The footlights are generally made to extend nearly the full opening of

the stage and the lights should be crowded into them as closely as

possible. The lighting should be divided into three groups suitable for

three colors. It is customary to have about half of the lights white and

the remaining half divided into two equal parts for different colors. A

small part of the white lights should be arranged upon a separate

circuit so that they may be used for rehearsals or other purposes, when

not very much light is needed.

No very definite recommendations concerning the type of lamp to be used

can be given. In some theaters the stage is very solid and tungsten

lamps are used to advantage; in others the jarring prevents their use.

The white lights should be arranged so that their light need not pass

through the colored lamps. In vaudeville houses some protection in the

form of chains or guards is often provided to prevent objects from being

rolled or thrown against the lights. Figures 161 and 162 show types of

footlights and the manner of installing the sockets.

_The National Electrical Code Rules for Wiring Footlights._

Must be wired in approved conduit or armored cable, each lamp receptacle

being enclosed within an approved outlet box, or the lamp receptacles

may be mounted in an iron or steel box, metal to be of a thickness not

less than No. 20 U. S. sheet metal gauge treated to prevent oxidation

and so constructed as to enclose all the wires. Wires to be soldered to

lugs of receptacles. Must be so wired that no set of lamps requiring

more than 1,320 watts nor more than 26 receptacles shall be dependent

upon one cut-out.

_Fuses._--See “Cut-outs.”

_Gallery Lighting._--The proper lighting of galleries is a difficult

matter where there is another gallery above. In such a case the ceiling

is always very low. An even distribution of light requires the use of

many small incandescent lamps evenly distributed. This will make the

wiring expensive. The light should be taken pretty well from the rear so

as to avoid placing lights in the range of visions of the audience.

Emergency lights should be provided here as well as in the main

auditorium.

_Gallery Pockets._--Pockets for arc lamps are often provided, as it

often happens that a moving-picture machine must be placed in the

gallery. The stage pockets should be wired with number 6 B. & S. gauge

wire, this being the smallest wire allowed to feed a moving-picture arc.

The stage pocket should be controlled by a switch on the switchboard. It

often happens that the operator at the lamp has a wrong cue and his

light can then be controlled by the stage manager at the stage

switchboard.

_Gas Lighting._--Electric gas lighting is very little used at the

present time, but in many theaters the emergency lighting is by gas and,

in order to save the time necessary to light these by hand before every

performance, an automatic gas lighting system has been installed in some

theaters. A diagram of such a system is shown in Figure 163. A battery

of considerable capacity is necessary and also a spark coil _S_. At each

gas jet a magnet _M_ is installed which, when energized, is capable of

turning the gas on and at the same time producing a spark. This magnet

is also capable of turning the gas off. Two buttons are provided, one to

turn the gas on and the other to turn it off.

[Illustration: FIGURE 163.]

As the wiring is always used in connection with gas piping, grounds are

of frequent occurrence, and in order to indicate a ground as soon as it

comes on, the bell and battery shown are provided. If a ground causes a

continuous current, the spark coil will attract the armature, thus

causing the bell to ring continuously.

_National Electrical Code Rule for Gas Lighting._

Electric gas lighting, unless it is the frictional system, must not be

used on the same fixtures with the electric light.

_Grid Floor._--This is the term given to the framework which supports

the pulleys over which the cables for handling curtains and scenery run.

It is usually made up of parallel iron slats or bars; hence the name. A

fairly good illumination should be provided here and all of the lights

should be arranged on three-way switches. One light for every 400 square

feet will be sufficient.

_National Electrical Code Rule for Ground Clamps._

Connections to grounded pipes and to conduit must be exposed to view or

be readily accessible, and must be made by means of approved ground

clamps to which the ground wire must be soldered.

_National Electrical Code Rule for Grounding._

The metal of conduit, armored cable, or metal molding must be

permanently and effectually grounded to water piping, gas piping, or

other suitable grounds, provided that, when connections are made to gas

piping, they must be on the street side of the meter. If the conduit

system consists of several separate sections, the sections must be

bonded to each other, and the system grounded; or each section may be

separately grounded, as required above.

Conduits and gas pipes must be securely fastened in outlet boxes,

junction boxes, and cabinets, so as to secure good electrical

connections.

If conduit, couplings, outlet boxes, junction boxes, cabinets, or

fittings, having protective coating of non-conducting material such as

enamel, are used, such coating must be thoroughly removed from threads

of both couplings and conduit and such surfaces of boxes, cabinets and

fittings where the conduit or ground clamp is secured in order to obtain

the requisite good connection. Grounded pipes must be cleaned of rust,

scale, etc., at place of attachment of ground clamp.

Connections to grounded pipes and to conduit must be exposed to view or

readily accessible, and must be made by means of approved ground clamps

to which the ground wires must be soldered.

Ground wires must be of copper, at least No. 10 B. & S. gauge (where

largest wire contained in conduit is not greater than No. 0 B. & S.

gauge), and need not be greater than No. 4 B. & S. gauge (where largest

wire contained in conduit is greater than No. 0 B. & S. gauge). They

shall be protected from mechanical injury.

The ground on the conduit system is not to be considered as a ground for

a secondary system.

_Guards._--A guard rail should be provided around the stage switchboard

to prevent actors from coming in contact with any live part of the

switchboard. All incandescent lamps about the stage, dressing rooms,

fly-floor, grid-floor, etc., should be provided with guards.

_Hanger-Boards._--Hanger-boards are not compulsory but where not used,

arc lamps must be hung from insulating supports other than their

conductors.

_National Electrical Code Rule for Hanger-Boards for Series Arc Lamps._

Hanger-boards must be so constructed that all wires and current-carrying

devices thereon will be exposed to view and thoroughly insulated by

being mounted on a non-combustible, non-absorptive, insulating

substance. All switches attached to the same must be so constructed that

they shall be automatic in their action, cutting off both poles to the

lamps, not stopping between points when started, and preventing an arc

between points under all circumstances.

_Heaters._--Heaters are used sometimes in cold dressing rooms, in box

offices and in other small spaces where other adequate heating

arrangements have not been made. The fire hazard incident to the use of

electric heaters is considerable and they should be carefully installed

according to the rules given below.

From one-half to three watts per cubic foot will be required to heat a

room. The quantity of heat necessary to be supplied depends largely upon

the ventilation. It will be small in closed dressing rooms and large,

for instance, in the box office. Always place a heater where the air

enters a room; never where it leaves.

_National Electrical Code Rules for Electric Heaters._

Each heater of more than 6 amperes or 660 watts capacity must be

protected by a cut-out, and controlled by a switch or plug connector

plainly indicating whether “on” or “off” and located within sight of

the heater. Heaters of 6 amperes or 660 watts capacity, or less, may be

grouped under the protection of a single set of fuses, provided the

rated capacity of the fuses does not exceed 10 amperes; or may be

connected individually to lighting circuits.

