FEED WATER HEATERS.

[Illustration: Fig. 97.]

There are two forms of feed water heaters: (1) _The closed heater_,

where the feed water passes through tubes, which are enclosed in a

shell, through which the exhaust steam passes.(2) _The open heater_, in

which the steam and water come into contact. In the latter the water is

sprayed into a space, through which the exhaust steam passes, or is run

over a number of inclined perforated copper plates, mingled with the

exhaust steam.

The original feed water heater called a “pot heater,” consisted of

a vessel so constructed that the feed water was sprayed through the

exhaust steam into a globe formed tank, from the bottom of which the

heated water was pumped into the boiler; its name was originally the

“pot heater,” but as it was open to the air through the exhaust pipe,

it was, with its successively improved forms called the open heater.

All the heat imparted to the feed water, before it enters the boiler,

is so much saved, not only in the cost of fuel, but by the increased

capacity of the boiler, as the fuel in the furnace will not have this

duty to perform. There are two sources of waste heat which can be

utilized for this purpose: the chimney gases and the exhaust steam.

The gases escaping to the chimney after being reduced to the lowest

possible temperature contain a considerable quantity of heat. This

waste of heat energy may be largely saved by the device illustrated on

page 186.

[Illustration: Fig. 98.]

How much saving is obtained under any given condition is a question

requiring for its solution a careful calculation of all of the

conditions which have a bearing on the subject. Exhaust steam under

atmospheric pressure only has a sensible temperature of 212 degrees,

but exhaust steam contains also a large number of heat units which are

given up when the steam is condensed into water; for this reason it

might be thought possible to raise the temperature of the feed water a

few degrees higher even than the sensible temperature of the exhaust

steam. But this should not be expected, on account of the radiation of

heat that would occur above that of the steam.

The steam which escapes from the exhaust pipe dissipates into the

atmosphere or discharges into the condenser over nine tenths of the

heat it contained when leaving the boiler. This can be best utilized

by _exhaust feed water heaters_, for the use of live steam heaters

represents no saving in fuel, as all the heat imparted to the feed

water by their use comes directly from the boiler. The purpose for

which they are used is to elevate the temperature of the feed water

above the boiling point, so as to precipitate the sulphate of lime

and other scale forming substances, and prevent them from entering

the boiler. Neither does the heat in the feed water introduced by

an injector represent saving, as it comes from the boiler and was

generated by the fuel.

It is important to note these two statements: 1, That neither live

steam feed water heaters, nor 2, injectors save the heat from the

escaping steam.

It is also well to remember that it requires _a pound of water_ to

absorb 1.146 heat units, and that this quantity of heat is distributed

through the whole quantity of water, and _as a pound of steam is the

same as a pound of water_, it may be understood that at 212° each pound

of exhaust steam contains 1,146 heat units; ten pounds of steam contain

11,460 heat units distributed through the mass, etc.: thus, to explain

still further:

To evaporate water into steam, it must first be heated to the boiling

point, and then sufficient heat still further added to change it from

the liquid to the gaseous state, or steam. Take one pound of water at

32 degrees and heat it to the boiling point, it will have received 212°

- 32° = 180 heat units. A heat unit being the amount of heat necessary

to raise one pound of water through one degree at its greatest density.

To convert it into steam after it has been raised to the boiling point,

requires the addition of 966 heat units, which are called latent, as

they cannot be detected by the thermometer. This makes 180 + 966 =

1146 heat units, which is the total heat contained _in one pound of

water_ made into steam at the atmospheric pressure. And at atmospheric

density the volume of this steam is equal to 26.36 cubic feet, and this

amount of steam contains 1,146 units of heat, distributed throughout

the whole quantity, while the temperature at any given point at which

the thermometer may be inserted is 212 degrees. If two pounds of water

be evaporated, making a volume of 52.72 cubic feet, then the number of

heat units present would be doubled, while the temperature would still

remain at 212, the same as with one pound.

If by utilizing the heat that would otherwise go to waste, the

temperature of the feed water is raised 125 degrees, the saving would

be 125/1146 of the total amount of heat required for its evaporation,

or about 11 per cent. Thus it can be seen the percentage of saving

depends upon the initial temperature of the feed water, and the

pressure at which it is evaporated.

For example, a boiler carrying steam at 100 pounds pressure has the

temperature of the feed water raised from 60 to 200 degrees, what is

the percentage of gain?

By referring to a table pressure of “saturated steam,” it will be seen

that the total heat in steam at 100 pounds pressure is 1185 heat units.

These calculations are from 32 degrees above zero, consequently the

feed must be computed likewise.

In the first case, the heat to be supplied by the furnace is the total

heat, less that which the feed water contains, or 1185 - 28 = 1157

heat units. In the second case it is 1185 - 168 = 1017 heat units,

the difference being 1157 - 1017 = 140, which represents a saving of

140/1157 or about 12 per cent.

