CHAPTER XIII.

LIGHTNING PROTECTION IN ENGLAND.

In its essence there cannot be anything more elementary than the theory

of protection against lightning. It is simply to lay a metallic line

from the top of a building, or other object to be protected, into moist

ground, so as to make a path for the electric force, along which,

not finding impediments, it will travel freely, without causing the

least damage. But, like many other simple theories, their practical

execution is not without perplexities. The first of these, in regard

to conductors, arises from the existence of more or less considerable

quantities of metals, to be found in almost every building which

requires protection against lightning. As the use of metals, especially

iron, in the construction of dwellings, both exterior and interior,

is rapidly extending, this becomes a very important consideration

in planning the design of lightning conductors. Of equal moment is

a second point--that of the existence of water or great moisture

under the buildings, or part of them. This must decide invariably

the direction of the conductor towards the earth, and its depth

underground. There are many minor matters to be taken into account, but

these two may be laid down as the chief questions to be kept in view

in settling the best mode of application of any conductors under given

circumstances. It happens often enough that a proper solution as to

what is best is not a little difficult. Still, it can always be arrived

at by careful study, which must, however, be aided by experience.

Keeping always in view the fact that there is nothing whatever that

may be called ‘erratic’ in the manifestations of the electric force,

but that it acts under a ruling principle as strict as that governing

the law of gravity, the first point in designing the protection of any

building will be to clearly ascertain what path the lightning will take

on its course from the clouds to the earth. It is absolutely certain

that the electric force will make its way through materials, termed

good conductors, which allow it free passage, and avoid those of the

opposite class, or bad conductors, the character of every substance on

earth being well known as regards these qualifications, although it

would not be easy to draw sharp lines of demarcation, all conductivity

being relative and not absolute. Looked at in this way, the fundamental

one in the application of lightning conductors, the simplest object for

protection will be a pyramid of stone, such as the Egyptian obelisk,

popularly called ‘Cleopatra’s Needle,’ erected on the Thames Embankment

in the summer of 1878. Stone being a bad conducting material, all that

is necessary to protect it against lightning, provided there is no

metal whatever near it, is to run a thin strip or rope of copper from

the summit to the base, and down into moist earth. Although fragile,

the strip of copper, if uninterrupted and rooted in moisture, will in

this case form an absolute protection. The question assumes another

aspect if, instead of a stone pyramid, a tall factory chimney, not

very dissimilar in outward form, is given as an object for protection.

Here there enters another element. A tall pile of bricks is as bad a

conductor of electricity as a solid mass of stone, but the mass of

bricks constituting a factory chimney is hollow, and the cavity being

filled with smoke and mineral fumes, which are more or less good

conductors of the electric force, the artificial path laid for the free

passage of lightning has to surpass in acceptability the natural one.

In other words, the copper rod laid alongside the factory chimney, to

secure it against damage from lightning, must be considerably thicker

than the one which will protect the simple stone pyramid. It is this

principle which has to be followed all through in the application

of conductors. They must form, in one word, the best path which can

possibly be made for the electric force.

The system employed by Mr. R. S. Newall, F.R.S., for the construction

and erection of lightning conductors is probably the most complete--and

certainly the most representative--of the various methods in vogue in

England. The special study Mr. Newall has made of the subject in all

its bearings, both theoretical and practical, added to the fact of his

possessing at his extensive cable works at Gateshead such exceptional

facilities for the production of copper ropes and bands composed of the

purest metal, render him one of the first authorities on all matters

connected with the application of lightning conductors to buildings. In

describing, therefore, the English method, reference will chiefly be

made to this gentleman’s apparatus and inventions.

The function of a lightning conductor is twofold. In the first

instance, it operates as a medium by which explosions of lightning,

or, to speak more accurately, disruptive discharges of electricity,

are led to the earth freely, and without the risk of their acting

with mechanical force, as they invariably do when compelled to pass

on their way to the earth through so-called non-conductors, that is

to say, bodies possessed of low conductivity, such as the atmosphere,

wood, stone, &c. In the second instance, the conductor acts as a means

whereby the accumulation of electricity existing in the atmosphere

is quietly drawn off and carried noiselessly into the earth, and

dissipated in the subterraneous sheet of water beneath it. Now this

accumulation of electricity, always greatly intensified during a

thunderstorm, invariably seeks the easiest road to earth; this road is

technically called ‘the line of least resistance.’ This line of least

resistance is influenced by various circumstances; the resistance of

any line may be lessened by the presence of streams of warm vapour or

rarefied air such as would come from chimneys, from barns or stacks

containing new hay; by a column of smoke, or by the presence of tall

trees moist from rain. It is not always easy to find the reason why

the lightning takes any particular path, but one thing is certain,

that is, it acts under certain fixed principles, and does not take any

particular route by chance, but always because it is the line of least

resistance. What the lightning conductor really does is to prevent the

possibility of an electric discharge within a certain district, for

instance, in the interior of a house or other building.

