restricted to small installations which require, in addition to the
standby unit, only one pump, the capacity of which is equal to the
maximum rate of sewage flow. When the receiving well has been pumped dry
the pump stops, allowing the well to fill again. Although the use of a
large receiving well, or an equalizing reservoir, for a large pumping
station would permit the operation of the pumps under more economical
conditions, the storage of sewage for the length of time required would
not be feasible. The sewage would probably become septic, creating odors
and corroding the pumps. The extra cost of the reservoir might not
compensate for the saving in the capacity and operation of the pumps.
The capacity of the receiving well should be so designed that the pump
when operating will be working at its maximum capacity, and the period
of rest during conditions of average rate of flow should be in the
neighborhood of 15 to 20 minutes. For example, assume an average rate of
flow of 2 cubic feet per second, with a maximum rate of double this
amount. The pump should have a capacity of 4 cubic feet per second, and
if the receiving well is to be filled in 15 minutes by the average rate
of sewage flow its capacity should be 15 × 5 × 60 × 7.5 or 14,000
gallons. Under these circumstances the pump will operate 15 minutes and
rest 15 minutes, during average conditions of flow.
=74. Types of Pumping Machinery.=—The two principal types of pumping
machines for lifting sewage are centrifugal pumps and reciprocating
pumps. A centrifugal pump is, in general, any pump which raises a liquid
by the centrifugal force created by a wheel, called the impeller,
revolving in a tight casing, as shown in Fig. 50. A reciprocating pump
is one in which there is a periodic reversal of motion of the parts of
the pump.
Centrifugal pumps are sometimes classified as volute pumps and turbine
pumps. A volute pump is a centrifugal pump with a spiral casing into
which the water is discharged from the impeller with the same velocity
at all points around the circumference, as shown in Fig. 51. A turbine
pump is a centrifugal pump in which the water is discharged from the
impeller through guide passages into a collecting chamber, in such a
manner as to prevent loss of energy in changing from kinetic head to
pressure head. A turbine pump is shown in section in Fig. 51.
Centrifugal pumps are sometimes classified as single stage and
multi-stage. A centrifugal pump from which the water is discharged at
the pressure created by a single impeller is called a single-stage pump.
If the water in the pump is discharged from one impeller into the
suction of another impeller the pump is known as a multi-stage pump. The
number of impellers operating at different pressures determines the
number of stages of the pump. A three-stage pump is shown in Fig. 52.
[Illustration:
FIG. 50.—Section through de Laval Single-Stage, Double Suction
Centrifugal Pump.
]
375 Lubricating ring.
380 Oil hole cap.
383 Oil drain tube.
404 Shaft sleeve lock nut.
440 Driving coupling.
441 Driven coupling.
443 Coupling check nut.
450 Coupling bolt.
451 Coupling bolt nut.
452 Coupling rubber.
453 Coupling rubber steel tube.
500 Pump case.
550 Bearing bracket cap.
551 Bearing.
552 Shaft.
553 Shaft sleeve, right hand thread.
PW Impeller.
554 Shaft sleeve, left hand thread.
555 Shaft stop collar, inner.
555–1 Shaft stop collar, outer.
556 Guide ring.
560 Packing gland.
563 Bearing.
567R Impeller protecting ring, right hand thread.
567L Impeller protecting ring, left hand thread.
583 Pump case protecting ring.
567 Labyrinth packing.
583 Labyrinth packing.
600 Pump case cover.
692 Impeller key.
815 Bearing bracket, outer.
815–1 Bearing bracket, inner.
[Illustration:
FIG. 51.—Types of Centrifugal Pumps.
]
[Illustration:
FIG. 52.—Section of a Multi-Stage Centrifugal Pump.
Courtesy DeLaval Steam Turbine Co.
]
Reciprocating pumps are generally driven by steam and are either
direct-acting, or of the crank-and-fly-wheel type. Power pumps are
reciprocating machines which may be driven by any form of motor, to
which they are connected by belt, chain or shaft. A Deming triplex
power pump is shown in Fig. 53. Power pumps can be used only where the
character of the sewage will not clog the valves nor corrode the pump.
A direct-acting steam pump is one in which the steam and water
cylinders are in the same straight line and the steam is used at full
boiler pressure throughout the full length of the stroke. The
crank-and-fly-wheel type of pumping engine permits the use of steam
expansively during a part of the stroke, the energy stored in the
flywheel carrying the machine through the remainder of the stroke.
Reciprocating pumps are sometimes classified as plunger pumps and
piston pumps. In the action of a plunger pump the water is expelled
from the water cylinder, by the action of a plunger which only partly
fills the water cylinder, as shown in Figs. 54 and 55. In a piston
pump the water is expelled from the water cylinder by the action of a
piston which completely fills the water cylinder, as shown in Fig. 63,
which illustrates a direct-acting piston pump.
[Illustration:
FIG. 53.—Triplex Power Pump.
Courtesy, The Deming Co.
]
Plungers are better than pistons for pumping sewage as the wear between
the pistons and the inside face of the cylinder soon reduces the
efficiency of the pump. Outside packed plungers are better than the
inside packed type because the packing can be taken up without stopping
the pump and the leakage from the pump is visible at all times. Outside
packed pumps are more expensive in first cost, but are easier to
maintain and have a longer life than piston pumps.
[Illustration:
FIG. 54.—Water End of Inside Center-Packed Plunger Pump.
]
In selecting a pump to perform certain work the size of the water
cylinder and the speed of the travel of the piston should be
investigated to insure proper capacity. The average linear travel of the
piston for slow speed pumps is estimated at about 100 feet per minute,
dependent on the length of stroke and the valve area. For short strokes
and small valve areas the speed may be as low as 40 feet per minute, and
for long stroke fire pumps with large valves the piston can be operated
at a speed of 200 feet per minute.[45] Vertical, triple-expansion,
crank-and-fly-wheel, outside packed plunger pumps with flap valves can
be operated at speeds of 200 feet per minute when lifting sewage, and
when equipped with mechanically operated valves and lifting water they
can be run at speeds of 400 to 500 feet per minute. The speed of travel
multiplied by the volume of piston or plunger displacement, with proper
allowance for slippage, will give the capacity of the pump. The slippage
allowance may be from 3 to 8 per cent for the best pumps, and for pumps
in poor conditions it may be a high as 30 to 40 per cent.
[Illustration:
FIG. 55—Water End of Outside Center-Packed Plunger Pump.
Courtesy Allis-Chalmers Co.
]
There are two types of ejector pumps used for lifting sewage. One of
these depends on the vacuum created by the velocity of a stream of water
or steam passing through a small nozzle. The operation of this pump is
described in Art. 139 and it is illustrated in Fig. 97. The other type
of ejector pump is known as the compressed-air ejector. It is operated
by means of compressed air which is turned into a receptacle containing
sewage. The details of this type are explained in Art. 83 and are
illustrated in Fig. 68.
=75. Sizes and Description of Pumps.=—The size of a centrifugal pump is
expressed as the diameter of the discharge pipe in inches. It has
nothing to do with the head for which the pump is suited. On the
assumption of a velocity of flow of 10 feet per second through the
discharge pipe the capacity of the pump can be approximated.
The size of a reciprocating pump involves the expression of the
diameters of the steam cylinders, the water cylinder, and the length of
the stroke in inches, in the order named, beginning with the steam
cylinder with the highest pressure. A complete description of a steam
pumping engine might be; compound, duplex, horizontal, condensing,
crank-and-fly-wheel, outside-center-packed, 12″ × 24″ × 18″ × 24″ pump.
The word compound means that there are a high-pressure and a
low-pressure steam cylinder; the word duplex means that there are two of
each of these cylinders; the word horizontal means that the axes of
these cylinders are in a horizontal plane; the word condensing means
that the steam is discharged from the low-pressure cylinders into a
condenser; the name crank-and-fly-wheel is self-explanatory; the name
outside-center-packed means that the water cylinder is divided into two
portions between which the plunger is exposed to the atmosphere, and
that the packing rings are on the outside of the two portions of the
cylinder as shown in Fig. 55; the figures shown mean that the
high-pressure steam cylinder is 12 inches in diameter, the low-pressure
24 inches in diameter, the water cylinder is 18 inches in diameter, and
the stroke of the pump is 24 inches.
=76. Definitions of Duty and Efficiency.=—The duty of a pump is the
number of foot-pounds of work done by the pump per million B.T.U., per
thousand pounds of steam, or per hundred pounds of coal, consumed in
performing the work. These units are only approximately equal as 100
pounds of coal or 1,000 pounds of steam do not always contain the same
number of B.T.U. and may only approximately equal 1,000,000 B.T.U.
Since 1,000,000 B.T.U. are equal to 778,000,000 foot-pounds of work, a
pump with a duty of 778,000,000 will have an efficiency of 100 per cent.
The efficiency of a pump is therefore its duty based on B.T.U. divided
by 778,000,000. The efficiencies or duties of various types of pumps are
given in Table 26.[46]
TABLE 26
APPROXIMATE DUTIES OF STEAM PUMPS
Small duplex, non-condensing 10,000,000
Large duplex, non-condensing 25,000,000
Small simple, flywheel, condensing 50,000,000
Large simple, flywheel, condensing 65,000,000
Small compound, flywheel, condensing 65,000,000
Large compound, flywheel, condensing 120,000,000
Small triple, flywheel, condensing 150,000,000
Large triple, flywheel, condensing 165,000,000
=77. Details of Centrifugal Pumps.=—A section of a centrifugal pump with
the names of the parts marked thereon is shown in Fig. 50. Among the
important parts which require the attention of the purchaser are: the
impeller (_PW_), the impeller packing rings (567 _R_ & _L_), the
bearings (551, 563), the thrust bearings (555–1), the shaft (552), and
the shaft coupling (440).
The impeller should be of bronze, gun metal, or other alloy, because
there is no rusting or roughening of the surface, and the efficiency
does not fall with age. Normal fresh sewage is not corrosive, but septic
sewage and sludge are usually so corrosive that iron parts cannot be
used with success in contact with them. The impeller should be machined
and polished to reduce the friction with the liquid. Impellers are made
either closed or open, i.e., either with or without plates on the sides
connecting the blades to avoid the friction of the liquid against the
side of the casing. The closed type of impeller is shown in Fig. 50.
Closed impellers are slightly more expensive, but generally give better
service and higher efficiencies than the open type. Single impeller
pumps should have an inlet on each side of the impeller to aid in
balancing the machine, unless the plane of the impeller is to be
horizontal when operating. Multi-impeller pumps usually have single
inlet openings for each impeller. Vibration in the pump is sometimes
caused by an unbalanced impeller. The moving parts may be balanced at
one speed and unbalanced at another. To determine if the moving parts
are balanced the pump should be run free at different speeds and the
amount of vibration observed. If the impeller is removed from the pump
its balance when at rest can be studied by resting it on horizontal
knife edges. If there is a tendency to rotate in any direction from any
position the impeller is not perfectly balanced.
Packing rings are used to prevent the escape of water from the discharge
chamber back into the suction chamber. These rings should be made of the
same material as the impeller. Labyrinth type rings, as shown in Fig.
50, are sometimes used as the long tortuous passages are efficient in
preventing leakage.
The bearings must be carefully made because of the high speed of the
pump. They are usually made of cast iron with babbitt lining. They
should be placed on the ends of the shaft on the outside of the pump
casing, as shown in Fig. 50, and should be split horizontally so as to
be easily renewed. Exterior bearings are oil lubricated by means of ring
or chain oilers with deep oil wells. Where interior bearings are
necessary, because of the length of the shaft, they should be made of
hard brass and should be water lubricated.
[Illustration:
FIG. 56.—Marine Type Thrust Bearing.
Courtesy, DeLaval Steam Turbine Co.
]
Thrust bearings or thrust balancing devices are used to take up the end
thrust which occurs in even the best designed pumps. To overcome this
pumps are designed with double suction, opposed impellers, or two pumps
with their impellers opposed may be placed on the same shaft. Due to
inequalities in wear, workmanship or other conditions, end thrust will
occur and must be cared for. Various types of thrust bearings are in
successful use, such as: the piston, ball, roller or marine types. The
marine type thrust bearing is shown in Fig. 56. The piston type of
hydraulic balancing device is shown in Fig. 57. In the figure _A_
represents the impeller, and _B_ a piston fixed to the shaft and
revolving with it. There is a passage for water through the openings
(1), (2), and (3) leading from the impeller chamber to the atmosphere or
to the suction of the pump. If the impeller tends to move to the right
opening (1) is closed resulting in pressure on the right of the impeller
forcing it to the left. If the impeller moves to the left (1) is opened
thus transmitting pressure to the piston _B_ forcing the impeller to the
right. The flange _C_ is not essential, but is advantageous in pumps
handling gritty matter. As the channel (2) wears larger the pressure
against the piston decreases allowing it to move to the left. This
partially closes (3) building up the pressure again.
[Illustration:
FIG. 57.—Piston Type of Thrust Balancing Device.
]
Flexible shaft couplings should be used if the shaft of the driving
motor and the pump are in the same line, as direct alignment is
difficult to obtain or to maintain. Where connected to steam turbines,
reduction gearing and rigid couplings are usually used on sewage pumps
to obtain slow speed and permit large passages. Flexible couplings are
of various types, one of which is shown in Fig. 50. A rigid coupling
would be formed by bolting the flanges firmly together. Shaft couplings
are usually not necessary where the pump is driven by belt connection to
the engine or motor, or where the pump and pulley rest on only two
bearings.
The stuffing box shown in Fig. 50 is packed loosely with two layers of
hemp between which is a lantern gland, in order to permit a small amount
of leakage. A drip box is placed below this gland to catch the leakage
and return it to the pump. The leakage is permitted as it aids in
lubrication and the tightening of the gland will cause binding of the
shaft. The gland on the suction side of the pump should be connected by
a small pipe to the discharge chamber in order to keep a constant supply
of water for lubrication and to prevent the entrance of air to the
suction end of the pump.
=78. Centrifugal Pump Characteristics.=—The capacity of a centrifugal
pump is fixed by the size and type of its impeller and by the speed of
revolution. Roughly, the capacity of a pump, for maximum efficiency,
varies directly as the speed of revolution, the discharge pressure
varies as the square of the speed, and the power varies as the cube of
the speed. These relations are found not to hold exactly in tests
because of internal hydraulic friction in the pump.
The characteristic curves for a centrifugal pump, or the so-called pump
characteristics, are represented graphically by the relation between
quantity and efficiency, quantity and power necessary to drive, and
quantity and head, all at the same speed. The quantities are plotted as
abscissas in every case. The curve whose ordinates are head and whose
abscissas are quantities is known as “the characteristic.” The curve
showing the relation between quantities and speeds is sometimes included
among the characteristics. Characteristics of pumps with different
styles of impellers are shown in Fig. 58. Fig. 59 shows the
characteristics of a pump run at different speeds, the efficiencies at
these speeds when pumping at different rates, and the maximum efficiency
at different speeds. It is to be noted that the information given in
this figure is more extensive than that in Fig. 58. The operating
conditions under any head, rate of discharge, and speed are given. The
curves of constant speed are parallel, and their distances apart vary as
the square of the speed. The line of maximum efficiency is approximately
a parabola.
