to the positions of the

armature coils with respect to each other and also with respect to

the field magnets.

[Illustration: FIG. 2,842.--Connection of General Electric equalizing

regulator for equalizing loads on an engine driven dynamo and rotary

converter running in parallel. Should the load on the dynamo become

greater than that on the rotary converter, the middle and upper

contacts on the regulator close, and thus by means of the relay

switch and control motor, cause the feeder regulator to boost the

voltage on the rotary until the loads again become equal. Should

the load on the rotary converter become greater than that on the

generator, the regulator contacts operate in the reverse direction

and the feeder regulator is caused to buck the rotary voltage.]

=Alternators in Parallel.=--When the load on a station increases

beyond that which can conveniently be carried by one alternator, it

becomes necessary to connect other alternators in parallel with it.

To properly switch in a new machine in parallel with one already in

operation and carrying load, requires a complete knowledge of the

situation on the part of the attendant, and also some experience.

The connections for operating alternators in parallel are

shown in fig. 2,843. In the illustration the alternator A is in

operation and is supplying current to the bus bars. The alternator

B is at rest. The main pole switch B' by means of which this

machine can be connected into circuit is therefore open.

[Illustration: FIG. 2,843.--Method of synchronizing with one lamp;

_dark lamp method_. Assuming A to be in operation, B, may be brought

up to approximately the proper speed, and voltage. Then if B, be

run a little slower or faster than A, the synchronizing lamp will

glow for one moment and be dark the next. At the instant when the

pressures are equal and the machines in phase, the lamp will become

dark, but when the phases are in quadrature, the lamp will glow at

its maximum brilliancy. Since the flickering of the lamp is dependent

upon the difference in frequency, the machines should not be thrown

in parallel while this flickering exists. The nearer alternator

approaches synchronism, in adjusting its speed, the slower the

flickering, and when the flickering becomes very slow, the incoming

machine may be thrown in the moment the lamp is dark by closing the

switch. The machines are then in phase and tend to remain so, since

if one slow down, the other will drive it as a motor.]

Now, if the load increase to such extent as to require the

service of the second alternator B, it must be switched in

parallel with A. In order that both machines may operate properly

in parallel, three conditions must be satisfied before they are

connected together, or else the one alternator will be short

circuited through the other, and serious results will undoubtedly

follow.

Accordingly before closing main switch B, it is necessary that

1. The frequencies of both machines be the same;

2. The machines must be in synchronism;

3. The voltages must be the same.

=Ques. How are the frequencies made the same?=

Ans. By speeding up the alternator to be cut in, or change the speed

of both until frequency of both machines is the same.

[Illustration: FIG. 2,844.--Diagram of connections of General

Electric automatic voltage regulator for several alternators running

in parallel with exciters in parallel.]

=Ques. How are the alternators synchronized or brought in phase?=

Ans. The synchronism of the alternators is determined by employing

some form of synchronizer, as by the single lamp method of fig.

2,843, or the two lamp method of fig. 2,845.

=Ques. In synchronizing by the one lamp method, when should the

incoming machine be thrown in?=

Ans. It is advisable to close the switch when the machines are

approaching synchronism rather than when they are receding from it,

that is to say, the instant the lamp becomes dark.

[Illustration: FIG. 2,845.--Method of synchronizing with two lamps;

_dark lamp method_. The two synchronizing lamps are connected as

shown, and each must be designed to supply its rated candle power

at the normal voltage developed by the alternators. Now since the

alternators are both running under normal field excitation the left

hand terminals of each of them will alternately be positive and

negative in polarity, while the right hand terminals are respectively

negative and positive in polarity. If, however, the alternators be

in phase with each other, the left hand terminals of both of them

will be positive while the right hand terminals are negative, and

when the left hand terminals of both machines are negative the right

hand terminals will be positive. Hence, when the machines are in

phase there will be no difference of pressure between the left hand

terminals or between the right hand terminals of the two machines.

Hence, if the synchronizing lamps be connected as shown, both will

be dark. The instant there is a difference of phase, both lamps

will glow attaining full candle power when the difference of phase

has reached a maximum. As the alternators continue to come closer

in step, the red glow will gradually fade away until the lamps

become dark. Then the switch may be closed, thereby throwing the

two machines in parallel. If the intervals between the successive

lighting up of the lamps are of short duration it is advisable to

wait until these become longer even though the other conditions are

satisfied, because where the phases pass each other rapidly there is

a greater possibility of not bringing them together at the proper

instant. An interval of not less than five seconds should therefore

be allowed between the successive lighting up of the lamps, before

closing the switch.]

