CHAPTER LVIII

CURRENT AND PRESSURE LIMITING DEVICES

In any electric installation there must be provided a number of

automatic devices to secure proper control. The great multiplicity

of devices designed for this purpose may be divided into two general

classes, as

1. Current limiting;

2. Pressure limiting.

Because of the heating effect of the current which increases in

proportion to the square of the strength of the current, it is

necessary to protect circuits with devices which do not allow the

current to exceed a predetermined value.

Accordingly fuses, circuit breakers, reactances, etc., are used, each

possessing certain characteristics, which render it suitable for

particular conditions of service.

For instance, just as in analogy, steam boilers must be

protected against abnormal pressures by safety valves, electric

circuits must be guarded against excessive voltages by pressure

limiting devices, otherwise much damage would occur, such as

the burning out of incandescent lamps, grounding of cables, etc.

The control of steam is simple as compared to the electric

current, the latter being the more difficult to manage because

of its peculiar behaviour in certain respects, especially in

the case of alternating current which necessitates numerous

devices of more or less delicate construction for safety both

to the apparatus and the operator.

~Fuses.~--A fuse is "an electrical safety valve", or more specifically,

_the actual wire or strip of metal in a cut out, which may be fused by

an excessive current_, that is to say, by a current which exceeds a

predetermined value. A fuse, thus serves to protect a circuit from any

harm resulting from an undue overload.

Fuses have been treated at such length in Guide No. 2, Chapter

XXV, that very little can be said here, without repetition.

[Illustration: FIG. 2,238.--Sectional view of Noark 250 volt, 400

ampere ~enclosed fuse~. The ~fusible element~ _is divided into strips_

A, B, C, and D. This parallel link construction results, upon the

operation of the fuse, in the formation of a number of small arcs, thus

facilitating the absorption of the metal vapor formed when the fuse

blows. ~The fusible strips~, of which there are two or four in number,

according to the ampere capacity of the fuse, are entirely surrounded

by a granular material which is chemically inactive with respect to the

fusible link and whose function is to absorb the metallic vapor formed

upon the blowing of the fuse. ~The contact blades~ T and L are made of

round edge copper, the round edges facilitating the insertion of the

fuses in the circuit terminals. R and S are the end ferrules, attached

to cover E, by the pin M.]

~Ques. What effect have the terminals on a fuse?~

Ans. The current at which a fuse melts may be greatly changed by the

size and shape of the terminals.

If near together and large, they may conduct considerable heat

from the fuse thus increasing the current required to blow the

fuse.

~Ques. What is the objection to large fuses?~

Ans. The discharge of molten metal when the fuse blows is a source of

danger.

~Ques. What should be used in place of large fuses?~

Ans. Circuit breakers.

~Ques. What are the objections to fuses in general?~

Ans. The uncertainty as to the current required to blow them; the

constant expansion and contraction is liable to loosen the terminal

screws when screws are used.

~Ques. What is the advantage of fuses?~

Ans. They form an inexpensive means of protecting small circuits.

[Illustration: FIG. 2,239.--Cross section through plug fuse. With this

type of fuse it is impossible to place any except the correct size of

plug in the socket.]

~Ques. Describe a plug fuse.~

Ans. It is constructed as shown in fig. 2,239, the fuse wire being

visible and stretching between the two metal portions of the plug.

~Ques. What is a cut out fuse?~

Ans. One similar to a simple fuse, but provided with clip contacts as

used for knife switch contacts.

The fuse wire is usually contained in a china or porcelain

tube, which also serves the purpose of a handle for withdrawing

the fuse.

~Ques. What is an expulsion fuse?~

Ans. One in which the fuse is placed in an enclosed chamber with a vent

hole.

In operation, when the fuse blows, the hot air and molten metal

are expelled through the vent.

~Ques. What is a no arc fuse?~

Ans. A cartridge type fuse, in which the space surrounding the fuse

wire is filled with powdered material.

[Illustration: FIG. 2,240.--Inside view of end ferrule of Noark

enclosed fuse. Two prongs O and V, which are a part of the knife blade

K, pass through the square holes in the ends of the ferrule R, and

are riveted to the anchor plate T. ~The object of this plate~ _is to

stiffen the structure and to increase the current carrying capacity

of the metal between the holes, also to permit of proper alignment

of the plates_. In each ferrule is placed a ~vent screen~, composed

of reticulate material, such as cheese cloth. The fuzz between the

threads of the cheese cloth prevents the escape of the granular

material through the vent holes A, but when the fuse operates, allows

free egress of the air, thereby permitting the vapor formed upon the

operation of the fusible element to quickly and freely pass through the

interstices of the filling material and become cooled, eliminating any

possibility of flame issuing from the ends of the tube.]

The object of the powdered material is to assist in

extinguishing the arc formed when the fuse blows.

~Ques. What is a magnetic blow out fuse?~

Ans. An enclosed fuse which is subject to the action of a magnetic

field produced by the current, the magnetic field tending to blow out

the arc when fusing occurs.

~Ques. What is a quick break fuse?~

Ans. One having a weight suspended from its center, or springs attached

to its ends so that the arc formed at fusing is quickly attenuated and

extinguished.

~Ques. What is the disadvantage of a fuse as compared to an oil switch

circuit breaker?~

Ans. When a fuse blows, the arc causes oscillations in the line, which

cause excessive rise of pressure under certain capacity conditions,

whereas this disturbance is reduced to a minimum with an oil switch.

[Illustration: FIG. 2,241.--~Quick break fuse.~ The fuse wire is

connected between the fixed terminal A and the movable arm B, and is

held under tension by the spring which exerts pressure on the movable

arm in a direction tending to separate A and B. ~In operation~, when

the fuse blows, the movable arm quickly moves to the position B´, thus

attenuating the arc and accelerating its extinguishment.]

~Ques. What metal is used for fuse wires?~

Ans. Various metals. Ordinary fuse wire is made of lead or an alloy of

lead and tin.

~Ques. What is the objection to aluminum?~

Ans. It becomes coated with oxide or sulphide, which acts as a tube

tending to retain the metal inside and prevent rupture.

~Ques. What is the objection to copper?~

Ans. Its high fusing point.

~Current Limiting Inductances.~--The great increase in capacity of

power stations, for supplying the demands of densely populated centers

and large manufacturing districts, together with the decrease in the

reactance of modern alternators and transformers due to improvement

in design to obtain better regulation, has presented a problem

in apparatus protection not contemplated in the earlier days of

alternating current distribution. This problem is entirely separate and

distinct from that of eliminating the tendency toward short circuit,

incident to the high voltages now common in transmission lines. It

accepts that all short circuits must occasionally occur and considers

only the protection of the connected apparatus against the mechanical

forces due to the magnetic stresses of such enormous currents.

[Illustration: FIG. 2,242.--~Notched end fuse.~ This is a simple form

of fuse ~consisting of~ _a strip of metal (or wire) fixed between

two end pieces to fit around the terminals_. This type is often

proportioned so that it is only possible to place the correct size of

fuse in the terminals. Sometimes, in place of the end pieces as shown,

the fuse metal is fixed between two clamping screws.]

~Ques. What means are employed to limit the value of a short circuit

current?~

Ans. A current limiting inductance coil (called a _reactance_) is

placed in series with the alternators or transformers.

[Illustration: FIG. 2,243.--General Electric current limiting

reactance; view showing details of construction. The core consists

of a hollow concrete cylinder, alloy anchor plates or sockets being

embedded in the core near the ends to receive the radial brass bolts.

An extension at each end of the core provides for clamping and bracing

the reactance in installation. The supports for the winding are made of

resin treated maple and are located upon the core by radial brass studs

screwed into the alloy sockets, and insulated by mica tubes. The nuts

by which the structure is tightened, rest upon heavy fibre washers.

Wooden barriers fitted and shellacked into the supports add to the

creepage surface between layers of the winding and between the winding

and the core. The supports of the layer next to the core are separated

from the core by strips of treated pressboard. The coil consists of

bare stranded cable in several layers, usually three in number. It is

wound into grooves in the treated wood supports, which are protected

from contact with the cable by heat shields of asbestos shellacked

into the grooves. The winding is usually in the form of two back turn

sections, thereby allowing the terminals of the coil to be brought out

at the ends of the outside layer. This assures accessibility and ease

of connection, and the removal of the leads from proximity to the core.

Two turns at each end of the winding are given extra spacing for the

purpose of additional insulation. The final turn at each end of the

coil is securely held in place by alloy clamps bolted to the supports.

The wood is protected from contact with the clamps by shields of

asbestos. The ends of the cable between the two sections are welded by

the oxyacetylene process.]

~Ques. What are its essential features of construction?~

Ans. It consists of bare stranded cable wound around a concrete core

and held in place by wooden supports as shown in fig. 2,243.

In order to avoid the prohibitive expense of high voltage

insulation, the reactance coil is designed for the low tension

circuit. This requirement prohibits the use of a magnetic core

which, if economically designed for normal operation, would

become saturated at higher densities, or, if designed large

enough to avoid saturation at short circuit conditions, would

become prohibitive in cost and dimensions.

