CHAPTER LXV

=ALTERNATING CURRENT WIRING=

In the case of alternating current, because of its peculiar

behaviour, there are several effects which must be considered in

making wiring calculations, which do not enter into the problem with

direct current.

Accordingly, in determining the size of wires, allowance must be made

for

1. Self-induction;

2. Mutual-induction;

3. Power factor;

4. Skin effect;

5. Corona effect;

6. Frequency;

7. Resistance.

Most of these items have already been explained at such length,

that only a brief summary of facts need be added, to point out

their connection and importance with alternating current wiring.

=Induction.=--The effect of induction, whether self-induction

or mutual induction, is to set up a back pressure of _spurious

resistance_, which must be considered, as it sometimes materially

affects the calculation of circuits even in interior wiring.

_Self-induction is the effect produced by the action of the

electric current upon itself during variations in strength._

=Ques. What conditions besides variations of current strength governs

the amount of self-induction in a circuit?=

Ans. The shape of the circuit, and the character of the surrounding

medium.

If the circuit be straight, there will be little self-induction,

but if coiled, the effect will become pronounced. If the

surrounding medium be air, the self-induction is small, but if it

be iron, the self-induction is considerable.

[Illustration: FIGS. 2,671 to 2,676.--=The effect of self-induction.=

In a non-inductive circuit, as in fig. 2,672, the whole of the

virtual pressure is available to cause current to flow through the

lamp filament, hence it will glow with maximum brilliancy. If an

inductive coil be inserted in the circuit as in fig. 2,674, the

reverse pressure due to self-induction will oppose the virtual

pressure, hence the effective pressure (which is the difference

between the virtual and reverse pressures), will be reduced and

the current flow through the lamp diminished, thus reducing the

brilliancy of the illumination. The effect may be intensified to such

degree by interposing an iron core in the coil as in fig. 2,676, as

to extinguish the lamp.]

=Ques. With respect to self-induction, what method should be followed

in wiring?=

Ans. When iron conduits are used, the wires of each circuit should

not be installed in separate conduits, because such arrangement will

cause excessive self-induction.

The importance of this may be seen from the experience of one

contractor, who installed feeders and mains in separate iron

pipes. When the current was turned on, it was found that the

self-induction was so great as to reduce the pressure to such an

extent that the lamps, instead of giving full candle power, were

barely red. This necessitated the removal of the feeders and main

and re-installing them, so that those of the same circuit were in

the same pipe.

=Ques. What is mutual induction?=

Ans. Mutual induction is the effect of one alternating current

circuit upon another.

[Illustration: FIG. 2,677.--Measurement of self induction when

the frequency is known. The apparatus required consists of a high

resistance or electrostatic a.c. voltmeter, d.c. ammeter, and a

non-inductive resistance. Connect the inductive resistance to be

measured as shown, and close switch M, short circuiting the ammeter.

Connect alternator in circuit and measure drop across R and across

X_{_i_}. Disconnect alternator and connect battery in circuit, then

open switch M and vary the continuous current until the drop across R

is the same as with the alternating current, both measurements being

made with the same voltmeter; read ammeter, and measure drop across

X_{_i_}. Call the drop across X_{_i_} with alternating current E, and

with direct current E_{_i_}, and the reading of the ammeter J. Then

____________________

L = √E^{2} + E_{_i_}^{2} ÷ 2π _f_ I. If the resistance X_{_i_}

be known, and the ammeter be suitable for use with alternating

current, the switch and R may be dispensed with.

______________________________

Then L = √E^{2} - X_{_i_}^{2} I_{_i_}^{2} ÷ 2π _f_ I,

where I_{_i_} is the value of the alternating current. The resistance

of the voltmeter should be high enough to render its current

negligible as compared with that through X_{_i_}.]

=Ques. How is it caused?=

Ans. It is due to the magnetic field surrounding a conductor cutting

adjacent conductors and inducing back pressures therein.

This effect as a rule in ordinary installations is negligible.

=Transpositions.=--The effect of mutual induction between two

circuits is proportional to the inter-linkage of the magnetic fluxes

of the two lines. This in turn depends upon the proximity of the

lines and upon the general relative arrangement of the conductors.

[Illustration: FIG. 2,678.--Transposition diagram for two parallel

lines consisting of two wires each.]

[Illustration: FIG. 2,679.--Transposition diagram for three phase,

three wire line, transposing at the vertices of an equilateral

triangle. The line is originally balanced and becomes unbalanced on

transposing, a procedure which should be resorted to only to prevent

_mutual induction_.]

[Illustration: FIG. 2,680.--Transposition diagram of three phase,

three wire line, with center arranged in a straight line.]

The inductive effect of one line upon another is equal to the

algebraic sum of the fluxes due to the different conductors of the

first line, considered separately, which link the secondary line.

The effect of mutual induction is to induce surges in the line where

a difference of frequency exists between the two currents, and to

induce high electrostatic charges in lines carrying little or no

current, such as telephone lines.

INDUCTANCE PER MILE OF THREE PHASE CIRCUIT

---------+-------+----------+------------

| Diam. | Distance | Self

Size | in | _d_ in | Inductance

B. & S. | inch. | inches. | L henrys.

---------+-------+----------+------------

0000 | .46 | 12 | .00234

| | 18 | .00256

| | 24 | .00270

| | 48 | .00312

| | |

000 | .41 | 12 | .00241

| | 18 | .00262

| | 24 | .00277

| | 48 | .00318

| | |

00 | .365 | 12 | .00248

| | 18 | .00269

| | 24 | .00285

| | 48 | .00330

| | |

0 | .325 | 12 | .00254

| | 18 | .00276

| | 24 | .00293

| | 48 | .00331

| | |

1 | .289 | 12 | .00260

| | 18 | .00281

| | 24 | .00308

| | 48 | .00338

| | |

2 | .258 | 12 | .00267

| | 18 | .00288

| | 24 | .00304

| | 48 | .00314

| | |

3 | .229 | 12 | .00274

| | 18 | .00294

| | 24 | .00310

| | 48 | .00351

| | |

4 | .204 | 12 | .00280

| | 18 | .00300

| | 24 | .00315

| | 48 | .00358

| | |

5 | .182 | 12 | .00286

| | 18 | .00307

| | 24 | .00323

| | 48 | .00356

| | |

6 | .162 | 12 | .00291

| | 18 | .00313

| | 24 | .00329

| | 48 | .00369

| | |

7 | .144 | 12 | .00298

| | 18 | .00310

| | 24 | .00336

| | 48 | .00377

| | |

8 | .128 | 12 | .00303

| | 18 | .00325

| | 24 | .00341

| | 48 | .00384

| | |

9 | .114 | 12 | .00310

| | 18 | .00332

| | 24 | .00348

| | 48 | .00389

| | |

10 | .102 | 12 | .00318

| | 18 | .00340

| | 24 | .00355

| | 48 | .00396

---------+-------+----------+------------

This effect may be nullified by separating the lines and by

transposing the wires of one of the lines so that the effect produced

in one section is opposed by that in another. Of two parallel lines

consisting of two wires each, one may be transposed to neutralize the

mutual inductance.

Fig. 2,678 shows this method. The length L' should be an even

factor of L so that to every section of the line transposed there

corresponds an opposing section.