Flexible conductors for smoothing irons and sad irons, and for all

devices requiring over 250 watts, must have an approved insulation and

covering.

With portable heating devices, approved plug connectors must be used so

arranged that the plug may be pulled out to open the circuit without

leaving any live parts so exposed as to render likely accidental contact

therewith. The connector may be located at either end of the flexible

conductor or inserted in the conductor itself.

Smoothing irons, sad irons, and other heating devices that are intended

to be applied to combustible articles, must be provided with approved

stands.

Stationary heaters such as radiators, ranges, plate warmers, etc., must

be so located as to furnish ample protection between the device and

surrounding combustible material.

Must each be provided with a name-plate, giving the maker’s name and the

normal capacity in volts and amperes.

_High Potential._--The National Electrical Code classifies all voltages

below 550 as low. Nevertheless voltages above 220 should not be

considered in the auditorium, stage, or dressing rooms of any theater.

And this voltage only in connection with a three-wire system where the

high voltage exists only between the outside wires, and 110 volts are

used for lamps and other devices. High potential systems should be used

only on the outside.

_Illumination._--Illumination is more an art than a science and the

rules that can be given have only a very general application. The best

practice, where really good illumination is desired, is to install a

large number of circuits in proportion to the number of lights, so that

lamps of large candle power may be used wherever desirable. The quantity

of light needed in theaters varies greatly with the color of decorations

and with their condition. Dust accumulates rapidly in theaters and may

absorb half of the light. If there is plenty of capacity the candle

power of lamps may be changed to suit conditions and obtain any result

desired.

The number of sockets installed in the auditorium varies widely. In some

of the cheaper theaters one light for each twenty seats is considered

sufficient; while in elaborately lighted houses, there are cases where

the number of sockets is equal to about half the number of seats. Good

illumination requires that the light come from the back, but very often

the purpose is to obtain a brilliant effect by placing lights in front

of the audience. In such cases, however, the lamps are always of low

candle power and should be frosted.

_Incandescent Lamps._--Practically all incandescent lamps are now rated

in watts. They can be obtained in voltages ranging from 2 to 250 and may

be operated in series or in multiple. All but the tantalum lamp operates

equally well on alternating or direct current. The tantalum cannot be

recommended for alternating-current circuits. No incandescent lamps will

operate well on frequencies lower than forty cycles. The natural

distribution of light is mostly in the horizontal plane and for good

illumination reflectors should be provided.

The color value is in the following order: Tungsten, tantalum,

graphitized filament, carbon filament. None are equal for color-matching

purposes to the intensified arc or the Moore tube.

The life of all incandescent lamps varies inversely with the voltage. An

increase in voltage will produce an increase in the efficiency of the

lamp but shorten its life. The efficiency decreases with continued use,

and it is generally considered that the useful life of a lamp is over

when its efficiency has fallen to 80 per cent of its original value.

Frosting or coloring shortens the life of lamps from 30 to 50 per cent

and reduces the candle power from 3 to 10 per cent, but the lamp yields

a more pleasing light. Frosting is ordinarily used only where lamps are

placed so as to come in the line of vision. Bowl frosting does not

materially reduce the life of a lamp.

_Efficiency of Lamps._

With incandescent lamps the term “efficiency” has a meaning quite

different from that usually given, it being the number of watts per

candle power. The lower the efficiency of an incandescent lamp, the

better it is and the more light it yields per watt consumed.

_Mazda Lamp._

The Mazda lamp has an efficiency of about 1.25 and is the most efficient

of all. It may be recommended in all places where lamps may be suspended

vertically; where there is not too much jarring; where there is ordinary

care in handling; and where the lamps are burning a large part of the

time. The operating expense of this lamp is low, but the initial cost is

high and the breakage is likely to be considerable. If lamps are much

handled and not burned much, the cost of broken lamps may exceed the

saving in energy. It is best not to clean Mazda lamps when cold. Shock

absorbers should be used where there is much jarring. The illumination

should be laid out for the use of lamps not smaller than 60 watts. The

lamps should not be used for temporary work or for coloring. Arrange

lamps as far as possible to be controlled by switches. Broken filaments

can often be united again by shaking the lamps gently until the broken

ends come together. The current will then weld them. When a bank of

Mazda lamps is turned on there is an excessive current for an instant.

_Tantalum Lamp._

The efficiency of this lamp is from 1.8 to 2 watts per candle power.

This lamp is much used for street-car and similar illumination

because it stands jarring very well. It should not be used on

alternating-current circuits. The filament can often be united in the

same manner as the Mazda.

_Graphitized Filament Lamp._

This lamp has an efficiency of 2.5 watts per candle power.

_Carbon Filament Lamp._

This lamp used on 110-volt circuits has an efficiency of from 3 to 3.2

watts per candle power. The efficiency of the smaller sizes is from 4 to

5 watts per candle power. The carbon filament lamp is the most

expensive of all to operate, but on account of the strength and

cheapness of the lamp it can be recommended in places where the breakage

is liable to be great or where the light is used for comparatively brief

periods.

_National Electrical Code Rules for Incandescent Lamps._

Must be provided with guards when liable to come in contact with

inflammable material or subject to rough usage. Must be protected by

vapor-proof globes where inflammable gases exist.

_National Electrical Code Rules for Insulating Joints._

When supported at outlets in metal conduit, armored cable, or metal

molding systems, or from gas piping or any grounded metal work; or when

installed on metal walls or ceilings, or on plaster walls or ceilings

containing metal lath, or on walls or ceilings in fireproof buildings,

fixtures must be insulated from such supports by approved insulating

joints placed as close as possible to the ceilings or walls. The

insulating joint may be omitted in conduit, armored cable, or metal

molding systems with straight electric fixtures in which the insulation

of conductors is the equivalent to insulation in other parts of the

system, and provided that approved sockets, receptacles, or wireless

clusters are used of a type having porcelain or equivalent insulation

between live metal parts and outer metal shells, if any.

Where insulating joints are required, fixture canopies of metal must be

thoroughly and permanently insulated from metal walls or ceilings, or

from plaster walls or ceilings on metal lathing, and from outlet boxes.

Canopy insulators must be securely fastened in place, so as to separate

the canopies thoroughly and permanently from the surfaces and outlet

boxes from which they are designed to be insulated.

_Inverted Lighting._--In this method of lighting the light is first

thrown upward against the ceiling and then reflected back. This method

can be used to advantage with light colored ceilings only. It is

especially suited for low ceilings and with high ceilings the advantage

disappears. The light obtained in this manner is very even and almost

shadowless. Much light is lost through absorption but, owing to the fact

that the light is of such an even quality, the eye readily accommodates

itself to a lower quantity and the net increase in energy required to

illuminate suitable spaces is not so very great. Those who wish to go

into the subject of illumination thoroughly will find it treated fully

in “Modern Illumination Theory and Practice”.

