CHAPTER LVII

SWITCHING DEVICES

A switch is _a piece of apparatus for making, breaking, or changing the

connections in an electric circuit_.

The particular form and construction of any switch is governed by the

electrical conditions under which it must operate.

_Since the electric current cannot be_ ~stopped instantly~ _when the

circuit in which it is flowing, is broken_, ~an arc is formed~ _as the

switch contacts separate_; this tends to burn the contacts, and to

short circuit, the severity of such action depending on the voltage and

the proximity of the switch terminals. Accordingly in switch design,

provision must be made to counteract these tendencies. Thus,

1. The contacts should separate along their entire length, rather than

at a point;

2. The terminals should be far enough apart and properly protected to

prevent short circuiting of the arcs;

3. The break should be quick;

4. The gap should be surrounded by the proper medium (air or oil) to

meet the requirements of the electrical conditions.

A great variety of switches have been introduced to suit the different

requirements. Knife switches are used for low pressure service, the

multiple break form being used where it is desired to reduce the arcing

distance.

~Ques. How should single throw switches be installed?~

Ans. They should open downward so gravity will keep them open.

[Illustration: FIGS. 2,199 and 2,200.--General Electric triple pole

solenoid operated, single throw remote control switch, and push button

switch for operating same. Switch is a self-contained unit with two

sets of contacts, main laminated copper brushes, and carbon auxiliary

contacts to take the arc on breaking the circuit. The main brushes are

so made that each lamination makes an end on contact with the switch

blade without any tendency to force the laminations apart. A wiping

effect, given to the contacts every time the switch is closed, keeps

the contact surfaces clean and insures good contact at all times.

The carbon auxiliary contacts are made of blocks of carbon fastened

without screws. ~In operation~, the switch is actuated by a double coil

solenoid, one coil for closing and one for opening, controlled by the

single pole double throw push button switch shown in fig. 2,200, which

is normally in the open position and remains closed only when held by

the operator. One of these switches is furnished with each control

switch and must always be used, as the solenoid coils are not intended

for continuous service. The power required to operate the remote

control switch is small, being approximately 1.6 amperes at 110 volts,

0.81 amperes at 220 volts direct current, and 10 amperes at 110 volts,

and 6 amperes at 220 volts alternating current 60 cycles. The main

switch can be closed and opened by hand, and the push button located at

any point.]

~Ques. How should double throw switches be installed?~

Ans. Horizontally.

[Illustration: FIGS. 2,201 and 2,202.--Palmer service switch and

fuse box, for either plug, cartridge or open link fuses. Fig. 2,201

illustrates the box in open position for the inspection of fuses, etc.

The cover is held open by a simple lock so that the switch cannot

fall closed by gravity, the box may be mounted so that the service

wires lead directly into a sealed terminal chamber from any direction,

and all current carrying parts made accessible by the opening of the

switch are dead. Fig. 2,202 illustrates the device with side of box

and cover cut away to show interior and the normally sealed cover

of terminal chamber removed. The switch contacts do not enter their

contact clips until the flanged cover of the box has closed the switch

opening, no current connections being made to line or load until the

box is completely closed, and in consequence there is no opportunity

to make improper connections to any live parts of switch, when conduit

connections are used to the service and meter wires.]

~Ques. What is a plug switch?~

Ans. A switch in which the current is ruptured in a tube enclosed at

one end, thereby confining the arc and limiting the supply of air.

They are used on high pressure circuits of from 10,000 to

20,000 volts, for transferring live circuits and for voltmeter

and synchronizing circuits where there is very little energy.

The usual current capacity is from 4 to 7½ amperes.

[Illustration: FIG. 2,203 and 2,204.--~Bus transfer plug switch.~ The

method of supporting the contact farthest from the panel consists

of a porcelain pillar of the same height as the receptacle, clamped

to a brass connecting or bus bar which in turn is fastened to the

receptacle.]