From the above remarks, it will easily be seen that lightning

conductors should be made of materials possessing the highest possible

power of conductivity, and be large enough to carry off the heaviest

electric discharge that is ever likely to fall upon them. The various

metals being by far the best conductors of electricity, it follows that

the lightning conductor must be constructed of metal of some kind.

But even metals differ to a great extent in their conducting powers,

as has been shown in a previous chapter. There are, however, only two

metals which are practically available for use as lightning conductors,

namely, iron and copper, and after repeated experiments Mr. E. S.

Newall has arrived at the conclusion that a conductor made of copper

of adequate size is the best--and, in the end, the cheapest--means

of protecting buildings from the effects of lightning. The relative

conductivity of iron and pure copper being as six to one, it follows

that if a copper cable or bar of a given size be sufficient, an

iron cable or bar ought to weigh six times as much per lineal foot

in order to be equally safe. It may be added, that while copper is

more expensive, weight for weight, than iron, it is not so liable to

oxidise; nor, on account of its higher conducting power, is it so

easily fused. The comparative smallness of its mass renders it far more

manageable than iron, and does not interfere with the architectural

features of the building on which it is used. On the contrary, it is

readily adapted to curves and angles.

It may therefore be taken for granted that, almost without exception,

pure copper is the best material that can be used in the construction

of lightning conductors.

[Illustration: Fig. 19.]

[Illustration: Fig. 20.]

[Illustration: Fig. 21.]

The size of the terminal rod or point used in Mr. Newall’s method

varies in length and diameter according to the extent and height of

the building to be protected. As a rule, they are from three to five

feet in length, and from five-eighths to three-quarters of an inch in

diameter; at the upper end they branch out as shown in fig. 19.

In conjunction with this terminal rod a short description of the

‘Auffangstange,’ or ‘reception rod’ of the Germans, may be given.

This ‘reception rod’ (see fig. 21) is made of iron, and varies in

length from ten to thirty feet. It consists of two parts, the higher

part, which measures two-thirds of the whole length, is fastened by a

flange to the lower part of the rod. In fixing this German ‘reception

rod,’ its height and weight have to be taken into consideration. It is

generally made fast by two strong staples, _b_ and _c_, as shown in

fig. 20, which pass through the king post of the roof and are fastened

behind by screw-nuts. The part marked _d_ rests in the lower ring _c_

so that it cannot sink, and the extreme end passes through this ring

_c_ and is screwed tightly to the nut _e_; _f_ is a cap to prevent the

rain getting into the roof.

It is much to be regretted that not only professors and amateurs

studying the manifestations of the electric force, but even learned

societies, such as the French ‘Académie des Sciences,’ should have

spread so many imaginative theories about this ‘reception rod.’ At the

bottom of all was the fancy, not often declared, but still visible in

its expression, of the metallic conductor possessing some occult power

of _attracting_ lightning. In France, as well as in Germany and Italy,

there existed for a long time, and to some extent still exists, quite

a mania for erecting huge rods, such as that shown in the engraving

(see fig. 21), on the top of buildings, the general belief being that

the more high-towering the greater would be the ‘area of protection.’ A

little common sense, brought to the aid of fanciful imaginings, should

have taught the supporters of this ‘area-of-protection’ theory that

it was absolutely untenable. The electric force, seeking its nearest

path to the earth, could not be expected to diverge from it through the

action of a rod raised somewhat higher than the surrounding building;

and the proper method clearly was to bring the metal everywhere as

near to any possible emanation of the force, whether lateral or

vertical, as could be done. Besides being really of no use, except

in rare instances, such as the neighbourhood of high trees, these

tall rods formerly employed, and still frequently seen on the roofs of

buildings, had the detriment of being unsightly, while at times they

were positively dangerous. Instances occurred in which a high wind

threw them down from their elevated position into the road below, on

the heads of passers-by. Thus two persons were killed in Paris in the

summer of 1830 by the fall of a gigantic ‘tige’ from the steeple of

the church of St. Gervais. Either at the same moment, or immediately

before, a stroke of lightning fell upon the church in its lower part,

away from the conductor, making a hole in one of the walls, and then

escaping, without doing further damage, by some iron water-pipes

running underground. The conductor in this case had been constructed

on the model approved by the ‘Académie des Sciences,’ but the accident

conclusively showed that there was no trust to be placed in any mere

theoretical calculations as to the extent of the ‘area of protection.’