_Joints._--Methods of making joints are illustrated in Figure 164. Be

careful not to overheat, especially at points where there is a strain on

the wire.

_National Electrical Code Rule for Joints._

Wires must be so spliced or joined as to be both mechanically and

electrically secure without solder. The joints must then be soldered

unless made with some form of approved splicing device, and covered with

an insulation equal to that on the conductors.

[Illustration: FIGURE 164.]

Stranded wires (except in flexible cords) must be soldered before being

fastened under clamps or binding screws; and, whether stranded or solid,

when they have a conductivity greater than that of No. 8 B. & S. gauge

they must be soldered into lugs for all terminal connections, except

where an approved solderless terminal connector is used.

_Junction Boxes._--Junction boxes are installed in conduit systems for

the purpose of facilitating the drawing in of the wire or of branching

off from a main run. See “Conduit Work.”

_Lamps._--See “Incandescent Lamps.”

_Lobby._--The lobby generally requires a number of lights and the aim

often is to create a lavish display. Very often a cut-out center is

arranged at some convenient place. The exit and emergency lights must be

controlled from the lobby. Sometimes outlets are provided for electric

bulletin boards or small signs.

_Lugs._--For solderless lugs, such as are used on rheostats or for arc

lamps, see “Portable Stage Equipment.”

_National Electrical Code Rule for Lugs._

For fuses rated over 30 amperes lugs, firmly screwed or bolted to the

terminals and into which the conducting wires are soldered, must be

used. On rheostats, resistances, etc., lugs will not be required when

leads are provided as a part of the device.

Switches for current of over 30 amperes must be equipped with lugs,

firmly screwed or bolted to the switch, and into which the conducting

wires shall be soldered. For the smaller sized switches simple clamps

can be employed, provided they are heavy enough to stand considerable

hard usage.

Where lugs are not provided, a rugged double-V groove clamp is advised.

A set screw gives a contact at only one point, is more likely to become

loosened, and is almost sure to cut into the wire. For the smaller

sizes, a screw and washer connection with up-turned lugs on the switch

terminal gives a satisfactory contact.

_National Electrical Code Rules for Metal Moldings._

Must not be used on stage side of proscenium wall.

Must not be used for circuits carrying more than 1,320 watts.

Wire used must be standard rubber covered, but may be single braid.

Must never be concealed or run in damp places.

Must not be used where the difference of potential exceeds 300 volts.

Must be continuous from outlet to outlet, to junction boxes, or approved

fittings designed especially for use with metal moldings, and must at

all outlets be provided with approved terminal fittings which will

protect the insulation of conductors from abrasion, unless such

protection is afforded by the construction of the boxes or fittings.

Such molding where passing through a floor must be carried through an

iron pipe extending from the ceiling below to a point five feet above

the floor, which will serve as an additional mechanical protection and

exclude the presence of moisture often prevalent in such locations.

Where the mechanical strength of the molding itself is adequate, this

ruling may be modified to require the protecting piping from the ceiling

below to a point at least three inches above the flooring.

Where such moldings pass through a partition the iron pipe, required for

passing through floors, may be omitted and the molding passed directly

through, providing the partition is dry and the molding is in a

continuous length with no joint or coupling within the partition.

Backing must be secured in position by screws or bolts, the heads of

which must be flush with the metal.

Must have the metal of molding permanently and effectually grounded to

water piping, gas piping, or other suitable grounds, provided that when

connections are made to gas piping, they must be on the street side of

the meter. If the metal molding system consists of several separate

sections, the sections must be bonded to each other and the system

grounded, or each section may be separately grounded, as required above.

Metal moldings and gas pipes must be securely fastened to outlet boxes,

junction boxes, and cabinets, so as to secure a good electrical

connection. Molding must be so installed that adjacent lengths of

molding will be mechanically and electrically secured at all points.

If metal molding, couplings, outlet boxes, junction boxes, cabinets, or

fittings having protective coating of non-conducting material such as

enamel are used, such coating must be thoroughly removed from threads of

couplings and metal moldings, and from the surfaces of boxes, cabinets,

and fittings, where the metal molding or ground clamp is secured in

order to obtain the requisite good connection. Grounded pipes must be

cleaned of rust, scale, etc., at the place of attachment of the ground

clamp.

Connection to grounded pipes and to metal moldings must be exposed to

view, or readily accessible, and must be made by means of approved

ground clamps, to which the wires must be soldered.

Ground wires must be of copper, at least No. 10 B. & S. gauge. They

shall be protected from mechanical injury.

[Illustration: FIGURE 165.]

Must be installed so that for alternating-current systems the two or

more wires of a circuit will be in the same metal molding. It is

suggested that this be done for direct-current systems also so that they

may be changed to the alternating-current system at any time, induction

troubles preventing such change if the wires are in separate moldings.

_Meters._--A good job of meter setting requires that the meter fittings

which are now on the market be used. Two separate meters will be

required in each theater; one for the general lighting and one for the

emergency system.

_Meter Reading._--Meter readings are indicated by pointers, arranged to

move over dials as shown in Figure 165. The various pointers are

connected together by gearing in such a manner, that alternate pointers

move in opposite directions, as indicated by the figures on the dials.

The gearing moving the pointers in Figure 165 is of such proportions

that a total revolution of any pointer represents one-tenth of a

revolution of the pointer to the left of it. Thus ten revolutions of one

pointer causes one revolution of the one at the left.

[Illustration: FIGURE 166.]

[Illustration: FIGURE 167.]

At the top of each dial the value of the reading of that dial is shown.

Where the figures given are followed by the letter “s”, as in Figures

167 and 168, it signifies that each division of the dial represents the

amount of energy indicated by the figures at the top. For instance, in

Figure 168 each division of the dial at the right represents one-tenth

of one kilowatt hour and a total revolution of the pointer ten-tenths,

or one kilowatt hour.

If the figures given at the top of the dial are not followed by the

letter “s”, or as shown in Figure 166, each division of the dial

represents one-tenth of the amount shown at the top of the dial, the

dial at the right of Figure 166 indicating nine-tenths of ten kilowatts

or nine kilowatts.

[Illustration: FIGURE 168.]

The meter must always be read from right to left, the lowest indicating

dial being the one at the extreme right, and the lower reading ones

always being used to check the higher ones just at the left. The

following example will illustrate the manner of reading meters:

In Figure 165 the right-hand pointer registers nine-tenths of 1000, or

900 watt hours; the pointer next to it registers eight, since it cannot

be considered as fully up to any number unless the pointer at the right

of it has just arrived at or passed 0. By the same token the middle

pointer also registers 8 and as the middle pointer has not reached 0 the

one at the left of it must be read as one, the last dial also indicates

one and the total reading is 1,188,900. On some types of meters a

multiplier is used. This is generally given on the meter dial and the

readings given by the pointers must be multiplied by this number to

obtain the correct reading of the meter.