[Illustration: FIG. 2,205.--~Ammeter jack.~ This plug switch is

insulated for high pressure and ~consists of two parts~: _the ammeter

jack, and the ammeter jack plug, cable, and bushing_. The receptacle,

which is simple in construction, consists of a brass bushing well

insulated from the panel and protected on the front of the panel by a

porcelain bushing. ~On the end of this tube~ and insulated from it,

is a phosphor bronze spring which, when the plug is out, rests on the

brass tube and keeps the circuit closed. ~The plug~ consists of a

brass rod well insulated and set in a brass tube, both being fastened

in a handle which is stained black and polished. Inside the handle

is run a twin conductor cable, one side being soldered in the brass

tube and the other to the brass rod. The other end of the cable is run

through a bushing set in the panel and thence to the ammeter or current

transformer. Where it is desired to remove the plug and cable from the

board, or to plug both ends of the cable in different receptacles, a

plug instead of a bushing should be used. In this case a cable should

be provided with a plug on each end.]

~Forms of Break.~--On high pressure circuits there are several types of

switch: they are classified with respect to the break, that is to say,

according as the break takes place,

1. In open air;

2. In an enclosed air space;

3. Aided by a metal fuse;

4. Aided by a horn;

5. In oil.

[Illustration: FIG. 2,206.--Westinghouse fused starting switch for

squirrel cage motors. It is arranged for National Electric Code fuses

on one end only and has springs on the other end to open the switch

automatically if left closed at this end. The corresponding terminals

at both ends of the switch are connected in grooves in the back of the

slate base so that the wiring need be connected to one set of these

terminals only, thus decreasing the number of connections necessary,

as shown in fig. 2,207. In starting an induction motor, the switch is

thrown to the end that is not fused and held there until the motor is

up to running speed; then it is quickly thrown to the fused position,

thus protecting the circuit under running conditions.]

[Illustration: FIG. 2,207.--Diagram of connections of Westinghouse

fused starting switch for squirrel cage motors. The starting current of

induction motors is several times the normal running current and, when

the controlling switch is fused to carry the running load only, the

fuses are apt to blow when the motor is started. The fuses must be of a

capacity to prevent overloads under running conditions. These switches

are designed to meet this difficulty and are used without auto-starters

to control motors up to 5 horse power rating.]

~Ques. What is the objection to open air break?~

Ans. The relatively long gap required to extinguish the arc, limiting

this form of switch to low or moderate pressure circuits.

The open air arc may cause very high voltage oscillations when

the circuit contains inductance and capacity unless the break

occur at zero value.

[Illustration: FIG. 2,208.--Westinghouse single pole disconnecting

switch. Disconnecting switches are used primarily for isolating

apparatus from the circuit for purposes of inspection and repair; also

for sectionalizing feeders. They are not designed for opening under

load, and therefore no attempt should be made to open them with current

in the circuit. In connection with lightning arrester installations,

disconnecting switches are particularly useful, providing a simple

and effective means for isolating the arresters while cleaning and

inspecting. The switch is opened and closed with a hook on the end of a

wooden pole, which hook engages in a hole provided in the switch blade.

This type of disconnecting switch is intended for wall mounting. The

live parts are mounted on porcelain insulators carried on a cast iron

yoke or base, forming a simple and substantial construction.]

~Ques. What are disconnecting switches?~

Ans. Knife switches in series with other switches so that the apparatus

controlled by the latter may be repaired in safety by entirely

disconnecting it from the bus bars or live circuit.

Such switches are not intended to rupture the load current.

[Illustration: FIGS. 2,209 and 2,210.--Westinghouse disconnecting

switches for pressures over 3,300 volts.]

[Illustration: FIGS. 2,211 and 2,212.--Westinghouse selector type

disconnecting switch. Fig. 2,211, view showing both sides closed; fig.

2,212, view with one side open. The selector type of disconnecting

switch is a transfer switch which does not require the circuit to be

interrupted while making the change. It can also be used to connect two

independent circuits in parallel. In construction, it is in effect two

single throw, single pole disconnecting switches with the hinge jaws

connected together and mounted on the same insulator. The hinge jaw is

also provided with dummy jaws to hold either blade of the switch in

the open position. Except for these differences in the hinge jaws, the

construction is similar to the switch shown in fig. 2,209. It should

not be used to open the circuit when loaded.]

[Illustration: FIG. 2,213.--Hook stick for operating a disconnecting

switch.]

