CHAPTER LXIV

SWITCHBOARDS

=General Principles of Switchboard Connections.=--The interconnection

of generators, transformers, lines, bus bars, and switches with

their relays, in modern switchboard practice is shown by the

diagrams, figs. 2,636 to 2,645. The figures being lettered A to J

for simplicity, the generators are indicated by black discs, and the

switches by open circles, while each heavy line represents a set of

bus bars consisting of two or more bus bars according to the system

of distribution. It will be understood, also, in this connection,

that the number of pole of the switches and the type of switch will

depend upon the particular system of distribution employed.

Diagram A, shows the simplest system, or one in which a single

generator feeds directly into the line. There are no transformers

or bus bars and only one switch is sufficient.

In B, a single generator supplies two or more feeders through a

single set of bus bars, requiring a switch for each feeder, and a

single generator switch.

In C, two generators are employed and required and the addition

of a bus section switch.

D, represents a number of generators supplying two independent

circuits. The additional set of bus bars employed for this purpose

necessitates an additional bus section switch, and also additional

selector switches for both feeders and generators.

E, shows a standard system of connection for a city street

railway system having a large number of feeders.

[Illustration: FIGS. 2,645 and 2,646.--Diagrams illustrating general

principles of switchboard connections.]

This arrangement allows any group of feeders to be supplied from

any group of generators.

[Illustration: FIG. 2,646.--Fort Wayne switchboard panel for one

alternator and one transfer circuit. Diagram giving dimensions,

arrangement of instruments of board, and method of wiring. The

different forms of standard alternating current switchboard panels

for single phase circuits made by the Fort Wayne Electric Works are

designed to fulfill all the usual requirements of switchboards for

this class of work. The line includes panels equipped for a single

generator; for one generator and two circuits; one generator and one

transfer circuit; one generator, an incandescent and an arc lighting

circuit; and also feeder panels of different kinds.]

It also permits the addition of a generator switch for each

generator.

F, represents the simplest system with transformers.

It requires a single generator transformer bank, switch and

line. The arrangement as show at F is used where a number of

plants supply the same system.

G, represents a system having more than one line.

In this case a bus bar and transformer switch is used on the

high tension side.

H, shows a number of generators connected to a set of low

tension bus bars through generator switches, and employing a low

tension transformer switch.

I, shows the connections of a system having a large number of

feeders supplied by several small generators. In this case, the

plant is divided into two parts, each of which may be operated

independently.

[Illustration: FIG. 2,647.--General Electric =small plant alternating

current switchboard=, _designed for use in small central stations and

isolated plants_. They are for use with one set of bus bars, to which

all generators and feeders are connected by means of single throw

lever switches or circuit breakers, suitable provision being made for

the parallel operation of the generators.]

J, represents the arrangement usually employed in modern plants

where the generator capacity is large enough to permit of a

generator transformer unit combination with two outgoing lines. By

operating in parallel on the high tension side only, any generator

can be run with any transformer. The whole plant can be run in

parallel, or the two parts can be run separately.

[Illustration: FIG. 2,648.--Crouse-Hinds =voltmeter and ground

detector radial switch=, arranged for mounting on the switchboard.

The switch proper is placed on the rear of the board with hand wheel,

dial, and indicator only on the front side. The current carrying

parts are of hard brass, with contact surfaces machined after

assembling. The contact parts are of the plunger spring type, and the

cross bar has fuse connections. Ground detector circuits are marked

G+ and G- for two wire system, and G+, G-, GN+ and GN- for three wire

system. When the voltmeter switch is to be used as a ground detector,

two circuits are required for a two wire system, and four circuits

for a three wire system, that is, a six circuit voltmeter and ground

detector switch for use on a two wire system has two circuits for

ground detector and four circuits for voltmeter readings. A six

circuit voltmeter and ground detector switch, for use on a three wire

system, has four circuits for ground detector and two circuits for

voltmeter readings.]

=Switchboard Panels.=--The term "panel" means the slab of marble or

slate upon which is mounted the switches, and the indicating and

controlling devices. There are usually several panels comprising

switchboards of moderate or large size, these panels being classified

according to the division of the system that they control, as for

instance:

1. Generator panel;

2. Feeder panel;

3. Regulator panel, etc.

In construction, the marble or slate should be free from

metallic veins, and for pressures above, say, 600 volts, live

connections, terminals, etc., should preferably be insulated from

the panels by ebonite, mica, or removed from them altogether, as

is generally the case with the alternating gear where the switches

are of the oil type.

[Illustration: FIGS. 2,649 and 2,650,--Wiring diagrams of

Crouse-Hinds voltmeter and ground detector switches. Fig. 2,649

voltmeter switch; fig. 2,650 voltmeter and ground detector switch. A

view of the switch is shown in fig. 2,648; it is designed for use on

two or three wire systems up to 300 volts.]