[Illustration:
FIG. 58.—Characteristics of Centrifugal Pumps with Different Styles of
Impellers at Constant Speed.
]
A study of the characteristics of any particular pump should be made
with a view to its selection for the load and conditions under which it
is to be used. Among the important things to be considered in the
selection of a centrifugal pump for the expected conditions of load are:
the capacity required, the maximum and minimum total head to be pumped
against, the maximum variations in suction and discharge heads, and the
nature of the drive. For example, the pump, whose characteristics are
shown in Fig. 59, should be operated at about 800 revolutions per
minute. Under total heads between 40 and 50 feet, the discharge for the
best efficiency will vary between 600 and 670 gallons per minute.
[Illustration:
FIG. 59.—Efficiency and Characteristic Curves of a Centrifugal Pump at
Different Speeds.
]
[Illustration:
FIG. 60.—Efficiencies of Centrifugal Pumps.
]
The efficiencies of centrifugal pumps increase with their capacities as
is shown approximately in Fig. 60.
=79. Setting of Centrifugal Pumps.=—In setting a centrifugal pump, care
should be taken to provide a firm foundation to hold the shafts of the
pump and the electric motor or the reduction gearing in good alignment,
or to prevent the pump from being displaced by the pull of a belt. It is
desirable that the foundation be level. Centrifugal pumps should be set
submerged for small pumping stations automatically controlled. Sludge
pumps must be set submerged as otherwise they will not prime
successfully. Provision should be made by which the pump can be lifted
from the sewage, or sludge, for inspection and repair. In many cases the
pump can be made self-priming by setting it in a dry, water-tight vault
below the low level of sewage flow. Where possible it is desirable not
to set the pump submerged as it will receive better care when easily
accessible.
[Illustration:
FIG. 61.—Centrifugal Pump in Manhole at Duluth, Minn.
Eng. Contracting, Vol. 43, 1915, p. 310.
]
The suction pipe should be free from vertical bends where air might
collect and should be straight for at least 18 to 24 inches from the
pump casing. An elbow on the suction pipe, attached directly to the
casing of the pump gives a lower efficiency than a suction pipe with a
short straight run. Centrifugal pumps will operate with as high a
suction lift as reciprocating pumps, but at the start they must be
primed and some provision must be made for priming them. The suction
pipe should be equipped with foot valves to hold the priming, or some
method may be provided for exhausting the air from the suction pipe. The
foot valves should be so installed as to form no appreciable obstruction
to the flow of water. They should have an area of opening at least 50
per cent greater than the cross-section of the suction pipe. A strainer
on the suction pipe is undesirable as it becomes clogged and is usually
in an inaccessible position for cleaning. A screen should be placed at
the entrance to the suction well to prevent the entrance of objects that
are likely to clog the pump. A gate-valve and a check-valve should be
provided on the discharge pipe, the former to assist in controlling the
rate of discharge and the latter to prevent back flow into the pump when
it is not operating.
Centrifugal pumps are well adapted to service in either large or small
units. An installation in a manhole at Park Point, Duluth, is shown in
Fig. 61. This station is controlled by an automatic electric device
which is operated by a float in the suction pit. Such automatic control
is an added advantage of the use of electrically driven centrifugal
pumps. The Calumet Pumping Station in Chicago, shown in Fig. 49, has a
capacity of approximately 1,000 cubic feet per second. The simplicity of
the layout of this station is shown in Fig. 62.
[Illustration:
FIG. 62.—Interior Arrangement of the Calumet Sewage Pumping Station,
Chicago.
Eng. News-Record, Vol. 85, 1920, p. 872.
]
=80. Steam Pumps and Pumping Engines.=—The direct-acting steam pump, one
type of which is shown in Fig. 63, is adapted to pumping sewage the
character of which will not corrode or clog the valves. In this form of
pump it is necessary to utilize the steam at full pressure throughout
the entire length of the stroke, which results in high steam
consumption. A flywheel permits the use of steam expansively during a
part of the stroke, thus increasing the economy of operation. Other
devices used for the same purpose are known as compensators. They are
not in general use.
Steam engines are classified in many different ways, for example;
according to the type of valve gear, as, plain slide valve, Corliss,
Lentz, etc.; or according to the number of steam expansions, as, simple,
compound, triple-expansion, etc.; or according to the efficiency of the
machine as low duty or high duty; or as
[Illustration:
FIG. 63.—Section of Duplex Piston Steam Pump.
Courtesy, The John H. McGowan Co.
]
STEAM END
2 Steam cylinder and housing combined.
8 Steam piston head.
9 Steam piston follower.
10 Steam piston inside ring.
11 Steam piston outside ring (2).
12 Steam cylinder head.
14 Steam chest.
16 Steam chest cover.
17 Steam slide valve.
18 Steam valve rod.
20 Steam valve rod, pin and nut.
22 Steam valve rod, collar and set screw.
23 Steam valve rod, stuffing box.
24 Steam valve rod, stuffing box, nut and gland.
38 Piston rod.
47 Piston rod stuffing box.
48 Piston rod, stuffing box, nut and gland.
49 Valve gear stand.
51 Long valve crank and shaft.
52 Short valve crank and shaft.
PUMP END
115 Pump body.
127 Brass liner.
129 Water piston head.
130 Water piston follower.
137 Cylinder head.
139 Valve plate.
140 Cap.
152 Suction flange.
161 Discharge flange.
162 Valve seat, suction or discharge.
163 Valve, suction or discharge.
164 Suction valve spring.
167 Discharge valve spring.
168 Valve plate, suction or discharge.
169 Valve stem, suction or discharge.
STEAM END
55 Crank pin.
56 Valve rod link.
61 Long rocker arm.
62 Short rocker arm.
63 Rocker arm wiper.
69 Cross head.
condensing or non-condensing, etc. Throttling engines or automatic
engines refer to the method of control of the steam by the governor. In
throttling engines the governor controls the amount of opening of the
throttle valve, in automatic engines the governor controls the position
of the cut-off.
The simple slide valve, low-duty, non-condensing, throttling engine, is
the lowest in first cost and the most expensive in the consumption of
fuel. The triple-expansion Corliss, or the non-releasing Corliss,
high-duty pumping engine is the most expensive in first cost but
consumes less steam for the power delivered than any other form of
reciprocating engine. For pumps of very small capacity the cost of fuel
is not so important an item as the first cost of the machine. For this
reason and because of the lower cost of attendance low-duty pumps are
more frequently found in small pumping stations.
[Illustration:
FIG. 64.—Diagram Showing Rates of Steam Consumption for Different Size
Units under Different Loads.
]
TABLE 27
WATER RATES OF PRIME MOVERS AT FULL AND PART LOADS
───────────────────────────────┬──────┬─────────────────────────┬──────
Type of Engine │ │ │Boiler
│Power,│ │Press.
│ K.W. │ Per Cent of Full Load │ Lbs.
───────────────────────────────┼──────┼────┬────┬────┬─────┬────┼──────
│ │ 25 │ 50 │ 75 │ 100 │125 │
───────────────────────────────┼──────┼────┼────┼────┼─────┼────┼──────
Single cylinder, high speed, │ │ │ │ │ │ │100 to
non-condensing │ 25│ 33│ 27│26.3│ 27.0│27.5│ 150
│ 250│ 42│37.5│ 35│ 34.0│34.0│
│ │ │ │ │ │ │
Automatic, flat four valve, │ │ │ │ │ │ │100 to
high speed │ 150│ │ 32│ 30│ 26.5│29.0│ 125
│ 250│ │ 33│ 31│ 28│30.0│
│ │ │ │ │ │ │
Tandem compound condensing, │ │ │ │ │ │ │100 to
high speed │ 125│ │ 23│ 19│ 17│ 18│ 150
│ │ │ 25│ 20│ 19.5│ 21│
│ │ │ │ │ │ │
Cross compound, condensing, │ │ │ │ │ │ │ 125
high speed │ │ 30│ 26│ 24│ 23│23.5│
│ │ │ │ │ │ │
Cross compound, non-condensing,│ │ │ │ │ │ │ 125
high speed │ │ 39│ 31│ 27│ 26│27.5│
│ │ │ │ │ │ │
Single cylinder Corliss, │ │ │ │ │ │ │ 100
condensing │ 120│23.7│20.4│ 19│ 18.5│19.0│
│ 500│26.3│22.8│21.3│ 20.8│21.3│ 125
│ │ │ │ │ │ │
Compound Corliss, condensing │ │16.5│ 14│12.5│ 12.1│12.5│ 100
│ │22.2│ 19│17.0│ 16.5│17.0│ 150
│ │ │ │ │ │ │
Single cylinder, rotary four │ │ │ │ │ │ │ 100
valve, non-condensing │ 75│26.2│22.3│21.3│ 21.6│22.8│
│ 400│35.0│27.2│26.4│ 26.0│26.8│ 180
│ │ │ │ │ │ │
Rotary four valve, tandem │ │ │ │ │ │ │ 100
compound non-condensing │ 125│32.0│22.0│ 20│18.25│18.5│
│ 600│40.0│28.3│23.2│ 22.5│22.7│ 150
│ │ │ │ │ │ │
Cross compound, non-condensing │ │ │ │ │ │ │ 100
rotary four valve │ 125│ 25│ 21│19.1│ 18.5│19.0│
│ 600│39.4│ 28│22.3│ 20.6│20.7│ 150
│ │ │ │ │ │ │
Single cylinder, poppett valve,│ │ │ │ │ │ │ 100
non-condensing │ 120│22.7│20.5│19.7│ 19.1│20.1│
│ 600│28.5│26.0│25.0│ 24.3│25.5│ 150
│ │ │ │ │ │ │
Single cylinder, poppett valve,│ │ │ │ │ │ │ 100
condensing │ 120│18.5│16.7│16.1│ 15.6│16.4│
│ 600│24.6│22.3│21.4│ 20.8│21.9│ 150
│ │ │ │ │ │ │
Compound condensing, poppett │ │ │ │ │ │ │ 100
valve │ 200│14.2│13.0│12.5│ 12.2│12.9│
│ 1200│18.4│16.9│16.3│ 15.9│16.8│ 150
│ │ │ │ │ │ │
Uniflow │ 125│14.6│13.7│13.4│ 13.4│13.3│ 150
│ 600│15.0│14.3│13.7│ 13.5│14.0│
│ │ │ │ │ │ │
Steam turbines, condensing, │ │ │ │ │ │ │ 125
Allis-Chalmers │ 300│ │ 24│ 17│ 160│16.5│
│ 2000│ │31.9│26.3│ 23.8│23.0│ 175
│ │ │ │ │ │ │
Steam turbines, condensing, │ │ │ │ │ │ │ 125
Westinghouse │ 300│ │13.7│12.8│ 12.2│12.6│
│ 2000│ │18.2│16.9│ 16.2│16.8│ 175
│ │ │ │ │ │ │
Steam turbines, high pressure, │ │ │ │ │ │ │
non-con., 12″ to 36″ wheel, │4 to 8│ │ │ │ │ │
1000 to 3600 R.P.M. │stages│ │ │ │ 28 5│ │
│ │ │ │ │116.5│ │
│ │ │ │ │ │ │
Ditto. Condensing, 26–inch │ │ │ │ │ 17 3│ │
│ │ │ │ │112.0│ │
│ │ │ │ │ │ │
───────────────────────────────┴──────┴────┴────┴────┴─────┴────┴──────
The steam consumption per indicated horse-power, better known as the
water rate of the engine, for various types of engines at full and at
part load is shown in Fig. 64. The steam consumption of other types at
full load is shown in Table 27. The indicated horse-power (I.H.P.) of a
steam engine is the product of the mean effective pressure (M.E.P.), the
area of the steam pistons, the length of the stroke, and the number of
strokes per unit of time. A common form of this expression is,
I.H.P = _PLAN_⁄33,000,
in which _P_ = the M.E.P. in pounds per square inch;
_L_ = the length of the stroke in inches;
_A_ = the sum of the areas of the pistons in square inches;
_N_ = the number of revolutions per minute.
The I.H.P. multiplied by the mechanical efficiency of the machine will
give the brake or water horse-power, that is, the horse-power delivered
by the machine. The product of the M.E.P., the sum of the areas of the
steam pistons and the mechanical efficiency of the machine, should equal
the product of the total head of water pumped against expressed in
pounds per square inch and the sum of the areas of the water pistons or
plungers. The M.E.P. is determined from indicator cards taken from the
steam cylinders during operation. These cards show the steam pressure on
the head and crank ends of each cylinder at all points during the
stroke.
=81. Steam Turbines.=—Among the advantages in the use of steam turbines
as compared with reciprocating steam engines for driving centrifugal
pumps are their simplicity of operation, the small floor space needed,
their freedom from vibration requiring a relatively light foundation,
and their ability to operate successfully and economically either
condensing or non-condensing under varying steam pressure. They can be
operated with steam at atmospheric or low pressure, thus taking the
exhaust from other engines. The greatest economy of operation for the
turbine alone will be obtained by operating with high pressure,
superheated steam and with a vacuum of 28 inches. In large units the
economy of operation of steam turbines is equal to that of the best type
of reciprocating engines. In order to develop the highest economy
turbines are operated at speeds from about 3,600 to 10,000 r.p.m. or
greater, the smaller turbines operating at the higher speeds. As these
speeds are usually too great for the operation of centrifugal pumps for
lifting sewage, reduction gears must be introduced between the turbine
and the pump. Although the best form of spiral-cut reduction gears may
obtain efficiencies of 95 to 98 per cent, or even higher, their use,
particularly in small units, is an undesirable feature of the steam
turbine for driving pumps.
The steam consumption of DeLaval turbines of different powers, and the
steam consumption of a 450 horse-power DeLaval turbine at different
loads are shown in Fig. 64. Some steam consumptions of other turbines
are recorded in Table 27. It is to be noted that the steam consumption
of the 450 horse-power turbine at part loads is not markedly greater
than that at full loads. This is an advantage of steam turbines as
compared with reciprocating engines. The steam consumption of any
turbine is dependent on the conditions of operation and is lower the
higher the vacuum into which the exhaust takes place.
[Illustration:
FIG. 65.—The DeLaval Trade Mark, Illustrating the Principle of the
DeLaval Steam Turbine.
Courtesy, DeLaval Steam Turbine Co.
]
There are two types of turbines in general use, the single stage or
impulse machines, and the compound or reaction type. The DeLaval is a
well-known make of the single stage or impulse type. The principle of
its operation is indicated in Fig. 65, which is the trade mark of the
DeLaval Steam Turbine Co. The energy of the steam is transmitted to the
wheel due to the high velocity of the steam impinging against the vanes.
In the compound or reaction type of machine the steam expands from one
stage to the next imparting its energy to the wheel by virtue of its
expansion in the passages of the turbine. For this reason the
single-stage or impulse type is operated at higher speeds than the
compound or reaction machines.