~Ques. What are the features of the enclosed air break?~

Ans. The switch is more compact than the open air break type, but

pressure oscillations are caused on opening the circuit the same as

with the open air break, and it is not desirable for heavy current.

[Illustration: FIG. 2,214.--Baum 35,000 volt, 200 ampere, double break

pole type switch. While designed for disconnecting purposes only, it

can break considerable amperage. The levers and couplings are fastened

with tape pins. The control shaft coupling is adjustable to any

angle, and the switch can be locked in the open or closed position. A

removable wooden handle is supplied and the switch can be handled in

any weather. The arms can be extended to hold fuse fittings, or dead

end insulators in the event of a heavy strain, but it is preferable

to have fuses on another structure as a precaution against coming

in contact with the energized portion of the switch, and it is also

preferable to take the strain of the line on a pole a few feet from the

switch, rather than on the switch structure, particularly in the larger

sizes. An insulating wood section in the control shaft separates the

control handle from the remainder of the switch. Discharging horns can

be fitted to this type of switch and when so equipped they have been

found capable of breaking considerable loads.]

~Ques. How is the fuse arranged in the metal fuse break type of switch?~

Ans. It is placed in a tube fitted with powdered carbonate of lime or

some other insulating powder.

[Illustration: FIG. 2,215.--Pacific swivel type blade for Baum pole

top switches. The ~twist type~ _of blade_, here shown, is especially

adapted to switches operating in freezing or sleety weather. ~It

will be seen~ that the first few degrees through which the rotating

insulator is moved _have the effect of twisting the blade between the

shoes of the contact_, which breaks any seal through freezing, or

corrosion.]

[Illustration: FIG. 2,216.--Pacific 22,000 volt, 100 ampere, ~pole

top switch~ equipped with fuse tubes; designed to meet the need for a

small group controlled disconnecting switch, having several features

making it suitable for use with service transformer installations and

line branches. ~The switch is made~ with clamped pipe arms permitting

adjustment. It is equipped with fuse tubes and fittings, but should

the fuses be not desired, the arm may be shortened. Provision is made

for fitting insulator pins to the top of the arms, when the switch is

mounted vertically, which will hold insulators at right angles to the

switch, making it possible to end a line on the top of these arms and

then drop down through the switch to the bank of transformers. _The

switch is so constructed that_ ~gravity~ _tends to hold it in either

the open or the closed position_. Provision can be made for locking.]

[Illustration: FIG. 2,217.--Horn break switch. ~In operation~, the

arc formed at break, will travel toward the extremities of the horns

because of the fact that a circuit will tend to move so as to embrace

the largest possible number of lines of force set up by it. Hence, the

arc that starts between the horns where they are near together rises

between them until it becomes so attenuated that it is extinguished.]

[Illustration: FIG. 2,218.--Westinghouse rear connected motor starting

switch, for pressures up to 600 volts. It is used for starting rotary

converters and direct current motors of large capacity having starting

torque small enough to permit cutting out the starting resistance in

few steps. The clips can be connected to any type of resistor, the

steps of which are successively short circuited as the switch closes;

the amount of resistance in the armature circuit is thus gradually

reduced. A pause should be made after each step of resistance is thrown

in to allow the motor speed to accelerate. If the starting switch do

not have to carry the full load current and can be short circuited by

another switch, a starting switch of smaller capacity equivalent to 50

per cent of running current of the machine can be used. The switch is

of the single pole, single throw, rear connected, four point, knife

blade type.]

~Ques. Describe its operation.~

Ans. The moving arm of the switch draws the fuse through the tube, thus

opening the circuit without much disturbance.

[Illustration: FIG. 2,219.--Baum disconnecting switch with horns and

auxiliary contacts (Pacific Mfg. Co.). This switch is for use on

systems operating at 100,000 volts or over. It has a spacing of five

feet between outer insulators, is equipped with auxiliary shoes that

break the circuit between the horns, diverting it from the current

carrying contacts so that they are not attacked by the arc.]

~Ques. What is the objection to the metal fuse switch?~

Ans. The powder is set flying by the explosion of the arc, which, as

it settles, gets into the bearings of any machine that may be in the

vicinity.

