The cause of the explosion was shortness of water, and as the glass

gauge was set unusually low, the man in charge may have been deceived.

The oval shape of the fireplace, and the laminated iron, as shown in

the fracture, rendered the tube peculiarly liable to collapse.

_No. 27. Durham. May 26th. 1 killed._

Plain Cylinder Boiler, 34ft. long, 5ft. diameter, 3/8 inch plates, 45

lbs., fitted with two 5-inch safety valves, and 2 floats.

The boiler was torn in two pieces, that were thrown to a considerable

distance. The first rent had taken place immediately over the fire.

The cause of the explosion was the weakening of the shell by frequent

repair over the fire, rendered necessary by the deposit from the muddy

water preventing proper contact of the water with the plates.

_No. 28. Durham. May 27th. 1 killed._

Plain Cylinder Boiler, 32ft. long, 6ft. diameter, 3/8 inch plates, 35

lbs., fitted with two safety valves, two floats, and two alarm whistles.

The boiler was lifted from its seat, and one end was separated and

thrown to a considerable distance.

The cause of the explosion was weakening of the shell from repair a few

days before, and perhaps over pressure, as the gauge was found some

time after, and indicated that the pressure had at some time exceeded

80 lbs.

_No. 29. Redruth. May 28th. 1 killed, 4 injured._

One Tube Cornish, 30ft. 8in. long, 6ft. 8in. diameter, tube, 4ft.

diameter, 7/16 inch plates, 40 lbs.

The tube collapsed, and rent, and the issuing steam and water scalded

those near, as it was too weak to bear the ordinary working pressure.

_No. 30. Leicester. (Fig. 17.) May 31st. 1 killed, 1 injured._

[Illustration: _Fig. 17._]

Plain Cylinder Boiler, with dished ends, and only 4ft. 2in. long, and

2ft. 6in. diameter, 1/4 inch plates. It was most inefficiently mounted,

the safety valve was only 1-5/8-inch diameter, and of such faulty

construction, that it would not open under a pressure of 162 lbs. There

was no steam gauge or float, and the gauge cocks were defective. There

was no means of putting water in the boiler when there was a pressure

of steam. The manhole was very large for so small a boiler.

Four rents started from the manhole and continued along the top of the

boiler and round the end seams. A tongue-shaped strip of the top plate

was attached to the back end plate; two strips about a foot wide on

either side were blown away. The boiler had been turned nearly round

in its flight, and fell with the back about 12 feet from the original

position of the front.

The boiler was worked until it was nearly dry, and, during a temporary

stoppage of the engine, an accumulation of steam caused a greater

pressure than the boiler could bear.

_No. 31. Newcastle. June 7th. none injured._

Marine Boiler in a Tug Boat.

The boiler was blown completely out of the vessel, and the greater part

of it fell into the water, and a large piece alighted on a crowded

quay, but without doing any damage.

The cause of the explosion was supposed to be over-pressure during a

temporary stoppage of the engine.

_No. 32. Barnard Castle. (Fig. 18.) June 11th. 2 injured._

[Illustration: _Fig. 18._]

Agricultural, of about 7 horse power. The barrel of the boiler was

6ft. 1in. long, 2ft. 5in. diameter; the fire-box end was 3ft. wide,

and 2ft. 4in. deep; the fire-box was 2ft. 5-1/2in. wide, and 2ft. 7in.

high, and 1ft. 9-1/2in. deep, with 23 tubes passing from it through the

barrel to the smoke box and chimney. The boiler was fitted with a 2in.

safety valve, which was intended to blow at 45 lbs., but as there was

no ferrule, it is supposed to have been screwed down to a much greater

pressure.

The upper portion of the shell over the fire-box rent through the

manhole, and allowed the shell to open out and fall on each side. A

large portion of the front plate was also torn off.

The cause of the explosion was the weakness of the manhole, which was

not strengthened by any ring, and also excessive pressure from want of

proper safety valve.