_Motors._--Motors are used in theaters for ventilation, for raising and

lowering the steel curtain in cities where such are required, and also

in some cases for operating drop curtains, but for this last purpose

they have not found much favor. In some localities motors are required

to keep up a certain water pressure to be used in case of fire. Voltages

higher than 550 are not considered in theater work.

_National Electrical Code Rules for 550-volt Motors and Less._

Motors operating at a potential of 550 volts or less must be thoroughly

insulated from the ground wherever feasible. Wooden base frames used for

this purpose, and wooden floors, which are depended upon for insulation

where, for any reason, it is necessary to omit the base frames, must be

kept filled to prevent absorption of moisture, and must be kept clean

and dry. Where frame insulation is impracticable special permission in

writing may be given for its omission, in which case the frame must be

permanently and effectively grounded.

The motor leads or branch circuits must be designed to carry a current

at least 25 per cent greater than that for which the motor is rated.

Where the wires under this rule would be over-fused in order to provide

for the starting current, as in the case of many of the

alternating-current motors, the wires must be of such size as to be

properly protected by these larger fuses.

Each motor and resistance box must be protected by a cut-out and

controlled by a switch; said switch plainly indicating whether “on” or

“off”.

Small motors may be grouped under the protection of a single set of

fuses, provided the rated capacity of the fuses does not exceed 6

amperes. With motors of one-fourth horse power or less, on circuits

where the voltage does not exceed 300, single-pole switches may be used.

The switch and rheostat must be located within sight of the motor,

except in cases where special permission to locate them elsewhere is

given, in writing.

Where the circuit-breaking device on the motor-starting rheostat

disconnects all wires of the circuit, the switch called for in this

section may be omitted. Overload-release devices on motor-starting

rheostats will not be considered to take the place of the cut-out

required by this section. An automatic circuit-breaker disconnecting all

wires of the circuit may serve as both switch and cut-out.

Auto starters, unless equipped with tight casings enclosing all

current-carrying parts, in all wet, dusty, or linty places, must be

enclosed in dust-tight, fireproof cabinets. Where there is any liability

of short circuits across their exposed live parts being caused by

accidental contacts, a railing must be erected around them.

Must not be run in series-multiple or multiple-series, except on

constant-potential systems, and then only by special permission.

Must, when combined with ceiling fans, be hung from insulated hooks, or

else there must be an insulator interposed between the motor and its

support.

Must each be provided with a name-plate, giving the maker’s name, the

capacity in volts and amperes, and the normal speed in revolutions per

minute.

All varying (or variable) speed alternating-current motors except those

used for railway service must be marked with the maximum current which

they can safely carry for 30 minutes, starting cold.

Terminal blocks when used on motors must be made of approved

non-combustible, non-absorptive, insulating material such as slate,

marble, or porcelain.

Adjustable-speed motors, unless of special and appropriate design, if

controlled by means of field regulation, must be so arranged and

connected that they cannot be started under weakened field.

The use of soft rubber bushings to protect the lead wires coming through

the frames of motors is permitted, except when installed where oils,

grease, oily vapors, or other substances known to have rapid deleterious

effect on rubber are present in such quantities and in such proximity to

motors as may cause such bushings to be liable to rapid destruction. In

such cases hardwood properly filled, or preferably porcelain or micanite

bushings must be used.

The following table shows the sizes of wire recommended to be used with

motors of the horsepower given. This table is an extract from the rules

of the Department of Gas and Electricity of the City of Chicago. The

column headed “Mains” may be used when there are a number of motors fed

by a single line. For all lines which supply a single motor only, the

column headed “Branches” must be used.

The difference between the two is due to the fact that it is not

believed that several motors fed by a single line will all be started at

the same time; hence it is not necessary to provide the overload

capacity for all of the motors as it is where but a single motor is

installed.

TABLE VIII.

SIZE OF WIRES FOR MOTORS OF DIFFERENT HORSE POWER.

DIRECT CURRENT

------------------------------------+------------------------------

110 Volts | 220 Volts

-----+---------+---------+----------+---------+---------+----------

H. P.| Full- | Size of | Size of | Full- | Size of | Size of

| load | Wire | Wire | load | Wire | Wire

| Current | Mains | Branches | Current | Mains | Branches

-----+---------+---------+----------+---------+---------+----------

1 | 8 | 14 | 14 | 4 | 14 | 14

2 | 15 | 14 | 12 | 8 | 14 | 14

3 | 23 | 10 | 8 | 12 | 14 | 14

4 | 30 | 8 | 6 | 15 | 14 | 12

5 | 38 | 6 | 6 | 19 | 12 | 10

7.5 | 56 | 5 | 4 | 28 | 8 | 8

10 | 75 | 3 | 1 | 38 | 6 | 6

-----+---------+---------+----------+---------+---------+----------

SINGLE-PHASE

-----+---------+---------+----------+---------+---------+----------

1 | 12 | ... | 12 | 6 | ... | 14

2 | 23 | ... | 8 | 11 | ... | 12

3 | 33 | ... | 6 | 16 | ... | 10

4 | 44 | ... | 4 | 22 | ... | 8

5 | 53 | ... | 3 | 26 | ... | 6

-----+---------+---------+----------+---------+---------+----------

THREE-PHASE

-----+---------+---------+----------+---------+---------+----------

1 | ... | ... | ... | 3 | 14 | 14

2 | ... | ... | ... | 5 | 14 | 14

3 | ... | ... | ... | 8 | 14 | 14

4 | ... | ... | ... | 10 | 14 | 14

5 | ... | ... | ... | 13 | 14 | 12

7.5 | ... | ... | ... | 19 | 12 | 8

10 | ... | ... | ... | 26 | 8 | 6

-----+---------+---------+----------+---------+---------+----------

_Music Stands._--Music stands are used by the musicians and are

generally placed between the first row of seats and the stage. Each

musician should be provided with an individual stand, although if

necessary, two or three can get along with one stand.

No first-class theater should be fitted up with less than twenty outlets

for musicians’ lights. In the Metropolitan Opera House of New York there

are one hundred. Houses used exclusively for vaudeville do not, however,

need that many. In houses devoted to grand opera, often as many as one

hundred or more musicians are employed at the same time. To take care of

such a number, the music stands should be wired with pin-plug connectors

so that connections may be made from one to the other. Long flexible

connections are necessary for most music stands.

Sometimes it is necessary to crowd the orchestra under the stage and at

other times, with musical comedies, for instance, they must be brought

out where they can see the movements of the actors.

The more the circuits are subdivided, and the different lights made

independent of each other, the better it will be and the less the

annoyance in case a fuse blows. The fuses should always be arranged at

the switchboard so that it will not be necessary for the electrician to

work in front of the audience in cases of trouble. For this reason extra

stands should also be kept on hand.

A main switch controlling the lights should be placed where one of the

musicians can handle it. In dark scenes these lights must often be

turned out. If these lights are left under the control of the stage

electrician they will be more likely to be forgotten at the critical

moment than if under the control of the men who need them.