=82. Steam Boilers.=—Among the important points to be considered in the
selection of a steam boiler for a sewage pumping station are: the
necessary power; the quality of the feed water; the available floor
space; the steam pressure to be carried; and the quality and character
of the fuel. Tubular boilers of the type shown in Fig. 66, are lower in
first cost than other types of boilers. They are not ordinarily built in
units larger than 250 to 300 horse-power and where more power is desired
a number of units must be used. They are objectionable because of the
relatively large floor space required, and because of their relatively
poor economy of operation. The efficiencies of water-tube boilers of
different types are given in Table 28. Large power units of the
water-tube type, as shown in Fig. 67, although more expensive in first
cost, require less floor space. Almost any desired steam pressure can be
obtained from either type but water-tube boilers are more commonly used
for high pressures. The grate or stoker can be arranged to burn almost
any kind of fuel under either water-tube or fire-tube boilers. The use
of poor quality of water in water-tube boilers is undesirable as the
tubes are more likely to become clogged than the larger passages of the
fire-tube boilers. If necessary, a feed-water purification plant should
be installed, as it is usually cheaper to take the impurities out of the
water than to take the scale out of the boiler.
[Illustration:
FIG. 66.—Horizontal Fire-tube Boiler.
]
[Illustration:
FIG. 67.—Babcock and Wilcox Water-tube Boiler.
]
Not less than two boiler units should be used in any power station,
regardless of the demands for power, and if the feed water is bad, three
or even four units should be provided, as two units may be down at any
time. An appreciable factor of safety is provided by the ability of a
boiler to be operated at 30 to 50 per cent overload, if sufficient draft
is available, but with resulting reduction in the economy of operation.
The number of units provided should be such that the maximum load on the
pumping station can be carried with at least one in every 6 units or
less, out of service for repairs or other cause.
TABLE 28
EFFICIENCIES OF STEAM BOILERS
From Marks’ Mechanical Engineer’s Handbook
────────┬───────────┬──────────┬──────┬────────┬──────┬──────┬──────────
Type │Horse-power│ Furnace │ │ │ │Evap. │
│ │ │ │ │ │ from │
│ │ │ │ │ │and at│
│ │ │ │ │B.T.U.│ 212° │ Combined
│ │ │ Sq. │Per Cent│ per │ per │Efficiency
│ │ │ Ft. │of Rated│ Lb. │ Lb. │of Boiler
│ │ │Grate │Capacity│ Dry │ Dry │ and
│ │ │ Area │D’v’l’d │ Coal │ Coal │ Furnace
────────┼───────────┼──────────┼──────┼────────┼──────┼──────┼──────────
Babcock │ 300│Hand-fired│ │ │ │ │
& │ │ │ │ │ │ │
Wilcox│ │ │ 84│ 118.7│11,912│ 8.81│ 71.8
Babcock │ 640│Hand-fired│ │ │ │ │
& │ │ │ │ │ │ │
Wilcox│ │ │ 118│ 121.5│14,602│ 10.83│ 72.0
Stirling│ 1128│B. & W. │ │ │ │ │
│ │ chain │ │ │ │ │
│ │ grate │ 187│ 198.3│12,130│ 9.51│ 76.1
Rust │ 335│Hand-fired│ 68│ 210.5│13,202│ 9.42│ 68.9
Heine │ 400│Green │ │ │ │ │
│ │ chain │ │ │ │ │
│ │ grate │ 83.5│ 123.8│11,608│ 8.79│ 73.5
Maximum efficiency recorded │ │ │ │ │ 83
───────────────────────────────┴──────┴────────┴──────┴──────┴──────────
The steam delivered by a boiler is the basis of the measurement of its
capacity or power. A boiler horse-power is the delivery of 33,320 B.T.U.
per hour. It is approximately equal to the raising of 30 pounds of water
per hour from a temperature of 100° Fahrenheit, to steam at a pressure
of 70 pounds per square inch, or to 34 pounds of water per hour changed
to steam from and at 212° Fahrenheit, at atmospheric pressure. The
horse-power of a boiler is sometimes approximated by the area of its
grate or heating surface. Such a method of measuring has a low degree of
accuracy on account of the variations in the quality of the fuel, and
the rate of combustion. For example, the rate of combustion under a
locomotive boiler is high and there is less than ⅒th of a square foot of
grate area and about 4.5 square feet of heating surface per boiler
horse-power. The Scotch Marine type of boiler used on steam ships, has
slightly more grate area and slightly less heating surface than the
locomotive type of boiler, because the rate of combustion is lower.
Stationary water-tube boilers may have 2 to 3 times as much grate area
and heating surface per horse-power as is found in locomotive boilers.
If a poor type of fuel is to be used the area of the grate should be
increased about inversely as the heat content of the fuel. The
approximate heat content of various types of fuels is shown in Table 29.
TABLE 29
APPROXIMATE HEAT VALUE OF FUELS
─────────────────────────────────────┬────────────────┬────────────────
Fuel │ │Pounds of Water
│ │Evaporated from
│ │ and at 212° F.
│ │ All heat
│B.T.U. per Pound│ utilized
─────────────────────────────────────┼────────────────┼────────────────
Anthracite │ 13,500│ 14.0
Semi-bituminous, Pennsylvania │ 15,000│ 15.5
Semi-bituminous, best, West Virginia │ 15,000│ 15.8
Bituminous, best, Pennsylvania │ 14,450│ 15.0
Bituminous, poor, Illinois │ 10,500│ 10.9
Lignite, best, Utah │ 11,000│ 11.4
Lignite, poor, Oregon │ 8,500│ 8.8
Wood, best oak │ 9,300│ 9.6
Wood, poor ash │ 8,500│ 8.8
─────────────────────────────────────┴────────────────┴────────────────
=83. Air Ejectors.=—The Ansonia compressed-air sewage ejector is shown
in Fig. 68. In its operation, sewage enters the reservoir through the
inlet pipe at the right, the air displaced being expelled slowly through
the air valve marked B. The rising sewage lifts the float which actuates
the balanced piston valve in the pipe above the reservoir when the
reservoir fills. The lifting of the valve admits compressed air to the
reservoir. The air pressure closes valve A and the inlet valve at the
right, and ejects the sewage through the discharge pipe at the left. As
the float drops with the descending sewage it shuts off the air supply
and opens the air exhaust through the small pipe at the top center.
Sewage is prevented from flowing back into the reservoir by the check
valve in the discharge pipe. Other ejectors operating on a similar
principle are the Ellis, the Pacific, the Priestmann and the Shone.
=84. Electric Motors.=—The most common form of alternating current
electric motor used for driving sewage pumps where continuous operation
and steady loads are met is the squirrel-cage polyphase induction motor.
These motors operate at a nearly constant speed which should be selected
to develop the maximum efficiency of the pump and motor set. While Fig.
59 shows the best efficiency under varying heads to be obtained with
variable speed, the advantages of cost, attention, and availability make
the use of a constant speed motor common.[47] This type of motor is
undesirable where stopping and starting are frequent because it has a
relatively small starting torque and it requires a large starting
current. Such motors can be constructed in small sizes for high starting
torques by increasing the resistance of the rotor, but at the expense of
the efficiency of operation.
[Illustration:
FIG. 68.—Ansonia Compressed-Air Sewage Ejector.
]
Alternating current motors are more generally used than direct-current
motors because of the greater economy of transmission of alternating
current, but where direct current is available constant speed shunt
wound motors should be adopted.
In the selection of a motor to drive a centrifugal pump it is important
that the motor have not only the requisite power, but that its speed
will develop the maximum efficiency from the pump and motor combined. If
the pump and motor operate on the same shaft the speed of the two
machines must be the same. If the two are belt connected, the size of
the pulleys may be selected so as to give the required speed. If the
motor is to be connected to a power pump an adequate automatic pressure
relief valve should be provided on the discharge pipe from the pump, to
prevent the overloading of the motor or bursting of the pump in case of
a sudden stoppage in the pipe. The motor must be selected to suit the
conditions of voltage, cycle, and phase on the line. Transformers are
available to step the voltage up or down to practically any value.
Rotary converters are used to change direct to alternating current or
vice versa.
=85. Internal Combustion Engines.=—Internal combustion engines are used
for driving pumps. Units are available in size from fractions of 1
horse-power to 2,000 horse-power or more, although the use of the larger
sizes is exceptional. These engines are not commonly used for sewage
pumping but when used they are ordinarily belt connected to a
centrifugal pump, or to an electric generator which in turn drives
electric motors which operate centrifugal pumps. This type of engine is
more commonly adapted to small loads, although not entirely confined to
this field, as they serve admirably as emergency units to supplement an
electrically equipped pumping station. The fuel efficiency of internal
combustion engines is higher than for steam engines as is indicated in
Table 30, but the fuel is more expensive.
The four-cycle gas engine shown in Fig. 69 is the type most commonly
used. Its horse-power is the product of: the mean effective pressure,
the length of the stroke, the area of the piston, and the number of
explosions per second divided by 550. The M.E.P. is dependent on the
character of the fuel used and the compression of the gas before
ignition. Producer gas will furnish mean effective pressures between 60
and 70 pounds per square inch, natural gas and gasoline, 85 to 90 pounds
per square inch, and alcohol from 95 to 110 pounds per square inch.
TABLE 30
COMPARATIVE FUEL COSTS FOR PRIME MOVERS
───────────────────────────────────────┬───────────────┬───────────────
Type of Engine │ Quantity of │Cost of Fuel in
│ Fuel per H.P. │ Cents per
│ Hour │ Horse-power
│ │ Hour
───────────────────────────────────────┼───────────────┼───────────────
Reciprocating steam engines, simple, │ 21 to 8 lb. │ 4.2 to 1.6
non-condensing, 25 to 200 H.P. │ coal │
Triple condensing, 2000 to 10,000 │2.3 to 1.9 lb. │ 0.46 to 0.37
H.P. │ coal │
───────────────────────────────────────┼───────────────┼───────────────
Steam turbines, high pressure, │ │
non-condensing, │ │
200 to 500 K.W. │6.5 to 4.2 lb. │ 1.3 to 0.86
│ coal │
500 to 3000 K.W. │2.6 to 1.9 lb. │ 0.52 to 0.37
│ coal │
Condensing 5000 to 20,000 K.W. │1.8 to 1.43 lb.│ 0.36 to 0.28
│ coal │
───────────────────────────────────────┼───────────────┼───────────────
Gas engines │ │
Natural gas, 50 to 200 H.P. │ 19 to 11 cu. │
│ ft. │
Producer gas, 50 to 200 H.P. │ 2 to 1.5 cu. │
│ ft. │
Illuminating gas, 10 to 75 H.P. │ 26 to 19 cu. │ 2.1 to 1.5
│ ft. │
Gasoline, 10 to 75 H.P. │ 1.5 to 0.8 │ 5.6 to 3.0
│ pints │
───────────────────────────────────────┼───────────────┼───────────────
Oil engines, 100 to 500 H.P. │1.1 to 0.75 lb.│
│ oil │
───────────────────────────────────────┴───────────────┴───────────────
NOTE.—Coal assumed at $4.00 per ton, illuminating gas at 80 cents per
thousand cubic feet, and gasoline at 30 cents per gallon.
[Illustration:
FIG. 69.—Bessemer Oil Engine. Twin Cylinder, Valve Side.
]
The Diesel Engine is the most efficient of internal combustion engines.
The original aim of the inventor, Dr. Rudolph Diesel, was to avoid the
explosive effect of the ordinary internal combustion engine by injecting
a fuel into air so highly compressed that its heat would ignite the
fuel, causing slow combustion of the fuel thus utilizing its energy to a
greater extent. The fuel and air were to be so proportioned as to
require no cooling. Although the ideal condition has not been attained,
the heat efficiency of Diesel engines is high. They will consume from
0.3 to 0.5 of a pound of oil (containing 18,000 B.T.U. per pound) per
brake horse-power hour, giving an effective heat efficiency of 25 to 30
per cent. Although not now in extensive use in the United States it is
probable that this engine will be more generally adopted for conditions
suitable for internal combustion engines.
=86. Selection of Pumping Machinery.=—Centrifugal pumps are particularly
adapted to the lifting of sewage because of their large passages, and
their lack of valves. The low lifts, nearly constant head, and the
possibility of equalizing the load by means of reservoirs are
particularly suited to efficient operation of centrifugal pumps. They
require less floor space than reciprocating pumps of the same capacity,
and because of their freedom from vibration they do not demand so heavy
a foundation. The discharge from the pump is continuous thus relieving
the piping from vibration. In case of emergency the discharge valve can
be shut off without shutting down the pump, an important point in “fool
proof” operation.
Volute pumps are better adapted to pumping sewage as their passages are
more free and they are better suited to the low lifts met. Gritty and
solid matter will cause wear on the diffusion vanes of turbine pumps in
spite of the most careful design. Although turbine pumps can possibly be
built with higher efficiency than volute pumps, their efficiency at part
load falls rapidly and the fluctuations of sewage flow are sufficient to
affect the economy of operation. Turbine pumps are more expensive and
heavier than volute pumps on account of the increased size necessitated
by the diffusion vanes.
Multi-stage pumps are used for high lifts and are seldom if ever
required in sewage pumping. As ordinarily manufactured, each stage is
good for an additional 40 to 100 pounds pressure, but wide variations in
the limiting pressures between stages are to be found.
Reciprocating plunger pumps are sometimes used for sewage pumping where
the character of the sewage is such that the valves will not be clogged
nor parts of the pump corroded. These pumps are seldom used in small
installations or for low lifts. They are not adapted to automatic or
long distance control as are electrically driven centrifugal pumps. The
use of reciprocating pumps for sewage pumping is practically restricted
to very large pumping stations with capacities in the neighborhood of
50,000,000 gallons per day or more. Steam-driven pumps are the most
common of the reciprocating type, but power pumps are sometimes used in
special cases for small installations and may be driven by either a
steam or gas engine or an electric motor.
Compressed air ejectors, as described in Art. 83 are used for lifting
sewage and other drainage from the basement of buildings below the sewer
level.
Centrifugal pumps electrically driven are, as a rule, the most
satisfactory for sewage pumping. Electric drive lends itself to control
by automatic devices, which are particularly convenient in small pumping
stations. The control can be arranged so that the pump is operated only
at full load and high efficiency, and when not operating no power is
being consumed, as is not the case with a steam pump where steam
pressure must be maintained at all times. The electric driven pump is
thrown into operation by a float controlled switch which is closed when
the reservoir fills, and opens when the pump has emptied the reservoir.
The choice between steam and electric power for large pumping stations
is a matter of relative reliability and economy.