A noteworthy example of the fallacy of the ‘area-of-protection’ theory

is to be found in the case of the explosion at the powder magazine

at the Victoria Colliery, BurntclifFe, Yorkshire, which was struck

by lightning and destroyed on August 6, 1878. The instance is also

instructive as showing how important it is that copper conductors

should possess the highest possible conductivity--i.e. be made of the

best and purest copper.

The magazine was an oblong building of brick, nine feet long, five feet

wide, and six feet high (internal dimensions), and it had a uniform

thickness of three bricks. At one end was a heavy iron door, and at

the other a lightning conductor, consisting of a copper-wire rope

seven-sixteenths of an inch in diameter. The point of the terminal rod

was about thirteen feet above the top of the building, and a similar

length was carried into the ground and terminated in clayey soil. The

conductor was fixed to a pole distant about two inches from the end of

the building opposite to that in which the iron door was fixed. _It

was not connected with the iron door in any way._ At the time of the

explosion the magazine contained about 2,000 pounds of gunpowder.

Major Majendie, H.M.’s Chief Inspector of Explosives, in his official

report ascribed the accident to the fact of the iron door being

unconnected with the lightning conductor, and in doing this he was

doubtless right, but only to a limited extent. The author of this work

visited the colliery shortly after the explosion, and found that the

conductor--the weight of which was about one pound per yard--had been

fastened to the pole, which was about twenty-one feet high, by two

glass insulators, and that the conductor was not connected with the

building. On testing the copper rope which formed the conductor, its

conductivity was found to be only 39·2 instead of 93 or 94 per cent.

The conductor, therefore, was but little better than if it had been

made of iron, and, even supposing it had been made of good copper, it

was of too small a size. It should have been of double the weight, and

_not_ insulated from the pole. In order to be thoroughly efficient it

ought to have been brought down the pole, carried through under the

roof, down the iron doorpost, and so into the ground.

According to the French theory, that the ‘area of protection’ afforded

by a lightning conductor is the space contained within the circular

area of a radius double the height of the conductor, the magazine was

thoroughly secured, for the conductor was twenty-one feet high, and the

building only nine feet long, five feet broad, and six feet high. This

case, however, with many others, entirely controverts this theory, and

shows very forcibly the fallacy of an argument that at one time was

accepted almost as an axiom.

One other case of more recent date may be instanced. At Cromer, in

Norfolk, the church--a fine perpendicular building of flint and

freestone, having a tower 159 feet high--was damaged by lightning in

August 1879. During a thunderstorm the lightning struck one of the

pinnacles with considerable force, although on another pinnacle, only

twenty-seven feet six inches distant, a good copper conductor, having

a diameter of five-eighths of an inch, was fixed. On testing the

conductor by means of a galvanometer, it and the earth connection were

found to be in thoroughly good order. After what has been said, comment

on this last example is needless.

[Illustration: Fig. 22.]

The general disposition and adjustment of a lightning conductor demands

the greatest care and consideration. No hard and fast rules can be

laid down, for each individual case must be studied and elaborated by

itself, especially in the instance of large structures, where much

depends upon style, outline, and other details. The main point is that

_every_ part of the building shall be placed beyond the possibility of

being damaged by a disruptive discharge of electricity.

It has been stated previously that the lightning invariably follows

the line of least resistance, and that this line may be influenced by

the presence of streams of warm vapour, columns of smoke, &c., which,

escaping into the air, furnish a ready path for the electric discharge.

