CHAPTER XXV

AUXILIARY APPARATUS

There are numerous devices that must be used in connection with dynamos

and motors for proper control and safe operation. Among these may be

mentioned:

1. Switches;

2. Fuses;

3. Circuit breakers;

4. Rheostats;

5. Switchboards.

=Switches.=--A switch is a device by means of which an electric

circuit may be opened or closed. There are numerous types of switch;

they may be either single or multi-pole, single or double throw and

either of the "snap" or knife form.

=Ques. What is the difference between a single and double pole

switch?=

Ans. A single pole switch controls only one of the wires of the

circuit, while a double pole switch controls both.

=Ques. What is the difference between a single break and a double

break switch?=

Ans. The distinction is that the one breaks the circuit at one point

only, while the other breaks it at two points.

=Ques. What is the advantage of a double break?=

Ans. If the circuit be opened at two points in series at the same

instant, the electromotive force is divided between the two breaks and

the length to which the current will maintain an arc at either break is

reduced to one-half; thus there is less chance of burning the metal of

the switch. Another reason for providing two breaks is to avoid using

the blade pivot as a conductor, the contact at this point being too

poor for good conductivity.

[Illustration: FIGS. 455 to 457.--Adam's single throw knife

switches without fuse connections. Fig. 455, single pole switch; fig.

456, double-pole switch; fig. 457, three-pole switch.]

[Illustration: FIGS. 458 to 460.--Adam's single throw knife

switches with fuse connections at the handle end. Fig. 458, single pole

switch; fig. 459, double pole switch; fig. 460, three pole switch.]

=Ques. When should a knife switch be used?=

Ans. When the capacity of the circuit in which it is to be placed

exceeds 10 amperes.

=Ques. Describe a knife switch.=

Ans. Fig. 461 illustrates a knife switch of the double pole, single

throw type. It consists of the following parts: base, hinges, blades,

contact jaws, insulating cross bar, and handle, as shown.

=Ques. How should knife switches be installed?=

Ans. They should be placed so that _gravity tends to open them_.

Otherwise if the hinges become loose, the weight of the blades

and handle would tend to close the switch, thus closing the

circuit and possibly resulting in considerable damage.

[Illustration: FIG. 461.--A single throw, two pole knife

switch. As usually constructed it is made of hard drawn copper with

cast terminal lugs and fibre cross bar.]

=Ques. How should switches be proportioned?=

Ans. The minimum area of the contact surfaces should not be less than

.01 square inch per ampere, and in those used on arc lighting or other

high voltage circuits where the current is usually small, the area of

the contact surfaces are usually from .02 to .05 inch per ampere.

Since dirt or oxidation would prevent good contact under a simple

pressure between the contact surfaces, the mechanism of a switch

provides a sliding contact.

In the general design of switches, all parts which carry

current are given a cross sectional area of at least one square

inch per 1,000 amperes if they be made of copper, and about

three times as much if made of brass, as the conductivity of

the latter is only one-third that of the former. Furthermore,

the current should never be permitted to pass through springs,

as the heat generated will destroy their elasticity.

[Illustration: FIG. 462.--Triple pole, double break double

throw knife switch for very heavy current. The blades are made up of

numerous strips to give adequate contact area. A double throw switch

is used when it is desirable to open one circuit and immediately close

another, or to transfer one or more connections from one circuit

to another in the least practical interval of time, also, when one

connection is to be broken and another closed and it is undesirable to

allow both to be closed at the same time.]

=Ques. What difficulty is experienced in opening a circuit in which a

heavy current is flowing?=

Ans. It is impossible to instantly stop the current by opening the

switch, consequently the current continues to flow and momentarily

jumps the air gap, resulting in a more or less intense arc which tends

to burn the metal of the switch.

=Ques. How is this remedied to some extent?=

Ans. The contact pieces are so shaped that they open along their whole

length at the same time, so as to prevent the concentration of the arc

at the last point of contact. This feature is clearly shown in fig. 461.

