50. TEST OF STRENGTH AND TIGHTNESS.

_a._ First, shut the main valve between the pump and the fire system

lest a sprinkler head be burst, then shut all water outlets nearly, but

not quite tight, so pump will move very slowly. Screw safety valve down

hard. Slowly and carefully admit steam pressure sufficient to give 240

pounds per square inch water pressure.

_b._ With this extreme pressure all joints should remain substantially

tight, and the slow motion of the pump should be tolerably smooth

and uniform. (The leakage of a few drops here and there and a little

unsteadiness of motion are to be expected.)

_c._ If boiler pressure is above 85 pounds, the safety valve on pump

should be attached and screwed down only enough to hold the required

pressure. For with 100 pounds or more of steam the water pressure might

be carried too high.

After completing the above test slack off on safety valve, setting it

so that it will begin to open at about 100 pounds pressure.