Consequently it sometimes happens that a building or barn may be struck

although it be provided with a lightning conductor. In order to

explain this it must be borne in mind that the line of least resistance

is not always the shortest line mathematically. The accompanying

illustration (fig. 22) is an example to the point. It represents a barn

furnished with a lightning conductor and filled with new-made hay,

which is a better conductor of electricity than the material of which

the barn is constructed. This hay is giving off the stream of warm

vapour which is pouring out of the opening at the end, and forms an

invisible band of conducting matter between the thunder-cloud and the

barn, as marked out in the engraving by the dotted lines, the direction

of the wind being shown by the arrow and the trees. Under these

circumstances the discharge of lightning would naturally follow the

path between _c_ and _d_ in preference to the shorter route between _a_

and _b_, because the former is the line of least resistance between the

cloud and the earth. Thus the barn--although furnished with a conductor

in good condition--would most likely be set on fire, or otherwise

damaged. The same deflection of the lightning-stroke might be caused by

a column of smoke, or by the fact of one portion of the building being

moistened by the rain and the other kept dry; an occurrence that might

easily happen when a strong wind is blowing during a storm.

In order to ensure complete protection, the conductor on the barn

should have been carried along the ridge and down the edges of the roof

at each gable. By this means the stroke of lightning would have been

intercepted.

The engraving on the next page shows a design for the protection of a

large detached mansion by means of a multiplication of short points

or terminal rods fixed on all the prominent features of the building.

The conductor is carried along the ridges in every direction, and down

the edges of the roof at each gable. Generally it is sufficient to

have two descending conductors, but occasionally the conformation of

the building or the nature of the ground renders necessary the use of

even more. It is imperative, for obvious reasons, that the descending

portion of the lightning conductor shall be carried from the roof

to the ground by the shortest possible route, and placed in perfect

electrical contact with the earth in the manner to be indicated in a

succeeding chapter.

[Illustration: Fig. 23.]

The projecting points of the conductor are drawn in fig. 23 larger

than they need be, in order to show them more clearly, distinguishing

them from the rest of the building. The same has been done with the

copper rod, running from the roof to the ground and thence into the

earth. In reality a conductor may be made perfectly safe, and yet

all but invisible to the naked eye. For private houses and buildings,

a rope made of copper ought to be at least five-eighths of an inch

in diameter, for a copper rod of half an inch in diameter has never

been known to be fused. For chimneys of manufactories, where gases are

liable to corrode the rope, it had better be a little thicker. Such

copper ropes as those manufactured by Messrs. R. S. Newall and Co.,

five-eighths of an inch in diameter, weighing two-thirds of a pound

per foot, and having a conductivity of 93 per cent., have never been

known to fail in protecting even the largest buildings. It is supposed

by some writers that the value of the conductor is in proportion to

the amount of surface of metal exposed. This, however, is a mistake,

for the conductivity depends on the weight per foot of metal used, the

purity in both being equal. Wire-rope is used simply because it is

so pliable that it is easily handled, and can be made of any length

required without joints.

[Illustration: Fig. 24.]

In fig. 24 is given an illustration of a small detached house, in which

the arrangement of the lightning conductor is indicated by the dark

lines. The method followed is exactly the same in principle as that

employed for the mansion just described. A terminal rod is placed upon

each chimney. These terminal rods are connected with each other by a

copper-rope conductor which is carried along the ridges and gables

of the roof, thus constituting a similar arrangement to the French

‘ridge-circuit’ (_circuit des faîtes_), with the additional advantage

of being far lighter and more sightly. The copper conductor descends

to the earth down the angle formed by the projecting entrance to the

house. By this means every corner of the building is protected; an

important matter in all detached buildings, and especially when they

happen to stand among trees. The preference of the electric force for

trees as its path to the earth in the absence of metal or other bodies

of higher conductivity than trees, has probably no other ground than

their being full of moisture; still this is a disputed question.

Fig. 25 exhibits a slightly different method of arranging the lightning

conductor. In this case the ridges of the roof are surmounted by

ornamental iron-work, instead of the usual terra-cotta, or earthenware,

tiles. This iron-work is utilised and carefully connected with the

conductor. The chimneys, in place of being fitted with terminal rods,

are provided with cast-iron caps--as shown in the engraving--to which

the conductor is attached. The conductor, after descending to the

ridge, is led along it and down the edges of every gable, and is

finally carried down to the ground and connected with the earth in the

usual manner. It is of course absolutely necessary that all masses of

metal, such as gutters, waterspouts, rain-pipes, &c., should be brought

into connection with each other and with the conductor, in order that

the house may constitute one electrically homogeneous body.

