RIVETED OR SCREW STAYS.

[Illustration: Fig. 49.]

In addition to palm and gusset stays, there are in use riveted or

screwed stays, as shown in Fig. 49.

This would not answer in furnaces, owing to the burning off of the

heads, hence driven stays are used there.

[Illustration: Fig. 50.]

These screwed stays, shown in Fig. 50, are used (in marine and similar

boilers) between the combustion chamber back and boiler back and also

between the sides of the combustion chambers.

The general plan is to have a large nut and washer inside and outside

the boiler with the outside washer considerably larger than the inside,

so as to hold more efficiently the back and front ends together.

In marine boilers it is customary to place the stays 15 to 18 inches

apart for ease of access to the parts of the boiler, and to make them

of 2-1/4 to 2-1/2 inch iron of the best quality.

INSPECTOR’S RULES RELATING TO BRACES IN STEAM BOILERS, ALSO TO BE

OBSERVED BY ENGINEERS.

Where flat surfaces exist, the inspector must satisfy himself that the

spacing and distance apart of the bracing, and all other parts of the

boiler, are so arranged that all will be of not less strength than the

shell, and he must also after applying the hydrostatic test, thoroughly

examine every part of the boiler.

No braces or stays employed in the construction of marine boilers shall

be allowed a greater strain than six thousand pounds per square inch

of section, and no screw stay bolt shall be allowed to be used in the

construction of marine boilers in which salt water is used to generate

steam, unless said stay bolt is protected by a socket. But such screw

stay bolts, without sockets, may be used in staying the fire boxes

and furnaces of such boiler, and not elsewhere, when fresh water is

used for generating steam in said boiler. Water used from a surface

condenser shall be deemed fresh water. And no brace or stay bolt used

in a marine boiler will be allowed to be placed more than eight and

one-half inches from centre to centre, except that flat surfaces,

other than those on fire boxes, furnaces and back connections, may

be reinforced by a washer or =T= iron of such size and thickness as

would not leave such flat surface unsupported at a greater distance,

in any case, than eight and one-half inches, and such flat surface

shall not be of less strength than the shell of the boiler, and able to

resist the same strain and pressure to the square inch, and no braces

supporting such flat reinforced surfaces, will be allowed more than 16

inches apart.

In allowing the strain on a screw stay bolt, the diameter of the same

shall be determined by the diameter at the bottom of the thread. Many

State laws and City ordinances allow a strain of seven thousand five

hundred pounds per square inch of section on good bracing without

welds. The following table gives the safe load of round iron braces or

stays.