[Illustration: FIG. 2,846.--Inductor type synchroscope. This type

is especially applicable where pressure transformers are already

installed for use with other meters. As it requires only about ten

apparent watts it may be used on the same transformers with other

meters. There are three stationary coils, N, M and C, and a moving

system, comprising an iron armature, A, rigidly attached to a shaft

suitably pivoted and mounted in bearings. A pointer is also attached

to the shaft. The moving system is balanced and is not subjected

to any restraining force, such as a spring or gravity control. The

axes of the coils N and M are in the same vertical plane, but 90

degrees apart, while the axis of C is in a horizontal plane. The

coils N and M are connected in "split phase" relation through an

inductive resistance P and non-inductive resistance Q, and these two

circuits are parallel across the bus bar terminals 3 and 4 of the

synchroscope. Coil C is connected through a non-inductive resistance

across the upper machine terminals 1 and 2 of the synchroscope. =In

operation=, current in the coil C magnetizes the iron core carried

by the shaft and the two projections, marked A and "iron armature."

There is however, no tendency to rotate the shaft. If current be

passed through one of the other coils, say M, a magnetic field will

be produced parallel with its axis. This will act on the projections

of the iron armature, causing it to turn so that the positive and

negative projections assume their appropriate position in the field

of the coil M. A reversal of the direction in both coils will

obviously not affect the position of the armature, hence alternating

current of the same frequency and phase in the coils C and M cause

the same directional effect upon the armature as if direct current

were passed through the coils. If current lagging 90 degrees behind

that in the coils M and C be passed through the coil N, it will cause

no rotative effect upon the armature, because the maximum value of

the field which it produces will occur at the instant when the pole

strength of the armature is zero. The two currents in the coils M and

N produce a shifting magnetic field which rotates about the shaft as

an axis. As all currents are assumed to be of the same frequency, the

rate of rotation of this field is such that its direction corresponds

with that of the armature projections at the instant when the poles

induced in them by the current in the coil C are at maximum value,

and the field shifts through 180 degrees in the same interval as is

required for reversal of the poles. This is the essential feature of

the instrument, namely, that the armature projections take a position

in the rotating magnetic field which corresponds to the direction of

the field at the instant when the projections are magnetized to their

maximum strength by their current in the coil C. If the frequency

of the currents in the coils which produce the shifting field be

less than that in the coil which magnetized the armature, then the

armature must turn in order that it may be parallel with the field

when its poles are at maximum strength.]

=Ques. What are the objections to the one lamp method?=

Ans. The filament of the lamp may break, and cause darkness, or the

lamp may be dark with considerable voltage as it takes over 20 volts

to cause a 100 volt lamp to glow.

=Ques. What capacity of single lamp must be used?=

Ans. It must be good for twice the voltage of either machine.

[Illustration: FIG. 2,847.--Brilliant lamp method of synchronizing.

The synchronizing lamps are connected as shown, and must be of the

alternator voltage. When the voltages are equal and the machines in

phase, the difference of pressure between _a_ and a given point is

the same as that between _a'_ and the same point; this obtains for

_b_ and _b'_. Accordingly, a lamp connected across _a b'_ will burn

with the same brilliancy as across _a' b_; the same holds for the

other lamp. When the voltages are the same and the phase difference

is 180° the lamps are dark, and as the phase difference is decreased,

the lamps glow with increasing brightness until at synchronism they

glow with maximum brilliancy. Hence the incoming alternator should be

thrown in at the instant of maximum brilliancy.]

=Ques. What modification of the synchronizing methods shown in

the accompanying illustrations is necessary when high pressure

alternators are used?=

Ans. Step down transformers must be used between the alternators and

the lamps to obtain the proper working voltages for the lamps.

[Illustration: FIG. 2,848.--Synchronizing with high pressure

alternators; dark and brilliant lamp methods. In both methods the

primaries of the transformers are connected in the same way across

the terminals of the alternators as shown. In the dark lamp method,

the connections between the secondary coils of the transformers must

be made so that when each is subjected to the same conditions the

action of the one coil opposes that of the other as in the dark lamp

method; then, if the transformers be both of the same design, there

will be no voltage across the lamps when the alternators are in phase

with each other. If the ratio of each transformer is such as to give,

for example, 100 volts across its secondary terminals, then the two

incandescent lamps since they are joined together in series must

each be designed for 100 volts. One 200 volt lamp could be used in

either method in place of the two 100 volt lamps. When, therefore,

the alternators are directly opposite in phase to each other, both

the lamps will burn brightly; as the alternators come together in

phase the lamps will produce less and less light, until when the

machines are exactly in phase no light will be emitted at all, at

which instant the incoming alternator should be thrown in. It must

be evident, if the transformer secondary connections are arranged as

in the brilliant lamp method, so that they do not oppose each other,

the lamps will be at maximum brilliancy when the alternators are in

phase and dark when the phase difference is 180°, assuming of course

equalized voltage.]

