CHAPTER XVIII.

THEATER WIRING.

The wireman should not fail to consult local rules or inspection

departments as to whether any rules conflict with those given below. He

must be warned to consult local authorities or rules, too, because

safety rules are liable to change.

The purpose of this chapter is to furnish a ready reference work

concerning questions of electrical construction in theaters which come

up daily in all progressive play houses. To this end the subjects have

been arranged in alphabetical order and the practical considerations, as

well as extracts from the National Electrical Code governing

construction, have been given together. The aim has been to enable the

workman to find all information concerning construction work grouped

together, so as to obviate the necessity of looking through various

parts of the book for the information sought. This order of things will

probably avoid the troubles now often caused by overlooking certain

points that should be considered.

_Aisle Light._--Figure 151 is an illustration of an aisle light. Such

lights are often placed along steps and aisles. The light illuminates

only the floor. Aisle lights should be arranged on a separate circuit

and controlled by a switch at the door.

_Alternating Current._--All wires of any circuit or mains or sub-mains

of any system must be run in the same conduit. Failure to do this will

cause an unnecessary drop in voltage and heating of the conduit.

_Arc Lamps._--For treatment and construction of portable arc lamps, see

the chapter on “Portable Stage Equipment”.

Permanently located arc lamps are used about theaters mostly for

out-door lighting. Very often, two or more lamps are arranged in front

of the house. Such lamps are mostly of the flaming arc lamp type and are

hung up high.

[Illustration: FIGURE 151.]

In some of the cheaper theaters a pair of arc lamps is used on the

stage, but they do not give satisfaction. The light is not even and

steady enough and cannot be properly “dimmed”. Where arc lamps are to be

arranged for stage illumination they must be suspended amid the scenery

and enclosed with wire guards. In some cities the use of arc lamps

suspended above the stage is prohibited.

In the auditorium, arc lamps are sometimes installed, but this practice

can not be recommended and, with the present high efficiency

incandescent lamps, there is but little excuse for it. The only

advantage in using arc lamps lies in the first cost of wiring, and this

is more than balanced by the difficulties of trimming lamps located in

such places. Wherever arc lamps are used it is essential that they be

hung high and those that do not naturally throw the light downward must

be equipped with suitable reflectors. The question of drop in voltage

need not be considered with arc lamps unless runs are very long.

_National Electrical Code Rules for Arc Lamps._

_Arc Lamps in General._

Must be provided with reliable stops to prevent carbons from falling out

in case the clamps become loose.

All exposed parts must be carefully insulated from the circuit.

Must, for constant-current systems, be provided with an approved hand

switch, and an automatic switch that will shunt the current around the

carbons, should they fail to feed properly.

The hand switch to be approved, if placed anywhere except on the lamps

itself, must comply with requirements for switches on hanger-boards.

Terminals must be designed to secure a thoroughly good and permanent

contact with the supply wires, which contact must not become loosened by

motion of the lamp during trimming.

Spark arresters must so close the upper orifice of the globe that it

will be impossible for any sparks, thrown off by the carbons, to escape.

_Series Arc Lamps._

Must be carefully isolated from inflammable material.

Must be provided at all times with a glass globe surrounding the arc,

and securely fastened upon a closed base. Broken or cracked globes must

not be used.

Must be provided with a wire netting (having a mesh not exceeding one

and one-fourth inches) around the globe and an approved spark arrester,

when readily inflammable material is in the vicinity of the lamps, to

prevent escape of sparks of carbon or melted copper.

Outside arc lamps must be suspended at least eight feet above sidewalks.

Inside arc lamps must be placed out of reach or suitably protected.

Arc lamps, when used in places where they are exposed to flyings of

easily inflammable material, must have the electrodes enclosed

completely in a tight globe in such manner as to avoid the necessity for

spark arresters.

“Enclosed arc” lamps, having tight inner globes may be used, and the

requirements of b and c above would, of course, not apply to them.

Where hanger-boards are not used, lamps must be hung from insulating

supports other than their conductors.

Lamps when arranged to be raised and lowered either for carboning or

other purposes, shall be connected up with stranded conductors from the

last point of support to the lamp, when such conductor is larger than

No. 14 B. & S. gauge.

_Arc Lamps on Constant-Potential Circuits._

Must have a cut-out for each lamp or each series of lamps.

The branch conductors must have a carrying capacity about fifty per cent

in excess of the normal current required by the lamp.

Must only be furnished with such resistances or regulators as are

enclosed in non-combustible material, such resistances being treated as

sources of heat. Incandescent lamps must not be used for this purpose.

_Arc Lamps Used as a Part of a Moving-Picture Machine._

Must be constructed, so far as practicable, similar to arc lamps of

theaters, and wiring to same must not be of less capacity than No. 6 B.

& S. gauge. See “Portable Stage Equipment”.

_Stage and Gallery Pockets._

Must be of approved type, insulated from ground and controlled from

switchboard, each receptacle to be of not less than 35 ampere rating for

arc lamps nor 15 amperes for incandescent lamps, and each receptacle to

be wired to its full capacity. Arc pockets to be wired with wire not

smaller than No. 6 B. & S. gauge and incandescent pockets with not less

than No. 12 B. & S. gauge.

Plugs for arcs and incandescent pockets must not be interchangeable.

_Armored Cable._--All wires in the stage part of theaters must be

enclosed in conduit or armored cable. Armored cable is thus the only

flexible conductor allowed for permanent work. This cable is very

convenient where wires must be “fished”, or run around beams or other

obstacles making many bends necessary. It should, however, be used only

where the rigid conduit cannot well be installed and it is advisable to

use the latter, even where the additional expense is considerable. Wires

run in rigid conduit can be taken out and replaced by new ones at any

time, while this is not the case with armored cable. Should a wire

incased in armored cable develop a serious fault, the old cable would

have to be abandoned and a new circuit run, which in many cases would

mean the tearing up of parts of the building.

[Illustration: FIGURE 152.]

Where armored cable is to be used great care should be exercised to see

that bends are not made too short, and that each length of cable is

tested for grounds, short circuits, and open circuits. Special attention

must be given to the wires at the place where the armor has been cut.

Careless workmen can do great damage at this point. The manner of

cutting the armor is shown in Figure 152. Each strand of the armor is

partly cut with a saw and may then be broken off, taking care that no

sharp edge is left in position to pierce the wire.

Installation rules are given below. Before installing any armored cable,

be sure that it is of approved make and guaranteed to pass inspection.

_National Electrical Code Rule for Armored Cables._

Must be continuous from outlet to outlet or to junction boxes or

cabinets, and the armor of the cable must properly enter and be secured

to all fittings, and the entire system must be mechanically secured in

position.

In case of service connections and main runs, this involves running such

armored cable continuously into a main cut-out cabinet or gutter

surrounding the panel board, as the case may be.

Must be equipped at every outlet with an approved outlet box or plate,

as required in conduit work.

Outlet plates must not be used where it is practicable to install outlet

boxes.

For concealed work in walls and ceilings composed of plaster on wooden

joist or stud construction, outlet boxes or plates and also cut-out

cabinets must be so installed that the front edge will not be more than

one-fourth inch back of the finished surface of the plaster, and if this

surface is broken or incomplete it shall be repaired so that it will not

show any gaps or open spaces around the edges of the outlet box or plate

or of the cut-out cabinet. On wooden walls or ceilings, outlet boxes or

plates and cut-out cabinets must be so installed that the front edge

will either be flush with the finished surface or project therefrom.