The selection of the proper type of pump, whether reciprocating or
otherwise, requires some experience in the consideration of the factors
involved. Fig. 70 is of some assistance. In discussing this figure,
Chester states:
“Fig. 70 attempts to represent graphically, the writer’s ideas
under general conditions, of the machines that should be selected
for certain capacities for both principal engine and alternate and
the station duty they may be expected to produce, but you must
realize that this intends the principal engine doing at least 90
per cent of the work and that the head, the cost of coal, the load
factor, the cost of real estate ... the boiler pressure, and the
space available, and finally ... the funds available, are factors
which may shift both the horizontal and curved lines. In the field
of low service pumps of 10,000,000 capacity or over, the
centrifugal pump reigns supreme, and for constant low heads of
20,000,000 capacity or over the turbine driven centrifugal usurps
the field.”
A reciprocating pump of any type would have to be specially built for
pumping sewage not carefully screened or otherwise treated, as the
valves, ordinarily used in such pumps for lifting water, would clog. The
vertical triple-expansion pumping engine with special valves and for
large installations, and the centrifugal pump for large or small
installations are the only suitable types for pumping sewage. With steam
turbine or electric drive the centrifugal has the field to itself.
[Illustration:
FIG. 70.—Expectancy Curves for Pumping Engines Working against a
Pressure of 100 Pounds per Square Inch.
J. N. Chester, Journal Am. Water Works Ass’n, Vol. 3, 1916, p. 493.
]
=87. Costs of Pumping Machinery.=—The cost of pumping machinery can not
be stated accurately as the many factors involved vary with the
fluctuations in the prices of raw materials, transportation, labor, etc.
The actual purchase price of machinery can be found accurately only from
the seller. The costs given in this chapter are useful principally for
comparative purposes and for exercise in the making of estimates. The
costs of complete pumping stations are shown in Table 31.[48] These
figures represent costs in 1911.
TABLE 31
COSTS OF COMPLETE PUMPING STATIONS
These costs include the best type of triple-expansion engines,
high-pressure boilers, brick or inexpensive stone building with slate
roof, chimney and intake. Cost of land is not included.
─────────────────┬─────────────────┬─────────────────┬─────────────────
Discharge │ Horse-power per │ │
Pressure, Lbs. │ Million Gals. │Cost, Dollars per│Cost, Dollars per
per Sq. In. │ Pumped │ Horse-power │ Million Gallons
─────────────────┼─────────────────┼─────────────────┼─────────────────
30│ 12│ 562│ 6,750
40│ 16│ 438│ 7,000
50│ 20│ 362│ 7,250
60│ 24│ 312│ 7,500
70│ 28│ 277│ 7,750
80│ 32│ 250│ 8,000
90│ 36│ 229│ 8,250
100│ 40│ 213│ 8,500
110│ 44│ 200│ 8,750
120│ 48│ 187│ 9,000
130│ 52│ 192│ 10,000
│ │ │
─────────────────┴─────────────────┴─────────────────┴─────────────────
=88. Cost Comparisons of Different Designs.=—In the design of a pumping
station and its equipment the relative costs of different designs should
be compared, and the least expensive design selected, due consideration
being given to serviceability, reliability, and other factors without
definite financial value. In comparing the costs of different types of
machinery, all items in connection with the pumping station should be
considered. For example, the cost of an electrically driven centrifugal
pump and equipment may be less than the total cost of a steam driven
reciprocating pump and equipment because of the saving in the cost of
boilers, boiler house, etc., but a comparison of the capitalized cost of
the two might show in favor of the reciprocating steam pump because of
the lower cost of operation.
The total cost of a plant, or any portion thereof, may be considered as
made up of three parts: (1) The first cost, (2) operation and
maintenance and, (3) renewal. The total cost S can be expressed as
_S_ = _C_ + _O_⁄_r_ + _R_,
in which _C_ = the first cost;
_O_ = the annual expenditure for operation and maintenance;
_R_ = the amount set aside to cover renewal;
_r_ = the rate of interest.
_S_ is called the capitalized cost of a plant. The annual payment
necessary to perpetuate a plant is
_A_ = _Sr_ = _Cr_ + _O_ + _Rr_.
The value of _R_ is useful when expressed in terms of the life of the
plant or machine and the current rate of interest. It is sometimes
called the depreciation factor or capitalized depreciation. If it is
borne in mind that _R_ is the amount to be set aside at compound
interest for the life of the plant, at the end of which time the accrued
interest should be sufficient to renew the plant, it is evident that
_R_(1 + _R_)^n − _R_ = _C_
or _R_ = _C_⁄((1+_r_)^n − 1)
in which _n_ is the period of usefulness, or life of the plant,
expressed in years, no allowance being made for scrap value.
A comparison of the annual expense of three different plants is shown in
Table 32. It is evident from this comparison that the machinery with the
least first cost is not always the least expensive when all items are
considered.
A sinking fund is a sum of money to which additions are made annually
for the purpose of renewing a plant at the expiration of its period of
usefulness. The annual payment into the sinking fund is equivalent to
the term _Rr_ in the expression for annual cost, or in terms of _C_,
_r_, and _n_, the annual payment is
_Cr_⁄((1 + _r_)^n − 1).
It is the same as the capitalized depreciation multiplied by the rate of
interest. The expression _r_⁄((1 + _r_)^n − 1) is sometimes called the
rate of depreciation.
The present worth of a machine is the difference between its first cost
and the present value of the sinking fund. If _m_ represents the present
age of a plant in years, then the present worth is
_P_ = _C_(1 – ((1 + _r_)^n − 1)⁄((1 + _r_)^m − 1)).
TABLE 32
COMPARISON OF COSTS OF THREE DIFFERENT PUMPING STATIONS. NOMINAL
CAPACITY THIRTY MILLION GALLONS PER DAY RAISED THIRTY FEET
────────────────┬──────────────────────────────────
Equipment │ Plant A
────────────────┼──────────────────────────────────
│One Acre of Land. Brick Building,
│ Steel Trussed Roof, Slate
│ Covered. Cross Compound
│ Condensing Horizontal Pumping
│ Engine
────────────────┼───────┬──────────┬───────┬───────
│Annual │ Years of │Sinking│ Total
│Payment│Usefulness│ Fund │
│ on │ │Payment│
│ First │ │ │
│ Cost │ │ │
────────────────┼───────┼──────────┼───────┼───────
Land │ 100│ │ 0│ 100
Permanent │ 1188│ 50│ 1080│ 2,260
Structures[49]│ │ │ │
Pumps and │ 440│ 15│ 435│ 875
Machinery │ │ │ │
Boilers │ 280│ 10│ 446│ 726
Labor │ │ │ │ 14,000
Fuel │ │ │ │ 5,500
Repairs, etc. │ │ │ │ 480
────────────────┼───────┼──────────┼───────┼───────
Total │ │ │ │ 23,941
────────────────┴───────┴──────────┴───────┴───────
────────────────┬──────────────────────────────────
Equipment │ Plant B
────────────────┼──────────────────────────────────
│One Acre of Land. Brick Building.
│ Steel Trussed Roof, Slate
│ Covered. Compound Condensing Low
│ Duty Horizontal Pumping Engine
│
────────────────┼───────┬──────────┬───────┬───────
│Annual │ Years of │Sinking│ Total
│Payment│Usefulness│ Fund │
│ on │ │Payment│
│ First │ │ │
│ Cost │ │ │
────────────────┼───────┼──────────┼───────┼───────
Land │ 100│ │ 0│ 100
Permanent │ 1180│ 50│ 1080│ 2,260
Structures[49]│ │ │ │
Pumps and │ 390│ 15│ 395│ 785
Machinery │ │ │ │
Boilers │ 252│ 10│ 400│ 652
Labor │ │ │ │ 14,000
Fuel │ │ │ │ 7,200
Repairs, etc. │ │ │ │ 400
────────────────┼───────┼──────────┼───────┼───────
Total │ │ │ │ 25,497
────────────────┴───────┴──────────┴───────┴───────
────────────────┬──────────────────────────────────
Equipment │ Plant C
────────────────┼──────────────────────────────────
│One Acre of Land. Frame Building,
│ Shingle Roof. Compound Duplex
│ Non-Condensing Pumping Engine.
│
│
────────────────┼───────┬──────────┬───────┬───────
│Annual │ Years of │Sinking│ Total
│Payment│Usefulness│ Fund │
│ on │ │Payment│
│ First │ │ │
│ Cost │ │ │
────────────────┼───────┼──────────┼───────┼───────
Land │ 100│ │ 0│ 100
Permanent │ 810│ 50│ 775│ 1,585
Structures[49]│ │ │ │
Pumps and │ 360│ 15│ 352│ 712
Machinery │ │ │ │
Boilers │ 308│ 10│ 490│ 798
Labor │ │ │ │ 14,000
Fuel │ │ │ │ 8,200
Repairs, etc. │ │ │ │ 550
────────────────┼───────┼──────────┼───────┼───────
Total │ │ │ │ 25,945
────────────────┴───────┴──────────┴───────┴───────
Where straight-line depreciation is spoken of it is assumed that the
worth of a machine depreciates an equal part of its first cost each
year. For example, if the life of a plant is assumed to be 20 years,
straight-line depreciation will assume that the plant loses 1/20 of its
original value annually. The present worth of a plant under this
assumption would be the product of its first cost and the ratio between
its remaining life and its total life. This method of estimating
depreciation and worth is frequently used, particularly for short-lived
plants and for simplicity in bookkeeping, but it is less logical than
the method given above.
=89. Number and Capacity of Pumping Units.=—In order to select the
number and capacity of pumping units for the best economy, a comparison
of the costs of different combinations of units should be made and the
most economical combination determined by trial. The principles outlined
in the preceding articles should be observed in making these
comparisons. In a steam pumping station, when the number of units
operating is less than the average daily maximum for the period, steam
must nevertheless be kept on a sufficient number of boilers to operate
the maximum number of pumps. This, and corresponding standby losses must
not be overlooked, as they may show that a smaller number of larger
units is ultimately more economical.
TABLE 33
SUMMARY OF FLUCTUATIONS OF SEWAGE FLOW AT A PROPOSED PUMPING STATION
─────────────────┬─────────────────┬─────────────────┬─────────────────
Number of Days │Flow in Thousand │ │
Loads Occurred in│ Gallons per │ │
One Year │ Minute │ Lift in Feet │ Horse-power
─────────────────┼─────────────────┼─────────────────┼─────────────────
1│ 293│ 6.0│ 450
8│ 163│ 8.6│ 354
15│ 119│ 10.0│ 300
18│ 106│ 10.6│ 284
23│ 88│ 11.2│ 249
31│ 69│ 12.2│ 211
32│ 65│ 12.4│ 204
45│ 51│ 13.4│ 173
41│ 50│ 13.5│ 169
30│ 45│ 13.8│ 158
28│ 44│ 13.9│ 154
23│ 40│ 14.2│ 143
21│ 38│ 14.4│ 137
18│ 35│ 14.6│ 129
12│ 29│ 15.0│ 111
8│ 24│ 15.6│ 95
5│ 20│ 16.0│ 79
3│ 16│ 16.5│ 65
2│ 14│ 16.8│ 58
1│ 6.5│ 18.0│ 29
─────────────────┴─────────────────┴─────────────────┴─────────────────
Total horse-power days for one year, 102,000.
Average load in horse-power, 280.
TABLE 34
POSSIBLE COMBINATIONS OF FIVE PUMPING UNITS TO CARE FOR THE LOADS SHOWN
IN TABLE 33[50]
──────────────────────────────────┬───────────────
40 Horse-power │ Load
Type 1[51] │
────────┬──────┬───────────┬──────┼───────┬───────
Per Cent│Pounds│ Load in │Pounds│Number │ Total
of Rated│Steam │Horse-power│Steam,│of Days│ Load
Capacity│ per │ │Units │Load is│Carried
│ H.P. │ │10,000│Carried│ on
│ Hour │ │Pounds│in Year│ these
│ │ │ │ │Days in
│ │ │ │ │ H.P.
────────┼──────┼───────────┼──────┼───────┼───────
151│ 45│ 60.4│ 6.5│ 1│ 681
120│ 44│ 48│ 40.5│ 8│ 542
102│ 45│ 40.8│ 66.1│ 15│ 458
96│ 45│ 38.4│ 74.8│ 18│ 434
98│ 45│ 39.2│ 97.5│ 23│ 381
│ │ │ │ 31│ 322
│ │ │ │ 32│ 312
│ │ │ │ 45│ 264
│ │ │ │ 41│ 258
101│ 45│ 40.4│ 131│ 30│ 242
98│ 45│ 39.2│ 119│ 28│ 235
│ │ │ │ 23│ 218
│ │ │ │ 21│ 210
│ │ │ │ 18│ 198
│ │ │ │ 12│ 170
104│ 45│ 41.6│ 20.9│ 8│ 145
│ │ │ │ 5│ 121
│ │ │ │ 3│ 100
99│ 45│ 39.6│ 8.5│ 2│ 89
113│ 44│ 45.2│ 4.8│ 1│ 45
│ │ │ ————│ │
Sub-total │ 596.6│ │
Grand total in pounds, 65,700,000
──────────────────────────────────────────────────
──────────────────────────────────┬───────────────
50 Horse-power │ Load
Type 1[51] │
────────┬──────┬───────────┬──────┼───────┬───────
Per Cent│Pounds│ Load in │Pounds│Number │ Total
of Rated│Steam │Horse-power│Steam,│of Days│ Load
Capacity│ per │ │Units │Load is│Carried
│ H.P. │ │10,000│Carried│ on
│ Hour │ │Pounds│in Year│ these
│ │ │ │ │Days in
│ │ │ │ │ H.P.
────────┼──────┼───────────┼──────┼───────┼───────
151│ 45│ 75.5│ 8.2│ 1│ 681
120│ 44│ 60.0│ 50.7│ 8│ 542
102│ 45│ 51.0│ 82.7│ 15│ 458
90│ 45│ 48.0│ 93.5│ 18│ 434
98│ 45│ 49.0│ 122.0│ 23│ 381
104│ 45│ 52.0│ 174.5│ 31│ 322
101│ 45│ 50.5│ 174.8│ 32│ 312
│ │ │ │ 45│ 264
103│ 45│ 51.5│ 228│ 41│ 258
│ │ │ │ 30│ 242
│ │ │ │ 28│ 235
│ │ │ │ 23│ 218
│ │ │ │ 21│ 210
│ │ │ │ 18│ 198
│ │ │ │ 12│ 170
│ │ │ │ 8│ 145
109│ 44│ 54.5│ 28.8│ 5│ 121
│ │ │ │ 3│ 100
99│ 45│ 49.5│ 10.7│ 2│ 89
│ │ │ │ 1│ 45
│ │ │ ————│ │
│ 973.9│ │
──────────────────────────────────────────────────
──────────────────────────────────┬───────────────
60 Horse-power │ Load
Type 1[51] │
────────┬──────┬───────────┬──────┼───────┬───────
Per Cent│Pounds│ Load in │Pounds│Number │ Total
of Rated│Steam │Horse-power│Steam,│of Days│ Load
Capacity│ per │ │Units │Load is│Carried
│ H.P. │ │10,000│Carried│ on
│ Hour │ │Pounds│in Year│ these
│ │ │ │ │Days in
│ │ │ │ │ H.P.