Where feed water is heated no more than 20 degrees above its normal

temperature the gain effected cannot amount to more than 2%, not

sufficient to pay for the introduction and maintenance of a feed water

heating device, no matter how simple, but if the temperature of the

water can be increased 60 degrees the gain will be in the neighborhood

of 5%. To make feed water heating practical and economical it would be

necessary to increase the temperature of the water about 180 degrees at

least, and to do this, using the exhaust from a non-condensing engine

without back pressure, would require such a capacity of heater as would

give fully 10 square feet of heating surface to each horse power of

work developed, and to raise the temperature above this would require a

certain amount of back pressure or an increased capacity of heater, so

that the subject resolves itself into a question of large capacity of

heater, or a higher temperature of the exhaust steam, which could only

be obtained through a given amount of back pressure.

In the same way has been calculated the following table, showing

percentages of saving of fuel by heating feed-water to various

temperatures by exhaust steam, otherwise waste:

_Percentage of saving._ (_Steam at 60 pounds gauge pressure._)

-----+--------------------------------------------------------------

Final| Initial Temperature of Water (Fahrenheit).

Temp.+--------+--------+--------+--------+--------+--------+--------

Fahr.| 32 Deg.| 40 Deg.| 50 Deg.| 60 Deg.| 70 Deg.| 80 Deg.| 90 Deg.

-----+--------+--------+--------+--------+--------+--------+--------

60 | 2.39 | 1.71 | 9.86 | … | … | … | …

80 | 4.09 | 3.43 | 2.59 | 1.74 | 0.88 | … | …

100 | 5.79 | 5.14 | 4.32 | 3.49 | 2.64 | 1.77 | .90

120 | 7.50 | 6.85 | 6.05 | 5.23 | 4.40 | 3.55 | 2.68

140 | 9.20 | 8.57 | 7.77 | 6.97 | 6.15 | 5.32 | 4.47

160 | 10.90 | 10.28 | 9.50 | 8.72 | 7.91 | 7.09 | 6.26

180 | 12.60 | 12.00 | 11.23 | 10.46 | 9.68 | 8.87 | 8.06

200 | 14.36 | 13.71 | 13.00 | 12.20 | 11.43 | 10.65 | 9.85

220 | 16.00 | 15.42 | 14.70 | 14.00 | 13.19 | 12.33 | 11.64

-----+--------+--------+--------+--------+--------+--------+--------

|100 Deg.|120 Deg.|140 Deg.|160 Deg.|180 Deg.|200 Deg.|

-----+--------+--------+--------+--------+--------+--------+--------

60 | … | … | … | … | … | … |

80 | … | … | … | … | … | … |

100 | … | … | … | … | … | … |

120 | 1.80 | … | … | … | … | … |

140 | 3.61 | 1.84 | … | … | … | … |

160 | 5.42 | 3.67 | 1.87 | … | … | … |

180 | 7.23 | 5.52 | 3.75 | 1.91 | … | … |

200 | 9.03 | 7.36 | 5.62 | 3.82 | 1.96 | … |

220 | 10.84 | 9.20 | 7.50 | 5.73 | 3.93 | 1.98 |

-----+--------+--------+--------+--------+--------+--------+--------

A good feed-water heater of adequate proportions should readily raise

the temperature of feed-water up to 200° Fahr., and, as is seen by

inspection of the table, thus effect a saving of fuel, ranging from

14.3 per cent. to 9.03 per cent., according as the atmospheric or

normal temperature of the water varies from 32° Fahr. in the height of

winter, to 100° Fahr. in the height of summer.

The percentage of saving which may be obtained from the use of exhaust

steam for heating the feed water, with which the boiler is supplied,

will depend upon the temperature to which the water is raised, and

this, in turn, will depend upon the length of time that the water

remains under the influence of the exhaust steam. This should be as

long as possible, and unless a sufficient amount of heating surface is

employed in the heater best results cannot be expected.

It does not necessarily require all the exhaust steam—or the whole

volume of waste steam passing from the engine to bring the feed water

up to the temperature desired, and the larger the heating appliance the

smaller proportion is needed—hence heaters are best made with two exits

nicely proportioned to avoid back pressure and at the same time utilize

enough of the exhaust to heat the feed water.

An impression prevails among many who are running a condenser on their

engine that a feed water heater can not be used in connection with it;

large numbers of heaters running on condensing engines with results as

follows: the feed water is delivered to the boiler at a temperature of

150° to 160° Fahr., depending on the vacuum: the higher the vacuum the

less the heat in the feed water.

A heater applied to a condensing engine generally increases the vacuum

one to two inches.

When cold water is used for the feed water, the saving in fuel by the

use of the heater is from 7 to 14 per cent.

When feed water is taken from the hot well, it will save 7 to 8 per

cent.

Where all the steam generated by a boiler is used in the engine and the

exhaust passed through a heater it is found by actual experiment, where

iron tubes are used in the heater, that approximately ten square feet

of heating surface will be required for each 30 lbs. of water supplied

to the boiler at a temperature of 200 degrees Fahr.

Ten square feet of heating surface in the feed water heater also

represents one horse power.

Maxims and Instructions for the Boiler Room Useful to Engineers, Firemen & Mechanics; Relating to Steam Generators, Pumps, Appliances, Steam Heating, Practical Plumbing, etc. · 第 184 / 328 题