This will not apply to concealed work in walls or ceilings composed of

concrete, tile or other non-combustible material.

In buildings already constructed where the conditions are such that

neither outlet box nor plate can be installed, these appliances may be

omitted by special permission, provided the armored cable is firmly and

rigidly secured in place.

Must have the metal armor of cables permanently and effectually grounded

to water piping, gas piping, or other suitable grounds, provided that

when connections are made to gas piping, they must be on the street side

of the meter. If the armored cable system consists of several separate

sections, the sections must be bonded to each other, and the system

grounded, or each section may be separately grounded, as required

above.

The armor of cables and gas pipes must be securely fastened in outlet

boxes, junction boxes, and cabinets, so as to secure good electrical

connection.

If armor of cables and metal of couplings, outlet boxes, junction boxes,

cabinets, or fittings having protective coating of non-conducting

material, such as enamel, are used, such coating must be thoroughly

removed from threads of both couplings and the armor of cables, and from

surfaces of the boxes, cabinets, and fittings where the armor of cables

or ground clamp is secured in order to obtain the requisite good

connection. Grounded pipes must be cleaned of rust, scale, etc., at

place of attachment of ground clamp. Connections to grounded pipes and

to armor of cables must be exposed to view or readily accessible, and

must be made by means of approved ground clamps, to which the ground

wires must be soldered.

Ground wires must be of copper, at least No. 10 B. & S. gauge (where

largest wire contained in cable is not greater than No. 0 B. & S.

gauge), and need not be greater than No. 4 B. & S. gauge (where largest

wire contained in cable is greater than No. 0 B. & S. gauge). They must

be protected from mechanical injury. The ground for the armored cable

system is not to be considered as a ground for a secondary system.

When installed in so-called fireproof buildings in course of

construction, or afterwards if exposed to moisture, or where it is

exposed to the weather, or in damp places, such as breweries, stables,

etc., the cable must have a lead covering placed between the outer braid

of the conductors and the steel armor. The lead covering is not to be

required when the cable is run against brick walls, or laid in ordinary

plaster walls unless same are continuously damp.

Where entering junction boxes, and at all other outlets, etc., must be

provided with approved terminal fittings which will protect the

insulation of the conductors from abrasion, unless such junction or

outlet boxes are specially designed and approved for use with the cable.

Junction boxes must always be installed in such a manner as to be

accessible.

For alternating-current systems must have the two or more conductors of

the circuit enclosed in one metal armor.

All bends must be so made that the armor of the cable will not be

injured. The radius of the curve of the inner edge of any bend not to be

less than 1-1/2 inches.

_Asbestos._--As all wiring in theaters is required to be run in conduit,

and metal cabinets are compulsory in this connection, there is but

little opportunity to use asbestos. Wherever the use of asbestos is

advisable it must conform to the general requirements as given for

wooden cutout cabinets, viz.: “for lining wooden cabinets, one-eighth

inch rigid asbestos board may be used when firmly secured in place by

screws or tacks”.

_Attachment Plugs._--Attachment plugs should be used to connect all

portable apparatus. All plugs should be of approved type and constructed

so as to pull out in case strain is put on them. On the stage, pin-plug

connectors should be used in place of attachment plugs, as none of the

latter are sufficiently rugged to withstand the hard usage.

_National Electrical Code Rules for Attachment Plugs._

Link fuse attachment plugs of the types now on the market are considered

unsafe, as under entirely possible conditions an arc may be produced

when the fuses blow, damaging the plug and perhaps causing fire.

Attachment plugs are not approved for more than six hundred and sixty

watts or two hundred and fifty volts.

_Auditorium._--Two separate systems of lighting are required: See

emergency or exit lighting. Metal moulding, as well as armored cable or

conduit, is permissible in wiring the auditorium part of the theater.

_Auto-Starters._--Auto-starters perform the same service with

alternating-current motors that resistances do with direct-current

motors. They are used with motors from two or three horse power upward,

and not generally with the smaller motors.

The following are extracts from the “National Electrical Code”

concerning their use:

In all wet, dusty, or linty places, auto-starters, unless equipped with

tight casings enclosing all current-carrying parts, must be enclosed in

dust-tight fireproof cabinets. Where there is any liability of short

circuits, caused by accidental contacts, across their exposed live parts

a railing must be erected around them.

The switch on the auto-starter must provide an off position, a running

position, and at least one starting position. It must be so arranged

that it will be held in off and running position, but not in starting

position or without the proper running overload-protection devices in

the circuit.

For currents above 30 amperes, lugs, into which the connecting wires may

be soldered, or approved solderless connectors must be used. Clamps or

lugs will not be required when leads are provided as a part of the

device.

The following rules are drawn for rheostats but may also apply to

auto-starters:

Where the circuit-breaking device on the motor-starting rheostat

disconnects all of the wires of the circuit, the switch called for in

this section (to disconnect all apparatus) may be omitted.

Overload-release devices on motor-starting rheostats will not be

considered to take the place of the cutout required to protect the motor

and the rheostat.

_Balconies._--The illumination of balconies is a difficult matter. The

ceilings under galleries above are always low, and to obtain even

illumination requires the use of many small candle-power lamps. These

should be set well back so as not to be visible too much to the

audience.

Stage-pocket capacity for one or more arc lamps should always be

provided. Where there are galleries above, the arc lamps used for stage

illumination are generally placed there, but it often happens that a

moving-picture machine must be installed and it is very disadvantageous

if this must be located in the galleries. Balconies require the same

exit and emergency light service as is required in the auditorium.

_Batteries._--See Portable Stage Equipment.

_Bells._--Systems of call bells are generally arranged between the box

office or the manager’s office and the stage switch board; also from the

stage switch board to the fly floor by which signals for raising and

lowering the curtain may be given; also to the orchestra leader. In some

cities all of this wiring is required to be in conduit. These signaling

circuits should be carefully installed, for they are as important as

any part of the wiring. Only the very best bells and push buttons should

be used, and it is advisable to avoid the use of the ordinary

annunciator wire so often seen in connection with bell work. Numerous

diagrams and much information concerning bell wiring is given in “Modern

Wiring Diagrams and Descriptions”, which should be consulted in case

some complicated annunciator system is to be installed. Figure 153 is a

diagram of a simple call-and-return-call system.

[Illustration: FIGURE 153.]

[Illustration: FIGURE 154.]

_Borders._--The number of borders used in theaters varies from one to

six, the latter number being sufficient for almost any stage. They are

generally made of a length about equal to the proscenium opening. The

borders placed in the rear are of less importance than those in front

and consequently are made shorter and are not provided with so many

lights. Each border should have at least three circuits, one for each

color; each circuit being taken through a separate dimmer so that any

color may be used alone and dimmed as desired.

Figures 154 and 155 show types of borders, and the method of wiring is

shown in Figure 156.

[Illustration: FIGURE 155.]

[Illustration: FIGURE 156.]

Large borders are very heavy and are usually suspended by wire rope and

provided with counterweights to make handling easy. The wire rope should

be kept well protected by oiling; the moisture given off by fireproofed

scenery is liable to rust them very fast, and as the ropes are made up

of very fine strands the rust soon cuts entirely through them. The

suspending ropes and also cables supplying lights must be long enough to

admit of bringing the border within five or six feet of the stage floor

for lamp renewals and cleaning. The cleaning is very important as the

dust which accumulates may absorb a large part of the light.