[Illustration: FIG. 463.--A "quick break" knife switch of the

single throw, single break, one pole, type. The contact blade is held

between the jaws by their clamping friction until the handle compresses

the spring sufficiently to force the blade out. As soon as it breaks

contact with the jaws, the spring expands and drives the blade away

from the jaws with greater rapidity than could be done by hand. The

object of this action is to break the arc as quickly as possible to

prevent burning the metal of the switch.]

[Illustration: FIGS. 464 and 465.--Snap switch; views showing

switch with cover on, and exposed to show mechanism. The switch is

provided with indicating dial which registers "on" and "off" positions.

FIG. 466.--Gas Engine snap switch. The first snap makes

connection so that igniter is run from storage battery; second snap

connections are changed so that igniter is supplied from dynamo; third

snap makes connections so that dynamo supplies igniter and charges

storage battery; fourth snap, all off.]

=Ques. For what service are "snap" switches suitable?=

Ans. They are used on circuits containing lamps in comparatively small

groups, and other light duty service.

=Ques. What is a quick break switch?=

Ans. A form of switch in which the contact pieces are snapped apart

by the action of the springs, as shown in fig. 463, so as to make the

duration of the arc as short as possible.

The current allowed in each branch circuit of an electric

lighting system is limited by the insurance rules to a maximum

of 660 watts equivalent to 12 lamps of 16 c.p. each at 110

volts. They are also employed to control lamps in groups in

theatres and other places where many lamps are turned on or off

at about the same time.

[Illustration: FIG. 467.--Spool of fuse wire. The wire is

usually made of an alloy of tin and lead, such as half and half solder.

Bismuth is frequently added to the alloy to lower the melting point For

half and half solder the melting point is 370° Fahr. The quickness with

which a fuse will melt after the current has reached the limit depends

upon the specific heat and latent heat of the metal. The current

required to "blow" a fuse increases somewhat with the age of the fuse

owing to oxidation and molecular changes. Fuses are sometimes rated

according to the number of amperes to be taken normally by the circuit

they are to protect. Thus, a 10 ampere fuse is supposed to protect a

circuit whose regular current should not exceed 10 amperes, and to blow

if the current rise to say 12 amperes. The Underwriters' rule requires

that the rating be about 80% of the maximum current it can carry

indefinitely, thus allowing about 25% overload before the fuse melts.

The fusing current varies considerably according to circumstances. The

temperature of the surrounding air or other substances affects the

melting current greatly, because the rate at which heat from the fuse

will be transferred to the surroundings depends upon the difference of

temperance between them and the fuse. Hence a fuse in a warm place will

be melted by a smaller current than a similar fuse in a cold place. For

a similar reason, a fuse in an enclosed place where there is little

chance for the heat to be dissipated, will melt with a smaller current

than the same in an open place. If the current increase gradually to

that which would ordinarily melt the fuse, the high temperature makes

the fuse wire oxidize rapidly; this sometimes makes a sort of tube of

oxide which will not break even after the fuse wire inside has melted,

and so the fuse carries more than its rated current. Open fuses are so

unreliable that circuit breakers are preferable for large currents;

when fuses are used, the enclosed type as shown in figs. 468 to 470, is

usually the more desirable.]

=Fuses.=--All circuits subject to abnormal increase of current

which might overheat the system, should be protected by fuses which

will melt and thus open the circuit. A fuse is simply a strip of

fusible metal, often consisting of lead with a small percentage of tin,

connected in series in the circuit.

Experiments have shown that for large fuses, a multiple fuse is

more sensitive than a single one. A one hundred ampere fuse may

be made by taking four wires of twenty-five amperes capacity.

A fuse block may be overloaded, not because the metal of the

terminals is not of sufficient cross section to carry the

current, but because of insufficient area of, contact, or loose

contact of fuse and wires; the overload thus caused results in

heating and frequently melts the fuse.