The elimination of all magnetic material from the construction

of the concrete core reactance permits of no saturation, and

assures a straight line voltage characteristic at all current

loads.

[Illustration: FIG. 2,244.--Westinghouse ~magnetic blow out circuit

breaker~, designed for the protection of street railway and electric

locomotive equipments; it serves the combined purpose of fuse block

and canopy switch. ~The contact tips~ _are surrounded by a moulded

arc chute which confines and directs the arc until the magnetic blow

out extinguishes it_. The current carrying contacts consist of copper

strips separated by air spaces. An auxiliary contact or "arcing tip"

at the end of the switch lever takes the burning of the arc when the

breaker opens, and thus confines the burning to a very small piece

which can be easily removed and replaced at small cost. The hand

tripping lever and the resetting lever have insulated handles, so that

they can be safely handled, even in the dark.]

~Ques. Where is the proper location for a current limiting reactance?~

Ans. As near the alternator as possible.

~Ques. Why?~

Ans. To lessen the possibility of a short circuit occurring between the

reactance and the alternator.

~Ques. Beside limiting the current, what other service is performed by

the reactance?~

Ans. It protects the alternator from high frequency surges coming in

from the outside, and limits the current from other machines on the

same bus.

[Illustration: FIG. 2,245.--General Electric magnetic blow out circuit

breaker. This type may be used in air or water tight boxes and is

peculiarly adapted for service where the arc must be confined.]

~Circuit Breakers.~--The importance of circuit protective devices,

commonly called circuit breakers, is fully recognized. The duty

of a circuit breaker is to protect the apparatus in an electrical

circuit from undesirable effects arising from abnormal conditions,

by automatically breaking the circuit. Accordingly a circuit breaker

must comprise a switch in combination with electrical control devices

designed to act under abnormal conditions in the circuit.

A circuit breaker is a _device which_ ~automatically~ _opens the

circuit in event of abnormal conditions, in the circuit_.

[Illustration: FIG. 2,246.--Magnetic blow out circuit breaker. This is

a direct current breaker in which the final break occurs in a magnetic

field. ~It is a principle in electromagnetics~ _that a conductor

carrying a current in a magnetic field will tend to move in a direction

at right angles to the field_. The arc set up on breaking a circuit

constitutes a conductor, and in magnetic blow out circuit breakers, as

generally manufactured, there is an electromagnet, energized by the

current to be broken, which produces a field in the neighborhood of

the arc, with the result that the arc moves outward, and so becomes

attenuated and is finally extinguished. The form shown in the figure is

used on cars equipped with heavy motors. When so used, it is in many

cases mounted in a box with the handle H projecting at one end. A and K

are the terminals of the breaker and B is the tripping coil, which also

serves to set up the magnetic field necessary for blowing out the arc.

X is the armature of coil B and is pulled down against the action of

the spring S whenever the current exceeds that for which the breaker is

set. The tripping current is adjusted by means of nut T. The iron plate

P and a similar one back of it are magnetized by the current in coil

B, and as the break takes place between these two poles, the arc is

promptly extinguished by the field that exists there. ~In operation~,

A and K are the terminals, D D is a contact that is forced up against

F, F when the breaker is set. The current then takes the path A-B-F-D

D-F-K. ~When the breaker trips~, the contact piece D D flies down

and the tendency is for an arc to form between F, F; the magnetic

field blows the arc upwards, and whatever burning takes place is on

the contacts E, E, which are so constructed that they may be readily

renewed. ~To trip the breaker by hand~, the knob N is pressed.]

In the design of circuit breakers, there are several methods used to

effect the rupturing of the arc between contacts when opened on heavy

overload, such as:

1. Magnetic blow out; 2. Thermal break; 3. Carbon break.

In the magnetic blow out type, the arc is extinguished between

auxiliary contacts confined by a chute in which the arc is rapidly

blown out due to a powerful magnetic field from one or more

electromagnets. This type may be used in air or watertight boxes and is

peculiarly adapted for service where the arc must be confined.

[Illustration: FIG. 2,247.--~Thermal overload circuit breaker.~ ~In

construction~ two contact blocks are fixed rigidly to, but insulated

from, the switch arm. They are connected electrically by two parallel

strips of suitable metal, each fitted with a steel catch piece. ~When

the switch is closed~ the strips are sprung apart over a fixed catch,

and the full rated current does not release the catch. Overload causes

the strips to move apart, and the circuit breaker flies off under the

action of a spring.]

In a carbon break type, the arc is finally ruptured between carbon

break contacts. The breaking of the circuit is accomplished

progressively, that is to say, it is done in three stages, by several

sets of contact, known respectively as

1. The main contacts;

2. The intermediate contacts;

3. The carbon contacts.

_In operation_, as the circuit breaker acts to break the circuit, first

the ~main~ _contacts_, separate, then the ~intermediate~ _contacts_,

and finally the ~carbon~ _contacts_ between which the arc is ruptured.

~Ques. What is the object of the intermediate contacts?~

Ans. To prevent the forming of an arc on the main contacts.

[Illustration: FIG. 2,248.--Carbon break discs of Condit circuit

breaker. The two pairs of similar discs which slide past each other

are so arranged that these surfaces coincide at the instant the

intermediate contacts separate after which, as the contact arm opens

further, they gradually disengage.]

~Ques. What is the object of the carbon contacts?~

Ans. First to protect the intermediate contacts by providing a path

for the current after the intermediate contacts separate, and 2, to

"slow down" the current by means of the considerable resistance of the

carbon, thus reducing to a minimum the arc which is formed when the

carbon contacts separate.

~Ques. How is the automatic operation of a circuit breaker usually

accomplished?~

Ans. Usually through the medium of a solenoid, or electromagnet

energized by current from the circuit controlled by the breaker.

[Illustration: FIG. 2,249.--Mechanically connected insulated latches

used on Condit circuit breakers to produce inter-locking tripping.]

The essential features of construction and operation of a

circuit breaker is shown in the elementary diagrams, figs.

2,250 to 2,253. ~In construction~ as shown in fig. 2,250 it

consists essentially of three sets of contacts, a swinging

contact arm which is set in the closed position by the handle

operating through the toggle joint, the movement of which is

limited in the closing direction by the stop. The latter is

made adjustable by an eccentric pin or equivalent. Connected

to the toggle is the plunger of the solenoid whose winding is

energized by current from the circuit which the circuit breaker

is to control.

[Illustration: FIGS. 2,250 to 2,253.--Elementary diagrams illustrating

the operation of a carbon circuit breaker of the overload type, showing

the progressive opening of such device. Fig. 2,250, closed position;

fig. 2,251, main contacts open; fig. 2,252, intermediate contacts open;

fig. 2,253, carbon contacts open, circuit broken.]

~In operation~, the circuit is closed by hand by turning the

handle downward to the position shown in fig. 2,250, that is as

far as it will go.

Since the toggle has passed the center line the arm will be

held normally in this position because of the spring action of

the contacts. Now, if the current rise above a predetermined

limit, the pull exerted by the solenoid will overbalance the

tendency of the toggle to remain in the closed position, and

pull the two toggle links downward below the center line,

drawing the contact arm back and breaking the circuit.

[Illustration: FIG. 2,254.--I-T-E overload circuit breaker. ~In

operation~: the current from one side of the circuit enters the circuit

breaker at A, passing through the laminated bridge B to contact block

C, thence through coil D and terminal E to the motor. The coil D

surrounds a magnetic core, having pole pieces F and G and armature H.

The effect of the current in the coil is to energize the magnet, thus

tending to lift the armature against the force of gravitation. The

volume of current required to trip the circuit breaker is determined

by the position of the armature, which is subject to ready adjustment,

and is indicated on the calibration plate P. From the opposite side

of the line, the current enters at I, passing downward through the

laminated bridge member J, into terminal K, whence it passes out to the

motor. When the current passing through the circuit breaker attains

sufficient volume, the force generated by the magnetic coil overcomes

the weight of the armature H; and the latter is drawn upward toward

the pole pieces with constantly increasing force, until the insulated

projections L and M strike against the respective restraining latches

N and O, thereby releasing the two switch members, which at once open

in response to the force supplied by the spring of the contact members

and auxiliary springs provided for the purpose. Positiveness in opening

is further assured by the blow of the armature, which is added to the

other opening forces; hence, the heavier the overload, the more violent

the blow and the quicker the circuit breaker opens; or the greater the

current the more promptly it is interrupted. This is the ~I-T-E~ or

~I~nverse ~T~ime ~E~lement principle.]

[Illustration: FIG. 2,255.--Condit 600 volt, 1,200 ampere, single pole,

type K, circuit breaker with pull down handle.]

[Illustration: FIG. 2,256.--Condit 600 volt, 6,000 ampere, single pole,

switch board mounting, circuit breaker, with pull down handle.]

[Illustration: FIG. 2,257.--General Electric triple pole, overload,

circuit breaker, with two overload coils, capacity 300 amperes, 480

volts.]