_The National Electrical Code Rules Governing Border and Proscenium

Sidelight Construction._

Must be constructed of steel of a thickness not less than No. 20 U. S.

sheet metal gauge; treated to prevent oxidation; be suitably stayed and

supported; and so designed that flanges of reflectors will protect

lamps.

Must be so wired that no set of lamps requiring more than 1,320 watts

nor more than 26 receptacles shall be dependent upon one cut-out.

Must be wired in approved conduit or armored cable, each lamp receptacle

to be enclosed within an approved outlet box, or the lamp receptacles

may be mounted in an iron or steel box, metal to be of a thickness not

less than No. 20 U. S. sheet metal gauge treated to prevent oxidation,

so constructed as to enclose all wires. Wires to be soldered to lugs of

receptacles.

Must be provided with suitable guards to prevent scenery or other

combustible material coming in contact with lamps.

Cable for borders must be of approved type and suitably supported;

conduit construction must be used from switchboard to point where cables

must be flexible to permit of the raising and lowering of border.

For the wiring of the border proper, wire with approved slow-burning

insulation must be used.

Borders must be suitably suspended, and if a wire rope is used same must

be insulated by at least one strain insulator inserted at the border.

_Box Office._--The box office is often a very stuffy place in summer and

very cold in winter. There should be an outlet for a fan motor, and also

one for a heater. Very many box offices depend upon electric heating

for comfort in winter. Plenty of light should be provided and the light

should be at the ceiling, out of the way, and directly over the ticket

window.

_Brackets._--Any brackets used in theaters should be at least seven feet

above the floor. Brackets used for emergency or exit lights must be

fitted with keyless sockets. See “Fixtures”.

_Branch Circuits._--The term, “branch circuit”, as here used refers to

the wires leaving the last cut-outs and connecting directly to the lamps

or other devices. Mains are often run from the switchboard to various

parts of the building to feed cut-out centers, and the branch circuits

are then run from these centers. This is often the cheapest method, but

it is by no means the best. In a well designed theater all branch

circuits lead out from the vicinity of the switchboard so that, in case

of any trouble with fuses, they may be replaced without interfering with

any part of the audience and in the shortest possible time. This method

of wiring involves some long runs of branch circuit wires and Table V,

which shows the drop in voltage, was prepared for the convenience of

wiremen. If possible the circuits should be so arranged that the lamps

fed are closely together so all may receive nearly the same voltage. The

drop should not much exceed two per cent.

Table showing drop in voltage due to 6 amperes, with sizes of wire and

distances given:

TABLE V.

DROP IN VOLTAGE DUE TO 6 AMPERES WITH SIZE OF WIRE AND DISTANCE GIVEN.

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Distance| 50 | 75 | 100 | 125 | 150 | 175 | 200 | 225 | 250 | 300

in feet | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Size of | | | | | | | | | |

Wire | 1.58| 2.37| 3.16| 3.95| 4.74| 5.53| 6.32| 7.11| 7.90| 9.48

No. 14 | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Size of | | | | | | | | | |

Wire | 0.99| 1.48| 1.98| 2.47| 2.97| 3.45| 3.96| 4.45| 4.95| 5.94

No. 12 | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Size of | | | | | | | | | |

Wire | 0.63| 0.94| 1.25| 1.56| 1.87| 2.19| 2.50| 2.81| 3.12| 3.75

No. 10 | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

Size of | | | | | | | | | |

Wire | 0.39| 0.59| 0.78| 0.97| 1.17| 1.36| 1.56| 1.75| 1.95| 2.34

No. 8 | | | | | | | | | |

--------+-----+-----+-----+-----+-----+-----+-----+-----+-----+-----

_National Electrical Code Rules Governing Size of Wire for Branch

Circuits and Fuses for Same._

No wire smaller than No. 14 B. & S. gauge must be used.

Each branch circuit must be protected by fuses, which must be so placed

that no set of small motors, small heating devices, or incandescent

lamps, whether grouped on one fixture or on several fixtures or pendants

(nor more than 16 sockets or receptacles) requiring more than 660 watts,

will be dependent upon one cut-out.

By special permission, in cases where wiring equal in size and

insulation to No. 14 B. & S. gauge approved rubber-covered wire is

carried direct into keyless sockets or receptacles, and where the

location of sockets and receptacles is such as to render unlikely the

attachment of flexible cords thereto, the circuits may be so arranged

that not more than 1,320 watts (or thirty-two sockets or receptacles)

will be dependent upon the final cut-out.

Except for signs and outline lighting, sockets and receptacles will be

considered as requiring not less than 40 watts each.

All branches or taps, from any three-wire system, which are directly

connected to lamp sockets or other translating devices, must be run as

two-wire circuits if the fuses are omitted in the neutral, or if the

difference of potential between the two outside wires is over 250 volts,

and both wires of such branch or tap circuits must be protected by

proper fuses.

The above shall also apply to motors, except that small motors may be

grouped under the protection of a single set of fuses, provided the

rated capacity of the fuses does not exceed 10 amperes.

When 1,320 watts are dependent upon one fusible cut-out, as is allowed

in theater wiring, outline lighting and large chandeliers, the fuses may

be in accordance with the following:

125 volts or less 20 amperes

125 to 250 volts 10 amperes

_Bus-Bars._--Bus-bars may be made of bare metal. They must, however, be

protected against accidental contact. The metal should be ample so that

it will not heat more than 50 degrees Fahrenheit above the surrounding

air.

It is customary to calculate the metal needed, on the basis of 1,000

amperes per square-inch cross section. On this basis bars of the sizes

given below would have the carrying capacities in amperes given in the

body of the table.

TABLE VI.

CURRENT-CARRYING CAPACITY OF BUS-BARS.

-----------+----+----+----+----+----+----+----+----+-----+-----+-----

Thickness |2/32|3/32|4/32|5/32|6/32|7/32|8/32|9/32|10/32|12/32|16/32

-----+-----+----+----+----+----+----+----+----+----+-----+-----+-----

| 1/2 | 30| 45| 60| 75| 90| 105| 120| 135| 150| 165| 180

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

| 5/8 | 37| 57| 75| 94| 108| 132| 150| 168| 188| 206| 225

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

| 6/8 | 45| 68| 90| 112| 135| 158| 180| 202| 225| 248| 270

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

Width| 7/8 | 53| 79| 105| 130| 158| 184| 210| 236| 263| 289| 315

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

in | 1.0 | 60| 90| 120| 150| 180| 210| 240| 270| 300| 330| 360

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

In- |1-1/4| 75| 112| 150| 188| 225| 263| 300| 338| 375| 412| 450

ches +-----+----+----+----+----+----+----+----+----+-----+-----+-----

|1-1/2| 90| 135| 180| 225| 270| 315| 360| 405| 450| 495| 540

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

|1-3/4| 105| 157| 210| 263| 315| 367| 420| 473| 525| 577| 630

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

| 2.00| 120| 180| 240| 300| 360| 420| 480| 540| 600| 660| 720

+-----+----+----+----+----+----+----+----+----+-----+-----+-----

| 3.00| 180| 270| 360| 450| 540| 630| 720| 810| 900| 990| 1080

-----+-----+----+----+----+----+----+----+----+----+-----+-----+-----

_Cabinets._--Cabinets are required to enclose all fuses. It is advised

that they be arranged so that it will not be necessary to open the fuse

compartment to operate switches.

Care should be exercised in locating cut-out cabinets. They should be in

a dry place, easily accessible to authorized persons, and not accessible

to the general public or miscellaneous employes. If too accessible they

are likely to be made receptacles for all sorts of rubbish. Wooden or

composition cabinets must not be used in theaters. Use only approved

cabinets.

