DIRECTIONS FOR FIRING WITH VARIOUS FUELS.

FIRING BOILERS NEWLY SET, ETC.—Boilers newly set should be heated up

very slowly indeed, and the fires should not be lighted under the

boilers for at least two weeks after setting, if it is possible to wait

this length of time. This two weeks enables all parts of the mason work

to set gradually and harden naturally; the walls will be much more

likely to remain perfect than when fires are lighted while the mortar

is yet green.

When fire is started under a new boiler the first time, it should

be a very small one, and no attempt should be made to do more than

moderately warm all parts of the brick work. A slow fire should be kept

up for twenty-four hours, and on the second day it may be slightly

increased. Three full days should elapse before the boiler is allowed

to make any steam at all.

When the pressure rises, it should not be allowed to go above four or

five pounds, and the safety valve weight should be taken off to prevent

any possibility of an increase. Steam should be allowed to go through

all the pipes attached for steam, and blow through the engine before

any attempt is made to get pressure on them. The object of all these

precautions and this care is to prevent injury by sudden expansion,

which may cause great damage.