CHAPTER V

MANAGEMENT OF HEATING PLANTS

The following instructions on the care and management of steam and

hot-water heating plants is printed with permission of the American

Radiator Co. They were prepared as a guide to the successful operation

of the Ideal heating plants but apply with equal force to other plants

of a similar character.

=General Advice.=--No set rules can be given for caring for every

boiler alike--chimney flues are not alike--some have strong draft,

some are average and some are weak. There is much more difference in

the heat-making qualities of coal than is commonly known, and it is

important that the right size coal for the draft be used. These rules

apply to most all fuels. A little trying of this way or that way of

leaving the dampers (when regulators are not used) often discovers the

better way. It is well to vary from the rules a little if any of them

do not seem to bring about the best results.

With good, average chimney flue draft and the right kind of fuel, these

rules will govern the large majority of cases.

=The Economy of Good Draft.=--In many cases a boiler with sluggish

draft will burn more coal than a boiler with good draft. In the first

case the fuel may be said to “rot”--in lacking air supply the gases

pass off unburned. The “nagging” which a boiler has to take under these

conditions increases the waste of fuel. A boiler under sharp, strong

draft maintains a clear intense fire and burns the gases--getting the

larger amount of heat from the coal.

=General Firing Rules.=--

1. Put but little coal on a low fire.

2. When adding coal to the boiler, open the smoke-pipe damper (inside

the smoke pipe) and close the cold-air check damper. This will make a

draft through the feed doorway inward and prevent the escape of dust or

gas into the cellar when the feed door is open to take fuel. Put these

parts back to their regular places after feeding.

3. When it can be done, in feeding a large amount of coal (as for

night) leave a part of the fire or flame exposed, so that the gases may

be burned as they arise.

4. When a regulator is not used, learn to use the dampers correctly

and according to the force of the chimney draft. Learn to use cold-air

check damper. Often, when closing, the ash-pit draft damper does not

check the fire enough; opening the cold-air check damper will check it

about right. Increasing or lessening the pressure of a steam boiler

must be done by changing the weight on the regulator bar.

5. Carry a deep fire or a high fire; let the live coals come up to the

feed door--even in mild weather when from 4 to 6 inches of ashes stand

on the grate.

[Illustration: FIG. 57_a_.--Indicates the general condition of the

furnace fire during very cold weather. The fuel should fill the

fire-pot to _C_. The ashes should not be allowed to accumulate beyond

_B_, on the grate. There should be no more ashes than appear at _H_, in

the ashpit.]

6. In severe weather give the heater the most careful attention the

last thing at night.

7. Do not overshake or poke the fire in mild weather; once in a while

shake enough to give place for a little more fuel.

8. Do not let ashes bank up under the grate in ash-pit. Grate bars are

very hardy, but it is possible to warp them with carelessness. Taking

up the ashes once a day is the best rule, even if but little has fallen

into the pit.

9. Keep the boiler surfaces and flues clean; a crust of soot 1/4 inch

in thickness causes the boiler to require half as much more fuel than

when the surfaces are clean.

10. If convenient, have a water hose to spray the ashes when cleaning

out the pit.

11. Attend the boiler from two to four times per day. In mild weather,

running with a checked fire, morning and night is usually often enough.

In severe weather, once in early morning, again at mid-day, again at

five or six o’clock and finally thorough attention at from nine to

eleven o’clock in the evening.

12. If, through burning poor coal, the fire pot gets full of ashes,

or slate and clinkers massed together, the quickest way to get a good

active fire is to dump the grate and then build a new fire--from the

kindling up.

13. If a _hard clinker_ lodges between the grate bars, do not force the

shaking, but first dislodge the mass with a poker or slicing bar. Then

the grate will operate without damage.

=Weather and Time of Day.=--In _severe weather_ keep the fire pot full

of coal, and run the heater by the dampers or regulator (if one is

used). Thoroughly clean the grate twice a day. Let the top of the fire

in front be level with the feed door sill. Bank up the coal higher to

the rear.