An eight candle-power lamp for each stand will be sufficient and this is

usually placed inside a special reflector which allows the light to fall

upon the music sheet only. Stage cable of good quality should be used

for the connections; there is too much rough handling for reinforced

cord. The use of the ordinary attachment plug should be avoided; use

approved pin-plug connectors.

_Open Work._--Open work is not allowed in theaters.

_Operating Room._--See special chapter on “Operating Room.”

_Panel Boards._--Panel boards are really small switchboards, the

switches and cut-outs being mounted usually upon slate. The slate must

be free of metal seams; these, if present, often manifest themselves by

heating. Panel boards, unless located in the immediate vicinity of the

main switchboard, and where they are enclosed in a compartment, must

always be placed in standard metal cabinets.

_National Electrical Code Rules for Panel Boards._

The following specifications are intended to apply to all panel and

distributing boards used for the control of light and power circuits,

but not to such switchboards in central stations, sub-stations, or

isolated plants as directly control energy derived from generators or

transforming devices.

_Design._

The specifications for construction of switches and cut-outs given in

the following pages must be followed as far as they apply.

In the relative arrangement of fuses and switches, the fuses may be

placed between the bus-bars and the switches, or between the switches

and the circuits, except in the case of service switches. When the

branch switches are between the fuses and the bus-bars, the connections

must be so arranged that the blades will be dead when the switches are

open.

When there are exposed live-metal parts on the back of a board, a space

of at least one-half inch must be provided between such live metal parts

and the cabinet in which the board is mounted.

_Spacings._

TABLE IX.

THE MINIMUM DISTANCE THAT MUST BE MAINTAINED BETWEEN BARE LIVE METAL

PARTS (BUS-BARS, ETC.)

-------------------+---------------------------+--------------

| Between Parts of Opposite |

| Polarity, Except |

| at Switches and | Between

| Link Fuses | Parts of

+------------+--------------+ Same Polarity

| When | | at Link

| Mounted on | When Held | Fuses

| the Same | Free in Air |

| Surface | |

+------------+--------------+--------------

Not over 125 volts | 3/4 inch | 1/2 inch | 1/2 inch

Not over 250 volts | 1-1/4 inch | 3/4 inch | 3/4 inch

Not over 600 volts | 2 inch | 1-3/4 inch |

-------------------+------------+--------------+--------------

At switches or enclosed fuses, parts of the same polarity may be placed

as close together as convenience in handling will allow. It should be

noted that the above distances are the minimum allowable, and it is

urged that greater distances be adopted wherever the conditions will

permit.

The spacings given in the first column apply to the branch conductors

where enclosed fuses are used. Where link fuses or knife switches are

used, the spacings must be at least as great as those given in the

following section on fuse spacing. The spacings given in the second

column above apply to the distance between the raised main bars and

between these bars and the branch bars over which they pass. The

spacings given in the third column are intended to prevent the melting

of a link fuse by the blowing of an adjacent fuse of the same polarity.

Panel boards of special design, in which the insulation and separation

between the bus-bars, and between the other current-carrying parts is

secured by means of barriers or insulating materials instead of by the

spacings given above, must be submitted for special examination and

approved before being used.

_Fuse Spacings._

Spacings must be at least as great as those given in Table X, which

applies only to plain, open link fuses. The spaces given are correct for

fuse blocks to be used on direct-current systems, and can therefore be

safely followed in devices designed for alternating currents. If the

copper fuse tips overhang the edges of the fuse block terminals, the

spacings should be measured between the nearest edges of the tips.

A space must be maintained between fuse terminals of the same polarity

of at least one-half of an inch for voltages up to 125 and of at least

three-quarters of an inch for voltages from 125 to 250. This is the

minimum distance allowable, and greater separation should be provided

when practicable.

For 250 volts, boards, or blocks with the ordinary front-connected

terminals, except where these have a mass of compact form equivalent to

the back-connected terminals usually found in switchboard work, a

substantial barrier of insulating material, not less than one-eighth of

an inch in thickness, must be placed in the “break” gap--this barrier to

extend out from the base at least one-eighth of an inch farther than any

bare live part of the fuse-block terminal, including binding screws,

nuts and the like.

For three-wire systems cut-outs must have the break-distance required

for circuits of the potential of the outside wires.

TABLE X.

FUSE SPACINGS.

---------------------+----------------------+-------------

|Minimum Separation of | Minimum

|Nearest Metal Parts of| Break

|Opposite Polarity | Distance

Not over 125 volts: +----------------------+-------------

10 amperes or less | 3/4 inch | 3/4 inch

11-100 amperes | 1 inch | 3/4 inch

101-300 amperes | 1 inch | 1 inch

301-1,000 amperes | 1-1/4 inches | 1-1/4 inches

---------------------+----------------------+-------------

|Minimum Separation of | Minimum

|Nearest Metal Parts of| Break

|Opposite Polarity | Distance

Not over 250 volts: +----------------------+-------------

10 amperes or less | 1-1/2 inches | 1-1/4 inches

11-100 amperes | 1-3/4 inches | 1-1/4 inches

101-300 amperes | 2 inches | 1-1/2 inches

301-1,000 amperes | 2-1/2 inches | 2 inches

---------------------+----------------------+-------------

_Switch Spacings and Dimensions._

When designed with 250-volt spacings between adjacent blades,

triple-pole switches must be marked 250 volts and may be used on 3-wire

D. C. or single-phase systems having not more than 250 volts between

adjacent wires and not more than 500 volts between the two outside

wires.

Spacings and dimensions must be at least as great as those given below:

TABLE XI A.

SWITCH SPACINGS AND DIMENSIONS FOR SWITCH-BOARDS AND PANEL BOARDS.

_Not Over 125 Volts D. C. and A. C._

--------+--------------------------+---------------+-----------

| | Minimum |

| | Separation of |

Current| Width and Thickness | Nearest Metal | Minimum

--------+--------------------------+ parts of | Break

| Blades | Clips and | Opposite | Distance

| | Hinges | Polarity |

--------+-------------+------------+---------------+-----------

30 amp. | 1/2 inch by | 1/2 inch by| 1 inch | 3/4 inch

60 amp. | 5/64 inch | 3/64 inch | 1-1/4 inch | 1-3/4 inch

--------+-------------+------------+---------------+-----------

TABLE XI B.

SWITCH SPACINGS AND DIMENSIONS FOR INDIVIDUAL SWITCHES.

_Not Over 125 Volts D. C. and A. C._

Inch Inch Inch Inch

30 amperes 1/2 by 5/64 1/2 by 3/64 1-1/4 1

60 and 100 amperes 1-1/2 1-1/4

200 amperes 2-1/4 2

400 and 600 amperes 2-3/4 2-1/2

800 and 1000 amperes 3 2-3/4

A 300-ampere switch with the spacings of the 200-ampere switch above may

be used on switchboards.