In some cities special rules, governing the construction of cabinets for

theaters, exist and these should be looked up.

_Cables._--For construction rules, see “Stage Cables” in the chapter on

“Portable Stage Equipment”. Cables are required to connect border

lights. The cable is usually run from an outlet on the grid floor above

the center of the border. It must be long enough to allow the border to

be lowered for the cleaning and renewal of lamps. The slack cable must

be taken up when the border is raised and some provision must be made to

support the cable without injury to the insulation. Wire ropes or cables

are generally used to support the borders, but the lower end, which is

handled by the stage crew, is of ordinary manilla rope. Wire cables must

be insulated from the border by strain insulators.

_Canopies._--Very many theaters are provided with canopies which extend

over the street. Sometimes these are fitted out with glass signs behind

which incandescent lamps are installed. Often, also, a row of lights is

arranged around the bottom of the canopy ceiling. The number of lights

to be used depends upon the design of the canopy, but the effect is best

if a large number of small candle-power lamps are used. These lamps

should be of low intrinsic brilliancy. If possible, the lamps and

sockets should be arranged to be out of the weather. In addition to the

small outline lamps, other lights are often placed under canopy to

provide bright illumination. Each circuit may carry 1,320 watts.

_National Electrical Code Rule._

Where insulating joints are required, fixture canopies of metal must be

thoroughly and permanently insulated from metal walls or ceilings, or

from plaster walls or ceilings on metal lathing, and from outlet boxes.

Canopy insulators must be securely fastened in place, so as to separate

the canopies thoroughly and permanently from the surfaces and outlet

boxes from which they are designed to be insulated.

_Carriage Call._--See “Program Board”.

_Carrying Capacity of Wires._--Table VII is designed to help the wiremen

select the proper size of wire to use in supplying a certain number of

lights. The first column at the left gives the B. & S. gauge number. The

second column gives the number of amperes allowed on each wire according

to the National Electrical Code. The third column gives the distance in

feet which will cause a loss of 2 volts with the current given; thus a

current of 70 amperes in a No. 4 B. & S. gauge wire will lose 2 volts

over a distance of 56 feet. The proper size of wire to be used can

easily be determined from the table. The loss will always be in

proportion to the product of distance and current. The balance of the

table is devoted to showing the number of watts and lamps of various

sizes the wires will be allowed to supply.

_Ceiling Fans._--Must be hung from insulated hooks, or else there must

be an insulator interposed between the motor and its support. Not more

than 660 watts may be on one circuit.

_Chandeliers._--Large and elaborate chandeliers are sometimes used in

the center of the auditorium ceiling for purposes of illumination. Such

chandeliers should be suspended in a manner which will admit of readily

raising or lowering them for lamping up or repairs. For rules governing

wiring, see “Fixtures”.

TABLE VII.

TABLE SHOWING CARRYING CAPACITY OF WIRES; DISTANCE TO WHICH FULL LOAD

MAY BE CARRIED AT 2 VOLTS DROP AND NUMBER OF LIGHTS EQUIVALENT TO FULL

CURRENT GIVEN.

=======+=======+========+============+=============================

B. & S.|Rubber |Distance| Total | Total Number of Lamps of

Gage | Insu- |in Feet |Capacity in | Different Voltages and

|lation |Causing | Watts |Wattages that may be supplied

|Amperes|a Loss | +---------+---------+---------

| | of 2 | | 25-Watt | 40-Watt | 60-Watt

| | Volts +-----+------+----+----+----+----+----+----

| | | 110 | 220 | 110| 220| 110| 220| 110| 220

| | | V. | V. | V. | V. | V. | V. | V. | V.

-------+-------+--------+-----+------+----+----+----+----+----+----

14| 15 | 26 | 1650| 3300| 66| 132| 41| 82| 27| 54

12| 20 | 30 | 2200| 4400| 88| 176| 55| 110| 36| 73

10| 25 | 38 | 2750| 5500| 110| 220| 68| 137| 46| 91

8| 35 | 43 | 3850| 7700| 154| 308| 96| 192| 64| 128

6| 50 | 50 | 5500| 11000| 220| 440| 137| 275| 91| 183

5| 55 | 56 | 6050| 12100| 242| 484| 151| 302| 100| 201

4| 70 | 56 | 7700| 15400| 308| 616| 192| 385| 128| 256

3| 80 | 61 | 8800| 17600| 352| 704| 220| 440| 146| 292

2| 90 | 68 | 9900| 19800| 396| 792| 247| 494| 165| 330

1| 100 | 67 |11000| 22000| 440| 880| 275| 550| 183| 366

0| 125 | 78 |13750| 27500| 550|1100| 343| 686| 229| 458

00| 150 | 82 |16500| 33000| 660|1320| 412| 824| 275| 550

000| 175 | 89 |19250| 38500| 770|1540| 481| 962| 320| 640

0000| 225 | 87 |24750| 49500| 990|1980| 618|1236| 412| 824

200000| 200 | 92 |22000| 44000| 880|1760| 550|1100| 367| 734

300000| 275 | 101 |30250| 60500|1210|2420| 756|1512| 504|1008

400000| 325 | 114 |35750| 71500|1430|2860| 893|1786| 596|1192

500000| 400 | 117 |44000| 88000|1760|3520|1100|2200| 733|1455

600000| 450 | 123 |49500| 99000|1980|3960|1237|2474| 825|1650

700000| 500 | 130 |55000|110000|2200|4400|1375|2750| 916|1832

800000| 550 | 135 |60500|121000|2420|4840|1512|3024|1008|2016

900000| 600 | 139 |66000|132000|2640|5280|1650|3300|1100|2200

1000000| 650 | 143 |71500|143000|2860|5720|1787|3574|1191|2382

1100000| 690 | 147 |75900|151800|3036|6072|1897|3794|1264|2528

1200000| 730 | 151 |80300|160600|3212|6424|2007|4014|1338|2676

1300000| 770 | 155 |84700|169400|3388|6776|2117|4234|1412|2824

1400000| 810 | 161 |89100|178200|3564|7128|2227|4454|1485|2970

1500000| 850 | 164 |93500|187000|3740|7480|2337|4674|1558|3116

-------+-------+--------+-----+------+----+----+----+----+----+----

=======+=======+========+============+=============================

|Rubber |Distance| Total | Total Number of Lamps of

| Insu- |in Feet |Capacity in | Different Voltages and

B. & S.|lation |Causing | Watts |Wattages that may be supplied

Gage |Amperes|a Loss | +--------+--------+-----------

| | of 2 | |100-Watt|150-Watt|250-Watt

| | Volts +-----+------+---+----+---+----+---+-------

| | | 110 | 220 |110| 220|110| 220|110|220

| | | V. | V. |V. | V. |V. | V. |V. |V.