In _moderate weather_ there should be from 2 to 6 inches of ashes

between the live coal and the grate. As the weather grows colder keep

the grate and the fire pot a little cleaner--sometimes it helps to run

the poker or slicing bar over it through the clinker door. With some

fuels this is never necessary.

=Night Firing.=--In very _cold weather_, when the house should be kept

warm all night, clean the grate well at a late hour--the last thing.

Clear the bottom of the fire pot of all ashes and clinkers so that the

grate is covered with clear-burning, red-hot coals, then fill the pot

full of fuel. If possible, leave some of the flame exposed to burn the

gases. Leave the drafts on long enough to burn off some of the gas,

then check the heater for the night. Thus there is plenty of coal

to burn during the night and some on which to commence early in the

morning. Some drafts do not make it necessary to leave the dampers on

to burn off the gas after feeding.

With the ash-pit draft damper closed and the cold-air check damper

open at night, but part of the coal is burned and there is much of it

not burned in the morning. So, by reversing the dampers in the early

morning the fire starts up quickly and often the house may be well

warmed before any coal is put into the fire pot.

Some boilers are run the other way--a very poor way. If the grate is

cleared off in very cold weather and coal added at five or six o’clock

in the afternoon, by eleven o’clock at night nearly one-half of the

coal is burned and the grate is covered over with a mass of ashes and

clinkers. With little coal remaining, to shake the grate will quite

likely put out the remaining fire; to put fresh coal on a low fire

reduces further its declining temperature. The result is a cold house

that will grow colder until a new fire is started.

Often in cold weather with this poor way of night firing, it takes one

or more hours of forced firing to warm the house in the morning, and

all the coal saved the night before is more than used to get the house

or building “heated up”--while the people who should be comfortable

have to get up, bathe and take breakfast in chilly rooms. At no time

in the day is heat more wanted than about the time of getting up and

starting the day. A fire well cared for late in the evening makes a

warm house all night. And so it follows that it is much easier to add

a little more heat in the morning. And surely less coal is burned, for

the forcing of a fire part of the time often overheats, and wastes coal.

=First-day Firing.=--In the morning of _moderate winter weather_,

with the ash-pit draft damper open, before adding any coal allow the

fire to brighten up if it seems to be low; then (for such conditions)

spread over a thin layer of fresh coal and set the drafts for a brisk

fire. After the new fire is well started add as much coal as may be

necessary to last until next firing. Do not shake much if any--just

enough to give space for more coal. Then by setting the regulator (if

one is used), or, by closing the ash-pit draft damper and opening the

cold-air check damper a little, the boiler should keep up its work

until the next firing time.

In _severe weather_, if the boiler has been attended to at night as

directed in the section on “night firing,” the drafts can be turned on

and the boiler run for half an hour before adding coal. Or, if more

convenient to give it immediate attention, the grate can be thoroughly

shaken and enough coal added to last until mid-day. Often the cold-air

check damper will need to be entirely closed and the ash-pit draft

damper partly open if the heater is a water boiler. If a steam boiler,

the regulator should then be set to maintain the number of pounds of

pressure wanted and so left.

=Other-day Firing.=--In _severe weather_ more coal should be added

about noon, sometimes the draft may be left on for a few minutes and

then checked. And in such weather it is often well to give the boiler

further attention at five or six o’clock. In severest weather the

boiler should not be attended more than four times a day; and generally

not less than three times.

Often much coal is wasted by “nagging” the fire--poking, shaking and

feeding it until it becomes “dyspeptic.” A sure cure is a little common

sense in regular feeding, etc.

=Economy and Fuels.=--In running many boilers for _moderate weather_

better results follow if the grate is not shaken too much or too often.

Sometimes in _moderate_ weather a body of ashes on the grate checks the

fire and there is enough heat without a useless burning of fuel. Many

houses are overheated in _moderate_ weather and too much coal burned by

running the boiler as for zero weather.

So we repeat--_it is not wise to overshake or overfeed a boiler in

moderate weather_. The fire should be in such shape that if a change

comes at night there is a basis for a good fire to start on. When

the grate is shaken but once during the 24 hours (during _moderate_

weather) late at night is the best time.