The progressive action which takes place during this operation

is shown in figs. 2,250 to 2,253 in which the main contacts

separate first, then the intermediate, and finally the carbon

contacts as mentioned before.

~Ques. What name is given to this type of circuit breaker?~

Ans. It is called an overload circuit breaker.

[Illustration: FIG. 2,258.--Parts of General Electric 2,000 ampere 650

volt circuit breaker. A, cover for secondary contact bracket; B, spring

washer for Ea.; C, pin for links and G; D, spring for carbon support;

E, plate for F; F, carbon support; G, secondary contact bracket; H,

contact plate; I, screw for H; J, nut for K and W; K, contact stud,

upper; L, laminated brush, complete with support; M, leather buffer for

L; N, main link; O, pin for Na and La left hand and Cb and Na right and

left hand; P, screw for N and magnet frame shaft; Q, washer for N and

magnet frame shaft; R, screw for S and V; S, index plate; T, plate for

Gb; U, screw for T; V, magnet frame; W, contact stud, lower; X, pin for

Cb, Na and V; Y, washer for X and O; Z, calibrating screw with thumb

nut; Aa, armature with contact plate; Ba, catch lever complete with

catch Ca, button handle for Ba; Da, spring cotter for Ea; Ea, pin for

F and Fa; Fa, operating link for G; Ga, pin for D; Ha, carbon holder

with copper and carbon contacts; Ia, flexible connections for G and F;

Ja, screw for G and flexible connection plate; Ka, screw for Na and Ha;

La, copper secondary contact; Ma, screw for La; Na, secondary contact

lever; Oa, cross bar for Na; Pa, screw for L and M; Qa, secondary

toggle link (left hand); Ra, spring cotter for Wa and O; Sa, brush

lever; Ta, buffer for Cb and Sa; Ua, secondary toggle link (right

hand); Va, washer for Wa; Wa, pin for Cb, Qa, Ua and N; Xa, pin for Sa

and Cv; Ya, spring cotter for all pins, except Wa, catch lever pin and

buffer; Za, secondary contact link; Ab, washer for Fb; Bb, guard for

Fb; Cb, handle lever; Db, catch for Cb; Eb, screw for Db; Fb, handle

with stud; Gb, secondary connection.]

~Automatic Features.~--There are three methods of connecting the

winding of the solenoid, or _trip coil_ as it is called:

[Illustration: FIGS. 2,259 to 2,262.--Elementary diagrams illustrating

the various methods of electromagnetic control for circuit breakers.

Fig. 2,259, overload trip; fig. 2,260, underload trip, fig. 2,261, low

voltage trip; fig. 2,262, control from auxiliary circuit by means of a

"relay."]

1. In series with the main circuit;

2. In shunt with the main circuit;

3. In shunt with an auxiliary circuit.

[Illustration: FIG. 2,263.--Diagram of General Electric low voltage

trip with tripping switch _normally_ ~open~.]

The automatic controls arising from these connections give various

kinds of protection to the circuit and are known as

1. Overload trip;

2. Underload trip;

3. Low voltage trip;

4. Auxiliary circuit trip.

[Illustration: FIG. 2,264.--Diagram of General Electric low voltage

trip, with tripping switch _normally_ ~closed~.]

~Ques. What is the object of the overload trip?~

Ans. It is intended to open the circuit when the current exceeds a

predetermined value.

~Ques. What modifications are made in the mechanism shown in the

elementary diagrams?~

Ans. Sometimes a latch is used in place of the toggle and a magnet in

place of the solenoid as in figs. 2,265 and 2,266.

~Ques. Why is a magnet used in combination with a latch?~

Ans. Because with this arrangement very little movement is required to

trip the breaker, and for such conditions, a magnet is more efficient

than a solenoid.

[Illustration: FIGS. 2,265 and 2,266.--Circuit breaker with automatic

control mechanism consisting of ~magnet and latch~; views showing

breaker in open and closed positions, and essential features. The

toggle is used to obtain sufficient leverage to easily close switch

against the pressure of the brush contacts but not to lock switch,

this being done by the latch as shown, the latter closing by the

action of a spring, there being a roller R at the end which engages

the arm to reduce friction. ~In operation~, when the current exceeds

a predetermined limit the magnet attracts the latch and releases the

contact arm. The brush contacts which are exerting pressure against the

contact arm, rapidly push it away, and assisted by gravity, the arm

flies open to the position shown in fig. 2,266.]

~Ques. How does the latch arrangement work?~

Ans. When the proper current is reached, the magnet pulls open the

latch and the contact arm of the breaker moves by the force of gravity

or other means and opens the circuit.

~Ques. How does the underload trip operate?~

Ans. The same as the overload type except that they operate on a

diminution of current instead of an excess.

[Illustration: FIGS. 2,267 and 2,268.--Positions in circuit of

_current_ and _pressure_ coils of circuit breakers.]

~Ques. Describe the no voltage trip.~

Ans. The energy for the trip of this breaker is derived from a high

resistance or fine wire coil which is arranged to be placed directly

across the line, in operation, when the current flowing through the

circuit falls below a predetermined value, the energy of the coil is

insufficient to counteract the force of a spring, which then trips the

breaker.

[Illustration: FIG. 2,269.--Diagram of General Electric shunt trip

with coil connected beyond breaker and thrown out of circuit after

tripping.]

~Ques. Describe the auxiliary circuit trip.~

Ans. A pressure coil is used which is energized by current from an

auxiliary circuit. The coil is only _momentarily_ energized, by push

button, relay or other control, as distinguished from the preceding

types, in which the coil is _constantly_ energized.

[Illustration: FIG. 2,270.--Diagram of General Electric shunt trip with

auxiliary circuit opening switch to throw coil out of circuit after

tripping.]

[Illustration: FIG. 2,271.--General Electric shunt trip attachment.

The shunt trip attachment has been designed to provide for conditions

under which the low voltage attachment cannot be successfully applied.

It resembles the low voltage attachment in construction, but differs in

that it trips the circuit breaker when energized. The shunt trip should

be allowed to remain only momentarily in circuit; hence it should

be so connected that the opening of the circuit breaker immediately

disconnects it from the circuit. Whenever it is impossible to connect

the shunt trip in this manner, the circuit opening auxiliary switch

should be used in connection with it.]

[Illustration: FIG. 2,272.--General Electric low voltage attachment

for circuit breakers. This low voltage trip is designed to operate the

circuit breaker when the line voltage drops to approximately 50 per

cent or less of the normal voltage. It should be noted that the coil

is always in circuit, as is the case with the overload and underload

coils, and that it operates with the _releasing_ of its armature. It is

always necessary to use a fixed amount of resistance (depending upon

the voltage of the system) in series with the low voltage release.

The low voltage release performs the functions of a shunt trip coil

when used in conjunction with a push button, auxiliary switch or

speed limiting device, and is generally preferred to the shunt trip

attachment.]

[Illustration: FIG. 2,273.--General Electric ~circuit opening~

_auxiliary switch_. This switch opens an auxiliary circuit when the

circuit breaker opens, and is intended to be used in connection with

a shunt trip attachment to insure the immediate disconnection of the

shunt coil from the circuit. It may also be employed to serve other

purposes, such as tripping another circuit breaker having a low voltage

attachment, and permitting another circuit breaker to remain closed

only when the circuit breaker equipped with the auxiliary switch is

open.]

~Ques. What other name is given to the auxiliary circuit trip?~

Ans. It is sometimes called the shunt trip, though ill advisedly so.

[Illustration: FIG. 2,274.--General Electric ~circuit closing~

_auxiliary switch_. This switch closes when the circuit breaker opens,

and may be used to announce the automatic opening of the circuit

breaker through the means of an indicating lamp or an alarm bell. It

is often necessary to arrange one circuit breaker so that, in opening,

it will trip others. This may be accomplished by using a circuit

closing auxiliary switch in connection with a low voltage or shunt trip

attachment on the circuit breakers to be tripped. The construction of

this type of switch is such that it may be opened by hand after the

circuit breaker opens, but it is automatically reset when the circuit

breaker is closed.]

~Relays.~--Oil break switches and carbon break circuit breakers are

commonly used to open electrical circuits at some given overload and

on short circuit. To secure additional protection under a variety of

abnormal conditions or to provide for a certain predetermined operation

or sequence of operations, relays may be employed.

[Illustration: FIG. 2,275.--General Electric type C circuit breaker.

Specially adapted to motor driven machine tool applications. For use in

mills, machine shops, factories, foundries and office buildings. For

general motor work, automobile charging outfits, storage batteries,

rectifier sets, cranes, etc. List of parts: A, calibrating post; B,

laminated contact; C, secondary contact spring; D, contact blade; E,

cotter pin for G; F, toggle link; G, pin for D and F; H, stop for Aa;

I, hinge frame; J, operating lever; K, pin for I and J; L, toggle

link; M, connection; N, screw for M, O and P; O, nut for N and P;

P, terminal; Q, tripping coil; R, calibrating screw; S, laminated

contact; T, calibrating scale; U, calibrating spring; V, connection

post; W, knob; X, washer for Y; Y, handle; Z, buffer; Aa, armature; Ba,

laminated connection; Ca, connection; Da, base.]