[Illustration: FIG. 2,681.--Capacity effect in single phase

transmission line. The effect is the same as would be produced by

shunting across the line at each point an infinitesimal condenser

having a capacity equal to that of an infinitesimal length of

circuit. For the purpose of calculating the charging current, a very

simple and sufficiently accurate method is to determine the current

taken by a condenser having a capacity equal to that of the entire

line when charged to the pressure on the line at the generating end.

The effect of capacity of the line is to reduce the pressure drop,

that is, improve the regulation, and to decrease or increase the

power loss depending on the load and power factor of the receiver.]

[Illustration: FIG. 2,682.--Capacity effect in a three phase

transmission line. It is the same as would be produced by shunting

the line at each point by three infinitesimal condensers connected in

star with the neutral point grounded, the capacity of each condenser

being twice that of a condenser of infinitesimal length formed by

any two of the wires. The effect of capacity on the regulation and

efficiency of the line can be determined with sufficient accuracy

in most cases by considering the line shunted at each end by three

condensers connected in star, the capacity of each condenser being

equal to that formed by any two wires of the line. An approximate

value for the charging current per wire is the current required to

charge a condenser, equal in capacity to that of any two of the

wires, to the pressure at the generating end of the line between any

one wire and the neutral point.]

The self inductance of lines is readily calculated from the

following formula:

L = .000558 {2.303 log (2A ÷ _d_) + .25} per mile of circuit

where

L = inductance of a loop of a three phase circuit in henrys.

_Note._--The inductance of a complete single phase

circuit = L × 2 ÷ √3.

A = distance between wires;

_d_ = diameter of wire.

CAPACITY IN MICRO-FARADS PER MILE OF CIRCUIT

FOR THREE PHASE SYSTEM

---------+-------+----------+--------------

| Diam. | Distance | Capacity

Size | in | A in | C in

B. & S. | inch. | inches. | micro-farads

---------+-------+----------+--------------

0000 | .46 | 12 | .0226

| | 18 | .0204

| | 24 | .01922

| | 48 | .01474

| | |

000 | .41 | 12 | .0218

| | 18 | .01992

| | 24 | .01876

| | 48 | .01638

| | |

00 | .365 | 12 | .0124

| | 18 | .01946

| | 24 | .01832

| | 48 | .01604

| | |

0 | .325 | 12 | .02078

| | 18 | .01898

| | 24 | .01642

| | 48 | .01570

| | |

1 | .289 | 12 | .02022

| | 18 | .01952

| | 24 | .01748

| | 48 | .0154

| | |

2 | .258 | 12 | .01972

| | 18 | .01818

| | 24 | .01710

| | 48 | .01510

| | |

3 | .229 | 12 | .01938

| | 18 | .01766

| | 24 | .01672

| | 48 | .01480

| | |

4 | .204 | 12 | .01874

| | 18 | .01726

| | 24 | .01636

| | 48 | .01452

| | |

5 | .182 | 12 | .01830

| | 18 | .01690

| | 24 | .01602

| | 48 | .01426

| | |

6 | .162 | 12 | .01788

| | 18 | .01654

| | 24 | .01560

| | 48 | .0140

| | |

7 | .144 | 12 | .01746

| | 18 | .01618

| | 24 | .01538

| | 48 | .01374

| | |

8 | .128 | 12 | .01708

| | 18 | .01586

| | 24 | .01508

| | 48 | .01350

| | |

9 | .114 | 12 | .01660

| | 18 | .01552

| | 24 | .01478

| | 48 | .01326

| | |

10 | .102 | 12 | .01636

| | 18 | .01522

| | 24 | .01452

| | 48 | .01304

---------+-------+----------+--------------

=Capacity.=--In any given system of electrical conductors, a

pressure difference between two of them corresponds to the presence

of a quantity of electricity on each. With the same charges, the

difference of pressure may be varied by varying the geometrical

arrangement and magnitudes and also by introducing various

dielectrics. The constant connecting the charge and the resulting

pressure is called the capacity of the system.

All circuits have a certain capacity, because each conductor

acts like the plate of a condenser, and the insulating medium,

acts as the dielectric. The capacity depends upon the insulation.

For a given grade of insulation, the capacity is proportional

to the surface of the conductors, and universally to the distance

between them.

A three phase three wire transmission line spaced at the corners

of an equilateral triangle as regards capacity acts precisely

as though the neutral line were situated at the center of the

triangle.

The capacity of circuits is readily calculated by applying the

following formulae:

C = 38.83 sc 10^{-3} / log (D ÷ d) per mile,

insulated cable with lead sheath;

C = 38.83 × 10^{-3} / log (4h ÷ d) per mile,

single conductor with earth return;

C = 19.42 × 10^{-3} / log (2A ÷ d) per mile of

parallel conductors forming metallic circuit;

in which

C = Capacity in micro-farads; for a metallic circuit, C =

capacity between wires;

sc = Specific inductive capacity of insulating material; = 1 for

air, and 2.25 to 3.7 for rubber;

D = Inside diameter of lead sheath;

d = Diameter of conductor;

h = Distance of conductors above ground;

A = Distance between wires.

=Frequency.=--The number of cycles per second, or the frequency,

has a direct effect upon the inductance reactance in an alternating

current circuit, as is plainly seen from the formula.

X_{i} = 2π_f_L

In the case of a transmission line alone; the lower frequencies

are the more desirable, in that they tend to reduce the inductance

drop and charging current. The inductance drop is proportional to

the frequency.

The natural period of a line, with distributed inductance and

capacity, is approximately given by

__

P = 7,900 / √LC

where L is the total inductance in millihenrys, and C, the total

capacity in micro-farads. Accordingly some lower odd harmonic of

the impressed frequency may be present which corresponds with the

natural period of the line. When this obtains, oscillations of

dangerous magnitude may occur. Such coincidences are less likely

with the lower harmonics than with the higher.

=Skin Effect.=--The tendency of alternating current to confine itself

to the _outer_ portions of a conductor, instead of passing uniformly

through the cross section, is called _skin effect_. The effect is

proportional to the size of the conductor and the frequency.

=Ques. What effect has "skin effect" on the current?=

Ans. It is equivalent to an increase of ohmic resistance and

therefore opposes the current.

[Illustration: FIGS. 2,683 to 2,687.--Skin effect and shield effect.

Fig. 2,683, section of conductor illustrating skin effect or tendency

of the alternating current to distribute itself unequally through the

cross section of a conductor as shown by the varied shading, which

represents the current flowing most strongly in the outer portions

of the conductor. For this reason it has been proposed to use hollow

or flat instead of solid round conductors; however, with frequency

not exceeding 100, the skin effect is negligibly small in copper

conductors of the sizes usually employed. In figs. 2,684 and 2,685,

or 2,686 and 2,687, if two adjacent conductors be carrying current

in the same direction, concentration will occur on those parts of

the two conductors remote from one another, and the nearer parts

will have less current, that is to say, they will be =shielded=.

In this case, the induction due to one conductor will exert its

opposing effect to the greatest extent on those parts of the other

conductor nearest to it; this effect decreasing the deeper the latter

is penetrated. After crossing the current axis, the induction will

still decrease in magnitude, but will now aid the current in the

conductor. Hence, the effect of these two conductors on one another

will make the current density more uniform than is the case where

the two conductors adjacent to one another are carrying current in

opposite directions, as in figs. 2,685 and 2,686, therefore, the

resistance and the heating for a given current will be smaller. If

the two return conductors be situated on the line passing through

the center of the conductors just considered, the effect will be to

still further concentrate the current; the distribution symmetry will

be further disturbed, and the resistance of the conductor system

increased. It is therefore difficult to say which of the two cases

considered holds the advantage so far as increasing the resistance is

concerned. The case, however, in which the phases are mixed has much

the smaller reactive drop.]