When one stops to think that heating is needed during about 7 months

out of the year, and that _a greater portion of this time is usually

moderate weather_ when a very little heat is needed, it must be seen

that the science of running the heater to save coal is to apply common

sense rules of limiting the feeding and the attention in such periods.

In _severe weather_ we believe in giving the boiler a liberal quantity

of fuel regularly and at the right time. The time to save coal is when

there is no need for burning it. This is where a great many people make

errors in running the boiler--in forgetting to “let up” on the shaking

and feeding in moderate weather.

With some drafts and for boilers using hard coal or coke, good

economical results often are secured by opening the feed door a little

when it is desired to check the fire in moderate weather. This depends

on the draft.

=For Burning Soft Coal.=--Some types of boilers are made to burn

soft coal with economy, with least work. Some types are made

specially to burn the meaner grades of soft coal. Firing to prevent

smoke is a source of economy and these ways of running should be

followed--specially with large sectional boilers.

There are two types of soft coal, viz.: The free-burning coal, which

breaks apart when burning, allowing the gases to freely escape; and

the fusing-coking coal, which, when burning, first fuses into a solid

burning mass with a hard crust over the top, slowly coking as it burns.

The latter kind is most valuable for house-heating boilers because the

gases are more thoroughly consumed. The fusing-coking coal is worth

about 20 per cent. more for this purpose than the free-burning coal.

The gases should be allowed to pass off from the coal _slowly_. Leave

air inlet on the feed door open if draft permits. If possible, use

uniform sizes of coal. Avoid using coal having too much dust--the

“run-of-the-mine” may be lower in price but its heat-making value is

also low.

For the purpose of slow burning of soft coal, it is well in feeding at

night to let the fire burn up freely so that the coals are very live

with heat. Then fill in enough coal to last all night--leaving some of

the live coals uncovered if possible. With large sectional boilers this

exposure should be at the rear of the fire so that the flame will pass

over the live coals. Thus the gases coming off from the fresh coal are

burned and a larger amount of the full heat-producing value of soft

coal is made use of and with less smoke.

After a boiler is so fed, the dampers (unless an automatic regulator is

used) should be left about as follows:

Ash-pit draft damper open a little or closed, as draft may require.

Cold-air check damper open about one-eighth to one-third distance of

the opening.

Smoke-pipe damper about one-half closed.

A little experiment with the draft will usually tell the operator the

best way of leaving these dampers.

It will be found in the morning that the entire charge of coal is well

burned or partly coked.

The coked fuel, or that which sticks together in a mass, should be

broken up by the poker and more added generally as by rules given in

other sections.

It must always be remembered that the soft coals mined in different

parts of the country have widely varying heat-making capacities. To

obtain satisfactory results brands must be selected which have an

established reputation for excelling results in small boilers.

=For Burning Coke.=--It is best to keep the pot _full_ of fuel--keeping

a large body of coke under a low fire rather than a little fuel under a

strong fire.

It must be remembered that coke makes a very “hot fire” because the

coke is free-burning. Care should be taken not to leave drafts on too

long in boilers not having regulators.

Coke burns best for house-heating purposes with less draft than is

required for coal, therefore to keep a low fire the ash-pit draft

damper should be kept closed, and the smoke-pipe damper almost entirely

closed. The regulator (when used) can be set to keep the dampers about

as here advised. Coke is practically smokeless and its quick-burning

character makes a cut-off damper in the smoke pipe (which will stay

fixed as it may be set) quite necessary.

It is well to keep a layer of ashes on the grates and when shaking stop

before red-hot coals come through the grate. The coke then burns more

slowly, which increases its effectiveness.

With some drafts it may be well to “bank the fire” at night with

coke--pea coal size. This is a matter of experiment, and depends on the

character of the chimney draft.

Fire should be tended regularly--two times a day, or four at the

outside.

With an extra strong draft, at night the fuel should be packed down by

tamping with the back of a shovel.