-------+-------+--------+-----+------+---+----+---+----+---+-------

14| 15 | 26 | 1650| 3300| 16| 33| 11| 22| 6| 13

12| 20 | 30 | 2200| 4400| 22| 44| 14| 29| 8| 17

10| 25 | 38 | 2750| 5500| 27| 55| 18| 36| 11| 22

8| 35 | 43 | 3850| 7700| 38| 77| 25| 61| 15| 30

6| 50 | 50 | 5500| 11000| 55| 110| 36| 73| 22| 44

5| 55 | 56 | 6050| 12100| 60| 121| 40| 80| 24| 48

4| 70 | 56 | 7700| 15400| 77| 154| 49| 99| 30| 61

3| 80 | 61 | 8800| 17600| 88| 176| 58| 117| 35| 70

2| 90 | 68 | 9900| 19800| 99| 198| 66| 132| 39| 78

1| 100 | 67 |11000| 22000|110| 220| 73| 146| 44| 88

0| 125 | 78 |13750| 27500|137| 274| 91| 182| 55|110

00| 150 | 82 |16500| 33000|165| 330|110| 220| 66|132

000| 175 | 89 |19250| 38500|192| 384|128| 256| 77|154

0000| 225 | 87 |24750| 49500|247| 404|165| 330| 99|198

200000| 200 | 92 |22000| 44000|220| 440|146| 292| 88|176

300000| 275 | 101 |30250| 60500|302| 604|201| 402|121|242

400000| 325 | 114 |35750| 71500|357| 714|238| 476|143|286

500000| 400 | 117 |44000| 88000|440| 880|293| 586|176|352

600000| 450 | 123 |49500| 99000|495| 990|330| 660|198|396

700000| 500 | 130 |55000|110000|550|1100|366| 732|220|440

800000| 550 | 135 |60500|121000|605|1210|403| 806|242|484

900000| 600 | 139 |66000|132000|660|1320|440| 880|264|528

1000000| 650 | 143 |71500|143000|715|1430|476| 952|286|572

1100000| 690 | 147 |75900|151800|759|1518|506|1012|303|606

1200000| 730 | 151 |80300|160600|803|1606|535|1070|321|642

1300000| 770 | 155 |84700|169400|847|1694|564|1128|338|676

1400000| 810 | 161 |89100|178200|891|1782|594|1188|356|712

1500000| 850 | 164 |93500|187000|935|1870|623|1246|374|748

-------+-------+--------+-----+------+---+----+---+----+---+-------

_National Electrical Code Rules for Fusing Chandelier Circuits._

When 1,320 watts are dependent upon one cut-out, as is allowed in

theater wiring, outline lighting, and large chandeliers, the fuse may be

in accordance with the following:

125 volts or less 20 amperes

125 to 250 volts 10 amperes

_Circuit Breakers._--Circuit breakers are not used much about theaters.

They are used mostly in connection with motors and on switchboards of

isolated plants. They are more sensitive and quicker to act than fuses

and, in case of a blow-out, can be more easily replaced. Where circuit

breakers are used it is good practice to set them for a higher amperage

than the fuses so that, in case of a heavy short circuit, the breaker

may act while the fuse will take care of an overload which comes on more

gradually.

_National Electrical Code Rides for Circuit Breakers._

With motors an automatic circuit breaker, disconnecting all wires of the

circuit, may serve as both switch and cut-out.

Where the circuit-breaking device on the motor-starting rheostat

disconnects all wires of the circuit, the switch may be omitted.

Circuit breakers must not be set more than thirty per cent above the

allowable carrying capacity of the wires, unless a fusible cut-out is

also installed on the circuit.

When installed without other automatic overload protective devices,

automatic overload circuit breakers must have the poles and trip coils

so arranged as to afford complete protection against overloads and short

circuits and, if also used in place of the switch, must be so arranged

that no one pole can be opened manually without disconnecting all the

wires.

_Concealed Work._--All concealed work must be in conduit or armored

cable. Wherever possible, rigid conduit should be used. Armored cable

should be used only where the whole cable may at any time be withdrawn,

or where it is impracticable to use rigid conduit.

_Conduit Work._--This is now considered the standard method of

construction. It is, however, somewhat over-rated and, especially in wet

places, has led to much disappointment. It is generally recognized that

wires, placed in conduit, will cause more trouble than those placed in

any other standard manner. The trouble is, however, confined to the

interior of the conduit and, if the conduit system be kept in good

order, and fuses at their proper limit, there is no chance of fire from

the wire confined within the conduit.

There are three points which, if carefully observed, will avoid most, if

not all, of the conduit troubles:

Avoid as far as possible locating conduit in wet or damp places.

Run all conduits so that they will drain.

Give particular attention to joints in outlet or junction boxes; tape

them heavily; and arrange them so they are not pressed against metal

more than is necessary; use large boxes.

Wires used in conduits must have approved rubber insulation and double

braid.

_National Electrical Code Rules for Wires and Interior Conduits._

_Wires for Conduit Work._

Must have an approved rubber insulated covering (Type Letter R. D.), and

must within the conduit tubing be without splices or taps.

Must not be drawn in until all mechanical work on the building has been,

as far as possible, completed.

Conductors in vertical conduit risers must be supported within the

conduit system in accordance with the following:

No. 14 to 0 every 100 feet

No. 00 to 0000 every 80 feet

No. 0000 to 350,000 C. M. every 60 feet

350,000 C. M. to 500,000 C. M. every 50 feet

500,000 C. M. to 750,000 C. M. every 40 feet

750,000 C. M. every 35 feet

The following methods of supporting cables are recommended:

(1) A turn of 90 degrees in the conduit system will constitute a

satisfactory support.

(2) Junction boxes may be inserted in the conduit system at the required

intervals, in which insulating supports of approved type must be

installed and secured in a satisfactory manner so as to withstand the

weight of the conductors attached thereto, the boxes to be provided with

proper covers.

(3) Cables may be supported in approved junction boxes on two or more

insulating supports so placed that the conductors will be deflected at

an angle of not less than 90 degrees, and carried a distance of not less

than twice the diameter of the cable from its vertical position. Cables

so suspended may be additionally secured to these insulators by tie

wires. Other methods may be used if specially approved.

Must, for alternating-current systems, have two or more wires of a

circuit drawn in the same conduit. It is suggested that this be done for

direct-current systems, also, so that they may be changed to alternating

systems at any time, induction troubles preventing such a change if the

wires are in separate conduits.

Except in the case of stage pocket and border circuits the same conduit

must not contain more than four two-wire, or three three-wire circuits

of the same system, except by special permission, and must never contain

circuits of different systems.

_Interior Conduits._

No conduit smaller than one-half inch electrical-trade size shall be

used.

Must be continuous from outlet to outlet or to junction boxes or

cabinets, and the conduit must properly enter, and be secured to all

fittings and the entire system must be mechanically secured in position.

In case of service connections and main runs, this involves running each

conduit continuously into a main cut-out cabinet or gutter surrounding

the panel board, as the case may be. Departure from this rule may be

authorized in case of underground services by special permission.

Must be first installed as a complete conduit system, without the

conductors.

Must be equipped at every outlet with an approved outlet box or plate.

At exposed ends of conduit (but not at fixture outlets), where wires

pass from the conduit system without splice, joint, or tap, an approved

fitting, having separately bushed holes for each conductor, must be

used. Departure from this rule may be authorized by special permission.

Outlet plates must not be used where it is practicable to install outlet

boxes.

For concealed work in walls and ceilings composed of plaster on wooden

joist or stud construction, outlet boxes or plates, and also cut-out

cabinets must be so installed that the front edge will not be more than

one-fourth inch back of the finished surface of the plaster; and if this

surface is broken or incomplete it shall be repaired so that it will not

show any gaps or open spaces around the edges of the outlet box or plate

or of the cut-out cabinet. On wooden walls or ceilings, outlet boxes or

plates and cut-out cabinets must be so installed that the front edge

will either be flush with the finished surface or project therefrom.

This will not apply to concealed work in walls or ceilings composed of

concrete, tile or other non-combustible material.