────────┼──────┼───────────┼──────┼───────┼───────
151│ 45│ 90.6│ 9.8│ 1│ 681
120│ 44│ 72.0│ 60.8│ 8│ 542
102│ 45│ 61.2│ 99.2│ 15│ 458
96│ 45│ 57.6│ 112│ 18│ 434
│ │ │ │ 23│ 381
104│ 45│ 62.4│ 209.0│ 31│ 322
101│ 45│ 60.6│ 210│ 32│ 312
102│ 45│ 61.2│ 325│ 45│ 264
│ │ │ │ 41│ 258
│ │ │ │ 30│ 242
│ │ │ │ 28│ 235
│ │ │ │ 23│ 218
│ │ │ │ 21│ 210
│ │ │ │ 18│ 198
106│ 45│ 63.6│ 137│ 12│ 170
│ │ │ │ 8│ 145
109│ 44│ 65.4│ 34.5│ 5│ 121
│ │ │ │ 3│ 100
│ │ │ │ 2│ 89
│ │ │ │ 1│ 45
│ │ │ ————│ │
│1197.3│ │
──────────────────────────────────────────────────
──────────────────────────────────┬───────────────
100 Horse-power │ Load
Type 4[51] │
────────┬──────┬───────────┬──────┼───────┬───────
Per Cent│Pounds│ Load in │Pounds│Number │ Total
of Rated│Steam │Horse-power│Steam,│of Days│ Load
Capacity│ per │ │Units │Load is│Carried
│ H.P. │ │10,000│Carried│ on
│ Hour │ │Pounds│in Year│ these
│ │ │ │ │Days in
│ │ │ │ │ H.P.
────────┼──────┼───────────┼──────┼───────┼───────
151│ 28│ 151│ 10.2│ 1│ 681
120│ 25│ 120│ 57.5│ 8│ 542
102│ 25│ 102│ 62.5│ 15│ 458
96│ 25│ 96│ 103.8│ 18│ 434
98│ 25│ 98│ 135.1│ 23│ 381
│ │ │ │ 31│ 322
│ │ │ │ 32│ 312
│ │ │ │ 45│ 264
│ │ │ │ 41│ 258
│ │ │ │ 30│ 242
│ │ │ │ 28│ 235
│ │ │ │ 23│ 218
│ │ │ │ 21│ 210
│ │ │ │ 18│ 198
106│ 25│ 106│ 76.5│ 12│ 170
104│ 25│ 104│ 29.1│ 8│ 145
│ │ │ │ 5│ 121
100│ 25│ 100│ 32.4│ 3│ 100
│ │ │ │ 2│ 89
│ │ │ │ 1│ 45
│ │ │ ————│ │
│ 507.1│ │
──────────────────────────────────────────────────
──────────────────────────────────┬───────────────
200 Horse-power │ Load
Type 5[51] │
────────┬──────┬───────────┬──────┼───────┬───────
Per Cent│Pounds│ Load in │Pounds│Number │ Total
of Rated│Steam │Horse-power│Steam,│of Days│ Load
Capacity│ per │ │Units │Load is│Carried
│ H.P. │ │10,000│Carried│ on
│ Hour │ │Pounds│in Year│ these
│ │ │ │ │Days in
│ │ │ │ │ H.P.
────────┼──────┼───────────┼──────┼───────┼───────
151│ 23│ 302│ 16.7│ 1│ 681
120│ 20│ 240│ 92.0│ 8│ 542
102│ 20│ 204│ 147│ 15│ 458
96│ 20│ 192│ 166│ 18│ 434
98│ 20│ 196│ 216│ 23│ 381
104│ 20│ 208│ 309.5│ 31│ 322
101│ 20│ 202│ 310│ 32│ 312
102│ 20│ 204│ 481│ 45│ 264
103│ 20│ 206│ 405│ 41│ 258
101│ 20│ 202│ 291│ 30│ 242
98│ 20│ 196│ 264│ 28│ 235
109│ 20│ 218│ 241│ 23│ 218
105│ 20│ 210│ 212│ 21│ 210
99│ 20│ 198│ 171│ 18│ 198
│ │ │ │ 12│ 170
│ │ │ │ 8│ 145
│ │ │ │ 5│ 121
│ │ │ │ 3│ 100
│ │ │ │ 2│ 89
│ │ │ │ 1│ 45
│ │ │ ————│ │
│3322.2│ │
──────────────────────────────────────────────────
TABLE 35
FINANCIAL COMPARISON OF PUMPING EQUIPMENTS
The loads to be cared for are shown in Table 34. An emergency unit is
supplied to bring the overload capacity of the plant, less the largest
unit, equal to the maximum load on the plant. No unit will be
overloaded more than fifty per cent of its rated capacity.
───────────┬───────────┬───────────┬───────────┬───────────┬───────────
Number of │ │ │ │ │
Units │ │ │ │ │
Exclusive │ │ │ │ │
of │ │ │ │ │
Emergency │ │ │ │ │
Unit │ 5 │ 4 │ 3 │ 2 │ 1
───────────┼───────────┼───────────┼───────────┼───────────┼───────────
Capacity │ 40 h.p.,│ │ │ │
and Type of│ Type 1│ │ │ │
Units │ 50 h.p.,│ 50 h.p.,│ │ │
│ Type 1│ Type 1│ │ │
│ 60 h.p.,│ 100 h.p.,│ 50 h.p.,│ │
│ Type 1│ Type 4│ Type 1│ │
│ 100 h.p.,│ 125 h.p.,│ 150 h.p.,│ 200 h.p.,│
│ Type 4│ Type 4│ Type 5│ Type 5│
│ 200 h.p.,│ 175 h.p.,│ 250 h.p.,│ 250 h.p.,│ 450 h.p.,
│ Type 5│ Type 5│ Type 6│ Type 6│ Type 7
───────────┼───────────┼───────────┼───────────┼───────────┼───────────
Emergency │ │ │ │ │
Unit, │ │ │ │ │
Capacity │ 200 h.p.,│ 175 h.p.,│ 250 h.p.,│ 250 h.p.,│ 450 h.p.,
and Type │ Type 5│ Type 5│ Type 6│ Type 6│ Type 7
───────────┼───────────┼───────────┼───────────┼───────────┼───────────
Annual │ │ │ │ │
payments,│ │ │ │ │
Dollars │ │ │ │ │
First │ │ │ │ │
cost of│ │ │ │ │
pumps │ 1,560│ 1,660│ 1,480│ 1,440│ 1,500
Renewal │ │ │ │ │
of │ │ │ │ │
pumps │ 1,340│ 1,430│ 1,270│ 1,240│ 1,290
First │ │ │ │ │
cost, │ │ │ │ │
boilers│ 1,024│ 1,089│ 1,125│ 1,115│ 1,410
Renewal, │ │ │ │ │
boilers│ 800│ 935│ 966│ 958│ 1,210
Fuel │ 13,140│ 11,860│ 10,490│ 9,420│ 9,400
Repairs, │ │ │ │ │
oil, │ │ │ │ │
etc. │ 2,000│ 1,800│ 1,500│ 1,300│ 1,200
Labor │ 35,000│ 31,500│ 29,500│ 27,000│ 27,000
Emergency│ │ │ │ │
unit. │ │ │ │ │
First │ │ │ │ │
cost │ 640│ 560│ 800│ 800│ 1,500
Emergency│ │ │ │ │
unit. │ │ │ │ │
Renewal│ 550│ 480│ 690│ 690│ 1,290
───────────┼───────────┼───────────┼───────────┼───────────┼───────────
Total │ 56,134│ 51,314│ 47,821│ 43,963│ 45,800
───────────┴───────────┴───────────┴───────────┴───────────┴───────────
Type 1. Simple duplex, non-condensing, horizontal.
Type 4. Compound condensing low duty horizontal.
Type 5. Low duty, triple, condensing, horizontal.
Type 6. Cross compound, condensing, horizontal.
Type 7. High duty, triple, condensing, vertical.
For example, the sewage flow expected at a proposed pumping station is
shown in Table 33. The steps involved in the selection of the number and
capacity of pumping units to care for these quantities are as follows:
(1) Determine the rated capacity of the equipment to be provided. In
this case the capacity will be taken as 450 horse-power, which is the
maximum load to be placed on the pumps. (2) Select any number of units
of such different types and capacities as are available for comparison,
and arrange them in different combinations so that each unit will
operate as nearly as possible at its rated capacity. The work involved
in such a study for 5 units is shown in Table 34. The weight of steam
consumed per indicated horse-power hour corresponding to the per cent of
the rated capacity at which the unit is operating is read from Fig. 64
or other data. (3) Repeat this step for other numbers and types of
units. (4) Prepare a table showing the annual costs of combinations of
different numbers and types of units as shown for this example in Table
35. The figures in Table 35 show that the least expensive of the
combinations of the units studied is one 200 horse-power unit, and one
250 horse-power unit, with a 250 horse-power unit in reserve. It is to
be noted that a reserve unit has been provided in each combination, the
capacity of which is equal to that of the largest unit of the
combination.
CHAPTER VIII
MATERIALS FOR SEWERS
=90. Materials.=—The materials most commonly used for the manufacture of
sewer pipe are vitrified clay and concrete. Cast iron, steel, and wood
are also used, but only under special conditions. For pipes built in the
trench, concrete, concrete blocks, brick, and vitrified clay blocks are
used. Concrete is being used to-day more than bricks or blocks because
it is cheaper. A decade or more ago all large sewers were built of
bricks. Vitrified clay and concrete are used for manufactured pipe 42
inches and less in diameter. Concrete is used almost exclusively for
larger sizes of pipe, particularly for pipe constructed in place,
although a brick invert lining is advisable when high velocities of flow
are expected.
The character of the external load, the velocity of flow and the quality
of sewage are important factors in determining the material to be used
in the construction of sewers. Reinforced concrete should be used for
large sewers near the surface subjected to heavy moving loads. A high
velocity of flow with erosive suspended matter demand a brick wearing
surface on the invert. Many engineers consider concrete less suitable
than vitrified clay or brick for conveying septic sewage or acid
industrial wastes, as concrete deteriorates more rapidly under such
conditions. Concrete should be used on soft yielding foundations,
whereas a hard compact earth, which can be cut to the form of the sewer,
is suitable to the use of brick or concrete.
Cast-iron pipe with lead joints is used for sewers flowing under
pressure, or where movements of the soil are to be expected. If the
sewage is not flowing under pressure, cement joints are sometimes used
in the cast-iron pipe. Movements of the soil are to be expected on side
hills, under railroad tracks, etc. Steel pipe is used on long outfalls
or under other conditions where external loads are light and the cost is
less than for other materials. Because of the thin plates used and the
liability to corrosion steel is not frequently used. It should never be
deeply buried nor externally loaded because of its weakness in resisting
such forces. Like wood pipe, its lightness is favorable to use on
bridges, but the greater heat conductivity of steel than wood
necessitates protection against freezing in exposed positions. Wood is
preferable only where the economy of its use is pronounced and the pipe
is running full at all times. It is desirable that the wood pipe should
be always submerged as the life of alternately wet and dry wood is
short.
Corrugated galvanized iron and unglazed tile have been used for sewers,
but usually only in emergencies or as a makeshift. Corrugated iron is
not suitable on account of its roughness and liability to corrosion, and
unglazed tile because of its lack of strength.
[Illustration:
FIG. 71.—Diagrammatic Section through Clay-pipe Press.
]
=91. Vitrified Clay Pipe.=—In general the physical and chemical
qualities of clays before burning are not sufficient to cause their
condemnation or approval by the engineer, as their behavior in the
furnace is quite individual and depends greatly on the manner in which
they are fired. The engineer is interested in the result and writes his
specifications accordingly.
In the manufacture of clay pipe, the clay as excavated is taken to a
mill and ground while dry, to as fine a condition as possible. It is
then sent to storage bins from which it is taken for wet grinding and
tempering. In this process the clay is mixed with water to the proper
degree of plasticity. A variation of 1 to 1½ per cent in the moisture
content will mean failure. Too wet a mixture will not have sufficient
strength to maintain its shape in the kiln. Too dry a mixture will show
laminations as it is pressed through the discs.
A press used in the manufacture of clay pipe is shown in cross-section
in Fig. 71. With the piston heads in the steam and mud cylinders at
their extreme upward positions, the mud cylinder is filled with clay of
the proper consistency. Steam is then turned into the steam cylinder
under pressure and the clay is squeezed into the space between the inner
and outer shells of the die and mandrel to form the hub of the pipe. The
pressure on the clay may be from 250 to 600 pounds per square inch. When
clay appears at the holes, marked _hh_ at the bottom of the mud
cylinder, the bottom plate and the center portion of the die are removed
and the remainder or straight portion of the pipe is formed by squeezing
the clay between the mandrel and the outer wall of the die. A completely
formed pipe can be seen issuing from the press in Fig. 72. Any sized
pipe that is desired can be formed from the same press by changing the
size of the dies and mandrel.
[Illustration:
FIG. 72.—Clay-pipe Press.
Courtesy, Blackmer and Post Manufacturing Co.
]
Curved pipes are made in two ways—by bending directly as they issue from
the press, or by shaping by hand in plaster of paris molds. Junctions
are made by cutting the branch pipe to the shape of the outside of the
main pipe, fastening the branch in place with soft clay and then cutting
out the wall of the main pipe the size of the branch. Special fittings
are usually made by hand in plaster molds.
After being pressed into shape the pipes are taken to a steam-heated
drying room where a constant temperature is maintained in order to
prevent cracking of the pipes. They remain in the drying room from 3 to
10 days until dry, when they are taken to the kilns. If taken to the
kilns when moist blisters will be produced.
The dried pipes are piled carefully in the kiln so that heat and weight
may be as evenly distributed as possible, and the fire is then started
in the kiln. The process of burning can be roughly divided into five
stages:
1st. Water smoking, which lasts about 72 hours during which the
temperature is raised gradually to 350 degrees Fahrenheit.
2nd. Heating, during which the temperature is raised to 800 degrees
Fahrenheit in 24 hours.
3rd. Oxidation, during which the temperature is raised to 1,400 degrees
Fahrenheit in 84 hours.
4th. Vitrification, in which the temperature is raised to 2,100 degrees
Fahrenheit in 48 hours, and finally,
5th. Glazing, during which the temperature is unchanged but salt (NaCl)
is thrown in and allowed to burn.
Oxidation must be complete before vitrification is started as otherwise
blisters will be raised due to imprisoned carbon dioxide. The important
points in vitrification are to make the required temperature within a
reasonable time and to maintain a uniform distribution of heat
throughout the kiln. When vitrification is complete as shown by a glassy
fracture of a broken sample taken from the kiln, glazing is accomplished
by throwing a shovelful of salt on the hottest part of the fire. About
five to six applications of salt from two to three hours apart may be
needed. The kiln is then allowed to cool and the manufacture of the pipe
is complete. The completeness of vitrification is indicated by the
amount of water that the finished pipe will absorb. Completely vitrified
pipe will absorb no moisture. Soft-burned pipe may absorb as much as 15
per cent moisture.