[Illustration: FIGS. 468 to 470.--D & W, enclosed "cartridge"

fuses. Fig. 468, type for 3 to 60 amperes; fig. 469, type for 61 to 100

amperes; fig. 470, type for 101 to 1,000 amperes.]

=Ques. Where should fuses be placed?=

Ans. They should be inserted wherever the size of wire changes or

wherever there is a branch of smaller size wire connected, unless the

next fuse on the main or larger wire is small enough to protect the

branch or small wire.

[Illustration: FIGS. 471 to 478.--Interior construction of

D. & W. fuses. In the manufacture of these fuses, four types of fuse

link are used according to capacity of fuse, and classified as: 1,

air drum link; 2, flat link; 3, multiple link; 4, cylinder link. In

the air drum link, figs. 471 and 472, a capsule provides an air space

about the center of the link, the rate of heat conduction through the

confined air being very slow, the temperature of that portion of the

link rises rapidly with increasing current, rendering the blowing point

practically constant; fig. 473 shows a section through the complete

fuse. In the flat link, fig. 474, the section is reduced in the center,

cutting down as far as possible the volume of metal to be fused.

Figs. 475 to 478 show various form of multiple link construction. By

sub-dividing the metal, increased radiating surface is obtained which

permits a reduction in the volume of fusible metal necessary, and

the metal vapor formed when the fuse blows on heavy overload is more

readily dissipated. Figs. 477 and 478 show two forms of the cylinder

link, the plain cylinder fig. 477, being used for low voltage and large

current, and fig. 478, for certain high tension service. The corrugated

cylinder presents more surface to the fuse filling than the plain type

and secures a maximum radiating surface with resulting minimum volume

of metal for a given current.]

=Ques. How should fuses be mounted?=

Ans. They should be placed on a base of slate, porcelain, marble, or

other incombustible material.

=Ques. What is the objection to copper fuses?=

Ans. They heat perceptibly soon after their rated capacity is passed.

The melting temperature is higher than lead alloy.

=Ques. Upon what consideration does the choice between switches and

circuit breakers depend?=

Ans. Simple knife switches are suitable for use when the circuit is not

liable to be opened while carrying large current. A circuit breaker,

operated automatically or by hand should be used for interrupting heavy

currents.

[Illustration: FIGS. 479 and 480.--D & W fuse indicator. The

operation is illustrated in the figures which show appearance of the

label before the blowing of the fuse, fig. 479, and the same fuse

blown, as indicated by the appearance of the black spot within the

circle fig. 480.]

=Circuit Breakers.=--A circuit breaker is a switch which is opened

automatically when the current or the pressure exceeds or falls below a

certain limit, or which can be tripped by hand.

=Ques. What is the construction of a circuit breaker?=

Ans. It is composed of a switch and a solenoid in the main circuit.

When the current, flowing through the circuit, exceeds a certain value,

the core of the solenoid is drawn in and trips a trigger which allows

the switch to fly open under the action of a spring.

[Illustration: FIGS. 481 to 486.--Various open fuses. Fig.

481, fuse for main and branch blocks; fig. 482, standard railway

fuse; fig. 483, Edison main style; fig. 484, W.U. pattern; fig. 485,

Bell telephone style; fig. 486, sneak current fuse. When an open fuse

"blows" as a result of overloading, the rupture is accompanied by a

flash, and by spattering of the fused material. With large currents

this phenomenon is a source of danger, and the use of enclosed fuses

is accordingly recommended whenever the rating of the fuse exceeds 25

amperes. Various types of enclosed fuse are shown in figs. 468 to 470.]

There are numerous kinds of circuit breaker to meet the varied

conditions of service of which may be mentioned the following:

1. Maximum circuit breaker;

2. Minimum circuit breaker;

3. Reverse current circuit breaker;

4. Maximum and reverse circuit breaker;

5. No voltage circuit breaker.

[Illustration: FIGS. 487 and 488.--Reverse current circuit

breaker; fig. 488, view looking at end of coils of cut out, showing

direction of current. A to + bus bar; B, resistance lamp; C, brush of

cut out; D, shunt coil; E, series coil; F, core that trips cut out; G,

to - bus bar; H, to + pole of dynamo.]