~Ques. What is a horn break switch?~

Ans. One provided with horn shaped extensions to the contacts, as shown

in fig. 2,219.

The arc formed on breaking the circuit, as it travels toward

the extremities of the horns, becomes attenuated and is finally

ruptured.

[Illustration: FIG. 2,220.--Kelman switching mechanism. The pantograph

arrangement of the contact blades gives a double horizontal break deep

down in the oil. This gives over the break a heavy head of oil which

immediately closes in around the thin blades as they leave the contacts

in opening, thus effectually extinguishing the arc. The opening spring

acts within the pantograph itself without any intervening mechanism,

and the light weight of the few moving parts enables the spring to

accelerate the blades rapidly, thus obtaining a quick break. The

contacts are of the return bend type, which makes a flexible contact,

to obtain alignment with the blades at all times. The pantograph and

contacts are supported on corrugated porcelain insulators on a hardwood

base or insulator board. The insulators are fitted with iron ends for

securing the different parts. At each end of the insulator board is an

upright or lifting board which serves to lift the switching mechanism

out of the tank. The leads are heavily insulated.]

~Ques. What are the objections to this type of switch?~

Ans. The considerable space required for the horns and arcs, and the

line surges caused by the arc.

Horn switches were used extensively for high pressure

alternating current circuits before the introduction of oil

switches.

[Illustration: FIG. 2,221.--Sectional view of Pacific weatherproof oil

switch for use in places exposed to the weather. All moving and contact

parts are supported from the cast iron top and are readily removable

for inspection or repair.]

~Oil Switches.~--The extensive use of high pressure currents and

alternating current motors and other devices introducing inductance

make it necessary to use switches radically different from the ordinary

air break types.

[Illustration: FIG. 2,222.--General Electric central station triple

pole single throw oil switch; view of switch in tank. This type is for

pressures up to 110,000 volts, being adapted for stations employing

open wiring, since the connections are made at the top of the switch

and its construction obviates the need for isolating it in a cell. One

tank with two breaks in series are used for each phase.]

The opening of circuits of considerable current value with inductive

loads is not possible with old style switches which were quite

adequate for the service for which they were designed. These circuits

are controlled with ease and certainty by the oil switch.

[Illustration: FIGS. 2,223 to 2,226.--Westinghouse indoor, two pole

double throw oil switch for pressures not over 6,600 volts. Fig. 2,223,

open position; fig. 2,225, closed position. This type of switch is

suited for a wide range of application, being made in both switchboard

and wall mounting styles; also for remote mechanical control by the

use of bell cranks and connecting rods. The wall mounting style is

adaptable to motor installations on account of the facility with which

it may be mounted on any support, convenient to the motor operator. The

lever and handle extend outward over the oil tank, so that the switch

may readily be mounted against a wall, post or any vertical support.

The characteristic features of this type of switch are: knife blade

contacts submerged in oil; live parts carried on a porcelain base

affording a permanent insulation between adjacent poles, and between

the frame and live parts; compactness and accessibility; enclosure of

all live metal parts; and low first cost. Each contact jaw has attached

to it an arcing piece which takes the final break, thus preventing any

burning of the jaws. These arcing pieces are inexpensive and readily

replaced when worn or burnt away. The contact making parts are enclosed

in a sheet metal oil tank which has an insulating lining. The leads are

brought out at the top. Connections to the outside circuit are made

inside the switch and a porcelain insulator is slipped over the joint,

thus providing a straight continuous connection from the line with

maximum insulation. On the 6,600 volt switch, insulation is obtained

by the use of porcelain bases for supporting the live parts. In the

3,300 volt switch specially treated wooden bases are used, suitable

barriers being provided between the poles where necessary to prevent

arcs communicating.]

~Ques. What is an oil switch?~

Ans. One in which the contact is broken under oil.

This type of switch is the one almost universally used on high

pressure alternating current circuits, because of the fact that

the oil tends to cause the current to break when at its zero

value, thus preventing the heavy arcing which would occur with

an air break switch, and the consequent surges in the line

which are so often the cause of breakdown of the insulation of

the system.