Vitrified clay blocks are made of the same material and in the same
manner as vitrified clay pipe.
The following data on vitrified pipe have been abstracted from the
specifications for vitrified pipe adopted by the American Society for
Testing Materials.
Pipes shall be subject to rejection on account of the following:
(_a_) Variation in any dimension exceeding the permissible
variations given in Table 36.
(_b_) Fracture or cracks passing through the shell or hub, except
that a single crack at either end of a pipe not exceeding 2 inches
in length or a single fracture in the hub not exceeding 3 inches
in width nor 2 inches in length will not be deemed cause for
rejection unless these defects exist in more than 5 per cent of
the entire shipment or delivery.
(_c_) Blisters or where the glazing is broken or which exceed 3
inches in diameter, or which project more than ⅛ inch above the
surface.
(_d_) Laminations which indicate extended voids in the pipe
material.
(_e_) Fire cracks or hair cracks sufficient to impair the
strength, durability or serviceability of the pipe.
(_f_) Variations of more than ⅛ inch per linear foot in alignment
of a pipe intended to be straight.
(_g_) Glaze which does not fully cover and protect all parts of
the shell and ends except those exempted in Sect. 31. Also glaze
which is not equal to best salt glaze.
(_h_) Failure to give a clear ringing sound when placed on end and
dry tapped with a light hammer.
(_i_) Insecure attachment of branches or spurs.
_Workmanship and Finish_
(29) Pipes shall be substantially free from fractures, large or
deep cracks and blisters, laminations and surface roughness.
(31) The glaze shall consist of a continuous layer of bright or
semi-bright glass substantially free from coarse blisters and
pimples.... Not more than 10 per cent of the inner surface of any
pipe barrel shall be bare of glaze except the hub, where it may be
entirely absent. Glazing will not be required on the outer surface
of the barrel at the spigot end for a distance from the end equal
to ⅔ the specified depth of the socket for the corresponding size
of pipe. Where glazing is required there shall be absence of any
well defined network of crazing lines or hair cracks.
(32) The ends of the pipe shall be square with their longitudinal
axis.
(33) Special shapes shall have a plain spigot end and a hub end
corresponding in all respects with the dimensions specified for
pipes of the corresponding internal diameter.
TABLE 36
PROPERTIES OF CLAY SEWER PIPE
Abstracts from Tentative Specifications of the American Society for
Testing Materials
─────────┬─────────┬───────────┬───────┬────────┬──────┬──────┬─────────
Internal │ Minimum │ Maximum │Laying │Diameter│Depth │Taper │ Minimum
Diameter,│Crushing │Absorption,│length,│ of │ of │ of │Thickness
Inches │Strength,│ Per Cent │ Feet │ Inside │Socket│Socket│ of
│ Pounds │ │ │ of │Inches│ │ Barrel.
│ per │ │ │Socket, │ │ │ Inches
│ Linear │ │ │ Inches │ │ │
│ Foot. │ │ │ │ │ │
│See Note │ │ │ │ │ │
│ 2 │ │ │ │ │ │
─────────┼─────────┼───────────┼───────┼────────┼──────┼──────┼─────────
│ │ │ │ │ │ │
│ │ │ │ │ │ │
│ │ │ │ │ │ │
│ │ │ │ │ │ │
│ │ │ │ │ │ │
─────────┼─────────┼───────────┼───────┼────────┼──────┼──────┼─────────
│ │ │ │ │ │ │
│ │ │ │ │ │ │
─────────┼─────────┼───────────┼───────┼────────┼──────┼──────┼─────────
6 │ 1430 │ 5 │2, 2½, │ 8¼ │ 2 │1 : 20│ ⅝
│ │ │ 3 │ │ │ │
8 │ 1430 │ 5 │2, 2½, │ 10¾ │ 2¼ │1 : 20│ ¾
│ │ │ 3 │ │ │ │
10 │ 1570 │ 5 │2, 2½, │ 13 │ 2½ │1 : 20│ ⅞
│ │ │ 3 │ │ │ │
12 │ 1710 │ 5 │2, 2½, │ 15¼ │ 2½ │1 : 20│ 1
│ │ │ 3 │ │ │ │
15 │ 1960 │ 5 │2, 2½, │ 18¾ │ 2½ │1 : 20│ 1¼
│ │ │ 3 │ │ │ │
18 │ 2200 │ 5 │2, 2½, │ 22¼ │ 3 │1 : 20│ 1½
│ │ │ 3 │ │ │ │
21 │ 2590 │ 5 │2, 2½, │ 26 │ 3 │1 : 20│ 1¾
│ │ │ 3 │ │ │ │
24 │ 3070 │ 5 │2, 2½, │ 29½ │ 3 │1 : 20│ 2
│ │ │ 3 │ │ │ │
27 │ 3370 │ 5 │ 3 │ 33¼ │ 3½ │1 : 20│ 2¼
30 │ 3690 │ 5 │ 3 │ 37 │ 3½ │1 : 20│ 2½
33 │ 3930 │ 5 │ 3 │ 40¼ │ 4 │1 : 20│ 2⅝
36 │ 4400 │ 5 │ 3 │ 44 │ 4 │1 : 20│ 2¾
39 │ 4710 │ 5 │ 3 │ 47¼ │ 4 │1 : 20│ 2⅞
42 │ 5030 │ 5 │ 3 │ 51 │ 4 │1 : 20│ 3
─────────┴─────────┴───────────┴───────┴────────┴──────┴──────┴─────────
─────────┬────────────────────────────────────────────────┬────────
Internal │ Permissible Variations │ Number
Diameter,│ │ of
Inches │ │Scorings
│ │ on
│ │ Spigot
│ │ and
│ │Socket ⅛
│ │ Inch
│ │ Deep
─────────┼───────┬─────────────┬────────┬───────┬─────────┼────────
│Length,│ Internal │ Length │ Depth │Thickness│
│ Inches│ Diameter, │ of Two │ of │ of │
│ (-), │ Inches │Opposite│Socket,│ Barrel, │
│ per │ │ Sides, │Inches │ Inches │
│ Foot │ │ Inches │ (-) │ (-) │
─────────┼───────┼──────┬──────┼────────┼───────┼─────────┼────────
│ │Spigot│Socket│ │ │ │
│ │ (±) │ (±) │ │ │ │
─────────┼───────┼──────┼──────┼────────┼───────┼─────────┼────────
6 │ ¼ │ 3/16 │ ¼ │ ⅛ │ ¼ │ 1/16 │ 2
│ │ │ │ │ │ │
8 │ ¼ │ ¼ │ 5/16 │ ⅛ │ ¼ │ 1/16 │ 2
│ │ │ │ │ │ │
10 │ ¼ │ ¼ │ 5/16 │ ⅛ │ ¼ │ 1/16 │ 2
│ │ │ │ │ │ │
12 │ ¼ │ 5/16 │ ⅜ │ ⅛ │ ¼ │ 1/16 │ 2
│ │ │ │ │ │ │
15 │ ¼ │ 5/16 │ ⅜ │ ⅛ │ ¼ │ 3/32 │ 3
│ │ │ │ │ │ │
18 │ ¼ │ ⅜ │ 7/16 │ 3/16 │ ¼ │ 3/32 │ 3
│ │ │ │ │ │ │
21 │ ¼ │ 7/16 │ ½ │ 3/16 │ ¼ │ ⅛ │ 3
│ │ │ │ │ │ │
24 │ ⅜ │ ½ │ 9/16 │ ¼ │ ¼ │ ⅛ │ 4
│ │ │ │ │ │ │
27 │ ⅜ │ ⅝ │11/16 │ ¼ │ ¼ │ ⅛ │ 4
30 │ ⅜ │ ⅝ │11/16 │ ¼ │ ¼ │ ⅛ │ 4
33 │ ⅜ │ ¾ │13/16 │ ¼ │ ¼ │ 3/16 │ 5
36 │ ⅜ │ ¾ │13/16 │ ⅜ │ ¼ │ 3/16 │ 5
39 │ ⅜ │ ¾ │13/16 │ ⅜ │ ¼ │ 3/16 │ 5
42 │ ⅜ │ ¾ │13/16 │ ⅜ │ ¼ │ 3/16 │ 5
─────────┴───────┴──────┴──────┴────────┴───────┴─────────┴────────
NOTE 1. For methods of making tests see Proc. Am. Soc. for Testing
Materials.
NOTE 2. Concentrated load at end of vertical diameter.
(_a_) Slants shall have their spigot ends cut at an angle of
approximately 45 degrees with the longitudinal axis.
(_b_) Curves shall be at angles of 90, 45, 22½, and 11¼ degrees as
required. They shall conform substantially to the curvature
specified.
(_c_) ... All branches shall terminate in sockets.
[Illustration:
FIG. 73.—Standard Clay Pipe Specials.
Courtesy, Blackmer and Post Manufacturing Co.
]
In Fig. 73 are shown the various forms of vitrified pipe and specials
which are ordinarily available on the market.
The life of vitrified clay sewers and some observations on the results
of the inspection of the sewers in Manhattan are discussed in Chapter
XII. The strength of vitrified sewer pipes is shown in Table 37.
TABLE 37
STRENGTH OF SEWER PIPE
Strength in pounds per linear foot to carry loads from ditch filling
material such as ordinary sand and thoroughly wet clay, with the under
side of the pipe bedded 60° to 90° by ordinary good methods. From Proc.
Am. Society for Testing Materials, Vol. 20, 1920, page 604.
────────┬──────────────────────────────────────────────────────────────
Height │
of Fill │
Above │
Top of │
Pipe, │
Feet │ Breadth of the Ditch a Little Below the Top of the Pipe
────────┼───────────┬───────────┬───────────┬────────────┬─────────────
│ 1 Foot │ 2 Feet │ 3 Feet │ 4 Feet │ 5 Feet
────────┼───────────┴───────────┴───────────┴────────────┴─────────────
│ Ditch Filling Material
────────┼─────┬─────┬─────┬─────┬─────┬─────┬─────┬──────┬──────┬──────
│sand │clay │sand │clay │sand │clay │sand │ clay │ sand │ clay
────────┼─────┼─────┼─────┼─────┼─────┼─────┼─────┼──────┼──────┼──────
2│ 265│ 280│ 615│ 635│ 970│ 990│ 1330│ 1,350│ 1,690│ 1,710
4│ 400│ 450│ 1055│ 1125│ 1745│ 1825│ 2455│ 2,535│ 3,165│ 3,250
6│ 470│ 545│ 1370│ 1500│ 2370│ 2525│ 3405│ 3,575│ 4,460│ 4,740
8│ 505│ 605│ 1600│ 1790│ 2875│ 3115│ 4215│ 4,495│ 5,595│ 5,890
10│ 525│ 640│ 1765│ 2015│ 3275│ 3610│ 4900│ 5,295│ 6,590│ 7,020
12│ 535│ 660│ 1880│ 2185│ 3600│ 4030│ 5485│ 6,000│ 7,460│ 8,035
14│ 540│ 675│ 1965│ 2320│ 3855│ 4380│ 5975│ 6,620│ 8,225│ 8,950
16│ 545│ 680│ 2025│ 2425│ 4065│ 4675│ 6395│ 7,165│ 8,890│ 9,775
18│ 545│ 685│ 2070│ 2505│ 4230│ 4920│ 6750│ 7,630│ 9,480│10,520
20│ 545│ 690│ 2100│ 2565│ 4365│ 5130│ 7050│ 8,060│ 9,995│11,190
22│ 545│ 690│ 2125│ 2610│ 4470│ 5305│ 7305│ 8,425│10,445│11,795
24│ 545│ 690│ 2140│ 2645│ 4560│ 5445│ 7525│ 8,750│10,840│12,340
26│ 545│ 690│ 2150│ 2675│ 4630│ 5575│ 7705│ 9,035│11,185│12,830
28│ 545│ 690│ 2160│ 2695│ 4685│ 5680│ 7860│ 9,280│11,490│13,270
30│ 545│ 690│ 2165│ 2715│ 4725│ 5765│ 7990│ 9,500│11,755│13,670
Very │ │ │ │ │ │ │ │ │ │
great │ 545│ 690│ 2180│ 2770│ 4910│ 6230│ 8725│11,075│13,635│17,305
────────┴─────┴─────┴─────┴─────┴─────┴─────┴─────┴──────┴──────┴──────
=92. Cement and Concrete Pipe.=—Although there is no general recognition
of a difference between cement and concrete pipe, there is a tendency to
term manufactured pipe of small diameter cement pipe, and large pipes or
pipes constructed in place, concrete pipe. Cement, unlike clay, is used
in the manufacture of pipe in the field or by more or less unskilled
operators in “one man” plants. Great care should be used in the
selection of cement, aggregate, and reinforcement for precast cement
pipe since the shocks to which it is subjected in transit are more
liable to rupture it than the heavier but steadier loads imposed on it
in the trench.
The United States Government, various scientific and engineering
societies, and other interested organizations have collaborated in the
preparation of specifications for cement and cement tests. These
specifications can be found in Trans. Am. Soc. Civil Engineers, Vol. 82,
1918, p. 166, and in other publications.
The following abstracts have been taken from the proposed tentative
specifications for Concrete Aggregates, of the Am. Society for Testing
Materials, issued June 21, 1921:
1. Fine aggregate shall consist of sand, stone screenings, or
other inert materials with similar characteristics, or a
combination thereof, having clean, hard, strong, durable uncoated
grains, free from injurious amounts of dust, lumps, soft or flaky
particles, shale, alkali, organic matter, loam or other
deleterious substances.
2. Fine aggregates shall preferably be graded from fine to coarse,
with the coarser particles predominating, within the following
limits:
Passing No. 4 sieve 100 per cent
Passing No. 50 sieve, not more than 50 per cent
Weight removed by elutriation test, not more than 3 per cent
Sieves shall conform to the U. S. Bureau of Standards
specifications for sieves.
3. The fine aggregate shall be tested in combination with the
coarse aggregate and the cement with which it is to be used and in
the proportions, including water, in which they are to be used on
the work, in accordance with the requirements specified in Section
6....
7. Coarse aggregate shall consist of crushed stone, gravel or
other approved inert materials with similar characteristics, or a
combination thereof, having clean, hard, strong, durable, uncoated
pieces free from injurious amounts of soft, friable, thin,
elongated or laminated pieces, alkali, organic or other
deleterious matter.
* * * * *
The following Table indicates desirable gradings, in percentages,
for coarse aggregate for certain maximum sizes.