=Ques. How is the voltage of an incoming machine adjusted so that it

will be the same as the one already in operation?=

Ans. By varying the field excitation with a rheostat in the

alternator field circuit.

=Ques. How may two or more alternators be started simultaneously?=

Ans. After bringing each of them up to its proper speed so as to

obtain equal frequencies, the main switches may be closed, thereby

joining their armature circuits in parallel. As yet, however, their

respective field windings have not been supplied with current, so

that no harm can result in doing this. The exciters of these machines

after being joined in parallel, should then be made to send direct

current simultaneously through the field windings of the alternators,

and from this stage on the directions previously given may be

followed in detail.

=Ques. What are the conditions when two or more alternators are

directly connected together?=

Ans. If rigidly connected together, or directly connected to the same

engine, they must necessarily run in the same manner at all times.

When machines connected in this way are once properly adjusted

so that they are in phase with each other, their operation in

parallel is even a simpler task than when they are all started

together but are not directly connected.

=Ques. When an alternator is driven by a gas engine, what provision

is sometimes made to insure successful operation in parallel?=

Ans. An amortisseur winding is provided to counteract the tendency to

"hunting."

[Illustration: FIG. 2,849.--Diagram of Lincoln Synchronizer. =In

construction=, a stationary coil F, has suspended within it a coil A,

free to move about an axis in the planes of both coils and including

a diameter of each. If an alternating current be passed through both

coils, A, will take a position with its plane parallel to F. If now

the currents in A and F be reversed with respect to each other, coil

A will take up a position 180° from its former position. Reversal

of the relative directions of currents in A and F is equivalent to

changing their phase relation by 180°, and therefore this change

of 180° in phase relation is followed by a corresponding change of

180° in their mechanical relation. Suppose now, instead of reversing

the relative direction of currents in A and F, the change in phase

relation between them be made gradually and without disturbing the

current strength in either coil. It is evident that when the phase

difference between A and F reaches 90°, the force between A and F

will become reduced to zero, and a movable system, of which A may

be made a part, is in condition to take up any position demanded

by any other force. Let a second number of this movable system

consist of coil B, which may be fastened rigidly to coil A, with its

plane 90° from that of coil A, and the axis of A passing through

diameter of B. Further, suppose a current to circulate through B,

whose difference in phase relation to that in A, is always 90°. It

is evident under these conditions that when the difference in phase

between A and F is 90°, the movable system will take up a position,

such that B is parallel to F, because the force between A and F is

zero, and the force between B and F is a maximum; similarly when the

difference in phase between B and F is 90°, A will be parallel to F.

That is, beginning with a phase difference between A and F of zero

a phase change of 90° will be followed by a mechanical change on a

movable system of 90°, and each successive change of 90° in phase

will be followed by a corresponding mechanical change of 90°. For

intermediate phase relation, it can be proved that under certain

conditions the position of equilibrium assumed by the movable element

will exactly represent the phase relations. That is, with proper

design, the mechanical angle between the plane of F and that of A

and also between the plane of F and that of B, is always equal to

the phase angle between the current flowing in F and those in A and

B respectively. =As commercially constructed= coil F consists of a

small laminated iron field magnet with a winding whose terminals

are connected with binding posts. The coils A and B are windings

practically 90° apart on a laminated iron armature pivoted between

the poles of the magnet. These two windings are joined, and a tap

from the junction is brought out through a slip ring to one of two

other binding posts. The two remaining ends are brought out through

two more slip rings, one of which is connected to the remaining

binding post, through a non-inductive resistance, and the other

to the same binding post through an inductive resistance. A light

aluminum hand attached to the armature shaft marks the position

assumed by the armature.]

=Ques. What is the action of the amortisseur winding?=

Ans. Any sudden change in the speed of the field, generates a current

in the amortisseur winding which resists the change of velocity that

caused the current.

The appearance of an amortisseur winding is shown in the cut

below (fig. 2,850) illustrating the field of a synchronous

condenser equipped with amortisseur winding.

[Illustration: FIG. 2,850.--General Electric field of synchronous

condenser provided with amortisseur winding. Hunting is accompanied

by a shifting of flux across the face of the pole pieces due to the

variation in the effect of armature reaction on the main field flux

as the current varies and the angular displacement between the field

and armature poles is changed. Copper short circuited collars placed

around the pole face have currents induced in them by this shifting

flux, which have such a direction as to exert a torque tending to

oppose any change in the relative position of the field and armature.