It was for a long time held that the protection of churches against

lightning offered special difficulties. This arose mainly from the

constant reports of churches being struck, often when they were

believed to be protected, whereas the accidents arose from the

conductor not being properly fitted. It is even now too often

forgotten that all so-called ‘conductors’ of the electric force are

only so in relation to ‘non-conductors,’ and that, strictly speaking,

all things on earth are to some extent conductors and to some extent

non-conductors. This being kept clearly in view, there is no more

difficulty in protecting the largest cathedral against lightning in the

most efficient manner than in similarly guarding the smallest cottage.

[Illustration: Fig. 25.]

A case in point occurred in May 1879. The steeple of the church at

Laughton-en-le-Morthen was struck by lightning and damaged, the

lightning conductor being thrown down and broken into two pieces. A

correspondence on the subject ensued in the _Times_, and Mr. R. S.

Newall had the remains of the conductor examined, with the following

result:

‘The spire is 175 feet in height, and it had attached to it a thin

tube, made of corrugated copper, about seven-eighths of an inch in

external diameter and five-eighths internal. The copper is about

one-thirty-second of an inch in thickness, and it weighs about one and

a quarter pound per yard. It is made in short lengths, joined together

by screws and coupling pieces, but there is no metallic contact

whatever between the pieces, which are much corroded.

‘The conductor appeared to be fastened to the vane. It was not in

contact with the building, which it ought to have been, but it was kept

at a distance of about two-and-a-half inches from it by twenty-one

insulators. The earth contact was obtained by bending the tube and

burying it in the ground at a depth of from six inches to eighteen

inches, the soil being dry loose rubbish; the length of the earth end

was only three feet, with two short pieces of about a foot in length

each tied to the tube by thin wires, thus forming altogether a most

inefficient conductor. It was placed in a corner formed by a double

stone buttress, which came between the conductor and a lead-covered

roof attached to the spire, the distance between the conductor and the

lead roof being about six feet six inches.

‘The lightning appears to have come down the conductor a certain

distance, and, finding the road to earth bad, it passed through the

buttress, dislodging about two cart-loads of stone, and then came down

the cast-iron down pipes leading from the lead-covered roof and so to

earth.’

Mr. Newall, in writing to the _Times_, goes on to say:—

‘Now if the conductor had been made of copper-wire rope, weighing about

two pounds per yard, and fixed in contact with the spire, without

insulators and with a proper earth contact, no damage whatever would

have been sustained by the building; and if the conductor had been

tested periodically by an expert he would have shown whether the

conductor was good or useless. This examination ought to be insisted

on, as the earth connection is often wilfully destroyed; but I have

never in all my experience known a building which had a conductor

properly fixed to suffer damage from lightning.’

What is really required is to make a lightning conductor of sufficient

calibre to carry down the electric discharge, however great it may be,

from the summit of the building into the earth, and that the earth

contact should be above suspicion and thoroughly good in all seasons.

[Illustration: Fig. 26.]

[Illustration: Fig. 27.]

[Illustration: Fig. 28.]

Fig. 26 shows a plain and simple design for protecting an ordinary

church. The conductor in the case of churches and all other high or

extensive buildings ought invariably to be made of copper rope, other

metals of less conductivity, such as iron, being inadmissible, since

their employment would necessitate the use of ponderous masses of

metal, which would be not only unsightly, but extremely heavy, and

difficult to manipulate successfully. In the accompanying engraving

(fig. 27) lent by the Society for Promoting Christian Knowledge, is

shown a somewhat more complex structure and the method of arranging

the conductors thereon. In this case there is a conductor attached to

each spire, leading to and connected with the metal-work of the roof

and gutters. On the gable _c_, and the transept gables _d e_, there

are fixed three conductors which unite in the centre of the roof, from

which they are carried down to the gutters. The same arrangement is

followed for the smaller gables _f g h_. The water-pipes and gutters

being connected with the conductors, these latter are carried down the

side to the earth. It need scarcely be explained how important it is

that all metal ornaments on the ridges of churches, as well as other

buildings, should either be connected with the general conductors or,

in the case of extensive buildings, with a conductor that is carried

straight to the earth, as shown in fig. 28. In the case of the finials

so often found on Gothic structures, it is necessary to splice the

conductor round the bottom of the finial, as shown in fig. 29. If,

instead of placing terra-cotta tiles along the ridges, a cresting of

fancy iron-work is fixed there, the expense of running a conductor

along the ridges will be saved.