In buildings already constructed where the conditions are such that

neither outlet box or plate can be installed, these appliances may be

omitted, providing the conduit ends are bushed and secured.

It is suggested that outlet boxes and fittings, having conductive

coatings, be used in order to secure better electrical contact at all

points through the conduit system.

Metal conduits, where they enter junction boxes and at all other

outlets, etc., must be provided with approved bushings or fastening

plates fitted so as to protect wire from abrasion, except when such

protection is obtained by the use of approved nipples, properly fitted

in boxes or devices.

Must have the metal of the conduit permanently and effectually grounded

to water piping, gas piping, or other suitable grounds, provided that

when connections are made to gas piping, they must be on the street side

of the meter. If the conduit system consists of several separate

sections, the sections must be bonded to each other, and the system

grounded; or each section may be separately grounded, as required above.

Where short sections of conduit (or pipe of equivalent strength) are

used for the protection of exposed wiring on side walls, and such

conduit or pipe and wiring is installed as required by the Code Rules,

the conduit or pipe need not be grounded.

Conduits and gas pipes must be securely fastened in outlet boxes,

junction boxes, and cabinets, so as to secure good electrical

connections.

If conduits, couplings, outlet boxes, junction boxes, cabinets or

fittings, having protective coating of non-conducting material such as

enamel, are used, such coating must be thoroughly removed from threads

of both couplings and conduit, and such surfaces of boxes, cabinets, and

fittings, where the conduit or group clamp is secured, in order to

obtain the requisite good connection. Grounded pipes must be cleaned of

rust, scale, etc., at place of attachment of ground clamp.

Connections to grounded pipes and to conduits must be exposed to view or

readily accessible, and must be made by means of approved ground clamps

to which the ground wires must be soldered.

Ground wires must be of copper, at least No. 10 B. & S. gauge (where

largest wire contained in conduit is not greater than No. 0 B. & S.

gauge), and need not be greater than No. 4 B. & S. gauge (where largest

wire contained in conduit is greater than No. 0 B. & S. gauge). They

shall be protected from mechanical injury. The ground on the conduit

system is not to be considered as a ground for a secondary system.

Junction boxes must always be installed in such a manner as to be

accessible.

All elbows or hands must be so made that the conduit will not be

injured. The radius of the curve of the inner edge of any elbow must not

be less than three and one-half inches, and must have not more than the

equivalent of four quarter bends from outlet to outlet, the bends at the

outlets not being counted.

_Contacts._--Must be mounted on non-combustible non-absorption insulated

bases. Other materials than slate, marble, or porcelain must be

submitted for special examination before being used.

_Cord._--The use of flexible cord should be reduced to a minimum.

Wherever drop lights are necessary they should be wired with reinforced

cord or stage cable.

_Current Taps._--Must be of approved construction and may be used if

properly installed.

_National Electrical Code Rules for Current Taps._

Where, in addition to sockets or receptacles already installed,

connections are desired to lighting circuits for portable lamps, for

motors, or other special appliances requiring only small amounts of

current, multiple-current taps may be used, provided the entire circuit

does not require more than 660 watts, and provided their use will not,

under any conditions, involve a departure from the requirements of Rule

23-d of the National Electrical Code. Current taps must not be used in

key or pull sockets if the device, controlled through such sockets,

requires more than 250 watts.

_Cut-Outs._--All cut-outs should be on the stage switchboard. This

requires considerable extra wire, but it will be profitable in the end.

Fuses should be inspected occasionally to see that contacts are bright

and screws kept tight. There is everywhere a very strong tendency to

over-fuse, and the principal reason for it is the failure to keep screws

tightly fastened.

There is no fuse better than the plug fuse but it is not permitted with

voltages higher than 125 or with more than 30 amperes. Refillable fuses

must not be used. Cartridge fuses, especially, require to be kept clean.

The spring contacts on these often grow weak and cause heating which

helps to blow the fuse. The neutral fuse in three-wire installations

should be larger than the outside fuses. Link fuses should be avoided on

account of the delay that may be caused through difficulty of

installing.

It is advisable not to place switches in the same cabinet with fuses.

_National Electrical Code Rules for Automatic Cut-outs (Fuses and

Circuit-Breakers)._

_Constant-Potential Systems._

Must be placed on all service wires, either overhead or underground, in

the nearest accessible place to the point where they enter the building,

inside the walls, and arranged to cut off the entire current from the

building. Departure from this rule may be authorized only under special

permission in writing. Where the service switch is inside the building,

the cut-out required by this section must be placed so as to protect it.

For three-wire (not three-phase) systems the fuse in the neutral wire

may be omitted, provided the neutral wire is of equal carrying capacity

to the larger of the outside wires and is grounded.

Must be placed at every point where a change is made in the size of wire

(unless the cut-out in the larger wire will protect the smaller). For

three-wire direct current or single-phase systems the fuse in the

neutral wire, except that called for under Section d, may be omitted,

provided the neutral wire is grounded.

Must be in plain sight, or enclosed in an approved cabinet, and readily

accessible. They must not be placed in the canopies or shells of

fixtures. Link fuses may be used only when mounted on approved bases and

must be enclosed in dust-tight, fireproofed cabinets, except on

switchboards.

Must be so placed that no set of small motors, small heating devices, or

incandescent lamps, whether grouped on one fixture or on several

fixtures or pendants (nor more than 16 sockets or receptacles) requiring

more than 660 watts, will be dependent upon one cut-out.

By special permission, in cases where wiring equal in size and

insulation to No. 14 B. & S. gauge approved rubber-covered wire is

carried direct into keyless sockets or receptacles, and where the

location of sockets and receptacles is such as to render unlikely the

attachment of flexible cords thereto, the circuits may be so arranged

that not more than 1,320 watts (or thirty-two sockets or receptacles)

will be dependent upon the final cut-out. Except for signs and outline

lighting, sockets and receptacles will be considered as requiring not

less than 40 watts each.

All branches or taps from any three-wire system which are directly

connected to lamp sockets or other translating devices, must be run as

two-wire circuits if the fuses are omitted in the neutral or if the

difference of potential between the two outside wires is over 250 volts,

and both wires of such branch or tap circuits must be protected by

proper fuses.

The above shall also apply to motors, except that small motors may be

grouped under the protection of a single set of fuses, provided the

rated capacity of the fuses does not exceed 10 amperes. When 1,320 watts

are dependent upon one fusible cut-out, as is allowed in theater wiring,

outline lighting, and large chandeliers, the fuses may be in accordance

with the following:

125 volts or less 20 amperes

125 to 250 volts 10 amperes

The rated capacity of fuses must not exceed the allowable carrying

capacity of the wire. Circuit breakers must not be set more than 30 per

cent above allowable carrying capacity of the wire, unless a fusible

cut-out is also installed on the circuit. Fixture wire or flexible cord

of No. 18 B. & S. gauge, will be considered as properly protected by

10-ampere fuses.

Each wire of motor circuits, except on main switchboard or when

otherwise subject to competent supervision, must be protected by an

approved fuse whether automatic overload circuit breakers are installed

or not. Single-phase motors may have one side protected by an approved

automatic overload circuit breaker only if the other side is protected

by an approved fuse.

For circuits having a maximum capacity greater than that for which

enclosed fuses are approved, circuit breakers alone will be approved.