A relay is defined as: _A device which_ ~opens~ _or_ ~closes~ _an_

~auxiliary circuit~ _under predetermined electrical conditions in the

main circuit_.

The object of a relay is generally to act as a sort of electrical

multiplier, that is to say, _it enables a comparatively weak current to

bring into operation a much stronger current_.

[Illustration: FIG. 2,276.--Diagram of connections of General Electric

shunt trip coil ~with~ and ~without~ circuit opening auxiliary switch.]

~Ques. For what service are relays largely used?~

Ans. They are employed in connection with high voltage switches

where the small amount of energy derived from an ordinary instrument

transformer is insufficient for tripping.

The connections between relays and circuit opening devices are

usually electrical. Combinations of this nature are extremely

flexible since they permit the use of a number of devices, each

having a different function, with a single circuit breaker or

oil switch as well as with two or more switches, to secure the

desired operation and protection.

~Selection.~--In all electrical installations protection of apparatus

is important, but in some large central stations this is secondary to

continuity of service.

To combine maximum protection without interruptions of service is

not always possible, but these requirements can be approximated very

closely by the use of reliable and simple controlling or protecting

devices if proper care be taken to select the relays suited to the

special conditions of the installation. To do this intelligently, a

knowledge of the various types of relay is necessary.

[Illustration: FIG. 3,073.--Diagram of connections of General Electric

low voltage release coil when used with speed limiting device on rotary

converter.]

There is a multiplicity of types and a classification to be

comprehensive, should, as in numerous other cases, be made from several

points of view. Accordingly relays may be classified:

1. With respect to the nature of the service performed, as

_a._ Protective;

_b._ Regulative;

_c._ Communicative.

2. With respect to the operating current, as

_a._ Alternating current;

_b._ Direct current.

3. With respect to the manner of performing their function, as

_a._ Circuit opening;

_b._ Circuit closing.

4. With respect to the operating current circuit, as

_a._ Primary;

_b._ Secondary.

5. With respect to the abnormal conditions which caused them to

operate, as

_a._ Overload;

_b._ Underload;

_c._ Over voltage;

_d._ Low voltage;

_e._ Reverse energy;

_f._ Reverse phase.

6. With respect to the time consumed in performing their function, as

_a._ Instantaneous (so called);

_b._ Definite time limit;

_c._ Inverse time limit.

7. With respect to the character of its action, as

_a._ Selective;

_b._ Differential.

8. With respect to whether it acts directly or indirectly on the

circuit breaker, as

_a._ Main;

_b._ Auxiliary.

[Illustration: FIG. 2,278.--General Electric overload and low voltage

type C circuit breaker for 600 volts or less. It has one overload, and

one low voltage coil as shown. Screens are provided between contacts.]

~Protective Relays.~--These are used to protect circuits from abnormal

conditions of voltage, or current, which would be undesirable or

dangerous to the circuit and apparatus contained therein.

~Ques. How do protective relays operate?~

Ans. They act in combination with automatic circuit breakers, operating

when their predetermined setting has been reached, energizing the trip

coil of the circuit breaker and opening the circuit.

Fig. 2,279 shows the principles of relay operation. When

the current or pressure in the main circuit reaches the

predetermined value at which the protective system should

operate, the relay magnet attracts the pivoted contact arm and

closes the auxiliary circuit; this permits current to flow from

the current source in that circuit and energize the trip coil

thus opening the main circuit.

[Illustration: FIG. 2,279.--Diagram illustrating the operation of a

~circuit closing relay~. When the predetermined abnormal condition is

reached in the main circuit, the relay closes the auxiliary circuit,

thus energizing the trip coil and opening the breaker.]

~Regulative Relays.~--This class of relay is used to control the

condition of a main circuit through control devices operated by a

secondary circuit.

~Ques. For what service are relays of this class employed?~

Ans. They are used as feeder circuit or generator regulators.

~Ques. How do they differ from protective relays?~

Ans. They have differentially arranged contacts, that is to say,

arranged for contact on either side of a central or normal position.

[Illustration: FIG. 2,280.--Diagram showing a railway synchronous

converter protected by a single pole overload circuit breaker with

low voltage release attachment and bell alarm switch. The low voltage

attachment trips the breaker on failure of direct current voltage also

when speed limit device closes. Internal troubles are taken care of by

the alternating current automatic devices (not shown).]

~Communicative Relays.~--These are used for signalling in a great

variety of ways for indicating the position of switching apparatus or

predetermining the condition of electric circuits.

~A. C. and D. C. Relays.~--As here used, the classification refers to

the kind of current used on the auxiliary circuit. In some cases direct

current is used to energize the trip gear of the circuit breaker or oil

switch, and in others, alternating current.

[Illustration: FIG. 2,281.--Diagram showing three phase motors

protected by triple pole overload circuit breakers, with two overload

coils, also one overload coil and low voltage release coil. The use

of the low voltage release allows the breaker to be tripped from a

distance by means of a short circuiting switch or push button.]

A. C. and D. C. relays are respectively known as _circuit opening_ and

_circuit closing_ relays, being later fully described.

~Circuit Opening Relays.~--The duty of a circuit opening relay is

_to open the_ ~auxiliary circuit~, _usually alternating current, nd

thereby cause the oil switch or circuit breaker to be opened by the use

of a trip coil in the secondary of a current transformer, or by low

voltage release coil_.

The trip coil of the breaker is generally shunted by the relay

contacts and when the moving contact of the relay disengages

from the stationary contact, the current from the transformer

which supplies the relay, flows through the trip coil thus

opening the breaker. These features of operation are shown in

fig. 2,282.

[Illustration: FIG. 2,282.--Diagram illustrating the operation of a

~circuit opening relay~. When the relay contacts are in the normal

closed position, as shown, the coil is short circuited. When the

predetermined abnormal condition is reached in the main circuit, the

relay contacts are opened with a quick break, sending the current

through the trip coil momentarily, and opening the breaker.]

~Ques. Where are circuit opening relays chiefly employed?~

Ans. In places where direct current is not available for energizing the

trip coil.

~Ques. What is the objection to alternating current trip coils?~

Ans. They have relatively high impedance and impose a heavy volt ampere

load on the transformers.

~Circuit Closing Relays.~--The duty of a circuit closing relay is to

close the auxiliary circuit at the time when the predetermined abnormal

condition is reached in the primary circuit. The closing of the

auxiliary circuit energizes the trip coil and opens the breaker.

[Illustration: FIGS. 2,283 to 2,291.--General Electric instantaneous

overload ~circuit opening~ relays, covers removed. Circuit opening

relays are used chiefly in those cases where direct current for the

tripping circuit is not available. Alternating current trip coils

have relatively high impedance and impose a heavy volt ampere load on

the current transformers. To reduce this load during normal operation

the circuit opening relay is frequently used and is usually necessary

where instruments and meters are to be operated on the same current

transformers as the trip coils if the greatest accuracy be required.

The relay contacts in the normal, closed position, short circuits

the trip coil. When the relay operates on overload or other abnormal

condition the contacts are opened with a quick break, sending the

current through the trip coil circuit momentarily and tripping the

switch. With circuit opening relays, the trip coils of the oil switch

must be set to trip somewhat lower than the setting of the relay. ~In

construction~ the relay consists of a solenoid with iron frame forming

the support for the relay; a central plunger or armature of special

construction which is picked up or released by the magnetic action of

the solenoid; a plunger rod which actuates the relay contacts, which

are mounted on an insulated base usually above the solenoid; a tube or

plate for the calibration marking and adjustment; covers of glass or

metal to keep out dust; terminal boards with points corresponding to

tagged leads from relay coils and external wiring diagrams. The relay

contacts are of two kinds, circuit opening, as shown above, and circuit

closing, as shown in figs. 2,292 to 2,300.]

~Ques. What kind of current is generally used for the auxiliary circuit

of a circuit closing relay?~

Ans. Direct current.

~Ques. At what pressure?~

Ans. From 125 to 250 volts.

~Ques. Where is this current usually obtained?~

Ans. From a storage battery, or from the exciter.

~Ques. For what current are the contacts ordinarily designed?~

Ans. About 10 amperes.

[Illustration: FIGS. 2,292 to 2,300.--General Electric alternating

current, instantaneous overload ~circuit closing~ relays, covers

removed. The function of a circuit closing relay is to close an

electrical circuit, usually direct current, through a trip coil on an

oil switch or circuit breaker, or it may short circuit a low voltage

release coil, and thereby open the oil switch or circuit breaker

on occurrence of the condition upon which the relay is designed to

operate. Direct current at 125 or 250 volts taken from exciter bus

bars or storage battery system is generally used for the tripping

circuit. Circuit closing contacts have a cone shaped central element

of carbon or metal which makes contact with flexible contact fingers

symmetrically arranged above the cone. These contacts will make and

break a circuit of 10 amperes at 125 volts without the use of auxiliary

circuit opening switches. Relays are made with two or three contacts

for connecting one side of a direct current circuit through one or

two separate circuits, or trip coils respectively, to the side of

opposite polarity. Usually only two contacts are required. Where two

or more trip coils are used, which may not be connected permanently in

parallel, the three contact relays are selected and in some cases four

contacts furnished.]