GRADINGS OF COARSE AGGREGATES
─────────┬─────────────────────────────────────────┬───────────────────
Maximum │ Circular Openings, Inches │ Passing Screen
Size of │ │ Having Circular
Aggregate│ │Openings ¼ Inch in
Inches │ │diameter, not more
│ │ than
─────────┼───┬───┬───┬─────┬─────┬─────┬─────┬─────┼───────────────────
│ 3 │2½ │ 2 │ 1½ │ 1¼ │ 1 │ ¾ │ ½ │
─────────┼───┼───┼───┼─────┼─────┼─────┼─────┼─────┼───────────────────
3 │100│ │ │40–75│ │ │ │ │ 15 per cent
2½ │ │100│ │ │40–75│ │ │ │ 15 per cent
2 │ │ │100│ │ │40–75│ │ │ 15 per cent
1½ │ │ │ │ 100 │ │ │40–75│ │ 15 per cent
1¼ │ │ │ │ │ 100 │ │ │35–70│ 15 per cent
1 │ │ │ │ │ │ 100 │ │40–75│ 15 per cent
¾ │ │ │ │ │ │ │ 100 │ │ 15 per cent
─────────┴───┴───┴───┴─────┴─────┴─────┴─────┴─────┴───────────────────
The manufacture of small size cement pipe requires relatively more skill
than equipment. As a result great care must be observed in the
inspection of cement pipe and in the enforcement of specifications. For
large size concrete pipe and reinforced concrete pipe the difficulty of
holding the pipe together during transportation and lowering into the
trench aid in insuring a good product.
Cement pipe is made by ramming a mixture of cement, sand, and water into
a cylindrical mold and allowing it to stand until set. The mold is then
removed and the pipe stands for a further period of time to become
cured. The selection and proportion of materials, the amount of water,
the method of ramming, the period of setting, the length of time of
curing, and the control of moisture and temperature during this period
are of great importance in the resulting product. E. S. Hanson[52]
states that the most conservative engineers recommend a mixture of one
sack of cement to 2½ cubic feet of aggregate measured as loosely thrown
into the measuring box. In making up the aggregate, clean gravel or
broken stone up to ¼ inch in size is used. The American Concrete
Institute recommends that 100 per cent pass a ½-inch screen, 70 per cent
a ¼-inch screen, 50 per cent a No. 10, 40 per cent a No. 20, 30 per cent
a No. 30, and 20 per cent a No. 40. The materials should be carefully
graded by experiment and not guessed at, as the behavior of all
aggregates is not the same. Too coarse an aggregate is difficult to
handle in manufacturing. It causes loss of pipe when the jacket or mold
is removed and results in rough pipe, stone pockets, and pin holes
through which water spurts when pressure tests are applied. Too fine an
aggregate causes loss of strength and with ordinary mixtures tends to
produce a pipe which will show seepage under internal pressure tests.
The amount of water in the mixture will vary, from 15 to 20 per cent.
The mixture should appear dry but should ball in the hand under some
pressure.
[Illustration:
FIG. 74.—Details of 24–Inch Concrete Pipe Form.
]
The mixture can be rammed into the molds by hand or machine. A
machine-made pipe is preferable as it produces a more even and stronger
product. There are two types of machines for this purpose. One type
consists of a number of tamping feet which deliver about 200 blows to
the minute with a pressure of about 800 pounds per square inch of area
exposed. In the other type a revolving core is drawn through the pipe,
packing and polishing the concrete as it is pulled through, with special
provision for packing the bell of the pipe. The tamping machines can
make 1,500 feet of small size pipe to 300 feet of 24–inch pipe in a day.
Machines of the second type can make 750 feet of 8–inch to 200 feet of
30–inch pipe in 30–inch lengths in 9 hours. The inside and outside forms
for a 24–inch pipe are shown in Fig. 74 as used with the tamping
machines. The forms are swabbed with oil before being filled in order to
facilitate their removal. In making a Y-branch or other special, a hole
is cut in the pipe or mold the size of the joining pipe which is then
set in place and the joint wiped smooth with cement.
TABLE 38
PROPERTIES OF CEMENT CONCRETE SEWER PIPE
1917 Specifications of American Society for Testing Materials, with
Subsequent Revisions
─────────┬───────┬────────┬───────┬───────┬──────┬─────────
│Laying │Diameter│Normal │ Depth │Taper │ Minimum
│Length,│ at │Annular│ of │ of │Thickness
│ Feet │ Inside │Space, │Socket,│Socket│ of
│ │ of │Inches │Inches │ │ Barrel,
│ │Socket, │ │ │ │ Inches
│ │ Inches │ │ │ │
Internal │ │ │ │ │ │
Diameter,│ │ │ │ │ │
Inches │ │ │ │ │ │
─────────┼───────┼────────┼───────┼───────┼──────┼─────────
│ │ │ │ │ │
│ │ │ │ │ │
│ │ │ │ │ │
│ │ │ │ │ │
│ │ │ │ │ │
─────────┼───────┼────────┼───────┼───────┼──────┼─────────
│ │ │ │ │ │
│ │ │ │ │ │
─────────┼───────┼────────┼───────┼───────┼──────┼─────────
│2, 2½, │ 8¼ │ ½ │ 2 │1 : 20│ ⅝
6 │ 3 │ │ │ │ │
│2, 2½, │ 11 │ ⅝ │ 2¼ │1 : 20│ ¾
8 │ 3 │ │ │ │ │
│2, 2½, │ 13¼ │ ⅝ │ 2½ │1 : 20│ ⅞
10 │ 3 │ │ │ │ │
│2, 2½, │ 15⅝ │ ⅝ │ 2½ │1 : 20│ 1
12 │ 3 │ │ │ │ │
│2, 2½, │ 19¼ │ ⅝ │ 2½ │1 : 20│ 1¼
15 │ 3 │ │ │ │ │
│2, 2½, │ 22¾ │ ⅝ │ 2¾ │1 : 20│ 1½
18 │ 3 │ │ │ │ │
│2, 2½, │ 26½ │ ¾ │ 2¾ │1 : 20│ 1¾
21 │ 3 │ │ │ │ │
│2, 2½, │ 30¼ │ ¾ │ 3 │1 : 20│ 2⅛
24 │ 3 │ │ │ │ │
27 │ 3 │ 34 │ ⅞ │ 3¼ │1 : 20│ 2¼
30 │ 3 │ 38 │ 1 │ 3½ │1 : 20│ 2½
33 │ 3 │ 41½ │ 1 │ 4 │1 : 20│ 2¾
36 │ 3 │ 45½ │ 1¼ │ 4 │1 : 20│ 3
39 │ 3 │ 49 │ 1¼ │ 4 │1 : 20│ 3¼
42 │ 3 │ 53 │ 1½ │ 4 │1 : 20│ 3½
─────────┴───────┴────────┴───────┴───────┴──────┴─────────
─────────┬──────────────────────────────────────┬─────────┬───────────
│ Limits of Permissible Variations │ Minimum │ Maximum
│ │Crushing │Absorption,
│ │Strength,│ Per Cent
│ │ Pounds │
│ │ per │
│ │ Linear │
Internal │ │ Foot at │
Diameter,│ │ End of │
Inches │ │Diameter │
─────────┼───────┬─────────────┬──────┬─────────┼─────────┼───────────
│Length,│ Internal │Depth │Thickness│ │
│ Inch │ Diameter, │of Hub│of Barrel│ │
│ per │ Inches │ (-) │ (-) │ │
│ Foot │ │Inches│ Inches │ │
│ (-) │ │ │ │ │
─────────┼───────┼──────┬──────┼──────┼─────────┼─────────┼───────────
│ │Spigot│Socket│ │ │ │
│ │ (±) │ (±) │ │ │ │
─────────┼───────┼──────┼──────┼──────┼─────────┼─────────┼───────────
│ ¼ │ 3/16 │ 3/16 │ ¼ │ 1/16 │ 1430 │ 8
6 │ │ │ │ │ │ │
│ ¼ │ ¼ │ ¼ │ ¼ │ 1/16 │ 1430 │ 8
8 │ │ │ │ │ │ │
│ ¼ │ ¼ │ ¼ │ ¼ │ 1/16 │ 1570 │ 8
10 │ │ │ │ │ │ │
│ ¼ │ ¼ │ ¼ │ ¼ │ 1/16 │ 1910 │ 8
12 │ │ │ │ │ │ │
│ ¼ │ ¼ │ ¼ │ ¼ │ 3/32 │ 1960 │ 8
15 │ │ │ │ │ │ │
│ ¼ │ ¼ │ ¼ │ ¼ │ 3/32 │ 2200 │ 8
18 │ │ │ │ │ │ │
│ ¼ │ 5/16 │ 5/16 │ ¼ │ ⅛ │ 2590 │ 8
21 │ │ │ │ │ │ │
│ ⅜ │ 5/16 │ 5/16 │ ¼ │ ⅛ │ 3070 │ 8
24 │ │ │ │ │ │ │
27 │ ⅜ │ 5/16 │ ⅜ │ ¼ │ ⅛ │ 3370 │ 8
30 │ ⅜ │ ⅜ │ ⅜ │ ¼ │ ⅛ │ 3690 │ 8
33 │ ⅜ │ ⅜ │ ⅜ │ ¼ │ 3/16 │ 3930 │ 8
36 │ ⅜ │ ½ │ ½ │ ¼ │ 3/16 │ 4400 │ 8
39 │ ⅜ │ ½ │ ½ │ ¼ │ 3/16 │ 4710 │ 8
42 │ ⅜ │ ½ │ ½ │ ¼ │ 3/16 │ 5030 │ 8
─────────┴───────┴──────┴──────┴──────┴─────────┴─────────┴───────────
After the removal of the mold the pipe may be cured by the water or the
steam process. Hanson states:
By the former the pipe are simply set on the floor of the plant
and as soon as they are sufficiently strong so that they can be
sprinkled with water without falling down; sprinkling is commenced
and continued at such intervals for 6 or 7 days that the pipe will
be moist at all times. This is a slower process than steam curing.
It is also less uniform and less subject to control than where the
product is cured by steam.
In the steam process the pipe is exposed to low-pressure steam with
plenty of moisture in a closed receptacle for 24 hours, or until
hardened. It has been found by tests that pipes sprinkled for 28 days
are as strong as steam-cured pipes.
The dimensions of cement concrete sewer pipe as recommended by the Am.
Society for Testing Materials are shown in Table 38.
The following has been abstracted from the description of the
manufacture of one form of concrete pipe by G. C. Bartram.[53] All pipe
are manufactured in 4–foot lengths near the site at which they are to be
installed because of their great weight, for example, 36–inch pipe
weighs one ton. The plant for the manufacture of the pipe consists of
cast-iron bottom and top rings for each size to be used on the job, and
inside and outside steel casings. There are three bases for each steel
casing as the pipes stand on the bases for 72 hours and the steel casing
remains on for only 24 hours after the concrete has been poured. The
pipes are then lifted off the bases and stored for aging. The pipes are
cast with the spigot end up.
The concrete is ordinarily mixed in the proportions of 1 : 2 : 4. The
materials are placed in the mixer in the following order: first, the
stone, then the sand, then the cement, and finally the water. Sufficient
water is added to make the concrete flow freely. In cold weather or for
a hurry-up job the molds are covered with canvas and are steamed for 2
or 3 hours immediately after the concrete is poured. The molds are then
removed but the pipe should be steamed before use. Otherwise they are
allowed to stand 72 hours, as explained above. In cold weather the steam
is used to prevent freezing and not to hasten the completion of the
pipe.
[Illustration:
FIG. 75.—Triangle Mesh Reinforced Concrete Pipe.
As made by the Am. Concrete Pipe and Pile Co., Chicago.
]
[Illustration:
FIG. 76.—Methods of Joining and Reinforcing Concrete Pipe.
]
One layer or ring of reinforcement is used for sizes from 24 to 48
inches and two layers or rings for larger pipe. A type of reinforcement
sometimes used is the American Steel and Wire Company’s Triangular Mesh,
an illustration of which is shown in Fig. 75. The wire mesh is cut to
fit and is placed in a slot in the cast-iron base. The slot is then
filled with sand so that the concrete cannot enter, thus leaving a
portion of the reinforcement exposed. The inside reinforcement extends
through and out of the spigot of the completed pipe. In the trench the
two reinforcements overlap in the key-shaped space left on the inside of
the pipe by the design of the bell and spigot. This space is shown in
Fig. 76 A. When the pipe is placed in the trench the key-shaped space is
plastered with mortar and a piece is knocked out of the bell to receive
the grout with which the joint is closed. A spring steel band is then
put on the outside of the joint and grout poured into the hole at the
top. The band is removed as soon as the joint materials have set.
The rules for the reinforcement of concrete pipe recommended in Volume
XV, 1919, of the Transactions of the Concrete Institute are as follows:
No reinforcement is approved for pipe between 30 and 60 inches in
diameter or in rock or hard soils. For pipe 36 inches in diameter
or less the minimum thickness of shell shall be 5 inches. For
60–inch pipe the minimum thickness shall be 7 inches with
intermediate sizes in proportion. Reinforcement for circular pipe
shall consist of one or two rings of circular wire fabric or rods
of the areas shown in Table 39. All sewers near the surface and
subject to vibration should be reinforced. For sewers 6 feet or
less in diameter the reinforcement should consist of at least ½ of
1 per cent of the area of the concrete. It should be placed near
the inside at the crown and near the outside at the haunches. If
large horizontal pressures are expected the pipe should be
reinforced for these reverse stresses, which involves placing the
reinforcement near the outside at the crown and near the inside at
the haunches. The minimum thickness of the walls of sewers greater
than 6 feet in diameter with flat bottom and arch, with or without
side walls, should be 8 inches.
TABLE 39
REINFORCEMENT FOR CIRCULAR CONCRETE SEWER PIPE
(See Vol. XV, Proceedings Am. Concrete Institute)
─────────────────┬─────────────────┬─────────────────┬─────────────────
Diameter in │Minimum Thickness│ Number of Rings │ Cross Sectional
Inches │ of Shell in │ │Area of Each Ring
│ Inches │ │
─────────────────┼─────────────────┼─────────────────┼─────────────────
24 │3 │1 │.058
27 │3 │1 │.068
30 │3½ │1 │.080
33 │4 │1 │.107
36 │4 │1 │.146
39 │4 │1 │.146
42 │4½ │1 │.153
48 │5 │2 │.107
54 │5½ │2 │.123
60 │6 │2 │.146
66 │6½ │2 │.168
72 │7 │2 │.180
84 │8 │2 │.208
96 │9 │2 │.245
─────────────────┴─────────────────┴─────────────────┴─────────────────
Three methods for the reinforcement of concrete sewers are shown in Fig.
76 B.
=93. Proportioning of Concrete.=—In the proportioning of concrete
questions of strength, of permeability, and of workability[54] may need
consideration. All of these qualities are affected by the amount of
cement, the nature and gradation and relative proportions of the fine
and the coarse aggregate, and the amount of mixing water used.
Other things being equal the strength varies with the amount of cement
put into the concrete. For the same amount of cement and the same
consistency of the mixture, the strength increases with increased
density of concrete (that is, with decreased voids), and the effort
should be made so to proportion the fine and coarse aggregates as to
produce the densest concrete (least voids) with the aggregates
available. For the same consistency, the strength then will vary with
the ratio of the amount of cement to the amount of the voids.