If the conductor be large, or the frequency high, the central

portion of the conductor carries little if any current, hence the

resistance is therefore greater for alternating current than for

direct current.

=Ques. For what condition may "skin effect" be neglected?=

Ans. For frequencies of 60 or less, with conductors having a diameter

not greater than 0000 B. & S. gauge.

=Ques. How is the "skin effect" calculated for a given wire?=

Ans. Its area in circular mils multiplied by the frequency, gives the

ratio of the wire's ohmic resistance to its combined resistance.

That is to say, the factor thus obtained multiplied by the

resistance of the wire to direct current will give its combined

resistance or resistance to alternating current.

The following table gives these ratio factors for large

conductors.

RATIO FACTOR FOR COMBINED RESISTANCE

+---------------+---------+---------------+---------+

| Cir. mils. | Ratio | Cir. mils. | Ratio |

| × frequency | factor | × frequency | factor |

+---------------+---------+---------------+---------+

| 10,000,000 | 1.00 | 70,000,000 | 1.13 |

| 20,000,000 | 1.01 | 80,000,000 | 1.17 |

| 30,000,000 | 1.03 | 90,000,000 | 1.20 |

| 40,000,000 | 1.05 | 100,000,000 | 1.25 |

| 50,000,000 | 1.08 | 125,000,000 | 1.34 |

| 60,000,000 | 1.10 | 150,000,000 | 1.43 |

+---------------+---------+---------------+---------+

=Corona Effect.=--When two wires, having a great difference of

pressure are placed near each other, a certain phenomenon occurs,

which is called _corona effect_. When the spacing or distance

between the wires is small and the difference of pressure in the

wires very great, a continuous passage of energy takes place through

the dielectric or atmosphere, the amount of this energy may be an

appreciable percentage of the power transmitted. Therefore in laying

out high pressure transmission lines, this effect must be considered

in the spacing of the wires.

=Ques. How does the corona effect manifest itself?=

Ans. It is visible at night as a bluish luminous envelope and audible

as a hissing sound.

=Ques. What is the critical voltage?=

Ans. The voltage at which the corona effect loss takes place.

=Ques. Upon what does the critical voltage depend?=

Ans. Upon the radius of the wires, the spacing, and the atmospheric

conditions.

[Illustration: FIG. 2,688.--Electromagnetic and electrostatic

fields surrounding the conductors of a transmission line. The

electromagnetic field is represented by lines of magnetic force

that surround the conductors in circles, (the solid lines), and

the electrostatic field by (dotted) circles passing from conductor

to conductor across at right angles to the magnetic circles. For

any given size of wire and distance apart of wires there is a

certain voltage at which the critical density or critical gradient

is reached, where the air breaks down and luminosity begins--the

critical voltage where corona manifests itself. At still higher

voltages corona spreads to further distances from the conductor

and a greater volume of air becomes luminous. Incidentally, it

produces noise. Now to produce light requires power and to produce

noise requires power. Air is broken down and is heated in breaking

down, and to heat also requires power; therefore, as soon as corona

forms, power is consumed or dissipated in its formation. When this

phenomenon occurs on the conductors of an alternating current circuit

a change takes place in relation to current and voltage. On the

wires of an alternating current transmission line, at a voltage

below that where corona forms--at a voltage where wires are not

luminous--considerable current, more or less depending on voltage

and length of wire, flows into the circuit as capacity current or

charging current.]

The critical voltage increases with both the diameter of the

wires, and the spacing.

The losses due to corona effect increase very rapidly with

increasing pressure beyond the critical voltage.

The magnitude of the losses as well as the critical voltage is

affected, by atmospheric conditions, hence they probably vary with

the particular locality, and the season of the year. Therefore,

for a given locality, a voltage which is normally below the

critical point, may at times be above it, depending upon changes

in the weather.

Such elements as smoke, fog, moisture, or other particles (dust,

snow, etc.) floating in the air, increase the losses; rain,

however, apparently has no appreciable effect upon the losses.

It follows then that in the design of a transmission line, the

atmospheric conditions of the particular locality through which

the line passes should be considered.

=Ques. How should live wires be spaced?=

Ans. They should be so spaced as to lessen the tendency to leakage

and to prevent the wires swinging together or against towers. The

spacing should be only sufficient for safety, since increased spacing

increases the self-induction of the line, and while it lessens the

capacity, it does so only in a slight degree.

The following spacing is in accordance with average practice.

SPACING FOR VARIOUS VOLTAGES

+---------+----------+

| Volts | Spacing |

+---------+----------+

| 5,000 | 28 ins. |

| 15,000 | 40 ins. |

| 30,000 | 48 ins. |

| 45,000 | 60 ins. |

| 60,000 | 60 ins. |

| 75,000 | 84 ins. |

| 90,000 | 96 ins. |

| 105,000 | 108 ins. |

| 120,000 | 120 ins. |

+---------+----------+

=Resistance of Wires.=--For quick calculation the following method

of obtaining the resistance (approximately) of wires will be found

convenient:

1,000 feet No. 10 B. & S. wire, which is about .1 inch in diameter

(.1019), has a resistance of one ohm, at a temperature of 68° F. and

weighs 31.4 pounds. A wire three sizes larger, that is No. 7, has

twice the cross section and therefore one-half the resistance. A wire

three sizes smaller than No. 10, that is No. 13, has one-half the

cross section and therefore twice the resistance.

Thus, starting with No. 10, any number three sizes larger will double

the cross sectional area and any wire three sizes smaller will halve

the cross sectional area of the preceding wire. This is true to the

extreme limits of the table, so that the area, weight and resistance

of any wire may be at once calculated to a close approximation from

this rule, intermediate sizes being obtained by interpolation.

For alternating current, the combined resistance, that is, the total

resistance, including skin effect, is obtained by multiplying the

resistance, as found above by the "ratio factor" (see table page

1,894).

[Illustration: FIGS. 2,689 to 2,692.--Triangles for obtaining

graphically, impedance, impressed pressure, etc., in alternating

current circuits. For a full explanation of this method the reader is

referred to Guide 5, Chapter XLVII on Alternating Current Diagrams. A

thorough study of this chapter is recommended.]

=Impedance.=--_The total opposition to the flow of electricity in an

alternating current circuit_, or the impedance may be resolved into

two components representing the ohmic resistance and the spurious

resistance; these components have a phase difference of 90°, and

they may be represented graphically by the two legs of a right angle

triangle, of which the hypothenuse represents the impedance.

Similarly, the volts lost or "drop" in an alternating circuit may be

resolved into two components representing respectively

1. The loss due to resistance.

2. The loss due to reactance.

These components have a phase difference of 90° and are represented

graphically similar to the impedance components. This has been

explained at considerable length in Chapter XLVII (Guide V).