The bus bars and connections should be supported by the

framework at the back of the board, or in separate cells, and the

instruments should be operated at low pressure through instrument

transformers.

The panels are generally held in position by bolting them to an

angle iron, or a strip iron framework behind them.

=Generator Panel.=--This section of a switchboard carries the

instruments and apparatus for measuring and electrically controlling

the generators. On a well designed switchboard each generator has, as

a rule, its own panel.

[Illustration: FIGS. 2,651 to 2,653.--Diagrams of connections for

generator panels. =Key to symbols=: =A=, ammeter; =A.S.=, ammeter

switch; =C.T.=, current transformer; =F.=, fuse; =F.A.=, direct

current field ammeter; =F.S.=, field switch; =G.C.S.=, governor

control switch; =L.S.=, limit switch (included with governor motor);

=O.S.=, oil switch; =P.I.W.=, polyphase indicating wattmeter;

=P.W.M.=, polyphase watthour meter; =P.R.=, pressure receptacle;

=P.P.=, pressure plug; =Rheo.=, rheostat; =S.=, shunt; =S.R.=,

synchronizing receptacle; =S.P.=, synchronizing plugs; =T.B.=,

terminal board for instrument leads; =V=, alternating current

voltmeter.]

[Illustration: FIGS. 2,654 and 2,655.--Diagrams illustrating =a

simple method of determining bus capacity= as suggested by the

General Electric Co. Fig. 2,654 relates to any panel; the method is

as follows: =1.= Make a rough plan of the _entire board_, regardless

of the number of panels to be ordered. _The order of panels_

shown is recommended, it being most economical of copper and best

adapted to future extensions. =2.= To avoid confusion keep on one

side of board everything pertaining to exciter buses, and on other

side everything pertaining to A. C. buses. =3.= With single lines

represent the exciter and A. C. buses across such panels as they

actually extend and by means of arrows indicate that portion of each

bus which is connected to feeders and that portion which is connected

to generators. _Remember that "Generator" and "Feeder" arrows must

always point toward each other_, otherwise the rules given below do

not hold. Note also that the field circuits of alternator panels are

treated as D. C. feeders for the exciter bus. =4.= On each panel

mark its ampere rating, that is, the maximum current it supplies

to or takes from the bus. For A. C. alternator panels the D. C.

rating is the excitation of the machines. =5.= Apply the following

rules _consecutively_, and note their application in fig. 2,654.

(For the sake of clearness ampere ratings are shown in light face

type and bus capacities in large type.) =A.= _Always begin with the

tail of the arrow and treat "generator" and "feeder" sections of

the bus separately._ =B.= _Bus capacity for first panel = ampere

rating of panel._ =C.= _Bus capacity for each succeeding panel =

ampere rating of panel plus bus capacity for preceding panel._ (See

sums marked above the buses in fig. 2,654.) =D.= _For a panel not

connected to a bus extending across it, use the smaller value of

the bus capacities already obtained for the two adjoining panels._

(See exciter bus for panel C.) =E.= _The bus capacity for any feeder

panel need not exceed the maximum for the generator panels_ (see A.

C. bus for panel G) _and vice versa_ (see exciter bus for panel B).

Hence the corrections made in values obtained by applying rules =B=

and =C=. The arrangement of panels shown in fig. 2,654 is the one

which is mostly used. The above method may, however, be applied to

other arrangements, one of which is shown in fig. 2,655. Here the

generators must feed both ways to the feeders at either end of the

board so that in determining A. C. bus capacities it is necessary to

first consider the generators with the feeders at one end, and then

with the feeders at the other end as shown by the dotted A. C. buses.

The required bus capacities are then obtained by taking the maximum

values for the two cases.]

[Illustration: FIG. 2,656.--End view showing =general arrangement of

switchboards= for 240, 480, and 600 volt alternating current. The cut

shows a single throw oil switch mounted on the panel.]

In the case of a dynamo, a good representative panel would have

mounted upon it a reverse current circuit breaker, an ammeter, a

double pole main switch (or perhaps a single pole switch, since

the circuit breaker could also be used as a switch) a double pole

socket into which a plug could be inserted to make connection with

a voltmeter mounted on a swinging bracket at the end of the board;

a rheostat handle, the spindle of which operates the shunt rheostat

of the machine, the rheostat being placed either directly behind

the spindle, if of small size, or lower down with chain drive from

the hand wheel spindle, if of larger size, a field discharge switch

and resistance, a lamp near the top of the panel for illuminating

purposes, a fuse for the voltmeter socket, and, if desired, a

watthour meter. If the dynamo be compound wound, the equalizing

switch will generally be mounted on the frame of the machine, and in

some cases the field rheostat will be operated from a pillar mounted

in front of the switchboard gallery. If the generator be for traction

purposes, the circuit breaker is more often of the maximum current

type, and a lightning arrester is often added, without a choke coil,

the latter as well as further lightning arresters being mounted on

the feeder panels.