[Illustration: Fig. 29.]

[Illustration: Fig. 30.]

The various methods of fixing weathercocks on to the terminal rod are

fully explained in another chapter. Fig. 30 shows the best arrangement

for connecting the conductor to the terminal rod on a church spire. The

copper rope which forms the conductor is spliced round the terminal

rod at the bottom of the finial, and as an additional security round

the base of the vane rod, which in this instance also serves as the

terminal rod of the lightning conductor.

There has been much controversy as to whether it is better to carry

the conductor from the roof to the ground inside a building than

outside the walls. As a matter of fact, it is a question of very small

importance which way the conductor is carried, so long as it arrives

at the ground by the shortest possible route. Benjamin Franklin, to

judge from many expressions in his works, seems to have been decidedly

in favour of the inside plan, which was adopted almost universally in

France and on the Continent in general on the first introduction of

lightning conductors. But the method was soon abandoned, owing partly

to a witty saying of Voltaire, constantly quoted to this day. Speaking

of the death of the unfortunate Professor Richman, of St. Petersburg,

killed while experimenting with electric discharges from the clouds,

Voltaire remarked, ‘There are some great lords whom one should only

approach with extreme precaution: lightning is such a one.’ A mere

jocular exclamation, it would have had no great force except in France,

where a _bon mot_ may cause the fall of a king and the dethronement of

a dynasty. In regard to Voltaire’s pleasantry about not approaching

too close to lightning, it really had in great part the effect of

preventing conductors to be laid inside the houses. Even such calm

philosophers and men of science as Professor Arago quote Voltaire with

approval. ‘I feel inclined,’ he remarks in his ‘Meteorological Essays,’

‘to admit that the illustrious author (Voltaire) may be right, when I

remember a case that occurred in the United States.’ The case relied

upon, a very curious one, was as follows, in Arago’s own words.

‘Lightning,’ Professor Arago tells his story, ‘having struck a rather

thick rod erected on a Mr. Raven’s house, in Carolina, United States,

afterwards ran along a wire carried down the outside of the house to

connect the rod on the roof with an iron bar stuck in the ground. The

lightning in its descent melted all the part of the wire extending

from the roof to the ground-storey, without injuring in the least the

wall down which the wire was carried. But at a point intermediate

between the ceiling and the floor of the lower storey things were

changed: from thence to the ground the wire was not melted, and at

the spot where the fusion ceased the lightning altered its course

altogether, and, striking off at right angles, made a rather large

hole in the wall and entered the kitchen. The cause of this singular

divergence was readily perceived, when it was remarked that the hole

in the wall was precisely on a level with the upper part of the barrel

of a gun which had been left standing on the floor leaning against the

wall. The gun barrel was uninjured, but the trigger was broken, and a

little further on some damage was done in the fire-place.’ Commenting

upon this case, Professor Arago goes on: ‘Here the lightning went off

horizontally through the wall, in order to strike a fowling-piece

standing upright in the kitchen. How much injury might not have

resulted from this lateral movement, if the lightning had not had to

traverse a thick wall?’ Consequently, he argues, Voltaire is right in

his jocular-oracular declaration about the perils of indoor lightning

conductors, in their being ‘great lords’ dangerous to approach.

It is really difficult to understand how a man like Professor Arago

could be misled into such false reasoning as this about an accident

which, in itself, was of the simplest, and of the very easiest

explanation. That the stroke of lightning falling upon Mr. Raven’s

house, in Carolina, should have melted the wire of the conductor

points to one cause, and to one only, namely, that there was no proper

earth connection. Had it existed, the wire, although thin, could not

possibly have been ‘melted all the part extending from the roof to the

ground-storey,’ nor could the electric force have left its appointed

path to seek a better one through a wall, and, still more astounding,

‘striking off at right angles.’ It is abundantly clear that such

cases, and others to the same effect, brought against the fixing of

lightning-conductors inside the walls of buildings, prove absolutely

nothing. What is beyond controversy is, that a good conductor, in

proper condition, is absolutely harmless to surrounding objects,

including human beings. A man, even with a ‘fowling-piece’ in his

hands, might lean full length against half-an-inch copper rod carrying

off a heavy stroke of lightning into ‘good earth’ without so much as

becoming aware of the passing of the electric discharge. If certainly a

‘grand seigneur,’ as Voltaire remarks, the electric force has this in

common with some of the greatest of men, of not wasting its time, but

following a clear aim.