[Illustration: FIG. 2,693.--Mechanical analogy of power factor, as

exemplified by a locomotive "poling" a car off a siding. The car and

locomotive are shown moving in parallel directions, and the pole

AB, inclined at an angle ϕ. Now, if the length of AB be taken to

represent the pressure exerted on the pole by the locomotive, then

the imaginary lines AC and BC, drawn respectively parallel and at

right angles to the direction of motion will represent respectively

the useful and no energy (wattless) components; that is to say, if

the pressure AB be applied to the car at an angle ϕ, only part of it,

AC, is useful in propelling the car, the other component, BC, being

wasted in tending to push the car off the track at right angles to

the rails, being resisted by the flanges of the outer wheels.]

=Power Factor.=--When the current falls out of step with the

pressure, as on inductive loads, the power factor becomes less than

unity, and the effect is to increase the current required for a

given load. Accordingly, this must be considered in calculating the

size of the wires. As has been explained, the current flowing in

an alternating current circuit, as measured by an ammeter, can be

resolved into two components, representing respectively the _active

component_ and the _wattless component_ or idle current. These are

graphically represented by the two legs of a right triangle, of which

the hypothenuse represents the current measured by the ammeter.

This _apparent_ current, as is evident from the triangle, exceeds

the _active_ current and lags behind the pressure by an amount

represented by the angle ϕ between the hypothenuse and leg

representing the energy current as shown in fig. 2,694.

[Illustration: FIG. 2,694.--Diagram showing that the apparent current

is more than the active current, the excess depending upon the angle

of phase difference.]

[Illustration: FIG. 2,695.--Diagram showing components of impedance

volts. Compare this diagram with figs. 2,689 and 2,671, and note that

the term "reactance" is the difference between the inductance drop

and the capacity drop if the circuit contain capacity, for instance,

if inductance drop be 10 volts and capacity drop be 7 volts then

reactance 10-7 = 3 volts.]

=Ques. What determines the heating of the wires on alternating

current circuits with inductive loads?=

Ans. The apparent current, as represented by the hypothenuse of the

triangle in fig. 2,694.

=Ques. How is the apparent current obtained?=

Ans. Divide the true watts by the product of the power factor

multiplied by the voltage.

Example.--A certain circuit supplies 20 kw. to motors at 220

volts and .8 power factor. What is the apparent current?

true watts 20,000

Apparent Current = -------------------- = -------- = 113.6 amperes

power factor × volts .8 × 220

=Ques. What else, besides power factor, should be considered in

making wire calculations for motor circuits?=

Ans. The efficiency of the motor, and the heavy starting current.

The product of the efficiency of the motor multiplied by the

power factor gives the _apparent efficiency_, which governs the

size of the wires, apparatus, etc., necessary to feed the motors.

Allowance should be made for the heavy starting current required

for some motors to avoid undue drop.

TABLE OF APPROXIMATE AMPERES PER TERMINAL

FOR INDUCTION MOTORS

Column headings: A-110 volts B-220 volts C-440 volts D-550 volts

+-----+----------------+------------------+------------------------+

| | | Two phase | Three phase |

|Horse| Single phase | four wire | three wire |

|power+----+-----+-----+-----+-----+------+-----+-----+------+-----+

| | A | B | C | A | B | C | A | B | C | D |

+-----+----+-----+-----+-----+-----+------+-----+-----+------+-----+

| .5| 6.6| 3.4 | 1.8| 3.3 | 1.7 | .9 | 3.7 | 1.8 | 1 | |

| 1 | 14 | 7 | 3.5| 6.4 | 3.2 | 1.6 | 7.4 | 3.7 | 1.9 | |

| 2 | 24 | 12 | 6 | 11 | 5.7 | 2.9 | 13 | 6.6 | 3.3 | 2.5 |

| 3 | 34 | 17 | 8.5| 16 | 8.1 | 4.1 | 19 | 9.3 | 4.7 | 3.5 |

| 4 | 52 | 26 | 13 | 26 | 13 | 6.5 | 30 | 15 | 7.5 | 6 |

| 5 | 74 | 37 | 18.5| 38 | 19 | 9.5 | 44 | 22 | 11 | 9 |

| 10 | 94 | 47 | 23.5| 44 | 22 | 11 | 50 | 25 | 12.5 | 11 |

| 15 | | | | 66 | 33 | 16.5 | 76 | 38 | 19 | 16 |

| 20 | | | | 88 | 44 | 22 | 102 | 51 | 25.5 | 22 |

| 25 | | | | 111 | 55 | 28 | 129 | 64 | 32 | 25 |

| 30 | | | | 134 | 67 | 33.5 | 154 | 77 | 38.5 | 32 |

| 40 | | | | 178 | 89 | 44.5 | 204 | 107 | 53.5 | 44 |

| 50 | | | | 204 | 102 | 51 | 236 | 118 | 59 | 52 |

| 75 | | | | 308 | 154 | 77 | 356 | 178 | 89 | 77 |

| 100 | | | | 408 | 204 | 102 | 472 | 236 | 118 | 100 |

+-----+----+-----+-----+-----+-----+------+-----+-----+------+-----+

=Ques. What are the usual power factors encountered on commercial

circuits?=

Ans. A mixed load of incandescent lamps and induction motors will

have a power factor of from .8 to .85; induction motors above .8 to

.85; incandescent and Nernst lamps .98; arc lamps, .85.

=Wire Calculations.=--In the calculation of alternating current

circuits, the two chief factors which make the computation different

from that for direct current circuits, is _induction_ and _power

factor_. The first depends on the frequency, and physical condition

of the circuit, and the second upon the character of the load.

=Ques. Under what conditions may inductance be neglected?=

[Illustration: FIGS. 2,696 to 2,698.--Example of wiring showing where

inductance is negligible, and where it must be considered in wire

calculations.]

Ans. In cases where the wires of a circuit are not spaced over an

inch apart, or in conduit work, where both wires are in the same

conduit.

Under these conditions the calculation is the same as for direct

current after making proper allowance for power factor.

=Ques. Under what conditions must induction be considered?=

Ans. On exposed circuits with wires separated several inches,

particularly in the case of large wires.

=Sizes of Wire.=--The size of wire for any alternating circuit may be

determined by slightly modifying the formula used in direct current

work, and which, as derived in Guide No. 4, page 748, is

amperes × feet × 21.6

circular mils = --------------------- (1)

drop

The quantity 21.6, is twice the resistance (10.8) of a foot of

copper wire one mil in diameter (_mil foot_). This resistance

(10.8) is multiplied by 2, giving the quantity 21.6, because the

length of a circuit, or feet in the formula, is given as the "run"

or distance one way, that is, one-half the total length of wire in

the circuit, must be multiplied by 2 to get the total drop, viz.:

amperes × feet × 10.8 × 2 amperes × feet × 21.6

circular mils = ------------------------- = ---------------------

drop drop

It is sometimes however convenient to make the calculation in terms

of watts. Formula (1) may be modified for such calculation.

In modifying the formula, the "drop" should be expressed in

percentage instead of actual volts lost, that is, instead of the

difference in pressure between the beginning and the end of the

circuit.

