48. TEST FOR SMOOTHNESS OF ACTION.

_a._ Provide outlets for the water; start the pump slowly, gradually

open steam-throttle to bring the pump to full speed.

The pump should run smoothly at the rated full speed of 70 revolutions

per minute (or 60 revolutions if a 1,500-gallon pump) with full length

of stroke, and meanwhile maintain a water pressure of 100 lbs. per

square inch.

If the hose lines are short, or discharge is too free, partly close the

water outlet valves, thus throwing an extra back pressure on the pump

equivalent to that which would be produced through a greater length of

hose.

During this trial it is preferable to discharge the water through

lines of 2-1/2-inch cotton rubber-lined hose, preferably each 150

feet long, each connected directly to the hose outlets on the pump,

and each line having a 1-1/8-inch smooth nozzle at its outer end. Two

lines should be connected for a 500-gallon pump, three for a 750, and

so on, having as many lines as rating of pump requires.

A hose line 150 feet long, with an inside surface of average

smoothness, and with a 1-1/8-inch nozzle attached, will require about

80 pounds pressure at the pump to discharge 250 gallons per minute,

and the nozzle pressure will be about 45 pounds. Therefore, with

lines attached as above, a pressure at the pump of about 80 pounds

should represent a discharge about equal to the rated capacity of

the pump, and would ordinarily correspond with the rated full speed

revolutions.

If the pump runs smoothly under these conditions, it is well to open

the throttle somewhat further, and bring the pressure at the pump

up to 100 pounds. This will give a discharge of about 280 gallons

per stream, or about 12 per cent. in excess of the rated capacity.

The revolutions will, of course, correspondingly increase, and

under all ordinary conditions a pump should run smoothly at this

higher capacity though a little more vibration and pounding would be

expected than when running simply at its rated speed.

After cushion valves are adjusted there should be no noteworthy water

hammer or valve-slam. Sometimes valve-slam is not the fault of the

pump, but arises from an obstructed suction pipe. It is objectionable

to doctor water hammer in a pump by “snifting” air into the suction,

as this cuts down the efficiency and is a poor expedient.

The quietness of that part of the hose near the pump, or its freedom

from rubbing back and forth crosswise an inch or more with each

pulsation of the pump, is a good index of the pump maker’s skill

in securing uniform delivery. Bad pulsation quickly wears holes in

the hose, and to reveal this is the object of testing _with hose

connected directly to the pump_.