Of these the maximum, reverse, and maximum and reverse types

are the more important.

A maximum circuit breaker is equivalent to a fuse, but has the

advantage that it can be at once reset, whereas a fuse must be

replaced.

A reverse breaker is used in connection with dynamos in

parallel, to automatically cut out a machine if it take more

than say, 10 per cent. motor current.

Maximum and reverse circuit breakers are frequently used on

dynamo panels.

[Illustration: FIGS. 489 and 490.--Front and top views of

I-T-E automatic overload circuit breaker. In fig. 489 the current in

the circuit enters at A, passes through the solenoid coil B (which

in its iron jacket becomes a powerful magnet), through the copper

terminal C, to the contact blades D, across the bridge at E to the

contact blades F, and out into the line at G. The path of the current

as indicated above is more clearly indicated in the top view fig. 490.

When the current in the solenoid coil produces sufficient magnetism

to overcome the weight of the plunger, the latter is drawn up with

constantly increasing velocity until it strikes a restraining latch

or trigger which forces the arm out of the switch, thus automatically

opening the circuit. The device is so constructed that in opening the

circuit the arc is broken on the carbon contacts instead of the copper

contacts.]

=Ques. Describe a reverse current circuit breaker or discriminating

cut out.=

Ans. This type of circuit breaker is arranged to open a circuit in the

event of current flowing in the circuit in a direction reverse to the

normal. This is sometimes effected by winding the electromagnet of the

circuit breaker with two coils, one connected as a shunt across the

main circuit and the other in series with the main circuit, the two

coils being so arranged that when the main current flows in the normal

direction their effects assist one another, whereas, when the main

current reverses, the effects of the coils are neutralized and the

breaker opens.

[Illustration: FIG. 491.--Roller-Smith "S.E." plain overload

circuit breaker. In operation, current entering through the lower

studs flows through the laminated strap windings C, from this into

the arm D, through the contact plate E, into the stationary brush F,

and finally out through the upper stud Q. In its passage through the

laminated windings C, the square core A is of course magnetized to

a degree dependent on the current strength. When this magnetization

reaches a pre-determined value, the attraction exerted on the ends

K of the pivoted armature causes the same to rise with great and

increasing velocity, finally bringing the finger D which forms part of

the armature into violent contact with the face R of the corresponding

projection on the housing which carries the handle and the roller H.

This heavy blow causes H, in its rotation about the shaft J, to go over

the center and consequently allows the strong outward pressure of the

brush F and the resilient coil C to throw the arm outward with a high

velocity and so break the circuit, first between the brush fingers

and the contact plate and finally between the carbons S and F, the

one of which is rigidly secured to the arm and the other of which is

resiliently mounted on its supporting spring. To reset the breaker,

the handle, which the act of opening has raised, is pulled down, thus

bringing roller H into engagement with roller G once more and in that

way forcing the arm back into its initial position.]

[Illustration: FIG. 492.--Roller Smith "S.E." combination

overload and underload circuit breaker. Attached to the supporting

frame B is the extension Z, which like B, is of non-magnetic material

and carries a rectangular magnetic core around which there are wrapped

laminated copper conductors. Hinged at U is a heavy cup-shaped mass

of magnetic material, and hinged at V is a flat lever X which bears

against the extension Y secured to the housing which carries the

operating handle. The circuit through the breaker conveys the current

around the windings of this underload coil carried by frame Z and

passes from it to the regular overload winding C from which it pursues

the same course and exercises the same function as in a plain overload

breaker. The core of Z being thus magnetized, the cup-shaped member W

is held in firm contact therewith and the lever X hangs free. Should,

however, the current fall below the minimum value, W is no longer

sustained by the magnetic attraction but drops away, swinging on its

hinge U until the projection on the heel thereof strikes the lever X,

which blow is transmitted through Y to the handle and thus trips the

breaker. When closing to reset the breaker, the handle is manipulated

just as in the case of a plain overload breaker, that is, it is pulled

down, thus not only closing and locking the breaker as before but

through the pressure exerted by Y on X and by X on W, putting the

latter into contact with its rectangular core to which it will adhere

if the necessary current be present.]