In any circuit the loss in percentage, or

drop

% loss = ------------------ × 100

impressed pressure

from which

% loss × impressed pressure

drop = --------------------------- (2)

100

Substituting equation (2) in equation (1)

amperes × feet × 21.6

circular mils = -----------------------------

% loss × imp. pressure

------------------------

100

amperes × feet × 2,160

= -------------------------- (3)

% loss × imp. pressure

Equation (3) is modified for calculation in terms of watts as

follows: The power in watts is equal to the _applied voltage_

multiplied by the current, that is to say, the power is equal to

the _volts at the consumer's end of the circuit_ multiplied by the

current, or simply

watts = volts × amperes

from which

watts

amperes = ----- (4)

volts

[Illustration: FIGS. 2,699 to 2,703.--Stranded copper cables. For

conductors of large areas and in the smaller sizes where extra

flexibility is required it becomes necessary to employ stranded

cables made by grouping a number of wires together in either

concentric or rope form. The concentric cable as here illustrated is

formed by grouping six wires around a central wire thereby forming

a seven wire cable. The next step is the application in a reverse

direction of another layer of 12 wires and a nineteen wire cable is

produced. This is again increased by a third layer of eighteen wires

for a 37 wire cable and a fourth layer of 24 wires for a 61 wire

cable. Successive layers, each containing 6 more wires than that

preceding, may be applied until the desired capacity is obtained. The

cuts show sectional views of concentric cables each formed from No.

10 B. & S. gauge wires.]

Substituting this value for the current in equation (3) and

remembering that the pressure taken is the volts at the consumer's

end of the line

watts

----- × feet × 2,160

volts

circular mils = ---------------------

% loss × volts

watts × feet × 2,160

= -------------------- (5)

% loss × volts^{2}

This formula (5) applies to a direct current two wire circuit, and to

adapt it to any alternating current circuit it is only necessary to

use the letter M instead of the number 2,160, thus

watts × feet × M

circular mils = ------------------ (6)

% loss × volts^{2}

in which M is a coefficient which has various values according to the

kind of circuit and value of the power factor. These values are given

in the following table:

=VALUES OF M=

--------+-----------------------------------------------------------

| POWER FACTOR

SYSTEM +-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

| 1.00| .98| .95| .90| .85| .80| .75| .70| .65| .60

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Single |2,160|2,249|2,400|2,660|3,000|3,380|3,840|4,400|5,112|6,000

phase | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Two |1,080|1,125|1,200|1,330|1,500|1,690|1,920|2,200|2,556|3,000

phase | | | | | | | | | |

(4 wire)| | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Three |1,080|1,125|1,200|1,330|1,500|1,690|1,920|2,200|2,556|3,000

phase | | | | | | | | | |

(3 wire)| | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

NOTE.--The above table is calculated as

follows: For =single phase= M = 2,160 ÷ power

factor^{2} × 100; for =two phase= four wire, or

three phase three wire, M = ½ (2,160 ÷ power

factor^{2})× 100. Thus the value of M for a

single phase line with power factor .95 = 2,160 ÷

.95^{2} × 100 = 2,400.

It must be evident that when 2,160 is taken as the value of M,

formula (6) applies to a two wire direct current circuit and also to

a single phase alternating current circuit when the power factor is

unity.

In the table the value of M for any particular power factor is found

by dividing 2,160 by the square of that power factor for single phase

and twice the square of the power factor for two phase and three

phase.

=Ques. For a given load and voltage how do the wires of a single and

two phase system compare in size and weight, the power factor being

the same in each case?=

Ans. Since the two phase system is virtually two single phase

systems, the four wires of the two phase systems are half the size of

the two wires of the single phase system, and accordingly, the weight

is the same for either system.

=VALUES OF T=

+-------------------+--------------------------------------------+

| | POWER FACTOR |

| SYSTEM +--------+--------+--------+--------+--------+

| | 1.00 | .98 | .90 | .80 | .70 |

+-------------------+--------+--------+--------+--------+--------+

| Single phase | 1.00 | .98 | .90 | .80 | .70 |

+-------------------+--------+--------+--------+--------+--------+

| Two phase, 4 wire | 2.00 | 1.96 | 1.80 | 1.60 | 1.40 |

+-------------------+--------+--------+--------+--------+--------+

|Three phase, 3 wire| 1.73 | 1.70 | 1.55 | 1.38 | 1.21 |

+-------------------+--------+--------+--------+--------+--------+

NOTE.--This table is for finding the value

of the current in line, using the formula I =

W ÷ (E × T), in which I = current in line; E =

voltage between main conductors at receiving or

consumers' end; W = watts. For instance, what

is the current in a two phase line transmitting

1,000 watts at 550 volts, power factor .80? I =

1,000 ÷ (550 × 1.60) = 1.13.

=Ques. Since there is no saving in copper in using two phases, what

advantage has the two phase system over the one phase system?=

Ans. It is more desirable on power circuits, because two phase motors

are self-starting.

That is to say, the rotating magnetic field that can be

produced by a two phase current, permits an induction motor to

start without being equipped with any special phase splitting

devices which are necessary on single phase motors, because the

oscillating field produced by a single phase current does not

produce any torque on a squirrel cage armature at rest.

=Ques. For equal working conditions, what is the comparison between

the single, two and three phase system as to size and weight of

wires?=

Ans. Each wire of the three phase system is half the size of one of

the wires of the single phase system, hence the weight of copper

required for the three phase system is 75% of that required for the

single phase system. Since in the two phase system half of the load

is carried by each phase, each wire of the three phase system is the

same size as one of the wires of the two phase system, hence, the

copper required by the three phase system is 75% of that required by

the two phase system.

=MISCELLANEOUS FORMULÆ FOR COPPER WIRES=

Diameter squared = circular mils

Circular mils × .7854 = square mils

.000003027 × circular mils = pounds per foot

.003027 × circular mils = pounds per 1,000 feet

.0159847 × circular mils = pounds per mile

.003879 × square mils = pounds per 1,000 feet

.33033 ÷ circular mils = feet per pound

.0000002924 × circular mils = pounds per ohm

.342 ÷ circular mils = ohms per pound

.096585 × circular mils = feet per ohm

10.353568 ÷ circular mils = ohms per foot

Breaking weight of wire ÷ area = breaking weight per square inch.

Breaking weight per square inch × area = breaking weight of wire.

The weight of copper wire is 1-1/7 times the weight of iron wire of

same diameter.

EXAMPLE.--What size wires must be used on a single phase circuit

2,000 feet in length to supply 30 kw. at 220 volts with loss of

4%, the power factor being .9?

The formula for circular mils is

watts × feet × M

circular mils = ------------------ (1)

% loss × volts^{2}

Substituting the given values and the proper value of M from the

table, in (1)

30,000 × 2,000 × 2,660

circular mils = ---------------------- = 82,438

4 × 220^{2}

Referring to the accompanying table of the properties of copper

wire, the nearest _larger_ size wire is No. 1 B. & S. gauge having

an area of 83,690 circular mils.

=TABLE OF THE PROPERTIES OF COPPER WIRE=

Giving weights, length and resistances of wires of Matthiessen's

Standard Conductivity for both B. & S. G. (Brown & Sharpe Gauge)

and B. W. G. (Birmingham Wire Gauge) from Transactions October

1903, of the American Institute of Electrical Engineers.

__________________________________________________________________

| | |

Gauges. To the nearest fourth | | Length.|Resistance.

significant digit. | | |

_____________________________________| |________|_________

| | | | Weight. | |

| | Diameter. | Area. | Lbs. | Feet | Ohms per

| | | | per | per lb.|1,000 ft.

______|_______|___________|__________| 1,000 |________|__________

| | | | feet. | |

| | | Circular | | |

B.& S.| B.W.G.| Inches. | mils. | | | @ 68° F.