[Illustration: FIGS. 2,657 and 2,658.--Two views of a =feeder panel=,

showing general arrangement of the devices assembled thereon. A,

circuit breaker; B, ammeter; C, voltmeter; D, switches.]

In the case of a high pressure alternating current plant of

considerable size, the bus bars oil switches, and the current and

pressure transformers are generally mounted either in stoneware

cells, or built on a framework in a space guarded by expanded metal

walls, and no high pressure apparatus of any sort is brought on to

the panels themselves.

[Illustration: FIGS. 2,659 to 2,666.--Diagram of connections for

three phase feeder panels. =Key to symbols=: A, ammeter; A.S.,

three way ammeter switch; B.A.S., bell alarm switch; C.T., current

transformer; F, fuse; O.S., oil switch; P.I.W., polyphase indicating

wattmeter; P.W.M., polyphase watthour meter; T.B., terminal board;

T.C., trip coils for oil switch.]

=Feeder Panel.=--The indicating and control apparatus for a feeder

circuit is assembled on a panel called the feeder panel.

The most common equipment in the case of a direct current feeder

panel comprises an ammeter, a double pole switch, and double pole

fuses or instead of the fuses, a circuit breaker on one or both

poles; in the case of a traction feeder a choke coil and a lightning

arrester are often added.

[Illustration: FIGS. 2,667 and 2,668.--Diagrams of connections for

two phase and three phase installations: A and A1, ammeter; C.C.,

constant current transformer; C.T., current transformer; D.R.,

discharge resistance; F, fuse; F.S., field switch; L.A., lightning

arrester; O.S., oil switch; P.P., pressure plug; P.R., pressure

receptacle; P.T., pressure transformer; S and S1, plug switches;

T.C., oil switch trip coil; V, voltmeter.]

The equipment of a typical high pressure three phase feeder panel is

an ammeter (sometimes three ammeters, one in each phase) operated

by a current transformer, and oil break switch with two overload

release coils, or three if the neutral of the circuit be earthed, the

releases being operated by current transformers.

[Illustration: FIG. 2,669.--Crouse-Hinds radial ammeter switch,

arranged for mounting directly on the switchboard. It is designed

for use with external shunt ammeters of any make or capacity, and in

connection with the required number of shunts, makes possible the

taking of current readings of a corresponding number of circuits by

means of one ammeter. The wiring diagram is shown in fig. 2,670.]

The switch when on a large system is often in a cell some distance

behind the panel, and is then controlled by a system of levers, or by

a small motor which is started and stopped by a throw over switch on

the panel, in which case there is generally a lamp or lamps on the

panel to show whether the switch is open or closed.

Air brake switches or links are placed between the bus bars

and the oil switch to allow of the latter being isolated for

inspection purposes, and as a general rule no apparatus carrying

high pressure current is allowed on the front of the panel. With

both direct and alternating current feeders, a watthour meter is

often added to show the total consumption of the circuit.

[Illustration: FIG. 2,670.--Wiring diagram for Crouse-Hinds radial

ammeter switch as illustrated in fig. 2,669. The switch proper is on

the rear of the switchboard, and the hand wheel dial and indicator on

the front.]

A typical three phase generator panel is provided with three

ammeters, one in each phase, operated from three current

transformers, one to each ammeter, a volt meter, a power factor

indicator, and an indicating watthour meter, all operated from

one or more pressure transformers, and the necessary current

transformers, the operating handle of the oil switch, which is

connected to the switch itself by means of rods, two maximum

releases operated by current transformers, or a reverse relay

for automatically tripping the switch, lamps for indicating when

the switch is tripped, a socket for taking the plug which makes

connection between the secondary of a pressure transformer and

the synchronizer on the synchronizing panel, and a lamp for

illuminating purposes, while on the base of the panel or on a

pillar at the front of the gallery is mounted the gear for the

field circuit. This consists of a double pole field switch and a

discharge resistance, an ammeter, a handle for the rheostat in

the generator field, and (if each alternator have its own direct

coupled exciter) possibly also a small rheostat for the exciter

field.

NOTE.--In some cases where the capacity of

the plant is not very great, the oil switch

is mounted on the back of the panel, and the

bus bars, current transformers, &c., on the

framework, also just at the back of the panel,

but under no circumstances, in good modern

practice, is high pressure apparatus permitted

on the front of the board. Where the capacity of

the plant is very large, the oil switches are

operated electrically by means of small motors,

and in this case the small switch gear for

starting and stopping this motor is mounted on

the generator panel, also the lamp or lamps to

indicate when the switch is open, and when closed.

Hawkins Electrical Guide v. 08 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 2 / 6 章