=Ques. State some disadvantages of a discriminating cut out.=

Ans. If one current reverse very rapidly, and soon reach a large value

in the opposite direction, it is possible the cut out may not open at

the desired instant, and thereafter the effect of the heavy reverse

current will be so great that the breaker will be held in more and more

strongly; a second disadvantage is that should the supply fail, the

breaker will open in any case, and have to be reset before the supply

can be resumed, though in certain cases, as, for instance where there

is a motor load, this feature is an advantage and not a disadvantage,

since the breaker acts as a no-voltage cut out as well as a reverse

current cut out.

Reverse breakers, however, can be made positive in their

action; that is, they can be so arranged that a reverse current

exerts a positive pull on the tripping gear, so that the

greater the reverse current, the greater the tripping effect.

=Ques. What are time limit attachments?=

Ans. Devices which are fitted to circuit breakers and which act as

dampers and prevent the too sudden operation of the breakers on what

may be only a temporary overload or reverse current.

By having different time limits on feeder and dynamo breakers

it can be ensured that the former operate before the latter,

and suitably in other cases where it is desired that one

breaker shall operate before another.

=Ques. Describe a time limit attachment.=

Ans. There are numerous types. It may consist of a clockwork device,

a weight acting on a small drum or pulley, a modified dash pot

arrangement, or a device operating by the expansion of a conductor due

to the heat generated by a current passing through it.

=Ques. How should a time limit device be arranged?=

Ans. It should be so arranged that the heavier the overload the quicker

the device acts, until with a short circuit the device is almost

instantaneous in its action.

[Illustration: FIG. 493.--Diagram showing connections of a

rheostat. The various resistance coils are connected to brass buttons

or "contacts." The rheostat is connected in series in the circuit that

it is to control. In operation when the lever is on contact 1, the

current is opposed by all the resistance of the rheostat so that the

flow is very small. As the lever is moved over contacts 1, 2, 3, etc.,

the coils are successively cut out, thus diminishing the resistance,

and when contact 11 is reached all the resistance is short circuited

allowing the full current to flow. In some types of rheostat the wire

is wound around an iron frame-work which has been previously dipped

into a fireproof insulating enamel. The advantage of this construction

is that the heat from the wire is dissipated much more rapidly, so that

a much smaller wire can be used to carry a given current. The size of

such an enameled rheostat required for absorbing a given amount of

energy is much smaller than one made of coils of wire stretched between

an iron supporting framework.]

=Rheostats.=--These devices consist of conductors inserted into

a circuit for the purpose of diminishing, either constantly or in a

variable degree, the amount of current flowing, or to develop heat by

the passage of a current through them. Rheostats designed to be used in

starting electric motors are frequently called "starting boxes."

=Ques. Describe the construction of a rheostat.=

Ans. In fig. 493, resistance coils, A, B, C, etc., are mounted in a

frame or box, and are connected at intervals to the contacts 1, 2, 3,

etc. The rheostat arm or lever L is pivoted at S, and when moved over

the contacts, inserts more or less of the resistance in the circuit

thus regulating the flow of the current. One terminal M of the rheostat

is connected to the first contact and the other terminal O, to the

lever at S.

[Illustration: FIG. 494.--Starter with no voltage release for

a series motor. A helical spring coiled around the lever pivot P, and

acting on the lever A, tends to keep it in the off position against the

stop S. This lever carries a soft iron armature I, which is held by

the poles of the electromagnet E, when, in starting the motor, the arm

has been gradually forced over as far as it will go. Should anything

happen to interrupt the current while the motor M is running, E will

lose its magnetism and A will be released, and will fly over to the off

position. E is usually shunted by a small resistance R, so that only a

portion of the main current flows through it. This device constitutes

the _no voltage release_, and ensures that all the resistance is in

circuit every time the motor is started.]