______|______ |___________|__________|_________|________|_________

| | | | | |

0000 | | 0.460 | 211,600 | 640.5 | 1.561 | .04893

| 0000 | 0.454 | 206,100 | 623.9 | 1.603 | .05023

| 000 | 0.425 | 180,600 | 546.8 | 1.829 | .05732

| | | | | |

000 | | 0.4096 | 167,800 | 508.0 | 1.969 | .06170

| 00 | 0.380 | 144,400 | 437.1 | 2.288 | .07170

00 | | 0.3648 | 133,100 | 402.8 | 2.482 | .07780

| | | | | |

| 0 | 0.340 | 115,600 | 349.9 | 2.858 | .08957

0 | | 0.3249 | 105,500 | 319.5 | 3.130 | .09811

| 1 | 0.3000 | 90,000 | 272.4 | 3.671 | .1150

| | | | | |

1 | | 0.2893 | 83,690 | 253.3 | 3.947 | .1237

| 2 | 0.2840 | 80,660 | 244.1 | 4.096 | .1284

| 3 | 0.2590 | 67,080 | 203.1 | 4.925 | .1543

| | | | | |

2 | | 0.2576 | 66,370 | 200.9 | 4.977 | .1560

| 4 | 0.2380 | 56,640 | 171.5 | 5.832 | .1828

3 | | 0.2294 | 52,630 | 159.3 | 6.276 | .1967

| | | | | |

| 5 | 0.2200 | 48,400 | 146.5 | 6.826 | .2139

4 | | 0.2043 | 41,740 | 126.4 | 7.914 | .2480

| 6 | 0.2030 | 41,210 | 124.7 | 8.017 | .2513

| | | | | |

5 | | 0.1819 | 33,100 |100.2 | 9.98 | .3128

| 7 | 0.1800 | 32,400 | 98.08 | 10.20 | .3196

| 8 | 0.1650 | 27,230 | 82.41 | 12.13 | .3803

| | | | | |

6 | | 0.1620 | 26,250 | 79.46 | 12.58 | .3944

| 9 | 0.1480 | 21,900 | 66.30 | 15.08 | .4727

7 | | 0.1443 | 20,820 | 63.02 | 15.87 | .4973

| | | | | |

| 10 | 0.1340 | 17,960 | 54.35 | 18.40 | .5766

8 | | 0.1285 | 16,510 | 49.98 | 20.01 | .6271

| 11 | 0.1200 | 14,400 | 43.59 | 22.94 | .7190

| | | | | |

9 | | 0.1144 | 13,090 | 39.63 | 25.23 | .7908

| 12 | 0.1090 | 11,880 | 35.96 | 27.81 | .8715

10 | | 0.1019 | 10,380 | 31.43 | 31.82 | .9972

| | | | | |

| 13 | 0.0950 | 9,025 | 27.32 | 36.60 | 1.147

11 | | 0.09074 | 8,234 | 24.93 | 40.12 | 1.257

| 14 | 0.08300 | 6,889 | 20.85 | 47.95 | 1.503

| | | | | |

12 | | 0.08081 | 6,530 | 19.77 | 50.59 | 1.586

| 15 | 0.07200 | 5,184 | 15.69 | 63.73 | 1.997

13 | | 0.07196 | 5,178 | 15.68 | 63.79 | 1.999

| | | | | |

| 16 | 0.06500 | 4,225 | 12.79 | 78.19 | 2.451

14 | | 0.06408 | 4,107 | 12.43 | 80.44 | 2.521

| 17 | 0.0580 | 3,364 | 10.18 | 98.23 | 3.078

| | | | | |

15 | | 0.05707 | 3,257 | 9.858 | 101.4 | 3.179

16 | | 0.05082 | 2,583 | 7.818 | 127.9 | 4.009

| 18 | 0.04900 | 2,401 | 7.268 | 137.6 | 4.312

| | | | | |

17 | | 0.045260 | 2,048 | 6.200 | 161.3 | 5.055

| 19 | 0.042000 | 1,764 | 5.340 | 187.3 | 5.870

18 | | 0.040300 | 1,624 | 4.917 | 203.4 | 6.374

| | | | | |

19 | | 0.035890 | 1,288 | 3.899 | 256.5 | 8.038

| 20 | 0.035000 | 1,225 | 3.708 | 269.7 | 8.452

| 21 | 0.032000 | 1,024 | 3.100 | 322.6 | 10.11

| | | | | |

20 | | 0.031960 | 1,022 | 3.092 | 323.4 | 10.14

21 | | 0.028460 | 810.1 | 2.452 | 407.8 | 12.78

| 22 | 0.028000 | 784.0 | 2.373 | 421.4 | 13.21

22 | | 0.025350 | 642.4 | 1.945 | 514.2 | 16.12

| 23 | 0.025000 | 625.0 | 1.892 | 528.6 | 16.57

23 | | 0.022570 | 509.5 | 1.542 | 648.4 | 20.32

| | | | | |

| 24 | 0.022000 | 484.0 | 1.465 | 682.6 | 21.39

24 | | 0.020100 | 404.0 | 1.223 | 817.6 | 25.63

| 25 | 0.020000 | 400.0 | 1.211 | 825.9 | 25.88

| | | | | |

| 26 | 0.018000 | 324.0 | .9808 | 1,020 | 31.96

25 | | 0.017900 | 320.4 | .9699 | 1,031 | 32.31

| 27 | 0.016000 | 256.0 | .7749 | 1,290 | 40.45

| | | | | |

26 | | 0.015940 | 254.1 | .7692 | 1,300 | 40.75

27 | | 0.014200 | 201.5 | .6100 | 1,639 | 51.38

| 28 | 0.014000 | 196.0 | .5933 | 1,685 | 52.83

| | | | | |

| 29 | 0.013000 | 169.0 | .5116 | 1,955 | 61.27

28 | | 0.012640 | 159.8 | .4837 | 2,067 | 64.79

| 30 | 0.012000 | 144.0 | .4359 | 2,294 | 71.90

| | | | | |

29 | | 0.011260 | 126.7 | .3836 | 2,607 | 81.70

30 | | 0.010030 | 100.5 | .3042 | 3,287 | 103.0

| 31 | 0.010000 | 100.0 | .3027 | 3,304 | 103.5

| | | | | |

| 32 | 0.009000 | 81.0 | .2452 | 4,078 | 127.8

31 | | 0.008928 | 79.70 | .2413 | 4,145 | 129.9

| 33 | 0.008000 | 64.0 | .1937 | 5,162 | 161.8

| | | | | |

32 | | 0.007950 | 63.21 | .1913 | 5,227 | 163.8

33 | | 0.007080 | 50.13 | .1517 | 6,591 | 206.6

| 34 | 0.007000 | 49.0 | .1483 | 6,742 | 211.3

| | | | | |

34 | | 0.006305 | 39.75 | .1203 | 8,311 | 260.5

35 | | 0.005615 | 31.52 | .09543 |10,480 | 328.4

36 | 35 | 0.005000 | 25.0 | .07568 |13,210 | 414.2

| | | | | |

37 | | 0.004453 | 19.83 | .06001 |16,660 | 522.2

| 36 | 0.004000 | 16. | .04843 |20,650 | 647.1

38 | | 0.003965 | 15.72 | .04759 |21,010 | 658.5

| | | | | |

39 | | 0.003531 | 12.47 | .03774 |26,500 | 830.4

40 | | 0.003145 | 9.888 | .02993 |33,410 |1047.