[Illustration: Fig. 31.]

[Illustration: Fig. 32.]

A very common, and, it may be added, a very mischievous opinion is

prevalent, that lightning conductors should be carefully insulated

from the buildings to which they are attached, and consequently many

conductors are made to pass through insulators of glass and other

materials of low conductivity. This practice of separating the building

from the lightning conductor is not only utterly useless but positively

dangerous. It is not unusually thought that by insulating the conductor

the electric discharge will be prevented from entering the building.

Such an idea is _ipso facto_ absurd, for it is preposterous to suppose

that a flash of lightning which can travel through thousands of feet of

air--itself a very bad conductor of electricity--and then shatter to

pieces the most compact bodies, would be stopped in its course by means

of a few inches of glass, or a few feet of air. It may therefore be

confidently asserted that no insulator can possibly be made that would

be capable of preventing the electric discharge leaving the lightning

conductor provided it could find an easier path leading to the earth.

Mr. Phin, in his work on ‘Lightning-Rods’ says very pertinently:--But

not only are insulators worthless--they are positively dangerous if

the principle upon which they are adopted is fully carried out, which,

however, is but rarely done. A little consideration will show this.

Thus, if a house be furnished with a carefully-insulated lightning-rod,

and should also have any large surface of metal, such as a tin roof,

an extensive system of gutters, or such like, connected with it, it

is easy to see that the house must resemble a large Leyden jar, of

which the tin roof, or other mass of metal, constitutes one coating,

and the lightning-rod and the earth constitute the other, while the

insulators and the dry material of the house represent the glass of the

jar. If both the outside and the inside of this jar (the tin roof and

the earth) had been connected together, it would have been impossible

to have brought one coating into a condition opposite to that of the

other. But the rod being carefully insulated from the roof, it is

obvious that the inductive action of the cloud will bring the roof

and the earth into opposite conditions; and if a man were to form the

path of least resistance between them, the discharge would take place

through his body, and he would probably be destroyed. It is obvious,

then, in the first place, that lightning-rods should be connected with

all large masses of metal which may exist in or upon the house, such

as metallic roofs, tin or iron gutters, or pipes, iron railings, &c.

In the second place, the rod should be attached to the house in the

neatest and least obtrusive manner possible.’

[Illustration: Fig. 33.]

It is indeed desirable for various reasons that the copper rope or band

forming the lightning conductor should be affixed to the building in

the neatest and least obtrusive manner possible. The conductor may be

fastened by means of ordinary metal staples made of stout copper wire.

A better method however is indicated in figs. 31 and 32, one showing

the rope conductor formed of forty-nine wires, usually employed by

Messrs. R. S. Newall and Co. for the protection of ordinary houses

and buildings, and the other the copper band used by them for the

same purpose. This fastening is simply a strap of copper bent to the

required shape and pierced with two holes, by means of which it is

fixed to any building by copper nails or screws. This method possesses

several advantages; it is very sightly and neat, it can be easily

applied without injury to any building, and as it allows the conductor

a certain freedom of movement, it readily permits the contraction and

expansion caused by the variations of temperature. The band conductor

shown here is one inch wide by one-eighth of an inch thick, and weighs

·44 pound per foot. The rope conductor, although it appears less, has

more metal in it; it measures five-eighths of an inch in diameter,

and weighs ·67 pound. Fig. 33 shows a different mode of attaching the

lightning conductor. It is generally used for the heavier ropes.

Fig. 34 exhibits an apparatus called a ‘tightening screw.’ It is used

for making the conductor taut when it gets loose from any cause. The

diagram explains itself, so there is no necessity for describing it.

The tall chimney shafts of factories and similar buildings, from which

smoke or rarefied air escapes, are peculiarly liable to be struck by

lightning. This is principally due to the current of smoke or warmed

air forming, with the soot in the chimney, a medium conductor leading

to the iron-work of the furnace or stove beneath, but ending there--a

result that must be carefully avoided; for although a conductor that

leads past any object is a protection (provided always that it has a

good earth connection), a conductor that leads to an object, and ends

in that object, is a distinct danger. It is therefore necessary to

offer to the electric discharge a better conductor, able to intercept

it and convey it safely to earth on the outside of the shaft.

[Illustration: Fig. 34.]

[Illustration: Fig. 35.]