_No. 33. Breage. June 11th. 1 killed._

Cornish Boiler, 36ft. 6in. long, and 6ft. diameter, 3/8 inch plates, 45

lbs.

The tube collapsed and rent, and the issuing contents caused the death

of the attendant.

The weak tube of such large diameter, was unable to bear the ordinary

working pressure, having no strengthening rings.

_No. 34. Nottingham. June 19th. 2 killed, 4 injured._

Locomotive, 1/2 inch plates, 140 lbs.

The explosion occurred at the left hand side of the ring of plates

in the barrel next the fire-box, and below the foot-plate. The rent

tore along the edge of the lap and into the next ring of plates. The

reaction of the issuing contents threw the engine off the rails.

The cause of the explosion was partial corrosion at the point of

rupture and strain of the plates, as the boiler itself formed part of

the frame of the engine.

_No. 35. Richmond. June 26th. 2 injured._

Locomotive, being tried for the first time. The funnel came in contact

with a bridge, and the dome was also torn off.

_No. 36. Gainsbro' June 29th. none injured._

No details have been obtained.

_No. 37. Durham. July 2nd. 4 killed._

Plain Cylindrical Boiler, 30ft. long, and 6ft. diameter, 3/8 inch

plates, 28 lbs. It had been repaired a short time before the explosion,

with 5 new plates.

The boiler was torn up into several pieces, but the main portion

remained flattened out on the seating, while some smaller pieces were

sent 250 yards away.

The cause of the explosion was the deterioration of the boiler, and its

frequent repair over the fireplace.

_No. 38. Liverpool. June 12th. 4 injured._

Elephant Boiler, 20ft. long, and 4ft. diameter, 3/8 inch plates, and

worked at low pressure. The bottom shell had a tube through its whole

length.

A rent took place in the lower part of the fireplace, and extended

along the bottom, and the reaction of the issuing contents caused the

top to rear up.

The cause of the explosion was supposed to be that the bottom plates

were worn too thin to bear the ordinary pressure.

_No. 39. Sheffield. July 4th. none injured._

Two Tube Cornish Boiler, externally fired, 30ft. long, and 6ft.

diameter, 3/8 inch plates, 40 lbs.

The second seam over the fire gave way, and the plate sank down upon

the fire.

The cause of the explosion was the deterioration of the seams over

the fire, in consequence of the deposit of scurf which could not be

properly cleared off owing to the internal tubes.

_No. 40. Oldham. July 14th. none injured._

Boiler, with two internal furnaces, 9ft. 6in. long, and 2ft. 11in.

diameter, 3/8 inch plates, uniting into one tube beyond. The furnace

crown collapsed near the front of the boiler.

There was an extra weight upon the safety valve, and the steam valve

was left closed, so that more pressure accumulated than the boiler

could bear.

_No. 41. Oxford. July 23rd. 3 injured._

Rag Boiler, not used for the generation of steam. It was a plain

cylinder, with hemispherical ends, about 16ft. long, and 7ft. diameter.

There was a neck at each end upon which the boiler revolved, and

through one of these the steam was admitted to a pressure of 30 lbs.,

in order to assist in cleaning the rags. There was a large manhole for

filling and emptying.

The boiler rent in the middle, and each half was blown to some distance.

The manhole was so large, that the strength of the boiler was too much

reduced, and the constant strain of revolving caused a central seam to

give way at the ordinary pressure.

The sketch to No. 63 is of a similar boiler.

_No. 42. Tunstall. (Fig. 19.) July 28th. 2 killed, 7 injured._

[Illustration: _Fig. 19._]

Boiler, 36ft. 6in. long, and 8ft. 9in. diameter, 7/16 inch plates,

with flat back and hemispherical front end, 36 lbs. A tube 3ft. 3in.

diameter, passed from the back end nearly to the front, and returned

to the back end, but of 6 inches less diameter and then passed to an

iron chimney. The fire grate was beneath the hemispherical end.