TABLE XI C.

SWITCH SPACINGS AND DIMENSIONS FOR ALL SWITCHES.

_250 Volts Only D. C. and A. C._

Inch Inch Inch Inch

30 amperes 1/2 by 5/64 1/2 by 3/64 1-3/4 1-1/2

TABLE XI D.

SWITCH SPACINGS AND DIMENSIONS FOR ALL SWITCHES.

_Not Over 250 Volts D. C. nor Over 500 Volts A. C._

Inch Inch Inch Inch

30 amperes 5/8 by 1/8 5/8 by 1/16 2-1/4 2

60 and 100 amperes 2-1/4 2

200 amperes 2-1/2 2-1/4

400 and 600 amperes 2-3/4 2-1/2

800 and 1000 amperes 3 2-3/4

A 300-ampere switch with the spacings of the 200-ampere switch above may

be used on switchboards.

Cut-out terminals on switches for over 250 volts must be designed and

spaced for 600-volt fuses.

TABLE XI E.

SWITCH SPACINGS AND DIMENSIONS FOR ALL SWITCHES.

_Not Over 600 Volts D. C. and A. C._

Inch Inch Inch Inch

30 amperes 5/8 by 1/8 5/8 by 1/16 4 3-1/2

60 amperes 4 3-1/2

100 amperes 4-1/2 4

_Paint Bridge._--The paint bridge is usually a scaffold which can be

raised and lowered, and which serves the purpose of carrying scene

painters at work on the curtains. A long strip is the best means of

illumination and it must be connected with long stage cable so as to be

portable.

_Paint Room._--Rooms in which paints are stored should not contain

switches or cut-outs. Lamps should be incased in vapor-tight globes.

_Program Board._--A simple form of program board is shown in Figure 169.

Except at the top and the bottom, where three lamps are shown together

in one compartment, each lamp is incased by itself. In front of the

lamps is usually colored glass, bearing numbers or letters. The lamp

behind any number being turned on, that number becomes visible. The top

and bottom are usually labeled, “Special”, or “Extra”.

[Illustration: FIGURE 169.]

Another form of program board is shown in Figure 170. This requires much

more wiring. Each lamp on the board is connected to a plug or switch at

the operator’s station. Whichever switch is closed on the small board at

the right causes a corresponding light on the large board to appear.

[Illustration: FIGURE 170.]

Two program boards are usually installed, one at each side of the stage,

facing the audience at angles, so that one can be seen from the extreme

right, the other from the extreme left.

[Illustration: FIGURE 171.]

A system that is often used for carriage call is shown in Figure 171.

The lights are arranged on circuits as indicated by numbers. All lamps

bearing the same number being connected to one wire leading to the

controlling station. Thus there are eight controlling or switch wires

and there is one wire common to all. A special switch is provided which

has a contact point for each wire. Paper cards, perforated specially for

the numbers they represent, are used. If a card bearing a certain number

is inserted in the proper place and the switch closed, the number

printed on the card will appear on the sign. If, for instance, the

shaded circles in the card at the left of the figure allow contact to be

made, the lights indicated by black circles will light up and make the

figure “6”.

Another form of program or call board is shown in Figure 172. This

requires more wires than the one just described, one wire being carried

to the controlling board from each lamp. The connections may be made in

various ways. Sometimes they are made with knife switches. If it is

desired to make the figure 1, for instance, only the three lights in a

vertical row in the center need be lighted, and to do this the three

wires from those lamps must be connected to one switch. To make the

figure 2, seven lamps would have to be lit by another switch. It is

capable of making any letter or number and when used as a program board

only may be somewhat simplified.

[Illustration: FIGURE 172.]

In connection with these signs a large number of wires may be required

and attention should be given to the following rule:

_National Electrical Code Rule for Wiring Program and Call Boards._

Except in the case of stage pockets the same conduit must never contain

more than four two-wire, or three three-wire circuits of the same system

except by special permission, and must never contain circuits of

different systems.

_Proscenium Side Lights._--These lights are located on each side of the

stage, as near as possible to the edge of the proscenium opening and

often in front of the steel curtain. They are of more use in musical

productions, where choruses spread over the whole stage, than in

dramatic productions where the interest is more in the center of the

stage. In some theaters the proscenium side lights extend the full

height of the opening and are arranged for three colors in the same

manner as footlights and borders. Very often, however, only ten or

twelve lights are arranged on each side of the stage.

The construction rules are the same as those governing foot-lights.

Lamps must be protected by strong wire mesh. This is essential as in

many cases actors are very likely to back into them while passing off

the stage. Portable strips are sometimes used as proscenium side lights.

_Receptacles._--See “Stage Pockets”.

_Retiring Rooms._--In these places a quiet subdued illumination is

usually desired. There are also often quaint objects and effects to be

illuminated. A large number of outlets conveniently located for the use

of table lamps, fire places, and illumination of pictures, should be

provided.

_Rheostats._

_National Electrical Code Rules for Rheostats._

_Location._

Must be placed on a switchboard, or at a distance of at least one foot

from combustible material, or separated therefrom by a slab or panel of

non-combustible, non-absorptive, insulating material such as slate,

soapstone, or marble, somewhat larger than the rheostat, which must be

secured in position independently of the rheostat supports. Bolts for

supporting the rheostat shall be countersunk at least one-eighth inch

below the surface at the back of the slab and the bolt heads shall be

covered with insulating material. For proper mechanical strength, slab

should be of a thickness consistent with the size and weight of the

rheostat, and in no case to be less than one-half inch.

If resistance devices are installed in rooms where dust or combustible

flyings would be liable to accumulate on them, they must be equipped

with dust-proof face plates.

_Materials._

Must be made entirely of non-combustible materials, except such minor

parts as handles, magnet insulation, etc. All segments, lever arms,

etc., must be mounted on non-combustible, non-absorptive, insulating

material.

_Connections._

Clamps for connecting wires to the terminals must be so designed as to

insure a thoroughly good connection and must be sufficiently strong and

heavy to withstand hard usage. For currents above 30 amperes, lugs into

which the connecting wires may be soldered, or approved solderless

connectors must be used. Clamps or lugs will not be required when leads

are provided as a part of the device.

_No-Voltage Release._

Motor-starting rheostats must be so designed that the contact arm cannot

be left on intermediate segments, and for direct-current circuits must

be provided with an automatic device which will interrupt the supply

circuit before the speed of the motor falls to less than one-third of

its normal value. In motor-starting rheostats for alternating-current

circuits the automatic interrupting device may be omitted.

_Overload Release._

Overload-release devices which are inoperative during the process of

starting a motor will not be approved, unless other circuit-breakers or

fuses are installed in connection with them.