--------------------------------------------------------------------

=Drop.=--In order to determine the drop or volts lost in the line,

the following formula may be used

drop = ((% loss × volts) / 100) × S (1)

in which the % loss is a percentage of the applied power, that is,

the power delivered to the consumer and not a percentage of the power

at the alternator. "Volts" is the pressure at the consumer's end of

the circuit.

=VALUE OF "S" FOR 60 CYCLES=

-----------------+------------------------+------------------------+

| .98 power factor | .90 power factor |

--------+--------+------------------------+------------------------+

Size of | Area | Spacing of | Spacing of |

wire | in | conductors | conductors |

B.&S. |circular| | |

gauge | mils. | | |

| +----+----+----+----+----+----+----+----+----+----+

| | 1" | 3" | 6" | 12"| 24"| 1" | 3" | 6" | 12"| 24"|

--------+--------+----+----+----+----+----+----+----+----+----+----+

500,000 |500,000 |1.21|1.45|1.61|1.77|1.92|1.32|1.80|2.11|2.44|2.75|

300,000 |300,000 |1.15|1.29|1.38|1.48|1.57|1.19|1.47|1.66|1.84|2.02|

0,000 |211,600 |1.12|1.22|1.28|1.34|1.41|1.13|1.33|1.45|1.58|1.63|

000 |167,800 |1.09|1.18|1.22|1.28|1.29|1.08|1.23|1.33|1.44|1.53|

00 |133,100 |1.07|1.14|1.18|1.21|1.25|1.03|1.16|1.24|1.32|1.40|

0 |105,500 |1.05|1.10|1.14|1.17|1.20|1.00|1.09|1.16|1.22|1.28|

1 | 83,690 |1.04|1.08|1.10|1.13|1.15|1.00|1.05|1.09|1.14|1.19|

2 | 66,370 |1.02|1.05|1.08|1.10|1.12|1.00|1.00|1.04|1.08|1.12|

3 | 52,630 |1.02|1.04|1.06|1.07|1.09|1.00|1.00|1.00|1.03|1.06|

| | | | | | | | | | | |

4 | 41,740}|1.00|1.02|1.03|1.04|1.07|1.00|1.00|1.00|1.00|1.00|

5 | 33,100}| | | | | | | | | | |

| | | | | | | | | | | |

6 | 26,250}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

7 | 20,820}| | | | | | | | | | |

| | | | | | | | | | | |

8 | 16,510}| | | | | | | | | | |

9 | 13,090}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

10 | 10,380}| | | | | | | | | | |

--------+--------+----+----+----+----+----+----+----+----+----+----+

--------+--------+----+----+----+----+----+----+----+----+----+----+

Size | | .80 power factor | .70 power factor |

of | Area +------------------------+------------------------+

wire | in | Spacing of | Spacing of |

B.&S. |circular| conductors | conductors |

gauge | mils. +----+----+----+----+----+----+----+----+----+----+

| | 1" | 3" | 6" | 12"| 24"| 1" | 3" | 6" | 12"| 24"|

--------+--------+----+----+----+----+----+----+----+----+----+----+

500,000 | 500,000|1.27|1.89|2.25|2.64|3.03|1.14|1.72|2.12|2.53|2.92|

300,000 | 300,000|1.11|1.46|1.68|1.90|2.12|1.00|1.33|1.56|1.78|2.01|

0,000 | 211,600|1.03|1.27|1.43|1.58|1.75|1.00|1.14|1.29|1.45|1.69|

000 | 167,800|1.00|1.16|1.28|1.41|1.53|1.00|1.02|1.15|1.28|1.50|

00 | 133,100|1.00|1.07|1.15|1.22|1.00|1.00|1.00|1.03|1.13|1.21|

0 | 105,500|1.00|1.00|1.07|1.15|1.00|1.00|1.00|1.00|1.01|1.09|

1 | 83,690}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

2 | 66,370}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

3 | 52,630}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

| | | | | | | | | | | |

4 | 41,740}| | | | | | | | | | |

5 | 33,100}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

| | | | | | | | | | | |

6 | 26,250}| | | | | | | | | | |

7 | 20,820}| | | | | | | | | | |

| | | | | | | | | | | |

8 | 16,510}| | | | | | | | | | |

9 | 13,090}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

10 | 10,380}| | | | | | | | | | |

--------+--------+----+----+----+----+----+----+----+----+----+----+

The coefficient S has various values as given in the accompanying

tables. As will be seen from the table, the value of S to be used

depends upon the size of wire, spacing, power factor and frequency.

These values are accurate enough for all practical purposes, and may

be used for distances of 20 miles or less and for voltages up to

25,000.

The capacity effect on very long high voltage lines, makes this

method of determining the drop somewhat inaccurate beyond the limits

above mentioned.

=VALUE OF "S" FOR 25 CYCLES=

---------+--------+------------------------+------------------------+

Size | | .98 power factor | .90 power factor |

of | Area +------------------------+------------------------+

wire | in | Spacing of | Spacing of |

B.&S. |circular| conductors | conductors |

gauge | mils. +----+----+----+----+----+----+----+----+----+----+

| | 1" | 2" | 6" | 12"| 24"| 1" | 3" | 6" | 12"| 24"|

---------+--------+----+----+----+----+----+----+----+----+----+----+

500,000 |500,000 |1.01|1.17|1.23|1.29|1.36|1.02|1.22|1.35|1.43|1.61|

300,000 |300,000 |1.04|1.10|1.13|1.18|1.21|1.00|1.08|1.16|1.25|1.31|

0,000 |211,600 |1.03|1.07|1.09|1.11|1.14|1.00|1.02|1.07|1.13|1.15|

000 |167,800 |1.00|1.05|1.06|1.09|1.10|1.00|1.00|1.02|1.07|1.11|

00 |133,100 |1.00|1.03|1.05|1.06|1.08|1.00|1.00|1.00|1.02|1.05|

0 |105,500 |1.00|1.01|1.02|1.03|1.04|1.00|1.00|1.00|1.00|1.00|

| | | | | | | | | | | |

1 | 83,690}| | | | | | | | | | |

2 | 66,370}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

3 | 52,630}| | | | | | | | | | |

| | | | | | | | | | | |

4 | 41,740}| | | | | | | | | | |

5 | 33,100}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

6 | 26,250}| | | | | | | | | | |

| | | | | | | | | | | |

7 | 20,820}| | | | | | | | | | |

8 | 16,510}| | | | | | | | | | |

9 | 13,090}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

10 | 10,380}| | | | | | | | | | |

---------+--------+----+----+----+----+----+----+----+----+----+----+

Size | | .80 power factor | .70 power factor |

of | Area +------------------------+------------------------+

wire | in | Spacing of | Spacing of |

B.&S. |circular| conductors | conductors |

gauge | mils. +----+----+----+----+----+----+----+----+----+----+

| | 1" | 3" | 6" | 12"| 24"| 1" | 3" | 6" | 12"| 24"|

---------+--------+----+----+----+----+----+----+----+----+----+----+

500,000 | 500,000|1.00|1.15|1.30|1.47|1.62|1.00|1.00|1.16|1.33|1.49|

300,000 | 300,000|1.00|1.00|1.09|1.16|1.25|1.00|1.00|1.00|1.02|1.12|

0,000 | 211,600|1.00|1.00|1.00|1.03|1.10|1.00|1.00|1.00|1.00|1.00|

000 | 167,800|1.00|1.00|1.00|1.00|1.01|1.00|1.00|1.00|1.00|1.00|

00 | 133,100|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

0 | 105,500|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

| | | | | | | | | | | |

1 | 83,690}| | | | | | | | | | |

2 | 66,370}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

3 | 52,630}| | | | | | | | | | |

| | | | | | | | | | | |

4 | 41,740}| | | | | | | | | | |

5 | 33,100}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

6 | 26,250}| | | | | | | | | | |

| | | | | | | | | | | |

7 | 20,820}| | | | | | | | | | |

8 | 16,510}| | | | | | | | | | |

9 | 13,090}|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|1.00|

10 | 10,380}| | | | | | | | | | |

---------+--------+----+----+----+----+----+----+----+----+----+----+

EXAMPLE.--A circuit supplying current at 440 volts, 60

frequency, with 5% loss and .8 power factor is composed of No. 2

B. & S. gauge wires spaced one foot apart. What is the drop in the

line?