The angle iron of the flat back end gave way, and separated from the

shell and with the tubes attached was blown to a good distance, and the

reaction drove the shell far in the opposite direction.

The cause of the explosion was the bad construction of the boiler, as

the back end was quite unsupported, as there were no stays, and the

bend of the tubes was not attached to the shell.

An adjoining boiler which was being cleaned inside by two men, was

rolled off its seat by the force of the explosion.

_No. 43. Widnes. August 2nd. 2 killed, 6 injured._

Plain Cylindrical Boiler, with flat ends, 23ft. long, 5ft. 3in.

diameter, 3/8 inch plates, 40 lbs.

Both the flat ends were blown out, and the first ring of plates at the

front end torn off.

The cause of the explosion was the weakness of the flat ends without

stays.

_No. 44. Sunderland. August 7th. 1 killed, 3 injured._

Locomotive, 13ft. 4in. long, 3ft. 11in. diameter, with 140 2-in. tubes.

The fire-box was 4ft. 5in. long, 3ft. 6in. broad, and 5ft. deep, and

made of copper, 1/2 inch thick, 100 lbs. It was fitted with two 4-in.

safety valves, and a steam gauge.

The fire-box gave way about the middle of the left side, 2ft. 6in.

below the water line, where corroded to 1/8 inch, and the issuing water

and steam scalded those near.

_No. 45. Runcorn. (Fig. 20.) August 22nd. 3 killed, 5 injured._

[Illustration: _Fig. 20._]

Marine Multitubular, 5ft. 8in. long, and 6ft. 6in. diameter, with two

internal tubular furnaces, which joined to an internal chamber of large

size, and small tubes passed to a smoke box and chimney in the front

over the fire doors. Both ends were flat.

The flat back end was insufficiently stayed, and was blown completely

out and torn into two pieces, the lower portion remaining in the

vessel, and the upper part falling in the water, and the reaction of

the issuing contents caused the boiler to be thrown on to the side of

the quay.

_No. 46. Hull. (Fig. 21.) August 25th. 1 injured._

[Illustration: _Fig. 21._]

One Tube Cornish, 24ft. 3in. long, and 6ft. diameter, taper tube 3ft.

5in. diameter, for about 7ft. 6in. in length, and 2ft. 6in. diameter

for the rest of the length, 33 lbs.

The tube was much corroded, and the fireplace gave way on left side,

and was so much torn, that the plates were forced out of the front.

_No. 47. Morecombe. August 27th. 3 killed, 1 injured._

Marine, of the usual construction, and had been tested to 60 lbs.

It gave way at the lower portion of the back, and the issuing steam and

water scalded those near.

A seam rent, 6ft. 6in. long, had not been detected by testing.

_No. 48. Tuddenham. August 29th. 2 killed, 2 injured._

Agricultural. It burst during a temporary stoppage from accumulation of

steam, causing undue pressure.

_No. 49. Glasgow. August 31st. 3 killed, 6 injured._

Upright Boiler, 36ft. high, 5ft. 6in. diameter, 7/16 inch plates, 45

lbs.

The bottom gave way from shortness of water, and the main bulk of the

boiler was thrown straight up into the air to a great height, but

descended again on its seating.

_No. 50. Chatham. (Fig. 22.) September 7th. 2 killed, 30 injured._

[Illustration: _Fig. 22._]

Two Tube Cornish, 22ft. long, 7ft. 6in. diameter, with tubes, 3ft.

diameter, 7/16 inch plate, 60 lbs.

Some rents took place at the under side of the shell, allowing the

central portion to open out and blow away. The portion containing the

dome was thrown to the left, and the other to the right. The front

end, with 3 rings of the shell, with the tubes and back end, were but

little moved from their original position. The tubes were dented in on

the top and bottom, by the fall of some large coping stones upon them,

but the crowns of the furnaces were uninjured, and there was no sign of

shortness of water or overheating.

Extensive corrosion on the under side of the shell, where it rested on

the brickwork, had so reduced the strength, that it was unable to bear

the working pressure.