=Ques. How is a starting box connected to a motor?=

Ans. In series.

=Ques. Why should a starting box be used with a motor?=

Ans. If the line voltage should be applied directly to the terminals

of the armature when not running, an excessive flow of current will

result, on account of the low resistance. Accordingly, to prevent

injury to the winding, a variable resistance or starting box is

inserted between one supply terminal and the armature so that the

pressure may be applied gradually while the motor is coming up to speed.

[Illustration: FIG. 495.--Starter with no voltage release

for a shunt motor. The terminals of the motor are at M, M', _m_, and

those of the starter at S, S', _s_. The lever SA is shown in the "on"

position. The current enters the motor at the terminal M, and there

divides, part going through the field coil F, and the main current

through the motor armature A. The armature current enters the starter

at the terminal S', and traversing the lever SA, leaves by the terminal

S. The field current enters the starter at the terminal _s_, traverses

the coil of the magnet E (which holds up the armature _a_ linked to

the lever) and thence completes its journey through the whole of

the resistance R, and through the lever SA, to the terminal S. When

the supply is cut off by opening SW, or should the field circuit be

accidentally broken, the magnet E will release _a_ and the lever,

which will thereupon fly to the "off" stop O. It should be noticed

that when SA is off, A and F form a closed circuit with the resistance

R and magnet E. The inductance of F has consequently no chance of

causing destructive sparking when the current is shut off. In starting

the motor, SW is first closed, and then, as the lever is slowly

moved, the resistance R, which at first is all in circuit with A, is

gradually transferred from A to F. The resistance of R is too small to

affect appreciably the current in F, which necessarily consists of a

comparatively large number of turns of fine wire. The arrangement is

adopted to render the breaking of the shunt circuit unnecessary and is

rendered clearer by the diagram fig. 496. It should be noted that E may

be provided with a short circuiting key or push if required.]

[Illustration: FIG. 496.--Simplified diagram of the

connections of fig. 495.]

[Illustration: FIG. 497.--Starter with no voltage release

and overload release connected to a compound motor. With a shunt

motor, the only difference in the diagram would be that the series

winding SE would be absent, and the armature A would then be

connected straight across between the main terminals M and M'. When

switch SW is closed, the current will enter the starter at

its terminal S, and pass through the magnet coil _m'_ of the overload

release to the switch lever L, which is shown in the off position. As

soon as L is moved up to make contact with the first contact S the

current divides; part going through the resistance R and the terminals

S' and M' to the series coil SE (if a compound motor) and

armature A; and part through the no voltage magnet E to the shunt

winding SH. As the lever L is moved up toward E, the effect

is to take R out of the armature circuit and put it into the shunt

circuit. When the iron armature _a_, fixed on the switch lever, comes

against the poles of E, the laminated copper brush C bears against the

blocks B, B, and so affords a better path for the current than through

the spindle _s_. Should the supply voltage fail, either temporarily or

permanently, E will release _a_, and L will fly off under the tension

of a helical spring coiled round _s_. If there should be an overload

on the motor, tending to pull it up and cause an excess of current to

flow through the armature; this excess current, passing through _m'_,

will make it attract its armature, so bringing two contacts together

at K which will short circuit E, and allow the switch to fly off. The

connections between E and _m'_ are not shown in the figure, but they

are indicated at C in fig. 498, which is a simplification of fig. 497,

and which should be carefully compared therewith. When only the normal

current is flowing, the attraction between _m'_ and its armature is not

sufficient to pull the latter up. The actual forms and arrangement of

parts on the starters are well shown in some of the figures.]

=Ques. What attachments should be provided on a starting box?=

Ans. An overload release, and a no voltage release.