This action is similar to that of the running torque of an induction

motor and the damping device has been still further developed until

in its best form it resembles the armature winding of a "squirrel

cage" induction motor. The pole pieces are in ducts, and low

resistance copper bars placed in them with their ends joined by means

of a continuous short circuiting ring extending around the field.

Such a device has proven very effective in damping out oscillations

started from any cause, the same winding doing duty as a damping

device and to assist the starting characteristics.]

=Ques. How are three phase alternators synchronized?=

Ans. In a manner similar to the single phase method.

Thus the synchronizing lamps may be arranged as in fig. 2,581,

which is simply an extension of the single phase method.

=Ques. Are three lamps necessary?=

Ans. Only to insure that the connections are properly made, after

which one lamp is all that is required.

=Ques. How is it known that the connections of fig. 2,851 are

correct?=

Ans. If, in operation, the three lamps become bright or dark

_simultaneously_, the connections are correct; if this action takes

place _successively_, the connections are wrong.

If wrong, transpose the leads of one machine until simultaneous

action of the lamps is secured.

[Illustration: FIG. 2,851.--Method of synchronizing three phase

alternators with, three lamps, being an extension of the single phase

method.]

=Ques. What is the disadvantage of the lamp method of synchronizing?=

Ans. Lack of sensitiveness.

=Ques. Which is the accepted lamp method, dark or brilliant?=

Ans. In the United States it is usual to make the connections for

a dark lamp at synchronism, while in England the opposite practice

obtains.

With the dark lamp method, the breaking of a filament might

cause the machines to be connected with a great phase difference,

whereas, with the brilliant lamp it is difficult to determine the

point of maximum brilliancy. This latter method, therefore may be

called the safer.

=Ques. What may be used in place of lamps for synchronizing?=

Ans. Some form of synchroscopes, or synchronizers.

=Ques. How does the Lincoln synchronizer work?=

Ans. The construction is such that a hand moves around a dial so

that the angle between the hand and the vertical is always the phase

angle between the two sources of electric pressure to which the

synchronizer is connected.

If the incoming alternator be running too slow, the hand

deflects in one direction, if too fast, in the other direction.

When the hand shows no deflection, that is, when it stands

vertical, the machines are in phase. A complete revolution of the

hand indicates a gain or loss of one cycle in the frequency of the

incoming machine, as referred to the bus bars.

=Cutting Out Alternator.=--When it is desired to cut out of circuit

an alternator running in parallel with others, the method of

procedure is as follows:

1. Reduce driving power until the load has been transferred

to the other alternators, adjusting field rheostat to obtain

minimum current;

2. Open main switch;

3. Open field switch.

=Ques. What precaution should be taken?=

Ans. _Never_ open field switch before main switch.

[Illustration: FIG. 2,852.--General Electric 500 kw., horizontal

mixed pressure Curtis turbine connected to a 500 kw. dynamo. In

a Curtis turbine it is not necessary to use the whole periphery

of the first stage for low pressure steam nozzles. A section can

be partitioned off and equipped with special expanding nozzles to

receive steam at high pressure direct from the boilers. Such nozzles

deliver their steam against the same wheel as do the low pressure

nozzles, but occupy only a small portion of its periphery. The steam

is expanded in these nozzles from high pressure all the way down

to the normal pressure of the first stage, and in such expansion

acquires a high velocity and consequently contains a great deal

of energy--much more than does an equal quantity of low pressure

steam. In consequence of this, high pressure steam is used with

a far lower water rate than is obtained with low pressure steam,

or with high pressure steam reduced to low pressure in a reducing

valve. This construction is called "mixed pressure." Its function

is the same as that of the reducing valve, that is, it makes up

for a deficiency of low pressure steam by drawing direct on the

boilers. With this construction, the full power of the turbine can be

developed with: All low-pressure steam, all high pressure steam, or,

any necessary proportion of steam of each pressure. Furthermore, the

transition from all low pressure to all high pressure, through all

the conditions intermediate between these extremes, is provided for

automatically by the turbine governor; a deficiency of low pressure

steam causes the high pressure nozzles to open automatically.]

=Ques. What is the ordinary method of cutting out an alternator?=

Ans. The main switch is usually opened without any preliminaries.

=Ques. What is the objection to this procedure?=

Ans. It suddenly throws all the load on the other alternators, and

causes "hunting."

=Ques. What forms of drive are especially desirable for running

alternators in parallel, and why?=

Ans. Water turbine or steam turbine because of the uniform torque,

thus giving uniform motion of rotation.