In the sketch the fragments are drawn so as to show their position when

in the boiler.

_No. 51. Newark. September 21st. none injured._

One tube Cornish. The tube collapsed from shortness of water, and the

escape of the steam and water blew off the door frame.

_No. 52. Ashton. September 23rd. 1 injured._

Plain Cylindrical Boiler, 7ft. long, and 2ft. diameter, 3/8 inch

plates, 30 lbs.

The upper part of the boiler at the first ring of plates was torn off,

and the front end was blown out.

Extensive external corrosion, where the plates rested against the

brickwork, rendered the boiler too weak to bear the ordinary pressure.

_No. 53. Norwich. (Fig. 23.) September 25th. 7 killed._

[Illustration: _Fig. 23._]

One Tube Cornish, 20ft. long, 4ft. 6in. diameter, tube 2ft. 6in.

diameter, 3/8 inch plates, 100 lbs. It was double-rivetted, and the

crown of tube was strengthened with angle iron. The shell was formed

of six rings, each of two plates alternately jointed top and sides.

The third ring from the front had stripped off, and was thrown to the

right and forwards against a wall. The line of rent was confined to the

plates forming the ring, which was an outer one, and covered the two

adjoining rings in the laps, the rent being from the edge of the inner

lap to the nearest rivets. The first rent had taken place in the solid

iron, about 1 inch from the rivets of a seam on one side, and from this

the rent had extended along the seams on either side, and of course

the whole ring soon tore off when the equilibrium was destroyed by the

first rent.

The fittings of the boiler were sufficient, except that there was only

one safety valve, and that was so constructed that it could only open a

very little way.

The cause was a defect in the iron at the point of the first rent, and

accumulated pressure during the time of standing.

_No. 54. Macclesfield. September 25th. none injured._

Multitubular Boiler, with large internal fireplace, 60 lbs.

The furnace crown became overheated from shortness of water, and was

crushed down and torn across two seams. The boiler was lifted from its

seat and thrown back against a stone wall.

_No. 55. Chelmsford. October 5th. 1 killed, 7 injured._

Agricultural, 45 lbs., and had only just been set to work.

The crown plate to the fire-box was so deeply corroded from long wear

that it gave way, and the issuing contents scalded those near.

_No. 56. Greenwich. (Fig. 24.) October 8th. 2 killed, 2 injured._

Marine, 16ft. long, slightly oval, front end flat, 8ft. 6in. wide,

7ft. 10in. high, and the dimensions of the back hemispherical end were

2ft. less each way, 3/8 inch plates, 26 lbs. There were two internal

fireplaces, of irregular shape, uniting at the back into one flue of

similar shape, which did not come to the front, but passed through the

steam space, and out at the top of the boiler.

While the vessel was waiting to start, with steam up, the wing furnace

of the starboard boiler collapsed on the wing side, as shown by the

dotted lines, and allowed the steam and water to escape into the stoke

hole.

[Illustration: _Fig. 24._]

The side of the furnace next the shell was rent along the edge of a

longitudinal seam in a line, which was slightly nicked in the caulking.

This rent extended about 5ft. 6in. from the front, and then at a cross

seam it went along the line of rivets from the crown to the bottom of

the furnace. Beyond this cross seam the furnace was collapsed, until it

nearly touched the other side of the furnace, and the bulge died away

towards the back end. There was also a rent in the lower part of the

front of the shell, as shown in dotted line.

The cause of the explosion was the weakness of the shape of the flue,

which was not stayed to the shell. It had evidently gradually been

giving way some time before the explosion, and eventually collapsed at

nearly the ordinary pressure. Symptoms of the same alteration of shape

were noticed in the corresponding flue of the other boiler.

_No. 57. Liverpool. (Fig. 25.) October 9th. 7 killed, 1 injured._

Crane Boiler, 5ft. 6in. high, and 2ft. 6in. diameter, with internal

conical fire-box, with two cross tubes and a chimney at the top, 1/4

inch plates, 75 lbs.