According to the formula

% loss × volts

drop = -------------- × S

100

Substituting the given values, and value of S as obtained from

the table for frequency 60

5 × 440

drop = ------- × 1 = 22 volts

100

=Current=.--As has been stated, the effect of power factor less than

unity, is to increase the current; hence, in inductive circuit

calculations, the first step is to determine the current flowing in a

circuit. This is done as follows:

apparent load

current = ------------- (1)

volts

and

watts

apparent load = ------------ (2)

power factor

Substituting (2) in (1)

watts

------------

power factor watts

current = ------------ = --------------------- (3)

volts power factor × volts

[Illustration: FIG. 2,704.--Rope type of stranded copper cable

which is used when a high degree of flexibility is required. The

construction of this cable is the stranding together of seven groups,

each containing seven wires and producing a total of 49 wires.

In cases when a greater carrying capacity is desired than can be

obtained through the use of the 7 × 7 or 49 wire cable, the number of

groups is increased to nineteen thereby making a total of 133 wires

(19 × 7).]

EXAMPLE.--A 50 horse power 440 volt motor has a full load

efficiency of .9 and power factor of .8. How much current is

required?

Since the brake horse power of the motor is given, it is

necessary to obtain the electrical horse power, thus

brake horse power 50

E.H.P. = ----------------- = -- = 55.5

efficiency .9

which in watts is

55.5 × 746 = 41,403

which is the actual load, and from which

actual load 41,403

apparent load = ------------ = ------ = 51,754

power factor .8

The current therefore at 440 volts is

apparent load 51,754

------------- = ------ = 117.6 amperes

volts 440

EXAMPLE.--A 50 horse power single phase 440 volt motor, having

a full load efficiency of .92 and power factor of .8, is to be

operated at a distance of 1,000 feet from the alternator. The

wires are to be spaced 6 inches apart and the frequency is 60, and

% loss 5. Determine: =A=, _electrical horse power_; =B=, _watts_;

=C=, _apparent load_; =D=, _current_; =E=, _size of wires_; =F=,

_drop_; =G=, _voltage at the alternator_.

=A=. _Electrical horse power_

brake horse power 50

E. H. P. = ----------------- × --- = 54.3

efficiency .92

or,

54.3 × 746 = 40,508 watts

=TABLE OF WIRE EQUIVALENTS=

(Brown and Sharpe gauge)

------+--------+--------+--------+---------+---------+---------

0000 | 2 # 0 | 4 # 3 | 8 # 6 | 16 # 9 | 32 # 12 | 64 # 15

000 | 2 " 1 | 4 " 4 | 8 " 7 | 16 " 10 | 32 " 13 | 64 " 16

00 | 2 " 2 | 4 " 5 | 8 " 8 | 16 " 11 | 32 " 14 | 64 " 17

0 | 2 " 3 | 4 " 6 | 8 " 9 | 16 " 12 | 32 " 15 | 64 " 18

1 | 2 " 4 | 4 " 7 | 8 " 10 | 16 " 13 | 32 " 16 | 64 " 19

2 | 2 " 5 | 4 " 8 | 8 " 11 | 16 " 14 | 32 " 17 | 64 " 20

3 | 2 " 6 | 4 " 9 | 8 " 12 | 16 " 15 | 32 " 18 | 64 " 21

4 | 2 " 7 | 4 " 10 | 8 " 13 | 16 " 16 | 32 " 19 | 64 " 22

5 | 2 " 8 | 4 " 11 | 8 " 14 | 16 " 17 | 32 " 20 | 64 " 23

6 | 2 " 9 | 4 " 12 | 8 " 15 | 16 " 18 | 32 " 21 | 64 " 24

7 | 2 " 10 | 4 " 13 | 8 " 16 | 16 " 19 | 32 " 22 | 64 " 25

8 | 2 " 11 | 4 " 14 | 8 " 17 | 16 " 20 | 32 " 23 | 64 " 26

9 | 2 " 12 | 4 " 15 | 8 " 18 | 16 " 21 | 32 " 24 | 64 " 27

10 | 2 " 13 | 4 " 16 | 8 " 19 | 16 " 22 | 32 " 25 | 64 " 28

11 | 2 " 14 | 4 " 17 | 8 " 20 | 16 " 23 | 32 " 26 | 64 " 29

12 | 2 " 15 | 4 " 18 | 8 " 21 | 16 " 24 | 32 " 27 | 64 " 30

13 | 2 " 16 | 4 " 19 | 8 " 22 | 16 " 25 | 32 " 28 |

14 | 2 " 17 | 4 " 20 | 8 " 23 | 16 " 26 | 32 " 29 |

15 | 2 " 18 | 4 " 21 | 8 " 24 | 16 " 27 | 32 " 30 |

16 | 2 " 19 | 4 " 22 | 8 " 25 | 16 " 28 | |

17 | 2 " 20 | 4 " 23 | 8 " 26 | 16 " 29 | |

18 | 2 " 21 | 4 " 24 | 8 " 27 | 16 " 30 | |

19 | 2 " 22 | 4 " 25 | 8 " 28 | | |

20 | 2 " 23 | 4 " 26 | 8 " 29 | | |

21 | 2 " 24 | 4 " 27 | 8 " 30 | | |

------+--------+--------+--------+---------+---------+---------

=B.= _Watts_

watts = E.H.P. × 746 = 54.3 × 746 = 40,508

=C.= _Apparent load_

apparent load or kva = (actual load or watts ÷ power factor)

= 40,508 ÷ .8 = 50,635

=D.= _Current_

current = (apparent load or kva ÷ volts)

= 50,635 ÷ 440

= 115 amperes

=E.= _Size of wires_

cir. mils = (watts × feet × M) ÷ (% loss × volts^{2})

= (40,508 × 1,000 × 3,380) ÷ (5 × 440^{2})

= 141,443

From table page 1,907, nearest size _larger_ wire is No. 00 B.&S.

gauge.

=F.= _Drop_

drop = ((% loss × volts) ÷ 100) × S

= ((5 × 440) ÷ 100) × 1.17

= 25.74 volts

NOTE.--Values of S are given on page 1910.

=G.= _Voltage at alternator_

alternator pressure = (volts at motor + drop)

= 440 + 25.74

= 465.7 volts.

Hawkins Electrical Guide v. 08 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 3 / 6 章