H - h = xL + 0.47(t_{2} - t_{1})

H - h - 0.47(t_{2} - t_{1})

or x = --------------------------- (4)

L

Almost invariably the lower pressure is taken as that of the atmosphere.

Under such conditions, h = 1150.4 and t_{1} = 212 degrees. The formula

thus becomes:

H - 1150.4 - 0.47(t_{2} - 212)

x = ------------------------------ (5)

L

For practical work it is more convenient to dispense with the upper

thermometer in the calorimeter and to measure the pressure in the steam

main by an accurate steam pressure gauge.

A chart may be used for determining the value of x for approximate work

without the necessity for computation. Such a chart is shown in Fig. 15

and its use is as follows: Assume a gauge pressure of 180 pounds and a

thermometer reading of 295 degrees. The intersection of the vertical

line from the scale of temperatures as shown by the calorimeter

thermometer and the horizontal line from the scale of gauge pressures

will indicate directly the per cent of moisture in the steam as read

from the diagonal scale. In the present instance, this per cent is 1.0.

Sources of Error in the Apparatus--A slight error may arise from the

value, 0.47, used as the specific heat of superheated steam at

atmospheric pressure. This value, however is very nearly correct and any

error resulting from its use will be negligible.

There is ordinarily a larger source of error due to the fact that the

stem of the thermometer is not heated to its full length, to an initial

error in the thermometer and to radiation losses.

With an ordinary thermometer immersed in the well to the 100 degrees

mark, the error when registering 300 degrees would be about 3 degrees

and the true temperature be 303 degrees.[19]

The steam is evidently losing heat through radiation from the moment it

enters the sampling nipple. The heat available for evaporating moisture

and superheating steam after it has passed through the orifice into the

lower pressure will be diminished by just the amount lost through

radiation and the value of t_{2}, as shown by the calorimeter

thermometer, will, therefore, be lower than if there were no such loss.

The method of correcting for the thermometer and radiation error

recommended by the Power Test Committee of the American Society of

Mechanical Engineers is by referring the readings as found on the boiler

trial to a "normal" reading of the thermometer. This normal reading is

the reading of the lower calorimeter thermometer for dry saturated

steam, and should be determined by attaching the instrument to a

horizontal steam pipe in such a way that the sampling nozzle projects

upward to near the top of the pipe, there being no perforations in the

nozzle and the steam taken only through its open upper end. The test

should be made with the steam in a quiescent state and with the steam

pressure maintained as nearly as possible at the pressure observed in

the main trial, the calorimeter thermometer to be the same as was used

on the trial or one exactly similar.

With a normal reading thus obtained for a pressure approximately the

same as existed in the trial, the true percentage of moisture in the

steam, that is, with the proper correction made for radiation, may be

calculated as follows:

Let T denote the normal reading for the conditions existing in the

trial. The effect of radiation from the instrument as pointed out will

be to lower the temperature of the steam at the lower pressure. Let

x_{1} represent the proportion of water in the steam which will lower

its temperature an amount equal to the loss by radiation. Then,

H - h - 0.47(T - t_{1})

x_{1} = -----------------------

L

This amount of moisture, x_{1} was not in the steam originally but is

the result of condensation in the instrument through radiation. Hence,

the true amount of moisture in the steam represented by X is the

difference between the amount as determined in the trial and that

resulting from condensation, or,