With reciprocating engines, the crank effect is very variable

during the revolution, resulting in pulsations driving the

alternator too fast or too slow, and causing cross current between

the alternators.

=Ques. Is a sluggish, or a too sensitive governor preferable on an

engine driving alternators in parallel?=

Ans. A sluggish governor.

=Alternators in Series.=--Alternators are seldom if ever connected

in series, for the reason that the synchronizing tendency peculiar

to these machines causes them to oppose each other and fall out of

phase when they are joined together in this way. If, however, they

be directly connected to each other, or to an engine, so that they

necessarily keep in phase at all times, and thus add their respective

voltages instead of counteracting them, series operation is possible.

NOTE.--According to the practice of the General

Electric Co., 2½ degrees of phase difference

from a mean is the limit allowable in ordinary

cases. It will, in certain cases, be possible to

operate satisfactorily in parallel, or to run

synchronous apparatus from machines whose angular

variation exceeds this amount, and in other cases

it will be easy and desirable to obtain a better

speed control. The 2½ degree limit is intended to

imply that the maximum departure from the mean

position during any revolution shall not exceed

2½ ÷ 360 of an angle corresponding to two poles

of a machine. The angle of circumference which

corresponds to the 2½ degree of phase variation

can be ascertained by dividing 2½ by ½ the

number of pole; thus, in a 20 pole machine, the

allowable angular variation from the mean would

be 2½ ÷ 10 = ¼ of one degree.

[Illustration: FIG. 2,853.--Diagram of connections for synchronizing

two compound wound three phase alternators. A and A' are the

armatures of the two machines, the fields of which are partly

separately excited, the amount of excitation current being controlled

by the series compounding rheostats B and B', which form a stationary

shunt. It is assumed that the alternator A is connected to the

bus bars 1, 2, and 3, by the switch 1S. If an increase make it

necessary to introduce the alternator A', it is first run up to

speed and excited to standard pressure by its exciter, and then

the double plug switch 3S is closed, connecting the primary of the

station transformer T and T' with the bus bars through the secondary

coil, so that the synchronizing lamps light up when the secondary

circuit is closed through the single pole switch 4S. The primary of

the station transformer T is thus excited through the double pole

switch 5S, connecting it with the outer terminals of the armature

A'. The two alternators will now work in opposition to each other

upon the synchronizing lamps, the transformer T being operated by

the new alternator A' through the switch 2S, and the transformer

T' being operated by the working alternator A, from the bus bars.

If the new alternator be not in step with the working alternator,

the synchronizing lamps will glow, growing brighter and dimmer

alternately with greater or lesser rapidity. In this case, the

armature speed of the new alternator must be controlled in such a

manner that the brightening and dimming will occur more and more

slowly, until the lamps cease to glow or remain extinguished for

a decided interval of time. The extinction of the light is due to

the disappearance of the secondary current, and indicates that

the alternators are in step. The switch 2S should now be thrown,

thus coupling the two machines electrically, and both of them will

continue to operate in step. The double pole equalizer switch 6S

should now be closed, connecting the two field windings in parallel

and equalizing the compounding, so that any variations of load will

affect the two alternators equally. After the alternators have been

connected in parallel, the switches 4S and 5S, may be opened leaving

the switch 3S closed, to operate the switchboard lamps K, K, as pilot

lights from the bus bars.]

=Transformers.=--These, as a whole, are simple in construction, high

in efficiency, and comparatively inexpensive. Their principles of

operation are also readily understood.

The efficiency of a transformer, that is, the ratio between full

load primary and full load secondary is greatest when the load on it

is such that the sum of the constant losses equals the sum of the

variable losses.

In general, transformers designed for high frequencies and

large capacities are more efficient than those designed for

low frequencies and small capacities. As a whole, however, a

transformer leaves but little to be desired as regards efficiency,

a modern 60 cycle transformer of 50 kilowatts capacity or more

possesses an efficiency of approximately 98 per cent. at full load

and an efficiency of about 97 per cent. at half load.

=Ques. How should a transformer be selected, with respect to

efficiency?=

Ans. One should be chosen, whose parts are so proportioned that the

point of maximum efficiency occurs at that load which the transformer

usually carries in service.

In many alternating current installations, comparatively light

loads are carried the greater part of the time, the rated full

load or an overload being occurrences of short durations. For such

purposes special attention should be given to the designing or

selecting of transformers having low core losses rather than low

resistance losses, because the latter are then of relatively small

importance.

=Ques. What kind of efficiency is the station manager interested in?=

Ans. The "all day efficiency."