With ordinary condition of draft, crushed coke, small egg size, should

be used.

=Other Rules for Water Boilers=--_To Fill System._--Open the feed-cock

when the heater is connected with a city or town water supply; if not,

fill by funnel at the expansion tank. Fill until the gage-glass on the

expansion tank shows about half full of water. In filling the system

see that all air cocks on the radiators are closed. Then beginning with

the lower floor, open the air cocks on each radiator, one at a time,

until each radiator is filled; then close the air cock and take the

next radiators on upper floors until all are filled, after which let

the water run until it shows in the gage-glass of the water tank. After

the water is heated and in circulation, vent the radiators by opening

the air valves as before. Then again allow the water to run into

the system until it rises to the proper level in the expansion tank

gage-glass.

Always keep the apparatus _full of water_ unless the building be

vacated during the winter months, when the water should be drawn off to

prevent freezing. _Never draw water off with fire in the heater._

To draw off water, open the draw-off cock at the lowest point in the

system, and then open air cocks on all radiators as fast as the water

lowers beginning with the highest radiator.

=Air-vent Valves on Radiators.=--In order to secure the full benefit of

the heating surface of a hot-water radiator, the inside of the section

must be free of air. When a radiator is “air-bound” it means that parts

of the sections are filled with air in pockets which remain until the

air is allowed to pass off through the vent valve.

Air will gather from time to time at the highest points inside the

radiators, especially in those placed in the upper stories of the

building. These air accumulations inside cut down the working power of

a radiator exactly in proportion as they rob the inside of the casting

of proper contact with heated water. Air pockets not only reduce

effective heating surface, but they also prevent the circulation of hot

water.

Therefore, it is well once in a while to take the little key provided

by the heating contractor and open the air valves on radiators to allow

the air (if any) to escape. When a radiator does not work as well as

usual, open the air valves until the water flows, which indicates that

the air has been fully released. Then close the valve.

=Valves on Cellar Mains.=--If cut-off valves have been placed on the

main and return pipes in the cellar, see that the valves on one line

of main and return pipes (at least) are open when the boiler is under

operation. Be sure that the system is open to circulate water through

the supply and return pipes before building a fire in the boiler.

=End of the Season.=--At the close of the heating season clean all

the fire and flue surfaces of the boiler. Let the water remain in the

system during the summer months. No bad results will follow if the

system is not refilled more often than once in 2 or 3 years. But,

generally, it is thought that best results are secured by emptying the

system once a year (after fire is out) and refilling with fresh water.

It is a very good idea to take down the smoke pipe in the spring,

thoroughly clean and put it back in place. Leave all doors open on the

boiler in the summer time.

=Other Rules for Steam Boilers=--_To Fill Boiler._--Open the feed-cock

when the heater is connected with city or town water supply; if not,

fill through the funnel. Let the water run until the gage-glass shows

about half full of water.

In the first filling, after the water has boiled, get up a pressure

of at least 10 pounds, draw the fire and blow off the boiler under

pressure through draw-off cock to remove oil and sediment, after which

refill with fresh water to the water line. This is best done usually by

the steam-fitter.

The damper regulator will control the pressure of steam, closing the

damper when the pressure is raised beyond the desired point and opening

the damper when the pressure falls below that point. By removing the

weight on the lever, different degrees of pressure can be kept up. The

regulator should be allowed to control the drafts without interference.

Examine the water glass often to see that the _water line_ is at the

proper height. If lower than normal open the supply pipe until the

water runs in and stands at the proper level. It is best when no water

stands in the glass, nor shows at the bottom of the try-cock, to

quickly dump the grate and do not put water into the boiler again until

it is cooled off.

If there is one or more shut-off valves on the main or return pipes,

before starting a fire see that one line of piping at least (main and

return) is open to circulate the steam.

=To Control Radiators.=--When it is desired to shut off steam from any

radiator (if the regular radiator valves are used), close the valve

_tight_, and when it is turned on see that the valve is _wide open_.

A valve partly turned off will cause the radiator to fill with water.