The outer shell of the boiler was rent into many pieces, leaving the

central conical fireplace intact. The nature of the rents showed that

the plate round the manhole, which was unstrengthened by a ring, had

first given way, and all the other fractures had led away from that

point. This is confirmed by the fact, that the manlid was thrown a good

distance, with force enough to make its way through the timber walls

of a cabin. The front plate divided into many pieces, and scattered

right and left, while the back plate was thrown through a cabin in the

opposite direction to the manhole.

[Illustration: _Fig. 25._]

The central flue showed a slight indication of overheating, but the

construction was such that the upper portion passed through the steam

space, and was always exposed to the action of the fire, without the

protection of the contact of water. The manhole without a ring on its

edge to strengthen the plate, and held in by two clamps, which caused

additional strain when carelessly screwed up, was by far the weakest

place. The engine was standing after a short time of working, and as

the safety valve was very defective, and could be screwed down until

tight, against almost any pressure, it is most probable that the

pressure mounted much higher than usual, when the weakest part gave

way, and led to the sudden tearing up and scattering of the whole

fabric.

Faulty construction of both boiler and fittings, rendered it unable to

bear that accumulated pressure, which the safety valve ought to have

made impossible.

_No. 58. Durham. October 13th. 1 killed._

One Tube Cornish, 14ft. long, 6ft. diameter, internal flue 3ft. 3in.,

by 2ft. 10in., 3/8 inch plates, 27 lbs., standing on three saddles,

with a bearing surface of 3ft. by 4 inches.

A portion of plate 20in. by 18in., at the bottom of the boiler, was so

corroded that it was blown out, and the issuing contents scalded a man

to death.

_No. 59. Bristol. (Fig. 26.) November 1st. 7 killed._

[Illustration: _Fig. 26._]

Two Marine Boilers exploded simultaneously. They were 16ft. long,

6ft. 6in. diameter at the flat front ends, and somewhat less at the

hemispherical back ends. Each had two internal fireplaces, united in

one flue, which returned nearly to the front and passed up through the

steam space, and out at the top of shell into the funnel. The central

fireplaces were not circular, and the outside fireplaces and the return

flues were still more distorted, but the weakness of the shape was

somewhat compensated for by stays between the tubes, and from the tubes

to the shell. The mountings to the boiler were of the ordinary kind and

efficient.

The under sides of the shells were so deeply corroded that they were

rent longitudinally for their whole length, allowing the sides to

open out and tear away from the front ends. Each shell fell at a

considerable distance. The furnaces, with parts of the front ends

attached, fell into the water, but except one of the side flues that

was a little collapsed, they were uninjured. Small pieces of the front

ends were thrown to a great distance. The sides of the vessel were so

completely blown out that she sank.

The corrosion was no doubt caused by the leakage of the vessel, keeping

the shells of the boilers constantly wet.

_No. 60. London. (Fig. 27.) November 3rd. none injured._

[Illustration: _Fig. 27._]

Agricultural, barrel was 3ft. 9in. long, and 2ft. 6in. diameter, 70

lbs. From the internal fire-box the heat passed through a number of

1-inch tubes to the front smoke box and chimney.

During a stoppage for breakfast, the fire-box end was torn from the

barrel, and from the position of those fragments that could be found,

the boiler appeared to have turned over. Part of the fire-box was sent

through the stage upon which the boiler was travelling, and the barrel

with the tubes remaining in it, first struck a rail which caused it to

be dented in, and then rebounded to a point about 100 yards from its

original position.

Enough of the fragments were not recovered from the river to trace the

cause of the explosion, but it is presumed that, although when the

boiler was left, only 20 lbs. pressure was shown by the gauge; the fire

door being left closed, the pressure must have risen to a point much

above the working pressure, and to more than the boiler could bear.