This expression, as commonly met with in practice, denotes

_the percentage that the amount of energy actually used by the

consumer is of the total energy supplied to his transformer during

24 hours_. The formula for calculating the all day efficiency of

a transformer is based upon the supposition that the amount of

energy used by the consumer during 24 hours is equivalent to full

load on his transformer during five hours and is as follows:

5w

E = -------------

24c + 5r + 5w

where

E = the all day efficiency of the transformer,

w = the full load in watts on the primary,

c = the core loss in watts,

r = the resistance loss in watts.

[Illustration: FIG. 2,854.--Performance curves of Westinghouse air

blast 550 kw, 10,500 volt transformer, 3,000 alternations.]

=Ques. What are the usual all day efficiencies?=

Ans. The average is about 85 per cent. for those of 1 kilowatt

capacity, 92 per cent. for those of 5 kilowatts capacity, 94 per

cent. for those of 10 kilowatts capacity, and about 94.5 per cent.

for those of 15 kilowatts capacity.

=Ques. What becomes of the energy lost by a transformer?=

Ans. It reappears as heat in the windings and core.

This heat not only increases the resistances of the windings and

core, producing thereby a further increase of their respective

losses, but in addition causes in time a peculiar effect on the

iron core which is intensified by the reversals of magnetism

constantly going on within it.

After about two years' service, the iron apparently becomes

fatigued or tired, and this phenomenon is called aging of the

iron. Since the life of the transformer depends to a great extent

upon this factor, the conditions responsible for its existence

should as far as possible be removed. Means must therefore be

provided in the construction to radiate the heat as quickly as it

is generated.

=Ques. What kind of oil is used in oil cooled transformers?=

Ans. Mineral oil.

[Illustration: FIG. 2,855.--General arrangement of air blast

transformers and blowers.]

=Ques. How is it obtained?=

Ans. By fractional distillations of petroleum unmixed with any other

substances and without subsequent chemical treatment.

=Ques. What is the important requirement for transformer oil?=

Ans. It should be free from moisture, acid, alkali or sulphur

compounds.

=Ques. How may the presence of moisture be determined?=

Ans. By thrusting a red hot iron rod in the oil; if it "crackle,"

moisture is present.

=Ques. Describe the Westinghouse method of drying oil.=

Ans. It is circulated through a tank containing lime, and afterwards,

through a dry sand filter.

=Ques. What is the objection to heating the oil (raising its

temperature slightly above boiling point of water) to remove the

moisture?=

Ans. The time consumed (several days) is excessive.

[Illustration: FIG. 2,856.--Small Curtis turbine generator set as

made by the General Electric Co., in sizes from 5 kw., to 300 kw.

It can be arranged to operate either condensing or non-condensing,

and at any steam pressure above 80 lbs. for the smaller sizes and

100 lbs. for the larger. There are only two main bearings. A thrust

bearing, consisting of roller bearings and running between hardened

steel face washers located at either end of the main bearings is

provided solely for centering the rotor so as to equalize the

clearance. A centrifugal governor is provided (in the smaller sizes)

completely housed, and mounted directly on the main shaft end. It

controls a balanced poppet valve through a bell crank. In the larger

sizes (75 kw. and above) the governor is mounted on a vertical

secondary shaft geared to the main shaft and controls a cam shaft

which opens or closes a series of valves in rotation, admitting the

steam to different sections of the first stage nozzles. In this

way throttling of the steam is avoided. There is also an emergency

governor which closes the throttle valve in the event of the speed

reaching a predetermined limit. The speeds of operation range from

5,000 R.P.M. for the smallest size to 1,500 R.P.M. for the largest.

The lubrication system is enclosed and is automatic. Air leakage

where the shaft passes through the wheel casing is prevented by steam

seal.]

=Ques. What effect has moisture?=

Ans. It reduces the insulation value of the oil. .06 per cent. of

moisture has been found to reduce the dielectric strength of oil

about 50 per cent. "dry" oil will withstand a pressure of 25,000

volts between two 9½ inch knobs separated .15 inch.

=Ques. What is understood by transformer regulation?=

Ans. It is the difference between the secondary voltage at no load

and at full load, and is generally expressed as a percentage of the

secondary voltage at no load.

=Ques. What governs its value?=

Ans. The resistance and reactance of the windings.

[Illustration: FIG. 2,857.--Cut off coupling for power transmission

by line shafting. It is used to cut off a driving shaft from a driven

shaft. Its use obviates the use of a _quill_, such as is shown in

fig. 2,858.]