_Signals._--Signals are necessary between the manager’s office and the

stage electrician’s station; for this purpose telephones are generally

used. In many cities a fire-alarm signal system is also required and it

is specified to what part of the house it shall lead. In addition to the

above, a means of signalling the fly floor and the orchestra leader must

be provided. Buzzers are used for these signals. It is best to use

batteries for all these signals instead of attempting to run them from

lighting circuits. Means of signalling the arc-lamp station in the

gallery or the balcony should also be provided for use in connection

with lantern slides, etc. Telephone connection to this point will also

be very useful in order to give instructions to the lamp operator.

Return-call systems are advisable in all places so that the electrician

can be called from any point.

In some cities the local laws require these wires to be in conduit so as

to preclude any possibility of their communicating fire to anything. At

any rate the wires should be very carefully installed.

_Signs._--In nearly all electric signs used about theaters the letters

are outlined by incandescent lamps. Small candle-power lamps are always

used. They are not only economical but much more attractive because the

glare from too much light is very annoying. Many signs are equipped with

low candle-power tungsten lamps wired in series. In order that the

letters should show to full advantage they should be glossy white and be

kept clean. Such letters will show as bright as the lamps. It is best to

wire the sign so that either side can be used independent of the other.

In many cases, also, signs are wired so that each letter is independent

of the others for use with flashers.

Attraction signs are used to advertise the attractions which appear from

time to time. Independent portable letters are used and changed as often

as the attractions change. Each letter must be fitted with cable and

attachment plug of some kind and should have a separate circuit.

Cut-outs are generally located on the frame and must be protected from

the weather.

_Sockets._--Sockets must be of approved construction. Key sockets must

not be used for emergency or exit lighting. Sockets with fiber linings

must not be used unless protected by insulating joints. In damp places

weatherproof sockets must be used. Where inflammable gases exist, lamps

must be incased in vapor-proof globes. Porcelain sockets should not be

used in theaters. Weatherproof sockets are generally used for portable

purposes because they have no screws, etc., to work loose.

_Stage Cable._--Stage cables are allowed in theaters only where flexible

conductors are absolutely necessary. All wiring that can possibly be

installed in conduit or strip construction should be so arranged. By the

use of plugging boxes the quantity of stage cable necessary can be much

reduced. Plugs for arc and incandescent lights must not be

interchangeable.

_Stage Flues._--In most cities stage flues, as described in the chapter

on “Theater Buildings”, are required. The requirement is also, often,

that they be released by electrical means. The rule below contemplates a

circuit containing an electro-magnet and at least two switches in

series. The magnet must be energized to hold the ventilator closed. If

the current fails or a switch is opened the dampers must fly open at

once. Where direct current is available the magnet is usually wound for

110 volts and connected to a circuit that is always alive. In case of an

isolated plant which is shut down at night some arrangement for tying

the dampers down should be made, but it is not always advisable, as once

tied they are likely to remain so and sure to fail when needed. Magnets

do not work well on alternating currents and in such cases the magnet

should be wound for a small current to be obtained from a gravity

battery which may be allowed to be always working. Locate the battery

where it will not freeze.

_National Electrical Code Rules for Control of Stage Flues._

In cases where dampers are released by an electric device, the electric

circuit operating same must be normally closed. Magnet operating dampers

must be wound to take full voltage of circuit by which it is supplied,

using no resistance device, and must not heat more than normal for

apparatus of similar construction. It must be located in loft above

scenery, and be installed in a suitable iron box with a tight,

self-closing door.

Such dampers must be controlled by at least two standard single-pole

switches mounted within approved iron boxes provided with self-closing

doors without lock or latch, and located, one at the electrician’s

station and the others as designated.

_Stage and Gallery Pockets._--Stage pockets are usually located on each

side of the stage just far enough from the center to be safely back of

the scenery. The more pockets there are the better it will be. Each

pocket usually contains four circuits, and one of these at least should

be for incandescent lights. It will be convenient if the stage pockets

are divided into four groups, each group under control of a separate

switch and the whole again under control of a main switch. This will

enable the operator to throw off all of the pockets at once, if

necessary, or to make any combination desired.

[Illustration: FIGURE 173.]

Sometimes lights fed through stage pockets require to be dimmed; but it

is hardly practicable to arrange dimmers for apparatus carried by

traveling companies, since a dimmer must be selected with respect to the

amperage it is to control.

In addition to the rules given below, some cities require the bottom of

stage pockets to be open, so as to avoid an accumulation of dust. This

is a very essential precaution, as otherwise the pockets soon fill up or

require very frequent cleaning. The covers must be substantial as heavy

trucks are sometimes run over them. Two illustrations of stage pockets

are given in Figures 173 and 174. The plugs used with these boxes are

shown in Figure 175.

[Illustration: FIGURE 174.]

[Illustration: FIGURE 175.]

Gallery pockets are not usually laid in the floor but along the railing.

The gallery pockets should be under separate control from the stage

switchboard.

_National Electrical Code Rules for Stage and Gallery Pockets._

Must be of approved type, insulated from ground and controlled from

switchboard, each receptacle to be of not less than 35-ampere rating for

arc lamps nor 15-ampere for incandescent lamps, and each receptacle to

be wired to its full capacity. Arc pockets to be wired with wire not

smaller than No. 6 B. & S. gauge and incandescent pockets with not less

than No. 12 B. & S. gauge. Plugs for arcs and incandescent pockets must

not be interchangeable.

_Switches._--All knife switches should be enclosed in cabinets unless

they are located on a switchboard. In exposed places, flush switches

should be used. The usual height at which scattered switches are located

is about four and one-half feet above floor. Door switches are of use

principally in dressing rooms.

[Illustration: FIGURE 176.]

Diagrams of three-way switches are given in Figures 176 and 177. In

Figure 177, the wiring by which a light can be controlled from three

different points is shown. The middle switch must be a pole-changing

switch. In this case a throw-over knife switch is wired to perform this

function. Omitting the knife switch we have two three-way switches

controlling the light. When both switches (indicated by broken lines)

connect to the same wire the light burns.

[Illustration: FIGURE 177.]

In Figure 176, when both switches connect to the same polarity the light

is out; when one of them is connected to the other pole the light burns.

Under certain conditions this arrangement is more economical in wire but

has the disadvantage which the other method avoids, of bringing both

poles to each switch. This method cannot be used with direct-current

arc lamps. Three-way switches are useful on stairways, enabling one to

turn on a light at the bottom of the stairway and turn it off when at

the top or vice versa.

_National Electrical Code Rules for Switches and Connections._

_Switches._

Must be placed on all service wires, either overhead or underground, in

the nearest readily accessible place to the point where the wires enter

the building, and arranged to cut off the entire current. Departure from

this rule may be authorized only under special permission in writing.

Switches controlling emergency lighting must be located only in the

lobby.

Must when used for service switches, indicate, on inspection, whether

the current be “on” or “off”. Switch cabinets must be deep enough to

allow the door to be closed when 30 ampere branch-circuit switches are

in any position, and when larger single-throw switches are thrown open

as far as their construction and installation will permit.