The ordinary porcelain link fuse cut-out will not be approved. Link

fuses may be used only when mounted on slate or marble bases conforming

to the rules, and must be enclosed in dust-tight, fire-proofed cabinets,

except on switchboards located well away from combustible material, as

in the ordinary engine and dynamo room, and where these conditions will

be maintained.

_Damp Places._--It is best to avoid wiring in damp places if possible.

If wires must be run in such places, they should be lead covered. If

armored cable is used, the wires in cable must be incased in lead.

Weatherproof sockets must be used and the use of cords should be

avoided. Where cords must be used they should be of the brewery or

packing-house type. If outside of the theater, proper open work may be

used. Conduit work is permissible but not advisable, except where wires

are subject to mechanical injury.

_Decorative Lighting Systems._--The commercial decorative lighting

systems are not suitable for use inside of theaters and should be used

only outside.

_National Electrical Code Rule for Decorative Lighting Systems._

Special permission may be given in writing for the temporary

installation of approved systems of decorative lighting, provided the

difference of potential between the wires of any circuit shall not be

over 150 volts and also provided that no group of lamps requiring more

than 1,320 watts shall be dependent on one cut-out.

[Illustration: FIGURE 157.]

_Dimmers._--“Dimmer” is the name given to the resistances which are used

to dim the electric lights on the stage. They are usually mounted at the

top or bottom of the switchboard with the operating handles in easy

reach of the operator. A dimmer should be provided for each color in

every border light and also for the foot lights. In some cases the

proscenium side lights are also arranged for several colors. The dimmers

should be mounted so that each one is directly above the switch which

controls the circuit to which it belongs. They should be protected by

wire guards against rubbish, which is likely to accumulate among them if

they are not enclosed. Good ventilation must be provided. A certain

dimmer can be used only while the amperage remains within the proper

limitations. If carbon lamps, for instance, are changed for tungsten,

the amperage will be much reduced and the dimmer may not work properly.

Modern dimmers are all of the interlocking type so that the whole bank

may be worked together or any one singly. Figure 157 is an illustration

of a small bank of dimmers.

_Door Switches._--Door switches are used mostly in connection with

dressing rooms. When the light in the room is burning, opening and

closing the door will turn it out.

_Dressing Rooms._--Many dressing rooms are wired with lights on pendant

cords, but this method is not to be recommended. It is better to arrange

the lights in sockets fitted into the outlet boxes. It will be well if

each dressing room is provided with a circuit for flatirons. If this is

considered too expensive, the fuses on circuits leading into dressing

rooms must be kept small enough to blow in case a flatiron is connected.

Many actors are in the habit of carrying flatirons and will use them on

incandescent-light circuits if no other circuit is provided. If metal

guards are fastened on securely, much of the trouble from flatirons will

be avoided, but they must be fastened so that an ordinary screwdriver

will not loosen the screws.

Dressing room illumination, if properly carried out, will save the

proprietor much annoyance. Actors have ways of obtaining the light they

want by fair means or foul, and it is much better to arrange the

lighting so that it will be satisfactory to those using it, than to have

it continually tampered with.

A bright illumination is essential for making up and both sides of the

face should be fully illuminated. To accomplish this it is necessary to

provide at least two lights for each mirror. Every lamp should be

provided with a substantial guard which may be securely fastened to the

outlet box. This is especially necessary if small candle power lamps are

furnished. For, if the light furnished is insufficient, there will be

strong efforts made to replace the small lamps by larger ones. Guards

are also necessary as a protection against fire. Actors are in the habit

of drying small articles of clothing on the lamps, and fires have been

known to start from this cause. The guards on the lamps throw shadows on

the faces of the actors, and for this reason are not liked. In order to

avoid the shadows, frosted lamps may be used, or two lamps on each side

of the mirror. One lamp will then illuminate the shadows caused by the

other. Where there are long dressing tables, as in rooms occupied by the

chorus, mirrors may be placed between each two lamps on each side of the

table and the lamps staggered vertically. In this way each party will

receive the benefit of at least four lamps and the shadows will be less

noticeable.

The color value of the lamps used in dressing rooms should match that of

the lamps used on the stage. Some stages, for instance, are illuminated

by flaming arcs which may give an altogether different effect to a “make

up” than the tungsten lamps, for instance.

Where there are a large number of sockets without lamps in them, it is

advisable to close the socket by a fuse plug from which the fuse has

been removed, or in some similar manner in order to avoid the chance of

short circuits from hat pins or similar objects used in dressing rooms.

_Drop Lights._--Drop lights should be avoided as much as possible.

Where they must be installed reinforced cord, armored cable, or flexible

steel armored cord should be used.

_Emergency Lighting._--Every theater must have an emergency lighting

system as outlined in the rules below. The object of this is to provide

a double system of illumination so as to reduce the likelihood of the

theater being left in total darkness. This is a frequent occurrence

where the theater is supplied by an isolated plant, and may also occur

where the supply is obtained from a large outside lighting system

although the latter is usually more reliable.

Every unnecessary light that is added to an emergency system increases

the likelihood of trouble. A sufficient number of lights added to it to

illuminate the space used by the audience in getting out is, therefore,

necessary but more than this is a detriment rather than a help. The

practice of connecting all of the hall and lobby lights to the emergency

system is to be condemned, since it defeats the purpose of the rule

which provides a double illumination system for every part of the

theater used by the audience. The two systems should be carried into the

auditorium, all stairways, exits, and lobby clear to the street. They

should, furthermore, be kept entirely separate, in separate conduits and

using separate meters.

The rule does not specify the number of exit and emergency lights

required. Good practice requires a light for every 400 square feet or

so. If each of these outlets be fitted with a 50 watt lamp the

illumination will interfere with many of the acts and so, smaller lamps

are generally used. One emergency light for each 60 seats will fill the

bill nicely.

[Illustration: FIGURE 158.]

Over each exit, an exit light must be provided, but as these exit lights

are usually incased in ruby glass such as shown in Figure 158 they

cannot be counted as giving any illumination. In many theaters gas is

used for emergency and exit lighting and in many respects this seems to

be a good practice. In some quarters, however, it is believed that a

fire in the scenery of a theater might create such an air pressure in

the building as to overcome the low gas pressure and thus put out the

gas at the very time when it is most needed. The very best suggestion

that can be made is that of a storage battery to supply the emergency

system. Where alternating current is used this, however, introduces some

complications and becomes quite expensive. Avoid the use of key sockets,

fan motors, or any unnecessary device on emergency or exit light

circuits.

_National Electrical Code Rules for Services._

Where supply may be obtained from two separate street mains, two

separate and distinct services must be installed, one service to be of

sufficient capacity to supply current for the entire equipment of

theater, while the other service must be at least of sufficient capacity

to supply current for all emergency lights. Where supply cannot be

obtained from two separate sources, the feed for emergency lights must

be taken from a point on the street side of main service fuses. By

“emergency lights” are meant exit lights and all lights in lobbies,

stairways, corridors, and other portions of theater to which the public

have access, which are normally kept lighted during the performance.

Where the source of supply is an isolated plant within the same

building, an auxiliary service of at least sufficient capacity to supply

all emergency lights must be installed from some outside source, or a

suitable storage battery within the premises may be considered the

equivalent of such service.

[Illustration: FIGURE 159.]

Exit lights must not have more than one set of fuses between same and

service fuses. Exit lights and all lights in halls, corridors, or any

other part of the building used by audience, except the general

auditorium lighting, must be fed independently of the stage lighting,

and must be controlled only from the lobby or other convenient place in

front of the house. All fuses must be enclosed in approved cabinets.