=Ques. How may the regulation be improved?=

Ans. By decreasing the resistances of the windings by employing

conductors of greater cross section, or decreasing their reactance by

dividing the coils into sections and closely interspersing those of

the primary between those of the secondary.

NOTE.--_The term_ ="regulation"= as here used

is synonymous with "drop." The _voltage drop_

in a transformer denotes the drop of voltage

occurring across the secondary terminals of a

transformer with load. This drop is due to two

causes: 1, the resistance of the windings; and

2, the reactance or magnetic leakage of the

windings. On non-inductive load, the reactive

drop, being in quadrature, produces but a slight

effect, but on inductive loads it causes the

voltage to drop, and on _leading current loads_

it causes the voltage to rise. As the voltage

drop of a good transformer is very small even

on inductive load, direct accurate measurement

is difficult. It is best to measure the copper

loss with short circuited secondary by means of

a wattmeter, and at the same time the voltage

required to drive full load current through. From

the watts, the resistance drop can be found, and

from this and the impedance voltage, the reactive

drop may be calculated. From these data a simple

vector diagram will give, near enough for all

practical purposes, the drop for any power

factor, or the following formula may be used

which has been deduced from the vector diagram.

_________________________

D = √(W + X)^{2} + (R + P)^{2} - 100 where R

= % resistance drop; X = % reactive drop; P = %

power factor of load; W = % wattless factor of

________

load (√1 - P^{2}); D = % resultant secondary

drop. For non-inductive loads where P = 100 and W

_____________________

= 0, D = √X^{2} + (100 + R)^{2} - 100. In the

case of leading currents it should be considered

negative.

In transformers where there is a great difference in voltage

between the primary and secondary windings, however, this remedy

has its limitations on account of the great amount of insulation

which must necessarily be used between the windings, and which

therefore causes the distances between them to become such as to

cause considerable leakage of the lines of force.

=Ques. How does the regulation vary for different transformers, and

what should be the limit?=

Ans. Those of large capacity usually have a better regulation than

those of small capacity, but in no case should its value exceed 2 per

cent.

[Illustration: FIG. 2,858.--Quill drive. This is the proper

transmission arrangement substitute for heavy service, requiring

large pulleys, sheaves, gears, rotors, etc. It is a hollow shaft

supported by independent bearings. The main driving shaft running

through the quill is thus relieved of all transverse stresses. The

power is transmitted to the quill by means of a friction or jaw

clutch. When the clutch is thrown out the pulley or sheave stands

idle and the driving shaft revolves freely within the quill. As there

is no contact between moving parts there is no wear. Jaw clutches

should be used for drives demanding positive angular displacement.

They can only be thrown in and out of engagement when at rest. All

very large clutch pulleys, sheaves, or gears designed to run loose on

the line shaft are preferably mounted on quills. The letters A, B, C,

etc., indicate the dimensions to be specified in ordering a quill.]

=Ques. What advantages have shell type transformers over those of the

core type?=

Ans. They have a larger proportion of core surface exposed for

radiation of heat, and a shorter magnetic circuit which reduces the

tendency for a leakage of the lines of force into the air.

Both types have advantages and disadvantages as compared with

the other. In the shell type, there is less magnetic leakage, but

also less surface exposed for radiation, and greater difficulty in

providing efficient insulation between the two circuits; in the

core type there is more surface exposed for radiation and less

difficulty in insulating the windings, but there is also a great

leakage of the lines of magnetic force into the outer air.

=Ques. How are the windings usually arranged?=

Ans. As a rule, there is only one primary winding but the secondary

winding is generally divided into two equal sections, the four

terminals of which are permanently wired to four connection blocks

which may be connected so as to throw the secondary sections either

in parallel or in series with each other at will.

=Ques. What is necessary for satisfactory operation of transformers

in parallel?=

Ans. They must be designed for the same pressures and capacities,

their percentages of regulation should be the same and they must have

the same polarity at a given instant.

One may satisfy himself as to the first of these conditions by

examining the name plates fastened to the transformers, whereon

are stamped the values of the respective pressures and capacities

of each.

Although equal values of regulation is given as one of the

conditions to be satisfied, transformers may be operated in

parallel when their percentages of regulation are not the same.

Ideal operation, however, can be attained only under the former

state of affairs. Suppose, for instance, a transformer having a

regulation of two per cent. be operated in parallel with another

of similar size and design but having a regulation of one per

cent. The secondary pressures of these transformers at no load

will of course be the same, but at full load if the secondary

pressure of the one be 98 volts, that of the other will be 99

volts. There will, therefore, be a difference of pressure of one

volt between them which will tend to force a current backward

through the secondary winding of the transformer delivering 98

volts. This reversed current, although comparatively small in

value, lowers the efficiency of the installation by causing a

displacement of phase and a decrease in the combined power factor

of the transformers.