~Primary and Secondary Relays.~--Primary relays are sometimes called

series relays as they have the current coils connected directly in

series with the line, both on high and low tension circuits.

Secondary relays receive their current supply from the secondary

circuits of current transformers. Alternating current relays connected

to secondary of pressure transformers and relays with both current and

pressure windings are included in this class.

~Ques. What is the usual winding of the coils?~

Ans. The current coils are usually wound for 5 amperes and the pressure

coils for 110 volts.

[Illustration: FIG. 2,301.--Alternating current low voltage circuit

closing low voltage relay, for 600 volts or less. The contacts are

similar to those of the circuit closing overload type except that they

are inverted. As long as the pressure is normal the contact cone is

held above the contacts. When the pressure falls below one half normal,

the cone and plunger rod drop and close the contact. This relay does

not pick up its own plunger. The plunger rod is pushed up by hand after

the pressure circuit is established. Low voltage relays are generally

used in connection with a low voltage release or shunt trip coil on

an oil switch or a circuit breaker. They are used in connection with

motor booster sets to prevent a disastrous speed of the booster which

might result from the loss of alternating current power. They are also

sometimes used for indicating purposes.]

~Ques. What refinement is made in the design of relays and why?~

Ans. Care is exercised to reduce to a minimum the volt ampere load

imposed by the relay on the current transformer to permit the use of

un-stranded meters and relays upon the same transformer.

The use of circuit opening relays to cut out the trip coil of

an oil switch during normal operation, has been described,

and in the short time that the trip coil is in circuit, it

does not affect the accuracy of the instrument readings. This

practice, however, does not apply in the case of curve drawing

meters, voltage compensators or other devices which have in

themselves sufficient load for separate current transformers.

In this connection it should be noted that to obtain accurate

instrument and meter readings; the current transformers should

not be loaded beyond certain limits which depend upon the volt

ampere load and power factor of each of the connected devices.

[Illustration: FIG. 2,302.--Condit type K circuit breaker with shunt

trip and no voltage attachment. ~The shunt trip~ is usually applied

as an auxiliary to other types of trip. It consists of a fine wire

coil which is mounted as a self-contained part of the breaker and

which when energized, trips the circuit breaker. It is used to open

the breaker from some distant point, and the coil is arranged to be

connected across the line. The coils are so arranged that the circuit

breakers will operate on a voltage 25% above or 25% below normal. The

shunt trip coil is not intended to remain across the line and should

be only momentarily energized. ~The no voltage trip~, receives energy

from a high resistance or fine wire coil which is arranged to be placed

directly across the line, but in contradistinction to the shunt trip

type, in which the coil is momentarily energized to trip the breaker,

the no voltage coil is _constantly_ energized and a _decrease_ or

failure of pressure trips the breaker. It can be used as a remote

control device the same as the shunt trip. Its general use, however, is

to cause the circuit breaker to open when the voltage of the line fails

from any cause. Its use is recommended on all motor circuits, as it

affords an additional protection against accidents, for if the voltage

should fail, the breaker immediately opens, and before the machine can

start again the attendant must close the breaker. It will not work for

the protection of storage batteries or of motor generator sets charging

storage batteries, as, when the voltage of the generator fails, the

voltage of the battery still maintains its full value. The action of

the coil is independent of the direction of flow of current; it simply

allows the breaker to stay closed as long as the voltage is on the line

and opens the breaker when the voltage on the line ceases. No voltage

circuit breakers are normally so adjusted that they will not release

until the voltage approaches 50% of normal.]

So great is the variety of combination used and the variations of these

factors in their several combinations at different loads and settings,

that special consideration of each arrangement is advisable.

[Illustration: FIG. 2,303.--General Electric alternating current high

pressure series overload relays controlling 45,000 volt oil switches.

These relays are connected in series with the line. If current

transformers are to be used on the same circuit for other purposes, and

have sufficient capacity to supply energy for operating relay coils,

then secondary relays would be more economical, otherwise the series

relays are much less expensive. By means of a specially treated wooden

rod, the relay operates a tripping switch, closing a separate tripping

circuit, usually 125 or 250 volts direct current. Relays and switches

are for mounting on flat surfaces. Series relays are essentially the

same as secondary relays except in the coil winding and insulation.

The corrugated horizontal arms which carry the relays, as shown, are

insulated posts, insulating the relays from the ground. The wood rod

from each relay is connected directly to a tripping shaft on the oil

switch which buckles an auxiliary toggle, thereby opening the main

toggle and tripping the oil switch.]

~Overload Relays.~--Series relays are connected directly in series with

the line and are chiefly used with high pressure oil break switches

for overload protection. If current transformers are to be used on the

same circuits for other purposes, and have sufficient capacity to admit

of adding a relay coil, secondary relays would be more economical;

otherwise, the series relays are less expensive.

By means of a specially treated wooden rod, the relay operates a

tripping switch, closing a separate tripping circuit, usually 125 or

250 volts direct current. Series relays are essentially the same as

secondary relays except in the coil winding and insulation.

~Underload Relays.~--These are similar in construction to low voltage

relays but have current instead of pressure windings.

~Over Voltage Relays.~--These are usually of the circuit closing type

and are similar to secondary overload relays, but have pressure instead

of current windings.

~Low Voltage Relays.~--Relays of this class are in most cases used

[Illustration: FIG. 2,304.--Condit 600 volt, 1,500 ampere single pole

back connected type K circuit breaker, ~motor operated~. The mechanical

and electrical features of the circuit breakers are no different than

when hand operated, the only difference being that the motor is used

for the operating means. This motor is so arranged that even should it

over travel, due to an accident to the controlling circuit, it cannot

produce more than a predetermined strain on the circuit breaker. In

other words, after the motor has closed the circuit breaker, further

travel of the motor will not result in putting a strain on the

operating parts. Suitable motors are supplied for this service, the

type of motor varying in accordance with the character of the operating

current supplied. The advantage of this type of electrical operation

is that it puts very little strain on the switch mechanism, takes very

little operating current, allows the use of standard parts, and makes

an extremely substantial and flexible structure. Its disadvantage is

that it closes slowly, and it must not, therefore, be used in places

where quick closing is essential.] for the protection of motors in the

event of a temporary weakening or failure of the pressure. They are

also used in connection with a low voltage release or shunt trip coil

on an oil switch or a circuit breaker.

~Reverse Energy Relays.~--The chief object of this species of relay is

to protect the generator. When so used, the overload adjustment is set

at the maximum value to give overload protection only at the maximum

carrying capacity of the generator and a sensitive reverse protection

to prevent a return of energy from the line.

[Illustration: FIG. 2,305.--General Electric direct current solenoid

control relay. Solenoids for operating large switches, etc., frequently

require comparatively large operating currents in the "closing" coils.

This necessitates the use of relatively heavy leads between the control

switch and the solenoid and is the cause of severe arcing at the

control switch, especially with solenoids of high inductance. These

objectionable features can best be eliminated by the use of a suitable

control relay located near the solenoids. The control relay consists

of a solenoid plunger and switch, the latter insulated from the frame

of the relay. It operates satisfactorily on one-half the rated voltage

and requires only a very small operating current. The terminals of the

switch and the relay coils are independent. The relay can be wound for

operation on 125, 250, or 600 volt circuits.]

~Reverse Phase Relays.~--This type of relay is used chiefly to prevent

damage in case of reversal of leads in reconnecting wiring to two or

three phase motors.

~Time Element.~--It is often inconvenient that a circuit breaker should

be opened immediately on the occurrence of what may prove to be merely

a momentary overload, so that time lag attachments are frequently

provided, particularly with relays. These devices, which may form part

of the relay or may be quite distinct from it, retard its action until

the overload has lasted for a predetermined time--several seconds or

more.

[Illustration: FIG. 2,306.--Alternating current series reverse phase

single pole, circuit closing, two contact relay for 600 volts or less.

This type of relay is used chiefly to open motor circuits for elevators

to prevent damage in case of reversal of leads in reconnecting wiring

to two or three phase motors. The relay is provided with a dust proof

metal cover.]

~Ques. What should preferably govern the time lag?~

Ans. It should depend on the extent to which the overload is reduced as

the time elapses.

~Instantaneous Relays.~--The so called instantaneous relays operate

almost instantly on the occurrence of the abnormal condition that they

are to control.

There is of course a slight time element comparable with that

of an overload circuit breaker, but for practical purposes, the

operation may be considered as instantaneous.

[Illustration: FIG. 2,307.--Electric circuits of Condit type "A" relay.

The construction is described in fig. 2,309. As here shown, the relay

is not in operation, but should the current passing through the coil

be of sufficient value to cause the lower movable half of the magnetic

circuit to approach the upper stationary half of the circuit, _the

relay will be transformed from an ordinary_ ~electromagnet~ _into a_

~repulsion motor~. The contact will short circuit the brushes of the

armature and thus cause it to revolve, the speed of rotation being

dependent on the amount of current flowing to a predetermined point,

and thereafter the speed of rotation of the motor remains constant

irrespective of the current value. ~Time adjustment:~ This is obtained

by varying the distance through which the contact travels, provision

being made whereby adjustment can be made as close as .1 of a second.