=Ques. Describe these devices.=

Ans. The overload release is an electromagnetic circuit breaker that

opens the circuit if the motor become greatly overloaded. A no voltage

release may consist of an electromagnet in series with the shunt field

circuit; it holds the rheostat arm in the operating position as long

as current flows through the shunt field from the line. If the line

switch be opened or the shunt field circuit accidentally broken, the

device becomes demagnetized and releases the arm, which returns to its

starting position by the action of a spring.

[Illustration: FIG. 498.--Simplified diagram of the

connections of starter connected to compound motor as shown in fig.

497.]

The general arrangement of switches, cut outs and starting boxes should

be in accordance with the requirements of the National Electrical Code

as follows:

"Each motor and starting box must be protected by a cut out and

controlled by a switch, said switch plainly indicating whether

'on' or 'off.' The switch and rheostat must be located within

sight of the motor, except in cases where special permission

to locate them elsewhere is given, in writing by the inspection

department having jurisdiction.

"Where the circuit breaking device on the motor starting

rheostat discs disconnects all wires of the circuit, this

switch may be omitted.

"Overload release devices on motor starting rheostats will not

be considered to take the place of the cut out required if they

be inoperative during the starting of the motor.

"The switch is necessary for entirely disconnecting the motor

when not in use, and the cut out to protect the motor from

excessive currents, or careless handling when starting. An

automatic circuit breaker disconnecting all wires of the

circuit, may, however, serve as both switch and cut out."

[Illustration: FIG. 499.--View showing general arrangement

of a switchboard. The wires are shown to illustrate the various

connections, but in actual construction these wires are connected on

the back of the switchboard.]

=Switchboards.=--A switchboard consists of a panel or series of

panels of slate, marble, soapstone or brick tile erected in an electric

plant for the purpose of mounting in a convenient group the instruments

for controlling and distributing the current and safeguarding the

system. Switchboards may be divided according to operation into two

classes:

1. Direct control;

2. Remote control.

A direct control switchboard has all its apparatus mounted directly

on the board and controlled by hand, while in the remote control

type, the main current carrying parts are at some distance from the

operating board, the control being effected by mechanical devices or

by electric motors or solenoids. When the control system of a plant is

very extensive, it sometimes occupies a separate building known as the

_switch house_.

=Ques. What may be said with respect to the material for

switchboards?=

Ans. In order to avoid danger of fire from short circuits, the panel

should be made of some non-combustible material, such as marble,

slate, glass plates or earthenware tiles. If slate be used, care

should be taken to have it free from conducting veins, or it should be

marbleized, that is, subjected to a treatment that will fill up the

pores of the veins and thus prevent the absorption of moisture.

Wood is seldom used, except in cases where the switches, fuse

blocks, wire supports, etc., are all mounted on porcelain or

other incombustible material.

=Ques. How should the instruments and connections be arranged on a

switchboard?=

Ans. They should be arranged so as to provide the shortest possible

path for the current, and preferably always in the same direction, that

is, from right to left or from top to bottom, the connecting wires

being brought in on one side and out on the other, and the crossing of

wires avoided as far as possible.

All wires and current carrying parts should be kept far

enough apart at all points to prevent accidental contact or

the jumping across of the current where there is a great

difference of voltage. Such wires should be also kept at a

sufficient distance from screw heads, metal brackets, gas

pipes, water pipes, and other conducting bodies, in order to

prevent accidental grounds or short circuits.

All instruments and switches should be placed so as to be

conveniently accessible for observation and operation, and

sufficiently out of reach of accidental contact by persons;

otherwise they should be protected by some form of insulating

shield.

[Illustration: FIG. 500.--Small switchboard suitable for

two dynamos; view showing ammeters and voltmeters, switches, circuit

breakers, etc.]

=Ques. What type of switch is used on switchboards?=

Ans. The "knife" switch.