[Illustration: FIG. 2,227.--Kelman electric control unit for oil

switch. It consists of an iron frame which contains the opening and

closing coils and the bearings for the operating bell crank. A small

switch on the frame automatically opens the coil circuit at the end of

the stroke in either direction and operates signal lamps to indicate

the open or closed position. The automatic overload release opens the

switch by closing the opening coil circuit. This electrical operating

unit gives satisfactory service through a wide variation of voltage.

It requires a momentary expenditure of energy of from 1,500 to 4,000

watts, depending on the size.]

~Ques. What is the nature of an oil break?~

Ans. It is not a quick break.

Oscillograph records show that the effect of the oil is to

allow the arc to continue during several cycles and then to

break the current, usually at the zero point of the wave.

~Remote Control Oil Switches.~--It is desirable in the case of switches

on high pressure circuits to locate the parts which carry the high

pressure current at some distance from the switchboard in order that

they may be operated with safety.

With respect to the manner in which the switches are operated they may

be classed, as

1. Hand operated;

2. Power operated.

[Illustration: FIGS. 2,228 and 2,229.--Views showing mechanism of hand

operated remote control switches. Fig. 2,228, straight mechanism; fig.

2,229, angular mechanism.]

~Ques. What kind of power is used?~

Ans. Electricity is used in most cases; in some installations, switches

are operated by compressed air.

~Ques. For what pressures should remote control switches be used?~

Ans. For pressures above 1,100 volts.

~Ques. Describe the operating mechanism of a remote control, hand, and

electrically operated switch.~

Ans. For hand operation, the mechanism between the operating lever and

switch proper, consists simply of a system of links and bell cranks.

Various shapes of bell crank are used, to permit change in direction or

position of the force applied to operate the switch.

[Illustration: FIG. 2,230.--Pacific ~oil switch with solenoid control~,

designed for 60,000 and 70,000 volt installations; it is capable of

handling a 25,000 kw. generating station. The break is horizontal,

made by the rotation of a flat member edgewise through the oil. The

solenoid, at its extreme outer position, has a free start before

commencing to move the control parts of the switch. As it approaches

the extreme inner position, where the opening spring and the contacts

begin to offer the greatest resistance, the magnetic action is, of

course, most powerful, and the leverage by which it is applied moves

to an increasing radius, by means of rollers working in the curved

slots of the control shaft levers. These curved slots and rollers have

the additional advantage of making the opening action very free and

smooth. The tripping coil does not act on the latch directly, but gives

a hammer blow that is positive. The latch proper is a roller having a

powerful hold and easy release. Current can not be left on either the

closing or opening coils, as they are automatically cut out by the

movement of the switch.]

~Ques. Name two classes of electrically operated remote control switch.~

Ans. Those operated by solenoids, and those operated by motors.

The solenoid type are closed by the action of a plunger

solenoid, and opened either by another solenoid called a

"tripping coil" or by gravity. Some examples of remote control

are shown in the accompanying illustrations.

~Ques. What indicating devices are used with electrically operated

switches?~

Ans. Red and green lamps; ~red~ for _closed_ and ~green~ for _open_ as

shown in fig. 2,231.

[Illustration: FIG. 2,231.--Diagram of connections of motor operated

remote control switch. The motor which operates the switch is

controlled by a small lever generally mounted on the panel with the

instruments which are in the circuit controlled by the switch. The

standard pressure for operating the motors is 125 volts.]

~Ques. For what service are motor operated switches used?~

Ans. For exceptionally heavy work where the kilowatt rupturing capacity

is greater than that for which the other types are suitable.

[Illustration: FIG. 2,232.--General Electric motor operated three

phase oil switch. The operation of the oil switch is accomplished by

a small hand controlling switch, generally mounted on the panel, with

the instruments which are in the circuit controlled by the oil switch.

The standard pressure for the operating motor is 125 volts. The switch

has six breaks, each break being a separate tank. In addition to this

isolation of the breaks, each phase is enclosed in a fireproof brick

compartment, making it impossible for trouble in one phase to be

communicated to another. The cells are constructed of brick with top

and bottom slabs of slate. The capacities of such switches, range from

2,500 to 60,000 volts, and from 100 to 1,000 amperes.]