Current adjustment: This is obtained by means of a calibrated spring.

Standard relays are calibrated at 6, 8, 10, and 12 amperes, the coils

being designed to carry five amperes continuously, with a temperature

rise not exceeding 86° Fahr. ~Power to operate relay:~ The relay

requires twenty volt amperes for its operation at full load; the

influence of this type of relay on the ratio and phase angle of current

transformers is small.]

~Time Limit Relays.~--Under this classification there are two

sub-divisions.

1. Definite time limit;

2. Inverse time limit.

[Illustration: FIG. 2,308.--Characteristic curves of Condit type A

selective relay. Curves 1, 2, 3, and 4 show the time variation of

this relay with different settings at the various current values. The

relay may be adjusted to trip the switch at any point represented

between curves 1 and 4. This relay is a combination of an _inverse time

limit_ relay and a _definite time limit_ relay. The combination of the

characteristics of the two types are seen in the curve, the first part

of which is ~inverse~, and the latter part ~definite~ from a point of

three or four times full load current. This combination of features

being desirable as, for instance, in transmission work, particularly

where it is necessary to use circuit breakers set selectively, as, due

to the inverse feature of the curve, the relays can be set so that on

a moderate overload, they will require the proper length of time to

operate, and at the same time will operate quickly enough on heavy

short circuits to prevent damage to the distribution system or its

apparatus. Due to the definite feature of the latter part of the curve,

the relays of the varying circuit breakers when once set to operate at

different time values will never operate simultaneously irrespective of

the value of the short circuit current, thus tending toward continuity

of service.]

~Ques. Describe the time mechanism of a definite time limit relay.~

Ans. It consists of an air dash pot, and an air diaphragm or equivalent

retarding device connected to the contact mechanism.

~Ques. How does it operate?~

Ans. In some designs, when the contacts are released, they descend

by gravity against the action of the retarding device thereby making

contact a definite interval after the occurrence of the abnormal

condition.

[Illustration: FIG. 2,309.--Condit type "A" ~selective relay~, designed

for use with circuit breakers where selective or discriminating

action is required. The circuits and connections of this relay are

illustrated in fig. 2,307, and its characteristics in fig. 2,308. ~In

construction~, the relay consists of _a special motor with a short

circuited armature and a split field_. ~Under normal conditions~, the

fields are separated from each other and the motor armature does not

revolve. The force tending to pull the two faces of the field together

is opposed by a spring, the compression of which determines the number

of amperes necessary to cause the relay to begin operation. The motor

structure performs the whole work and the motor itself un-meshes and

meshes the gears without the aid of any external device.]

~Ques. How does the inverse time limit type operate?~

Ans. The actuating and contact mechanism is attached directly to an

air bellows and in operation tends to compress the bellows against the

action of a specially constructed escape valve in the latter.

[Illustration: FIG. 2,310.--Condit type "B" ~time limit attachment~,

designed to give sufficient time to allow an induction motor to start

without opening the circuit breaker, and not have the circuit breaker

trip on the momentary rush of current. ~Its action is inverse~; that

is, _the greater the current the less time it takes to operate_ and

is so arranged that four to five times full load current or a short

circuit will trip the circuit breaker instantly. The time limit

attachment is applied directly to the armature which trips the circuit

breaker and is adapted for the so called primary trip. It consists

of an air vacuum dash pot with a graphite piston, the dash pot being

fastened to the stationary calibrating ring of the trip coil and the

moving outside cylinder is fastened to the armature of the circuit

breaker. When the current reaches a point where it overcomes the weight

of the armature and lifts the same, the magnetic force tending to raise

the armature is opposed by the vacuum created in the interior of the

cylinder. As the magnetic force continues the vacuum is overcome due to

the leakage of air past the plunger and the armature gradually moves up

until it reaches the point where it trips the circuit breaker. If at

any point of the armature travel, the current drop back to normal, the

armature immediately resets itself by means of a ball valve in the top

of the brass cylinder.]

~Ques. Why is the arrangement called _inverse_ time limit?~

Ans. Because the retardation varies inversely with the pressure on the

bellows, and therefore inversely with the magnitude of the abnormal

condition.

~Ques. What other device may be used to retard the operation?~

Ans. A damping magnet is sometimes used which acts on a disc or drum

and which may be adjustable.

[Illustration: FIGS. 2,311 and 2,312.--General Electric alternating

current ~low pressure~ series overload relays. Fig. 2,311,

instantaneous time limit relay; fig. 2,312, inverse time limit relay.

These relays have carbon contacts and will make or break a direct

current circuit of 10 amperes at 125 volts without auxiliary circuit

opening switch. They are used where several circuits are controlled

by one automatic oil break switch or one shunt trip, overload and

shunt trip or low voltage release carbon break circuit breaker. These

relays may be used for signal purposes; they are back connected, the

connections can be seen in the illustrations.]

~Ques. How is the inverse time element introduced by this arrangement?~

Ans. The retardation is due to eddy currents induced by moving the disc

or drum through the magnetic field. The reaction thus induced varies

inversely with the magnitude of the force with which the disc or

drum is urged through the field and hence inversely with the abnormal

condition.

~Ques. What are the ordinary limits of adjustment for inverse time

limit relays?~

Ans. From one-half second to 30 seconds, depending upon the time

setting and magnitude of the overload current.

[Illustration: FIGS. 2,313 to 2,321.--General Electric time limit

overload circuit opening relays with covers removed. The construction

of this relay is similar to that of the inverse time limit relay,

except that it has a compression spring interposed between the plunger

and diaphragm. The plunger compresses the spring and further motion

is prevented by a stop, making the relay practically independent of

the amount of the overload, only the stored energy of the spring, if

the overload continue, applies power, dependent on its own mechanical

strength, to the diaphragm. The time limit therefore becomes

practically a constant for any given setting under ordinary conditions

of overload or short circuit. If, however, the overload come on slowly

so that the spring is not fully compressed at once, the time limit will

vary slightly. If the scheme of selective operation make it necessary

to take care of a creeping load of this character, two relays may

be used and definite time limit positively secured. In this case,

an instantaneous circuit closing, overload relay would be used and

a definite time limit relay, provided with a direct current coil in

circuit with the closing contacts of the first relay. The time limit

relay would be of the circuit closing type and control a direct current

trip coil on the oil switch.]

A setting of from two to six seconds is ordinarily used,

depending upon the requirements. Where selective operation is

desired a minimum setting of two seconds is recommended.

~Differential Relays.~--In this type of relay there are two

electromagnets. In normal working these oppose and neutralize each

other. Should, however, either winding become stronger or weaker than

the other, the balance is upset, the magnet energized, and the relay

comes into operation.

[Illustration: FIG. 2,322.--Differential relay transformer and reverse

current circuit breaker discriminating device. A differential relay is

_one whose electromagnet has two windings_. ~In normal working~ _these

oppose and neutralize one another_. Should however, either winding

become stronger or weaker than the other, the balance is upset, the

magnet is energized, and the relay comes into operation. A modification

of such a relay for alternating current is here shown, from which it

will be seen that when the currents are as indicated, the circuit A has

the larger pressure induced in it, whereas, should the main current

reverse with reference to the shunt current, the circuit B would have

the larger induced pressure.]

A modification of such a relay for alternating current is shown in

fig. 2,322, from which it will be seen that when the currents are

as indicated, the circuit A has the larger pressure induced in it,

whereas, should the main current reverse with reference to the shunt

current, the circuit B would have the larger induced pressure.

[Illustration: FIG. 2,323.--Diagram of modern power house wiring and

busses showing location of relays.]

~[1]How to Select Relays.~--The following general information on

relays, together with reference to the one line diagram, fig. 2,323,

will be of interest and assistance in making a selection from the

various relays previously described to meet the requirements of modern

power house and sub-station layouts.

[1] NOTE.--As suggested by the General Electric Co.

~Single pole relays~ are used on single phase and on balanced

three phase circuits.

~Double pole relays~ are used on ungrounded three phase and on

quarter phase.

[Illustration: FIG. 2,324 to 2,329.--General Electric inverse time

limit overload circuit closing relays. In this type of relay its

mechanism is so designed that a delay or lapse of time in opening the

circuit breaker after a predetermined condition of the circuit has

been reached, depends on the flow of current, that is, if the current

be great, the time will be small, and if the current be of a moderate

value, the time will be correspondingly longer.]

~Triple pole relays~ are used on three phase grounded neutral

and interconnected quarter-phase.

~Circuit closing relays~ are recommended in all cases where a

constant source of direct current is available for operating

trip coils.

The conditions for which relays have been designed for power

circuits may perhaps be best described, by considering a

one line diagram from the generator end to the sub-station

auxiliary machines and feeders.