=Ques. Describe the polarity test.=

Ans. The test for polarity consists in joining together by means of a

fuse wire, a terminal of the secondary winding of each transformer,

and then with the primary windings supplied with normal voltage,

connecting temporarily the remaining terminals of the secondary

windings. The melting of the fuse wire thus connected indicates that

the secondary terminals joined together are of opposite polarities,

and that the connections must therefore be reversed, whereas if the

fuse wire do not melt, it shows that the proper terminals have been

joined and that the connections may be made permanent.

[Illustration: FIG. 2,859.--Single overhung tangential water wheel

equipped with Doble ellipsoidal buckets. The central position of the

front entering wedge or lip of the bucket is cut away in the form of

a semi-circular notch, which allows a solid circular water jet to

discharge upon the central dividing wedge of the bucket without being

split in a horizontal plane.]

The object of this test is, obviously, not to determine the

exact polarity of each secondary terminal, but merely to indicate

which of them are of the same polarity.

[Illustration: FIG. 2,860.--Motor generator exciter set driven by

a Pelton-Doble tangential water wheel. The water wheel runner is

mounted on the shaft overhung and the jet is regulated by either a

hand actuated or governor controlled needle nozzle. The speed of the

water wheel is equivalent to the synchronous speed of the induction

motor, hence, the latter floats on the line, and under certain

conditions may perform the functions of an alternator by feeding into

the circuit, should the water wheel tend to operate above synchronous

speed. Should any interruption to the operation of the wheel occur,

causing a diminution of speed, the induction motor would drop back

to full load speed and take up the exciter load, resulting in no

appreciable drop of exciter voltage. The only variation of speed

possible is dependent upon the "slip" of the motor. Where two or more

exciter sets are employed in the station, an advantageous arrangement

embraces the installation of a water wheel driven motor generator set

and an exciter set, consisting of merely the direct current generator

and water wheel. The induction motor being electrically tied into

the circuit, the possibility of a runaway of the water wheel is

eliminated, since its speed can only slightly exceed the synchronous

speed of the system.]

=Motor Generators.=--In motor generator sets, either the shunt or

series wound type of motor may be employed at the power producing

end of the set, but the field of the generator is either shunt

or compound wound, depending upon whether or not it is desired

to maintain or to raise the secondary voltage near full load. In

either case a rheostat introduced in the shunt field winding of the

generator will be found very essential. Both generator and motor are

so mounted on the base that their respective commutators are at the

outer ends of the set. By this means ample space surrounds all of the

working parts, and repairs can readily be made.

Motor generators are frequently used as boosters to raise or boost

the voltage near the extremities of long distance, direct current

transmission lines. Of these, electric railway systems in which it is

desired to extend certain of the longer lines, form a typical example.

[Illustration: FIG. 2,861.--Automatically governed Pelton-Doble

tangential water wheel driving exciter dynamo. The water wheel is

mounted on one end of the shaft, while the opposite end is extended

to carry a fly wheel of suitable design to compensate for the low fly

wheel effect of the direct current armature. Two bearings support

the shaft which carries the rotating elements of the unit. A needle

nozzle actuated by a direct motion Pelton-Doble governor (designed

for operation by either oil or water pressure) maintains constant

speed.]

Owing to the great cost of changing such a system over to one

employing alternating current, or storage batteries, or of

constructing an additional power station, these solutions of the

problem are usually at variance with good judgment and the amount

of money at hand. The choice then remains between the purchase of

additional wire for feeders, the connection of a booster in the old

feeders, or the installation of both larger feeders and a booster.

Of these, it is generally found that either the second or the third

mentioned alternative meets the conditions most satisfactorily.

A booster installed in a railway system for the purpose just

mentioned, would have a series wound motor, and the conditions

to which it must conform would be as follows: The motor having a

series winding must provide for the full feeder current passing

through both armature and field windings.

Owing to the varying loads on a railway system, due to the

frequent starting and stopping of cars, the feeder current varies

between zero and some such value as 150 amperes. This fluctuation

of current through the field winding will, in ordinary cases, vary

the magnetization of the pole pieces from zero almost to the point

of saturation; that is, the maximum feeder current will so nearly

fill the magnet cores with lines of force that it would be quite

difficult to cause more lines of magnetic force to pass through

them.

So long as the point of saturation is not reached, however, the

proportion of current to field strength remains constant, and

therefore the ratio of amperes to volts will not vary.

Hawkins Electrical Guide v. 08 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 5 / 6 章