This rule applies only to one-pipe heating systems.

=The Air Valves.=--If little keyed air valves (sometimes called

“pet-cocks”) are used, follow generally the same directions as outlined

for hot-water radiators on page 49--only, of course, in releasing the

air from the radiator open the valve with the key provided and close it

just as soon as the steam unmixed with air comes through the nose of

the valve.

If “automatic” air valves are used they must be carefully adjusted by

the steam-fitter and then left to operate without undue interference.

=End of the Season.=--At the close of the heating season fill the steam

boiler with water to the safety valve and let it thus stand through the

summer.

Also thoroughly clean all the fire and flue surfaces of the boiler and

at the opening of the next season withdraw the water and refill with

fresh water to the water line, starting the boiler as before.

It is advisable to have a competent steam-fitter blow off the boiler

under pressure and thus give the inside a thorough cleaning when the

boiler is first set up and ready for fire.

A low-pressure boiler, using good water, rarely needs blowing off after

it is once cleaned at time of setting up.

THE RIGHT CHIMNEY FLUE

The area of the flue should never be less than 8 inches in diameter

if round, or 8 by 8 inches if square--unless for a very small heating

boiler or tank heater. Nine or 10 inches round, or 8 by 12 rectangular

is a good average size. The flue should generally have a little more

area than that of the connecting smoke pipes.

Draft force depends very much on the height of the flue.

The chimney top should run above the highest part of the roof and

should be so located with reference to any higher buildings nearby that

the prevailing wind currents will not form eddies which will force the

air downward in the shaft. Often a shifting cowl which will always turn

the outlet away from the source of adverse currents will promote better

draft.

The flue should run as nearly straight up from the base to the top

outlet as possible. It should have no other openings into it but the

boiler smoke pipe. Sharp bends and offsets in the flue will often

reduce the area and choke the draft. The flue must be free of any

feature which prevents a free area for the passage of smoke. The outlet

must not be capped with any device which makes the area of the outlet

less than the area of the flue.

The best form of flue is a round tile--in such there is less friction

than in the square form and the spiral ascent of the draft moves in the

easiest and most natural manner.

If the flue is made of brick only, the stack should be at least two

4-inch courses in thickness.

If there is a soot pocket in the flue below the smoke-pipe opening, the

clean-out door should always be closed. If this soot pocket has other

openings in it--from fireplaces or other connections--such arrangements

are very liable to check the draft and prevent best action in the

boiler.

The smoke pipe should not extend into the flue beyond the inside

surface of the flue, otherwise the end of the pipe cuts down the area

of the flue and injures its drawing capacity.

The inside of a flue should be smooth (pointed or plastered). When

the courses are laid with the mortar bulging out from the joints the

friction within the flue is very much increased. Often a troublesome

flue is corrected by lowering some sharp-edged weight by a rope which

should be worked against the sides of the flue until the clogging is

scraped off.

A new chimney when “green” will not have a good drawing capacity. Short

use dries out the mortar and better results follow.

=“Smokey” Chimneys.=--The failure of draft in flues may be due to a

variety of causes, one of which is illustrated in Fig. 57_b_. The short

chimney on the left side of the roof shows the course of the wind

as it passes over the ridge of the roof and why the draft in such a

chimney is retarded whenever this condition exists. The force of the

wind, as it comes into contact with the roof, causes a compression of

the air on the windward side and a rarification on the lee side. This

inequality of pressure causes a downward sweep of the wind as indicated

by the arrows. The effect on the low chimney is to retard the draft and

sometimes the pressure is great enough to reverse the action of the

flue and force the smoke into the house. The only remedy for such a

condition is an extension of the chimney that will raise its top above

the ridge.

[Illustration: FIG. 57_b_.--Effect of the wind in causing down draft in

low chimneys.]

The same effect is often produced by a neighboring building or a border

of trees that are higher than the chimney and dense enough to effect

the wind pressure.

Mechanics of the Household A Course of Study Devoted to Domestic Machinery and Household Mechanical Appliances · 第 5 / 14 章