Considering first alternating current circuits, the

prevailing practice is to make the circuit breakers by

which the alternators are connected to the low tension bus

_non-automatic_, in order to insure minimum interruption of

alternator service. The chance of trouble in this part of the

circuit is remote, but should it occur, the station attendant

could generally open the circuit breaker before the machines

would be injured.

~Reverse current relays~ of instantaneous or time limit types

are often connected to the secondaries of current and of

pressure transformers to indicate by lamp or bell any trouble

that may occur in the generator circuit.

These relays operate with a low current reversal at full

pressure and conversely with a proportionally greater current

at voltages less than normal. At zero pressure, the relay would

act as an overload one, set for high overload. At zero current,

a voltage considerably in excess of normal would be required to

operate it.

[Illustration: FIG. 2,330.--Diagram showing two phase motor or feeder

circuit protected by double pole double coil, overload circuit breaker

(or two single pole breakers interlocked) with bell alarm switch.]

Specifications sometimes call for automatic generator circuit breakers:

in this case _definite time limit overload relays_ are used. They are

connected in the secondaries of current transformers and are designed

to give the same time delay for all trouble conditions; they allow the

defective circuit to be opened, if possible, at a point more remote

from the generator than the generator circuit breaker.

When the total generator capacity exceeds the rated rupturing capacity

of the circuit breakers, one or more sectionalizing circuit breakers

are placed in each bus.

If operating conditions admit, these devices are made

non-automatic and are left disconnected except in case of

emergency; but if it be necessary for them to be continually in

service, they may be made automatic by _means of instantaneous

overload relays_ connected to current transformers in the low

voltage bus; the relays being adjusted to trip the circuit

breaker under short circuit conditions, confining the trouble

to one section and preventing the circuit breakers rupturing

more than their rated capacity.

Installations with but _one bank of power transformers_, and without

high voltage bus, are provided with automatic circuit breakers operated

by an _inverse time limit relay_.

The relay is connected to the secondaries of current

transformers, which in turn are connected in the low voltage

side of the power transformer.

Stations with _more than one bank of power transformers_, a

high voltage bus, and high and low voltage circuit breakers,

may have both circuit breakers arranged to trip at the same

time or one after the other. As in the former case, they are

operated from the inverse time limit relay connected in the low

voltage side.

[Illustration: FIG. 2,331.--Condit 600 volt, 1,500 ampere, single pole

type K circuit breaker ~pneumatically operated~. It is the same as the

electrically operated circuit breaker, except that a pneumatic cylinder

mechanism is supplied in place of either the electromagnet or the

motor. This cylinder mechanism is so arranged that the air pressure is

only on the cylinder at the instant of operation. At all other times

the air pressure is shut off by means of a control valve. The kind of

remote control to be used depends on local conditions. In general, the

hand operated remote control device is preferable where conditions are

such that it can be used, and where it is necessary to use electrically

operated, the motor operated type is recommended if conditions be such

that slow closing is not objectionable.]

[Illustration: FIGS. 2,332 and 2,333.--Diagram showing two phase

four wire no voltage connections for I-T-E circuit breaker. The two

no voltage coils for two phase four wire circuits are connected

respectively to binding posts B, C and A, D on the face of the base. B

and D are connected to lower spring contacts 2 and 1 respectively, of

the small disconnecting switch. (In instruments supplied on individual

bases, these connections are made in the factory, let into channels

in back of base and covered with wax.) Each of the upper contacts _a_

and _b_ of the disconnecting switch is connected respectively through

resistance R2 and R1 to one main in each phase at _aa_ and _bb_. C

and A are respectively connected to the other main in each phase at

3 and 4. Thus each of the no voltage coils operates across one phase

independent of the other. The terminals 3, _aa_, _bb_ and 4, must,

in all cases, be so connected that they will be subject to the full

voltage of the circuit, irrespective of the position of the starting

switch.]

[Illustration: FIGS. 2,334 and 2,335.--Diagram showing two phase

three wire no voltage connections for I-T-E circuit breaker. The two

no voltage coils for two phase, three wire circuits are connected

respectively to binding posts B, C and A D on the face of the base,

and from A and C connections are made to lower contacts 2 and 1

respectively of the disconnecting switch. Binding posts B and D are

connected together on the back of the board. (In instruments supplied

on individual bases, these connections are made in the factory, let

into channels in back of base and covered with wax.) Each of the upper

contacts _a_ and _b_ is connected respectively through resistance R2

and R1 to one of the mains at _aa_ and _bb_ as shown. D is connected

through resistance R3 to the common wire of both phases at 3 B and D

being connected as aforesaid, thus forming a common connection for

both no voltage coils. Terminals _aa_ and _bb_ of the resistances must

be connected to the outside main across the two phases, terminal 3 to

the main common to both phases, the connections being so made that

these terminals will be subject to the full voltage of the circuit

irrespective of the position of the starting switch.]

[Illustration: FIG. 2,336 and 2,337.--Diagram showing three phase no

voltage connections for I-T-E circuit breaker. The no voltage coils

for three phase circuits are connected in Δ by means of binding posts

A, B, C and D on the face of the base, and from the A and B of the no

voltage coils, connections are made respectively to spring contacts

1 and 2 of the small disconnecting switch. Each of the contacts

_a_ and _b_ of the disconnecting switch is connected respectively

through resistance R2 and R1 to one of the mains at _aa_ and _bb_.

The terminal C is connected through resistance R3 on the back of

the board to the middle main as shown at point 3. The terminal D is

linked on the back of the board to terminal B to complete the [Greek:

D] connection. The terminals _aa_, _bb_ and 3 of the circuit breaker

must, in all cases, be so connected that they will be _subject to full

voltage of the circuit_ irrespective of the position of the starting

switch. Each no voltage coil is supplied with two terminal wires, one

covered with green and one with black insulation. In replacing these

coils particular care should be taken to see that the terminal wires

connected to any one binding post are of unlike color.]

In plants in which two or more banks of transformers are operated in

parallel between high and low voltage busses, it is desirable to have

for each transformer bank, an automatic circuit breaker equipment which

will act selectively and disconnect only the bank in which trouble

may occur. With a circuit breaker on each side of transformer bank,

selective action may be secured in two ways as follows:

1. By means of an instantaneous differential relay connected in the

secondaries of current transformers installed on both the high and low

voltage sides of each transformer bank.

The relay operates on a low current, reversal on either side of

the bank.

2. By means of one inverse time limit, secondary or series relay

installed on that side of the transformer bank which is opposite the

source of power, the relay being arranged to trip both the high and low

voltage circuit breakers.

_The first method_ has the disadvantage of high first cost

due to the high voltage current transformers required, but is

more positive than the second method and is independent of the

number of transformer banks in parallel.

_The second method_ is the less expensive of the two and

protects against overloads as well as short circuits in the

transformers, but it is less positive and introduces delay

in the disconnection of the transformer when trouble occurs.

Furthermore, it is not selective when less than three banks are

operating in parallel.

The automatic circuit breakers in the outgoing line may be operated

from inverse time limit relays connected in the secondaries of current

transformers; or in case transformers are not necessary for use with

instruments, series high voltage inverse time limit relays connected

directly in the line may be used.

Whether to select current transformers with relays insulated for low

voltage, or to choose series relays, is a question of first cost and

adaptability to service conditions. Below 33,000 volts, the commercial

advantages in favor of the series relay are slight, and since it

is somewhat difficult to design this device for the large current

capacities met with at the lower voltage, it is generally the practice

to use the relay with current transformer, because of its operating

advantage. This practice, however, is not entirely followed, since some

service conditions (described later) make the use of series relays very

desirable and practical.

[Illustration: FIGS. 2,338 and 2,339.--General Electric instantaneous

direct current reverse current or ~"discriminating" relays~. Fig.

2,238, for 500 amperes; fig. 2,339 for 2,000 amperes. These relays are

designed for mounting directly on circuit breaker studs. ~These relays

consist~ _of a horseshoe magnet with a shunt wound armature pivoted

between its poles_. ~The magnet~ is mounted on the current carrying

stud of the circuit breaker between the back of the panel and the

first contact or supporting nut, and is placed in a vertical position.

~The contacts~ are insulated from the magnet permitting the use of an

auxiliary circuit for the tripping device, independent of the circuit

controlled by the circuit breaker. The magnet is excited by the current

flowing through the stud, and the armature is connected across the

line in series with suitable resistance. Rotation of the armature in

the normal direction is prevented by a stop. ~Reversal of the current~

flowing through the stud _changes the direction in which the armature

tends to rotate_, causing it to move away from the stop and close the

circuit through an auxiliary trip coil and trip the circuit breaker.

~These relays are used~ to protect dynamos, storage batteries, or main

station busses from damage on reversal of current due to short circuit,

or from the grounding of machines or connection. Relay contacts must

not be used to open the shunt trip coil circuits. An auxiliary switch

should be provided for this purpose in all cases where the opening of

the circuit breaker does not disconnect the trip coil from the source

of supply.]

_Inverse time limit_ relays are satisfactory for one, or more than two

outgoing lines in parallel as they act selectively to disconnect the

defective line only, but installations with only two outgoing lines

in parallel have the same load conditions in both lines and selective

tripping of the circuit breakers in the defective line is obtained by

means of a selective relay acting instantaneously under short circuit

conditions only.