_No. 61. Bilston. (Fig. 28.) October 1st. none injured._

One Tube Cornish, 22ft. long, 6ft. diameter, tube 4ft. 6in. diameter,

3/8 inch plates, 12 lbs. There was an unusually large dome at the back

end, 5ft. diameter, and the whole of the shell was cut out from under

it, so that the construction was peculiarly weak.

[Illustration: _Fig. 28._]

The boiler had been off for cleaning, and steam was being got up in the

night, and it was said that an extra pressure was caused by the stop

valve being left closed, but it could not have been very great, or the

large tube would have collapsed.

The dome was split in two, in the line marked in the sketch, owing to

the extreme weakness of the shell at the juncture of the dome, and the

shell was a little ruptured on each side of it, and so large a rent was

suddenly made, that the contents of the boiler passed harmlessly into

the air, without moving the boiler on its seat.

_No. 62. Preston. (Fig. 29.) November 11th. 1 killed, 1 injured._

[Illustration: FRONT VIEW. BACK VIEW.

_Fig. 29._]

One Tube Cornish, 16ft. 3in. long, and 5ft. 8in. diameter, tube 3ft.

1in. diameter, 7/16 inch plates, 60 lbs.

The tube collapsed from end to end, from over-pressure, as the man in

charge had fastened 3 bricks to the lever of the safety valve causing

27 lbs. extra pressure, under the impression that he could thus

accumulate a quantity of steam during the night, to be available on

commencing work on the morrow.

_No. 63. Tamworth. (Fig. 30.) November 20th. none injured._

[Illustration: _Fig. 30._]

Revolving Steam Chamber, 12ft. 6in. long, and 5ft. diameter, 12 lbs.

The manhole was large, to facilitate filling and emptying, and was

rectangular and unstrengthened on the edges, and measured 3ft. 6in. in

length, and 1ft. 6in. in width, and the lid fitted on the inside and

was held by clamps.

The boiler was much out of repair, and a crack shown in sketch, from

one corner of the manhole to the commencement of the hemispherical end

was only temporarily prevented from leaking by a screw-patch, which did

not restore the strength.

The explosion happened when in revolving, the manlid was downwards, and

the lid was driven nearly through the floor, and the shell was rent

from opposite corners of the manhole, and blown through the roof.

The large manhole cut away nearly all the strength on one side, and

the fastenings of the lid were not contrived to compensate at all for

the loss of strength. The constant strain when revolving, also tended

to weaken it. These two causes together were sufficient to account for

the explosion, at the usual working pressure of 12 lbs., although it is

possible that it might have been increased to 35 lbs., as that was the

pressure in the boiler supplying the steam, although the pressure was

regulated by a check valve.

This explosion (and also No. 41 in this year) clearly show that a mere

vessel of steam not exposed to the fire, or any chance of overheating

of the plates, can burst and cause very great destruction, although

there could be no sudden _increase of pressure_ which is so often

supposed necessary to account for the havoc caused by explosions.

_No. 64. Manchester. November 26th. none injured._

This Boiler was 28ft. long, 7ft. diameter, made of 7/16 inch plates,

and worked at 50 lbs. pressure, with two internal fireplaces united

into one tube beyond.

The sides of the oval chamber forming the junction of furnaces and

tube, crushed inwards, being of such a weak shape as to be unable to

resist the ordinary working pressure.

_No. 65. Hull. (Fig. 31.) December 1st. 3 killed, 2 injured._

[Illustration: _Fig. 31._]

Agricultural, 7ft. 6in. long, and 3ft. 8in. diameter, 1/4 inch plates,

35 lbs., fire-box 2ft. long, and 2ft. 10in. broad. Two 11-1/2-inch

tubes led to an internal chamber at the other end of the boiler, and

three 8-1/4-inch tubes led back again to an external smoke box and

chimney fixed over the fire door.

The bottom of the right hand side lower tube was forced upwards, and

rent along to within 12 inches of the fire-box.

The tubes were so corroded from leakage of patches, that they were

unable to bear the slight increase of pressure during a short stoppage.

Records of Steam Boiler Explosions · 第 6 / 12 段