So far as the mixing water is concerned, the greatest strength in the
concrete will be attained at a rather dry mix; that which produces the
least volume of concrete. The addition of more water results in a
concrete of less strength; 40 per cent more water may give a concrete of
less than half the normal strength. The reduction in strength is then
very marked for the wetter mixes, and the water content used is a
feature of considerable importance in the design of concrete mixtures.
Permeability is affected by the same elements as strength, but the size
and discontinuity of the pores have a greater influence.
Workability is an important quality; in some respects it will have to be
obtained at the expense of strength. Increasing the amount of mixing
water increases the workability of the mixtures, with a resulting
decrease in strength which may have to be accepted or else overcome by
increasing the cement in the mix.
An excess of water is often used unnecessarily through ignorance of the
injurious results. A high proportion of coarse aggregate, up to a
certain limit, will give concrete of high strength, but the mixture will
be harsh-working and not easy to place. Lower proportions of coarse
aggregate will give greater workability and better uniformity of
product, the latter being an important matter. It is apparent that the
degree of workability of the mixture needed will depend upon the nature
of the construction—for a pavement where the concrete will receive
substantial tamping or working the water content may be much less than
that which may need to be used in placing concrete around reinforcement
in narrow members, or where little tamping or spading can be done. The
nature of the work will affect the standard of consistency to be
specified.
The proportioning of the concrete should then be dependent upon the
needs of the structure and the manner of placing the concrete. The
proportions selected should be carefully adhered to and especially
should care be taken to see that the right quantity of mixing water is
used.
The materials are commonly measured volumetrically (by bulk). Because of
the variations which are introduced by volumetric measurement of the
materials by the presence of varying degrees of moisture, measurements
by weight would be more accurate, but these would also be affected by
differences in the specific gravity of the materials. The methods of
measuring, the allowance for moisture, as well as the proportions of the
materials, should be specified.
The methods for proportioning concrete are:
(1) Arbitrarily selected proportions.
(2) Proportions based on minimum voids.
(3) Proportions based on trial mixtures.
(4) Proportions based on a sieve analysis curve.
(5) Proportions based on the surface area of the aggregates.
(6) Proportions based on the water-cement ratio and the fineness
modulus.
(7) Proportions based on mortar-voids and cement-voids ratio.
Arbitrarily selected proportions are in quite general use; they are
intended to apply to the materials most commonly used in the vicinity of
the work. The most common practice is to use twice as great a volume of
coarse aggregate as fine aggregate, as for instance 1 part cement, 2
parts fine aggregate, and 4 parts coarse aggregate. Decreasing the ratio
of coarse aggregate to fine aggregate may give a more easily worked mix
or require relatively less water for a given workability, and in some
cases it will be proper to increase this ratio and thus secure an
increase of strength. Judgment and experience with given materials may
warrant changes from a stated ratio. The proportions are now frequently
given as one part cement to a certain number of parts of the mixed
aggregate, leaving the proportions of the fine to coarse to be
determined otherwise, since small variations in the relation of these
will not greatly affect the strength. Proportions in common use are:[55]
Mortar for
Laying brick and stone masonry from 1 : 0 to 1 : 3
Filling joints in sewer pipe 1 : 0 to 1 : 2
Surfaces, floors, sidewalks, pavements 1 : 0 to 1 : 2
Waterproof linings 1 : 0 to 1 : 2
Cement, bricks, and blocks 1 : 2½ to 1 : 4
Concrete for
Gravity retaining walls, heavy
foundations, structures needing mass
more than strength from 1 : 3 : 6 to 1 : 4 : 8
Retaining walls, piers, sewers,
pavements, foundations, and work
requiring strength. (Compressive
strength in 28 days, 1,500 to 2,000
pounds per square inch) from 1 : 2 : 4 to 1 : 3 : 6
Floors, beams, pavements, reinforced
concrete, arch bridges, low-pressure
tanks. (Compressive strength in 28
days, 2,000 to 3,000 pounds per
square inch) from 1 : 1½ : 3 to 1 : 2½ : 4½
Reinforced concrete columns, conduit
pipe, impervious concrete.
(Compressive strength in 28 days,
3,000 to 4,000 pounds per square
inch) from 1 : 1 : 2 to 1 : 1½ : 3
The usual method of proportioning based on minimum voids is to assume
that the particles of fine aggregate should fill the voids in the coarse
aggregate and that the particles of the cement will fill the voids in
the fine aggregate. About 5 to 10 per cent additional fine aggregate is
generally added to push the particles of the coarse aggregate apart and
thus give a more easily worked concrete and one freer from void spaces.
This method is inaccurate, principally because of the effect of the
moisture on the volume of the voids, and because the effect on the
volume by the addition of water is unknown.
Trial mixtures may be made by carefully weighing each of the ingredients
and then combining them to give a workable concrete. Using a given
amount of cement, the proportion of ingredients, of the same total
weight, which will give the least volume and therefore the densest
concrete is adopted. When making the comparison the consistency of the
mixes must be maintained constant.
Proportioning may be based on an ideal sieve analysis curve of the mixed
cement and aggregates. The sieve analysis of the aggregates is made by
screening a predetermined weight of the sample through a series of 5 to
8 sieves graded in size from slightly below the size of the largest
particle to slightly above the smallest particle of the aggregate. The
analysis is then expressed in the form of a curve. The ideal curve,
according to Fuller,[56] is shown in Fig. 77.
[Illustration:
FIG. 77.—Gravel Analysis.
The dotted line indicates the ideal combination of the coarse and fine
portions. The heavy full line indicates the combination attained.
]
The method of proportioning concrete by surface areas is based on the
theory that the strength of a concrete depends on the amount of cement
used in proportion to the surface area of the aggregates.[57]
The proportioning of concrete on the basis of a water-cement ratio and a
fineness modulus was introduced by Prof. D. A. Abrams.[58] It is based
on the theory that with fixed conditions of aggregate, moisture, etc.,
the ratio of water to cement determines the strength of the concrete.
A method of proportioning concrete by determining experimentally the
voids in mortars made up with a given amount of sand and definite
proportions of cement, and then calculating the voids in the concrete
made up by adding a definite amount of coarse aggregate to the mixture,
has been developed.[59] The method is based on the theory that the
strength of the concrete is a known function of the ratio of the volume
of cement to the volume of the voids in the concrete. The effect of
varying the proportion of the ingredients, including an increase in the
amount of mixing water beyond that required to give the densest mixture,
may be found by the method, and a comparison may be made of results
obtainable with different classes of fine and coarse aggregates.
Arbitrarily selected proportions, proportions based on voids, and
proportions based on trial mixtures are usually satisfactory for small
jobs where the amount of materials involved is not large. Where the
saving in materials will permit, more accurate methods should be used.
The methods can be studied more fully by reference to the original
articles quoted in the footnotes, or to the following texts:
Materials of Construction, Johnson, 5th Edition, 1918.
Materials of Engineering, H. F. Moore, 2d Edition, 1920.
Masonry Construction, I. O. Baker, 10th Edition, 1912.
Concrete Engineer’s Handbook, Hool and Johnson, 1918.
Concrete, Plain and Reinforced, Taylor and Thompson, 1916.
=94. Waterproofing Concrete.=—The waterproofing of concrete is most
satisfactorily done by making dense mixtures. In practice such
substances as hydrated lime, clay, alum and soap, and proprietary
compounds such as Ceresit, Medusa, etc., are frequently mixed with the
concrete under the theory that these very fine substances will fill any
remaining voids and render the concrete impervious. The specifications
of the Joint Committee issued on June 4, 1921, are much briefer and
contain less detailed instruction than those issued earlier.[60] The
earlier instructions follow.
Many expedients have been resorted to for making concrete
impervious to water. Experience shows, however, that when mortar
or concrete is proportioned to obtain the greatest practicable
density and is mixed to the proper consistency, the resulting
mortar or concrete is impervious under moderate pressure.
On the other hand concrete of dry consistency is more or less
pervious to water, and, though compounds of various kinds have
been mixed with the concrete or applied as a wash to the surface,
in an effort to offset this defect, these expedients have
generally been disappointing, for the reason that many of these
compounds have at best but temporary value, and in time lose their
power of imparting impermeability to the concrete.
In the case of subways, long retaining walls, and reservoirs,
provided the concrete itself is impervious, cracks may be so
reduced, by horizontal and vertical reinforcement properly
proportioned and located, that they will be too minute to permit
leakage, or will be closed by infiltration of silt.
Asphaltic or coal tar preparations applied either as a mastic or
as a coating on felt cloth or fabric, are used for waterproofing,
and should be proof against injury by liquids or gases.
For retaining and similar walls in direct contact with the earth,
the application of one or two coatings of hot coal tar pitch,
following a painting with a thin wash of coal tar dissolved in
benzol, to the thoroughly dried surface of concrete is an
efficient method of preventing the penetration of moisture from
the earth.
Tar paper and asphaltic compounds are not often used in sewer work as
absolute imperviousness is seldom necessary.
=95. Mixing and Placing Concrete.=—Careful workmanship is desirable in
the mixing and placing of concrete in sewers since water-tight
construction is desired. Because of the difficulty of inspecting
concrete in wet, dark and crowded excavations, and the careless habits
of workmen experienced in concrete sewer construction, the highest class
of concrete work cannot be expected. The situation is met by designing
thick walls as shown in the sections illustrated in Fig. 22 and 23.
In the report of the Joint Committee on Concrete and Reinforced Concrete
in Transactions of the American Society of Civil Engineers for 1917, on
page 1101 the recommendation is made concerning the mixing and placing
of concrete as follows:[61]
The mixing of concrete should be thorough and should continue
until the mass is uniform in color and is homogeneous. As the
maximum density and greatest strength of a given mixture depends
largely on thorough and complete mixing, it is essential that this
part of the work should receive special attention and care.
Inasmuch as it is difficult to determine by visual inspection
whether the concrete is uniformly mixed, especially where
aggregates having the color of cement are used, it is essential
that the mixing should occupy a definite period of time. The
minimum time will depend on whether the mixing is done by machine
or hand.
(_a_) Measuring Ingredients: Methods of measurement of the various
ingredients should be used which will secure at all times separate
and uniform measurements of cement, fine aggregate, coarse
aggregate and water.
(_b_) Machine Mixing: The mixing should be done in a batch machine
mixer of a type which will insure the uniform distribution of the
materials throughout the mass, and should continue for the minimum
time of 1½ minutes after all the ingredients are assembled in the
mixer. For mixers of 2 or more cubic yards capacity, the minimum
time of mixing should be 2 minutes. Since the strength of the
concrete is dependent on thorough mixing, a longer time than this
minimum is preferable. It is desirable to have the mixer equipped
with an attachment for automatically locking the discharging
device so as to prevent the emptying of the mixer until all the
materials have been mixed together for the minimum time required
after they are assembled in the mixer. Means should be provided to
prevent aggregates being added after the mixing has commenced. The
mixer should also be equipped with water storage, and an automatic
measuring device which can be locked if desired. It is also
desirable to equip the mixer with a device recording the
revolutions of the drum. The number of revolutions should be so
regulated as to give at the periphery of the drum a uniform speed.
About 200 feet per minute seems to be the best speed in the
present state of the art.
(_c_) Hand Mixing: Hand mixing should be done on a water-tight
platform and especial precautions taken after the water has been
added, to turn all the ingredients together at least 6 times, and
until the mass is homogeneous in appearance and color.
(_d_) Consistency: The materials should be mixed wet enough to
produce a concrete of such a consistency as will flow sluggishly
into the forms and about the metal reinforcement when used, and
which at the same time can be conveyed from the mixer to the forms
without separation of the coarse aggregate from the mortar. The
quantity of water is of the greatest importance in securing
concrete of maximum strength and density; too much water is as
objectionable as too little.
(_e_) Retempering: The remixing of concrete and mortar that has
partly reset should not be permitted.
_Placing Concrete_
(_a_) Methods: Concrete after the completion of the mixing should
be conveyed rapidly to the place of final deposit; under no
circumstances should concrete be used that has partly set.
Concrete should be deposited in such a manner as will permit the
most thorough compacting such as can be obtained by working with a
straight shovel or slicing tool kept moving up and down until all
the ingredients are in their proper place. Special care should be
exercised to prevent the formation of laitance; where laitance has
formed it should be removed, since it lacks strength and prevents
a proper bond in the concrete.
Care should be taken that the forms are substantial and thoroughly
wetted (except in freezing weather) or oiled, and that the space
to be occupied by the concrete is free from all debris. When the
placing of concrete is suspended, all necessary grooves for
joining future work should be made before the concrete has set.
When work is resumed concrete previously placed should be
roughened, cleansed of foreign material and laitance, thoroughly
wetted and then slushed with a mortar consisting of one part
Portland cement and not more than 2 parts of fine aggregate.
The surfaces of concrete exposed to premature drying should be
kept covered and wet for at least 7 days.
Where concrete is conveyed by spouting, the plant should be of
such a size and design as to insure a practically continuous
stream in the spout. The angle of the spout with the horizontal
should be such as to allow the concrete to flow without separation
of the ingredients; in general an angle of about 27 degrees or 1
vertical to 2 horizontal is good practice. The spout should be
thoroughly flushed with water before and after each run. The
delivery from the spout should be as close as possible from the
point of deposit. Where the discharge must be intermittent, a
hopper should be provided at the bottom. Spouting through a
vertical pipe is satisfactory when the flow is continuous; when it
is checked and discontinuous it is highly objectionable unless the
flow is checked by baffle plates.
(_b_) Freezing Weather: Concrete should not be mixed or deposited
at a freezing temperature, unless special precautions are taken to
prevent the use of materials covered with ice crystals or
containing frost, and to prevent the concrete from freezing before
it has set and sufficiently hardened.
As the coarse aggregate forms the greater portion of the concrete,
it is particularly important that this material be warmed to well
above the freezing point.
The enclosing of a structure and the warming of a space inside the
enclosure is recommended, but the use of salt to lower the
freezing point is not recommended.
(_c_) Rubble Concrete: Where the concrete is to be deposited in
massive work, its value may be improved and its cost materially
reduced by the use of clean stones saturated with water,
thoroughly embedded in and completely surrounded by concrete.
(_d_) Under Water: In placing concrete under water, it is
essential to maintain still water at the place of deposit. With
careful inspection the use of tremies, properly designed and
operated, is a satisfactory method of placing concrete through
water. The concrete should be mixed very wet (more so than is
ordinarily permissible) so that it will flow readily through the
tremie and into place with practically a level surface.
The coarse aggregate should be smaller than ordinarily used and
never more than one inch in diameter. The use of gravel
facilitates the mixing and assists the flow. The mouth of the
tremie should be buried in the concrete so that it is at all times
entirely sealed and the surrounding water prevented from forcing
itself into the tremie. The concrete will then discharge without
coming in contact with the water. The tremie should be suspended
so that it can be lowered quickly when it is necessary either to
choke off or to prevent too rapid flow. The lateral flow
preferably should not be over 15 feet.