~Rupturing Capacity of Oil Switches.~--While an oil switch may be

designed for a given pressure and to carry a definite amount of

current, it should not be understood that the switch will necessarily

rupture the amount of normal energy equivalent to its volt ampere

rating.

[Illustration: FIGS. 2,233 to 2,235.--Diagrams showing connections for

General Electric single, double, and triple pole, solenoid operated

remote control switches. The operating coils are shown connected to

main switch circuit, but may be connected to an entirely separate

control circuit. Connections are the same for either alternating or

direct current.]

Oil switches are often used on systems with generator capacity of

many thousand kilowatts. It is therefore essential that the switches

shall be able to break not only their normal current, but also greatly

increased current that would flow if a short circuit or partial short

circuit occur.

[Illustration: FIG. 2,236.--Westinghouse three pole hand operated

remote control oil switch, adapted for the control of alternating

current circuits of small and moderate capacities, the pressures of

which do not exceed 25,000 volts. Each unit is installed in a separate

masonry compartment. The open position of contacts is maintained by

gravity. Up to and including the 600 ampere capacity, the contacts

are cone shaped with an arcing tip, as shown for capacities in excess

of 600 amperes, brush contacts are furnished with auxiliary arcing

contacts of the butt type. Each pole has two sets of contacts, thus

providing a double break in each line. With both types of contact, the

final break of the arc is taken and the main contacts protected by

auxiliary arcing contacts which are inexpensive and readily renewable.

The upper or stationary contacts are mounted on porcelain insulators

secured in the soapstone base. The lower or movable contacts are

carried by a wooden rod connected to and moved vertically by the

operating mechanism. The operating mechanism of the hand operated

breaker consists of a simple system of levers, bell cranks, and rods.

The necessary energy for making a positive contact is small owing to

the use of a toggle mechanism. The leads are brought out of the top

of the breaker through heavy porcelain insulators. On breakers above

3,500 volts, the connections to the line wires are made by means of

a union which can be tightened with a socket wrench fitting inside

the insulator. As the leads coming into the switch are necessarily

insulated wire or cable, this arrangement eliminates all exposed live

parts and is well adapted to making connections readily to bus bars

located above or in the rear of the circuit breakers.]

[Illustration: FIG. 2,237.--Cutler-Hammer ~enclosed float switch~,

designed for the automatic control of alternating current motors

operating pumps used to fill or empty tanks, sumps or other reservoirs.

~The switch is operated~ _by the rise and fall of a copper float which

is connected to the switch lever by a brass rod or copper chain_. As

the water level rises and falls, the float moves up and down. This

movement is transmitted to the switch lever and the switch (if the

movement be sufficient) is tripped to make or break the motor circuit.

~To insure the best operation~ it is necessary that the float rod be

provided with a guide so that the float will move up or down in a

vertical line, as shown. The minimum difference in water level at which

the switch will operate is approximately 10 to 12 inches. When the

float is placed in a closed tank, the minimum height inside from the

bottom of the tank to the top should be at least 6 inches greater than

the difference in water level to provide sufficient clearance for the

float. ~When this type switch is used as a tank switch~, the contacts

are closed when the water level is low, putting the motor, driving the

pump, in motion. When the water in the tank reaches a predetermined

high level the float arm opens the switch contacts, and the motor is

disconnected from the line. ~For sump pump purposes~, the contacts open

on low level and close on high level, the lever being reversed for this

purpose. Two pole, three pole and four pole switches of this type are

made, all arranged to completely disconnect single phase, two phase and

three phase motors from their circuits. When used with small motors

which may be thrown across the line to start, the switch may be used

without a self starter if desired.]

Under short circuit conditions alternators develop instantaneously many

times their normal load current, while the sustained short circuit

current is approximately two and a half to three times normal, or even

higher with turbine alternators. Hence, circuit breakers of the so

called instantaneous type must be capable of rupturing the circuit

when the current is at a maximum, whereas, non-automatic switches, or

circuit breakers with time limit relays will be required to interrupt

only the sustained short current circuit. The reason is evident, since

the delay in opening the switch allows the current to approach the

sustained short circuit conditions.

Hawkins Electrical Guide v. 07 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 3 / 8 章