Figure 159 shows a diagram of an emergency lighting system together with

that of the house lighting system. The main house switch is sometimes

arranged with two sets of fuses, so that it need only be thrown over

when a fuse blows. See Figure 159 at the right.

_Exit Lights._--Exit lights are usually required over all doors leading

from any part of the auditorium to the lobby or outside of the theater.

They are usually incased in ruby glass on which the word EXIT has been

etched in large letters. See also Emergency Lighting.

_Fan Motors._--In large theaters, sometimes as many as ten or twelve fan

motors are arranged along the walls of the auditorium, to blow air

toward the audience. In small theaters there is a strong temptation to

connect these to the emergency circuit, but this should never be done.

The motors are too noisy to be allowed to run during an act and must be

wired so that they can all be thrown on or off together from the stage

switchboard. Not more than 660 watts should be connected to any one

circuit and the connection should be by means of attachment plugs and

reinforced cord, a bracket for the motor being placed as near as

possible to the outlet, so as to reduce the amount of cord required to a

minimum.

_Fire Alarm._--In some of the cities a special signal system between

stage and box office is required and it is necessary to consult

authorities about this. Ordinarily a bell circuit, such as shown under

“Bells,” will answer.

_Fish Work._--The fishing of wires incased in loom, as is permitted in

other places, is not permissible in theaters. If wires are to be

“fished” they must be incased in metal armor.

_Fixtures._--Fixtures require careful inspection before installing. It

is seldom that the piping is properly reamed out as required by the

rule. Chain fixtures especially, must be closely watched. There is

little if any trouble to be expected from the wires laced among the

chain links, but there is much trouble to be looked for from the wires

at the points where they leave the chain support and where they enter

the socket. The openings for the wires at these points are seldom large

enough to admit of the proper wire being used, and they are not well

reamed either. The result of these conditions is that the wire is very

quickly abraded and short circuits are common.

Fixtures may be tested for short circuit by connecting a magneto at the

feed end of the wires and turning it briskly. If a ring is obtained it

is an indication that something in wrong. The test for open circuit may

be made with the same connection. Insert a screw driver or a plug into

each socket; if it is not possible to obtain a ring there must be an

open circuit. The test for “ground” may be made by connecting both feed

wires to one pole of the magneto, and the other pole to the metal of the

fixture taking care that there is no lacquer on that part of the

fixture. If a ring is obtained it is an indication that some bare spot

on the wire is in contact with the fixture. Fixtures used for emergency

lighting must carry no key sockets and must not feed fan motors.

_National Electrical Code Rules for Fixture Wire and Fixtures._

_Wires for Fixture Work._

Must not be smaller than No. 18 B. & S. gauge, and must have an approved

rubber insulating covering. In wiring certain designs of show-case

fixtures, ceiling bull-eyes, and similar appliances in which the wiring

is exposed to temperature in excess of 120 degrees Fahrenheit (49

degrees centigrade), from the heat of the lamps, approved slow-burning

wire must be used. All such forms of fixtures must be submitted for

examination, test and approval before being introduced for use.

Supply conductors, and especially the splices to fixture wires, must be

kept clear of the grounded part of gas pipes, and, where shells or

outlet boxes are used, they must be made sufficiently large to allow the

fulfillment of this requirement.

Must, when fixtures are wired outside, be so secured as not to be cut or

abraded by the pressure of the fastenings or motion of the fixture.

Wires of different systems must never be contained in or attached to the

same fixture, and under no circumstances must there be a difference of

potential of more than 300 volts between wires contained in or attached

to the same fixtures.

On chains of similar parts where conductors are not completely enclosed

in metal, wires must be stranded and must have rubber insulation not

less than one thirty-second of an inch in thickness; or approved pendant

or portable cord may be used.

_Fixtures._

When supported at outlets in metal conduit, armored cable, or

metal-molding systems, or from gas piping or any grounded metal work, or

when installed on metal walls or ceilings, or on plaster walls or

ceilings containing metal lath, or on walls or ceilings in fireproof

buildings, fixtures must be insulated from such supports by approved

insulating joints placed as close as possible to the ceilings or walls.

The insulating joint may be omitted in conduit, armored cable, or

metal-molding systems with straight electric fixtures in which the

insulation of conductors is the equivalent of insulation in other parts

of the system, and provided that approved sockets, receptacles, or

wireless clusters are used of a type having porcelain or equivalent

insulation between live metal parts and outer metal shells, if any.

Where insulating joints are required, fixture canopies of metal must be

thoroughly and permanently insulated from metal walls or ceilings, or

from plaster walls or ceilings on metal lathing, and from outlet boxes.

Canopy insulators must be securely fastened in place so as to separate

the canopies thoroughly and permanently from the surfaces and outlet

boxes from which they are designed to be insulated.

Fixtures having so-called flat canopies, tops, or backs, will not be

approved for installation, except where outlet boxes are used.

In non-metallic fixtures wireways must be metal-lined unless approved

armored conductors with suitable fittings are used.

_Flashers._--Flashers are used to economize electrical energy in sign

illumination. An electric sign is often just as effective if only one

side or one letter is in use at a time and in such a case there is

considerable saving by the use of a flasher.

[Illustration: FIGURE 160.]

Flashers are made up in a variety of forms, one of them being shown in

Figure 160. The manner of wiring to the sign will be readily understood

by reference to the figure. The neutral wire is carried direct to the

sign and fuses for that wire are often installed up in the sign, while

those for the other side of the circuits must be close to the flasher to

comply with the rule which requires fuse protection where a small wire

is tapped off from a larger one, unless the fuse in the larger wire is

below the carrying capacity of the smaller.

_National Electrical Code Rule for Flashers._

Time switches, sign flashers, and similar appliances must be of approved

design and enclosed in approved cabinets.

_Flat Irons._--See Heaters.

_Flexible Cord._--The ordinary flexible cord should not be used in any

part of a theater. It is recommended that only those cords described

below be used, each of course in its proper place. Approved reinforced

cord for pendants. Approved asbestos-covered cord for portable heaters.

Approved Stage and Border Cables on Stage.

See “Stage Cables.”

_Flexible Tubing._--Flexible tubing is not permissible in theaters.

_Floor Pockets._--These are always a source of trouble and their use

should be avoided as much as possible. If it is necessary to use any

they must be of a type approved by the inspection department having

jurisdiction.

_Fly Floor._--This is the name given to that part of the gallery above

the stage upon which those employes, whose duty it is to raise and lower

curtains and scenery, work. No great illumination is required, but the

lights should be arranged so as to be convenient to the men for reading

during long waits. If this is not done there will always be considerable

objectionable cord wiring found in this place. Fly-floor and

rigging-loft lights should be provided with three way switches so that

lights may be turned on or off either at the stage switchboard or on the

fly floor.

_Footlights._--These form the most important and effective part of the

permanently located stage lights. To locate them properly requires

careful consideration. If they are brought too high they will obstruct

the view of the audience; if located too low they will not illuminate

the lower part of the stage.

Opinion is somewhat divided as to whether they ought to be arranged in

circular form or be laid out straight across the stage. In large

theaters there is a circular space between the front seats and the front

of the stage. A circular stage will utilize this space and this form of

stage with footlights arranged in a similar manner will also allow the

actors to approach more closely to the audience and will procure for

them some illumination from the side. The difficulty of making up a

circular strip of footlights is somewhat greater than that of making

them up in a straight line.

[Illustration: FIGURE 161.]

[Illustration: FIGURE 162.]