[Illustration: FIG. 2,340.--General Electric ~direct current, reverse

current relay,~ _used to protect dynamos, storage batteries, or main

station busses from damage on reversal of current due to short circuits

or from the grounding of machine or connections._ It is mounted on

vertical bus bars as in the case of cables, on the side wall, or other

flat surface, and the cables threaded through the frame. ~When used

to trip a circuit breaker,~ the breaker is provided with a shunt trip

connected across the circuit, the tripping circuit being closed through

the relay contacts on the occurrence of sufficient reverse current to

lift the relay armature. The relay is either instantaneous or time

limit as desired. ~In the time limit relay,~ the time interval is

obtained by the leather bellows shown in the illustration. The time

setting can be varied within certain limits by means of a valve on the

bellows outlet. ~The operation of the relay~ _depends on the relative

value and direction of magnetic flux set up by a pressure coil, shown

in the illustration, and the current in the vertical bars._ Under

normal conditions these fluxes are in the same direction and circulate

around a closed magnetic circuit. ~When the current in the bars

reverses,~ _the two fluxes oppose each other and force flux through

the normally open leg of the magnetic circuit._ When the reversal of

current is of predetermined value, the relay armature is lifted and the

purpose of the relay accomplished.]

The relay design and action is similar to the reverse current

relay previously mentioned, and is connected to the secondaries

of current transformers in each high voltage line and pressure

transformers in the low voltage bus.

In the sub-station, the conditions are the reverse of those in

the main station, the incoming lines becoming the source of

power.

If there be only one incoming line and no high voltage bus,

the line circuit breaker is generally non-automatic. With

one incoming line and high voltage bus, the circuits from the

service side of the bus are equipped with automatic circuit

breakers and relays. These relays and those used for other

arrangements of two or more incoming lines in parallel, as

well as high and low voltage circuit breakers, are of the same

design and are applied in the same manner as for the generating

station.

Regarding the relay equipments for auxiliary machines, the same

practice is recommended with the generator end of alternating

current motor generator sets as with the main generators, the

outgoing feeder circuit breakers being tripped from inverse

time limit or instantaneous relays.

[Illustration: FIG. 2,341.--General Electric ~direct current

differential relay~ for balancer set; instantaneous, 500 (or less) volt

type for mounting on panel. In many power plants direct current, three

wire, power service is furnished by "high voltage" two wire dynamos

operating in connection with balancer sets consisting of two "low

voltage" machines on a common shaft. With this combination of machine,

a short circuit or heavy overload on one side of the system will shift

the neutral considerably, and the lamps on the opposite side may "burn

out". To protect the lamps, a differential relay operating on 15 volts

unbalancing, is commonly used; it is connected to trip either the

dynamo's circuit breakers (or a circuit breaker connected in the bus

between the balancer set and the other dynamos).]

With several synchronous machines in parallel, the relays

are arranged to operate with the least time delay with which

it is possible to get selective action, in order to prevent

the machines being thrown out of step in event of trouble

conditions causing a decrease of voltage.

The various types of _induction motor_ and various conditions

under which they are employed, have brought about the

development of several types of relay to protect the motors and

the apparatus with which they are used.

It is desirable to disconnect a _large motor_ in case of voltage

failure, and with conditions requiring either a motor operated, or

a solenoid operated circuit breaker, a _low voltage relay_ is used

to close the tripping circuit whenever the voltage decreases to,

approximately, 50 per cent. below normal.

[Illustration: FIG. 2,342.--Condit ~time limit relay~, designed

primarily for use in connection with feeder circuits, where close

selection or discrimination of circuit breakers is not required.

~It may be used~ satisfactorily on lighting and power circuits and

also where there are sudden, momentary fluctuations of current. This

relay is used in connection with series transformers. The contact

arrangements are provided so that the relays may be used as circuit

closing or circuit opening relays. ~The delayed action~ is produced

by an air vacuum dash pot with a graphite piston. The piston of the

dash pot is connected to an arm arranged to be moved by the armature.

When the current reaches a point where it overcomes the weight of the

armature and lifts the same, the magnetic force tending to lift the

armature is opposed by the pull of the vacuum created in the interior

of the shell into which fits the graphite piston. As the magnetic pull

continues the vacuum is overcome due to the leakage of air past the

piston, and the armature gradually moves until it reaches a point where

it causes the circuit breaker to trip, either by closing the contacts

in the circuit closing type, or by opening the contacts in the circuit

opening type. If, at any portion of its travel, the current drop to

normal, the armature immediately resets. ~The time adjustment~ consists

of an arrangement whereby the distance through which the armature moves

before tripping the breaker, may be changed, thus altering the time of

tripping. ~The current adjustment~ is made _by changing the effective

turns of the actuating coil_, the travel of the armature and the force

exerted by it being the same for all current adjustment. The winding is

designed to carry 5 amperes continuously with a temperature rise not

exceeding 68° Fahr. standard calibration is provided so that the relay

will start to operate at 5, 6, 8 and 12 amperes.]

Up to 550 volts, these relays may be connected across the line,

but for higher voltages they are connected to secondaries

of pressure transformers. _Smaller motors_ with which hand

operated circuit breakers are used, are generally provided with

low voltage release attachments that perform the same function

as the relay.

Induction motors are sometimes subjected to _high voltage conditions_

and to protect them from injury, high or excess voltage relays are

employed to trip the automatic circuit breaker. These relays are of

similar design and wired in the same manner as the low voltage relays.

[Illustration: FIG. 2,343.--Characteristic curves of Condit time limit

relay as illustrated in fig. 2,342. Settings: curve A, 5 amperes; curve

B, 6 amperes; curve C, 8 amperes; curve D, 12 amperes.]

_Reverse phase relays_ have been developed for operating conditions

under which a _reversal of phase_ would cause trouble, as for example,

in the case of _elevator motors_.

These are so designed that any phase reversal that would

reverse an induction motor, would operate the relay and

disconnect the automatic circuit breaker.

The design is based on the principle of the induction motor,

and in the case of low voltage motors of limited capacity,

the relay may be connected in series in the motor leads. If

the voltage or capacity of the motor make this arrangement

inexpedient, the relay may be placed in the secondaries of

current or pressure transformers connected in the motor leads.

_Underload relays_ are often used to trip the automatic circuit breaker

that is placed in the primaries of _arc lighting circuits_ to prevent

an abnormal rise of secondary voltage in case of a break in the

secondary circuit.

[Illustration: FIG. 2,344.--Diagram showing _storage battery and

charging dynamo protected by_ ~double pole single coil underload

circuit breaker. In operation,~ _the circuit breaker disconnects the

battery when fully charged, and protects the dynamo from reverse

current_.]

The underload relay is similar in design to the low voltage

relay excepting that it acts on a decrease of current.

The problem of _protecting induction motors_, from injury, that may

result from running on single phase, or from an overload, and at the

same time permit the motor to be started with the necessarily high

starting current that may be greatly in excess of the overload current,

has caused the development of the _series relay_.

[Illustration: FIG. 2,345.--Diagram showing direct current motors

protected by overload circuit breakers with bell alarm switches: _a_,

double pole single coil breaker no switch required. Low voltage device

is on the starting rheostat; _b_, single pole breaker in series with

lever switch. Low voltage attachment on the breaker.]

[Illustration: FIG. 2,346.--Diagram showing two wire dynamo, protected

by a single pole overload circuit breaker with bell alarm switch.

Breakers must be on opposite side from the series field.]

[Illustration: FIG. 2,347.--Diagram showing dynamo protected by a

single pole overload circuit breaker with reverse current relay and

combined circuit opening and bell alarm switch.]

This device may be connected in series with the motor leads for

voltages up to 2,500; it is designed with an inverse time limit

device which may be adjusted to give the desired protection.

The field for relays is more extensive for alternating current than

for direct current power circuits, the latter being generally confined

to much smaller and simpler systems and areas of distribution, and

generally sufficient selective action can be obtained by the use of

fuses or circuit breakers arranged with instantaneous trip.

[Illustration: FIG. 2,348.--Diagram showing three wire dynamo protected

by double pole double coil overload circuit breaker (or two single pole

breakers with interlock) with bell alarm switches. Complete protection

is secured as breaker is connected between armature and series field.]

Operating conditions sometimes make it advisable for the generator

circuit breakers to open only after the auxiliary and feeder circuit

breakers have failed to isolate the trouble.

This is accomplished by using direct current _series inverse

time limit relays_ to trip the generator circuit breakers.

_Instantaneous reverse current relays_ are used to trip the machine

circuit breaker of battery charging sets, rotaries and motor generator

sets to prevent their running as a motor on the charging or direct

current end. These relays can act only in case of current reversal.

To prevent serious unbalancing of voltages in Edison three-wire systems

causing trouble, _differential balance relays_ are used to trip the

circuit breakers on a small percentage of unbalancing.

Hawkins Electrical Guide v. 07 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 4 / 8 章