=Ques. Describe a small switchboard.=

Ans. Fig. 500 shows one suitable for two dynamos. At the top is a

voltmeter and two ammeters. Immediately below is a row of feeder

switches serving to connect and disconnect the various feeders with

and from the bus bars which are mounted behind the board. Below are two

rheostat handwheels, and two large switches connecting the dynamos with

the bus bars. VS is a voltmeter switch connecting the voltmeter with

various parts of the system. Below the voltmeter switch is a double

throw switch to transfer the bus bars from connection with the dynamo

switches to one with some other source of current such as a street

circuit, in the event of a breakdown. At the bottom are two circuit

breakers.

[Illustration: FIG. 501.--Diagram showing various connections

of voltmeter switch of the small switchboard shown in fig. 500.]

=Ques. Describe the voltmeter switch.=

Ans. Fig. 501 shows the connections, from which it can be seen that

the voltmeter can be connected with the terminals of either dynamo or

with the bus bars, or with either a central or remote part in the lamp

circuits.

Under ordinary conditions it remains connected to the circuit

at the central point of distribution. When one dynamo is

already in circuit, however, and it becomes necessary to

connect up the other one, the voltage of the latter must be

the same as that at the bus bars. Accordingly, connections

are provided to the voltmeter switch such that the attendant

can compare the voltages at the dynamo terminals and bus bars

before closing the dynamo switch. All the positive connections

are on one side of the circle swept by the switch and all the

negative connections on the other side.

[Illustration: FIG. 502.--Roller-Smith, single pole, plain

overload circuit breaker. As its name indicates, the function of the

plain overload circuit breaker is to automatically interrupt the

circuit in which it is placed when the flow of current through it

exceeds the predetermined limit for which the apparatus is set. It is

the most common of all of the types and is utilized for the protection

of dynamos and motors and all other electrical apparatus which, by

reason of the conditions of operation, may become subject to loads

in excess of the normal. The single pole type may be used separately

for the protection of a single wire of a given circuit or grouped to

protect the two or more wires of one circuit, becoming in the latter

case the so called independent arm multipole apparatus. The action of

this type of circuit breaker is fully explained in fig. 491.]

HAWKINS PRACTICAL LIBRARY OF

ELECTRICITY

IN HANDY POCKET FORM PRICE $1 EACH

_They are not only the best, but the cheapest work published on

Electricity. Each number being complete in itself. Separate numbers

sent postpaid to any address on receipt of price. They are guaranteed

in every way or your money will be returned. Complete catalog of series

will be mailed free on request._

=ELECTRICAL GUIDE, NO. 1=

Containing the principles of Elementary Electricity, Magnetism,

Induction, Experiments, Dynamos, Electric Machinery.

=ELECTRICAL GUIDE, NO. 2=

The construction of Dynamos, Motors, Armatures, Armature Windings,

Installing of Dynamos.

=ELECTRICAL GUIDE, NO. 3=

Electrical Instruments, Testing, Practical Management of Dynamos and

Motors.

=ELECTRICAL GUIDE, NO. 4=

Distribution Systems, Wiring, Wiring Diagrams, Sign Flashers, Storage

Batteries.

=ELECTRICAL GUIDE, NO. 5=

Principles of Alternating Currents and Alternators.

=ELECTRICAL GUIDE, NO. 6=

Alternating Current Motors, Transformers, Converters, Rectifiers.

=ELECTRICAL GUIDE, NO. 7=

Alternating Current Systems, Circuit Breakers, Measuring Instruments.

=ELECTRICAL GUIDE, NO. 8=

Alternating Current Switch Boards, Wiring, Power Stations, Installation

and Operation.

=ELECTRICAL GUIDE, NO. 9=

Telephone, Telegraph, Wireless, Bells, Lighting, Railways.

=ELECTRICAL GUIDE, NO. 10=

Modern Practical Applications of Electricity and Ready Reference Index

of the 10 Numbers.

=Theo. Audel & Co., Publishers. 72 FIFTH AVENUE, NEW YORK=

[Transcriber's Note:

Inconsistent spelling and hyphenation are as in the original.]

End of Project Gutenberg's Hawkins Electrical Guide Number 2, by Hawkins

Hawkins Electrical Guide v. 02 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 9 / 9 章