Must, for constant-current systems, close the main circuit and

disconnect the branch wires when turned “off”; must be so constructed

that they shall be automatic in action, not stopping between points when

started, and must prevent an arc between the points under all

circumstances. They must indicate whether the current be “on” or “off”.

Service cut-out and switch must be arranged to cut off current from all

devices including meters.

Must always be placed in dry, accessible places, and be grouped as far

as possible. Single-throw knife switches must be so placed that gravity

will not tend to close them. Double-throw knife switches may be mounted

so that the throw will be either vertical or horizontal as preferred,

but if the throw be vertical a locking device must be provided, so

constructed as to insure the blades remaining in the open position when

so set.

When practicable switches must be so wired that blades will be “dead”

when the switch is open.

When switches are used in rooms where combustible flyings would be

likely to accumulate around them, they must be enclosed in dust-tight

cabinets.

Up to 250 volts and thirty amperes, approved indicating snap switches

are suggested in preference to knife switches on lighting circuits.

Single-pole switches must never be used as service switches nor for the

control of outdoor signs or circuits located in damp places, nor placed

in the neutral wire of a three-wire system, except in the two-wire

branch or tap circuit supplying not more than 660 watts.

Where flush switches or receptacles are used, whether with conduit

systems or not, they must be enclosed in an approved box constructed of

iron or steel, in addition to the porcelain enclosure of the switch or

receptacle.

Hinges of knife switches must not be used to carry current unless they

are equipped with spring washers, held by lock-nuts or pins, or their

equivalent, so arranged that a firm and secure connection will be

maintained at all positions of the switch blades.

Spring washers must be of sufficient strength to take up any wear in the

hinge and maintain a good contact at all times.

_Connections._

Switches for currents of over thirty amperes must be equipped with lugs,

firmly screwed or bolted to the switch, and into which the conducting

wire shall be soldered. For the smaller sized switches simple clamps can

be employed, provided they are heavy enough to stand considerable hard

usage.

Where lugs are not provided, a rugged double-V groove clamp is advised.

A set screw gives a contact at only one point, is more likely to become

loosened, and is almost sure to cut into the wire. For the smaller

sizes, a screw and washer connection with up-turned lugs on the switch

terminal gives a satisfactory contact.

_Spacings._

See “Panel Boards”.

_Switchboards._--The stage switchboard is usually located on the

right-hand side of the stage. This position enables the operator to

watch cues easily and handle his switches with the right hand. This side

is also the one from which the stage manager prefers to work. It is

preferable to have the board raised high enough above stage level to

allow all space on the stage to be used by actors. If the switchboard is

located on stage level it takes up much room that is valuable and makes

stage exits for actors difficult.

The wiring of a good switchboard should be divided into three parts,

each part independent of the others, so that any one part can be

entirely cut off without interfering with the other. All of the house

lights should be fed through one main switch, and all of the stage light

connected to another set of bus-bars, but it is best not to have the

stage side of the board as a whole controlled by a main switch. If the

stage side of the board is controlled by a single switch there exists

the possibility that this switch may be used to cut off everything for a

dark scene and when light is again wanted a part of the lighting of the

previous setting may be left on and possibly interfere with the new

scene.

[Illustration: FIGURE 178.]

The stage lighting is usually divided into four groups, viz.: three

color groups and a group of stage pockets. The number of white lights

is usually equal to that of all of the colors.

Figure 178 shows a well laid out switchboard. All of the lights in the

auditorium are controlled by switches shown in the upper right-hand

corner and all of these are under the control of the main switch. The

house lights are usually thrown on or off as a whole and this main

switch must be convenient for the operator.

The stage pockets are controlled by the bank of switches shown at _E_.

Lights burning off the stage pockets generally are controlled by special

operators on the stage or by actors, and need not be so very convenient

to the switchboard operator. They must, however, be under his control

when necessary; but here also a main switch is not advisable.

In addition to the three groups of lights spoken of above, there are a

number of lights which should be controlled from the switchboard but

must be so connected that they will be left on, no matter what is done

with either house or stage light.

In this group belong a few lights mounted at the top of the switchboard

which enable the operator to see his switches when all else is dark.

These lights are generally shielded so as to throw no light in the

direction of the stage opening. The orchestra lights also belong in this

group, but a special switch may, with advantage, be arranged on this

circuit to bring it under the control of one of the musicians. In some

dark scenes these lights are turned out for a short time, but it is very

important that they be turned on again at the proper moment, and this is

more certainly assured, by giving the musicians control, than by

leaving it to an electrician on the stage who may be very busy with

other matters at the time.

The lights on the fly floor and in the rigging loft, as well as those in

dressing rooms and basement, must also be independent. Fan motor

circuits should also be independent of the house circuit. They are often

needed when the house lights are thrown off.

With the switchboard illustrated in Figure 178 we have shown only the

switches governing the house and stage proper. The switches governing

the other lights are usually worked into the vacant spaces between the

two groups. Each switch should be labeled in such a manner that a new

operator can learn the board easily.

The most important part of the board is that part governing the stage

lighting, and this should always be placed as conveniently as possible

to the operator. A stage switchboard is like a house in that no one is

wholly satisfied with the one he has, but thinks he could improve it a

little if he could build it over again. The arrangement shown in Figure

178 is, however, quite satisfactory for general purposes. The white

lights predominate in the ratio of two to one and are laid out in two

groups _A_ and _B_. Both groups are controlled by the switch _C_. The

switches _A_ and _B_ do not control the lights at all if the smaller

throw-over switches at the right are thrown downward. A diagram of these

switch connections is given in Figure 179 where the switches _B_ and _C_

are indicated. The object of the switches _A_ and _B_ is to help in

quickly increasing or decreasing the illumination on the stage. If in

the beginning of a certain scene, for instance, only a small quantity of

light is wanted, while a little later full illumination is desired, the

low illumination may be obtained by throwing the proper switches down;

the additional illumination which will be needed a few minutes later may

be prepared for by setting the other switches needed to the upward

position and at the proper moment closing switch _B_; this will

instantly produce the effect which otherwise would be possible only by

operating a number of switches in succession. In the same way, by a

reversal of this process, the illumination may be reduced in any amount.

This feature is very valuable in many stage settings.

[Illustration: FIGURE 179.]

To throw off all of the white lights the switch _C_ must be opened. The

switches _D_ and _F_ are main switches controlling colored lamps. All

lamps of one color should be connected to one or the other of these

groups unless some special color effect is desired.

From the three groups of switches, circuits extend into the foot lights,

into every border, and into the proscenium side-light strips so that the

color scheme may be carried out in any of these.

The handles of all switches in a row should be of the same height so

that the operator may more readily accustom himself to catch them

quickly. It is better to have switches of some excess capacity, as the

heavy metal stands the arcing much better.

A main switch by which the whole board may be cut off should be

installed but this need not be on the front of the board.