The mode by which this is generally accomplished in England is by

fixing a copper terminal rod (four or five feet long), on to the side

of the top of the chimney shaft. This method is open to one serious

objection: if the wind should happen to blow the stream of smoke or

heated vapour in a direction opposite to the terminal rod, the electric

discharge might go down the chimney shaft and effect considerable

damage. By far the best plan is that shown in fig. 35. It consists

simply of an iron or copper cap, to the centre of which is attached

the terminal rod. This latter, however, is by no means essential, and

may be said to be merely placed on the top for ornament. A structure

of such small circumference really wants no terminal rod, the most

important thing being to provide a copper rope or band conductor of

sufficient size to carry any electric discharge in safety to the

ground. It will conduce greatly to the strength and stability of such

a conductor if it be built up together with the chimney shaft, and

fastened into the brickwork by clamps on the plan shown in fig. 36. A

conductor of this kind should be made of copper rope or band of much

greater calibre and weight than that used for ordinary buildings. That

made of seven solid wires twisted together (see fig. 37) being the best.

[Illustration: Fig. 36.]

A theory propounded some years ago by the late Prof. Clerk Maxwell,

F.R.S., one of the most eminent physicists in Europe, deserves some

notice here, perhaps more from its ingenuity than its practical

accuracy. On investigation, it proves to be a revival of an old

presumption that it is possible to protect a powder magazine or other

building from the effects of lightning by having its roof, walls, and

ground floor surrounded with a covering of sheet metal, or a network of

lightning conductors, and disconnecting the said covering or network

from the earth, or even insulating it by means of a layer of asphalt or

some similar substance. Prof. Clerk Maxwell argues that the presence of

a lightning conductor induces a larger number of electric discharges

in its immediate neighbourhood than would occur provided no conductor

was present, although at the same time these discharges are rendered

less intense and smaller by reason of the existence of the conductor.

Therefore, it is possible that fewer discharges take place in the area

just outside the radius of the conductor. Reasoning from this, Prof.

Clerk Maxwell considers that an ordinary lightning conductor tends

rather to mitigate the accumulation of electricity in the clouds than

to protect the building on which it is placed.

[Illustration: Fig. 37.]

He says: ‘What we really wish to prevent is the possibility of an

electric discharge taking place within a certain region--say, in the

inside of a gunpowder manufactory. If this is clearly laid down as our

object, the method of securing it is equally clear.

‘An electric discharge cannot occur between two bodies unless the

difference of their potentials (i.e. their electrical conditions)

is sufficiently great, compared with the distance between them. If,

therefore, we can keep the potentials of all bodies within a certain

region equal, or nearly equal, no discharge will take place between

them. We may secure this by connecting all these bodies by means of

good conductors, such as copper wire ropes, but it is not necessary

to do so, for it may be shown by experiment that if every part of the

surface surrounding a certain region is at the same potential, every

point within that region must be at the same potential, provided no

charged body is placed within the region.

‘It would therefore be sufficient to surround our powder-mill with a

conducting material, to sheath its roof, walls, and ground-floor with

thick sheet-copper, and then no electrical effect could occur within

it on account of any thunderstorm outside. There would be no need of

any earth connection. We might even place a layer of asphalt between

the copper floor and the ground, so as to insulate the building. If

the mill were then struck with lightning, it would remain charged for

some time, and a person standing on the ground outside and touching the

wall might receive a shock, but no electrical effect would be perceived

inside, even on the most delicate electrometer. The potential of

everything inside with respect to the earth would be suddenly raised or

lowered as the case might be; but electric potential is not a physical

condition, but only a mathematical conception, so that no physical

effect would be perceived.

‘It is therefore not necessary to connect large masses of metal, such

as engines, tanks, &c., to the walls, if they are entirely within the

building. If, however, any conductor, such as a telegraph-wire, or a

metallic supply-pipe for water or gas, comes into the building from

without, the potential of this conductor may be different from that

of the building, unless it is connected with the conducting shell of

the building. Hence the water or gas supply-pipes, if any enter the

building, must be connected to the system of lightning conductors; and

since to connect a telegraph-wire with the conductor would render the

telegraph useless, no telegraph from without should be allowed to enter

a powder-mill, though there may be electric bells and other telegraphic

apparatus within the building. I have supposed the powder-mill to

be entirely sheathed in thick sheet copper. This, however, is by no

means necessary in order to prevent any sensible electrical effect

taking place within it, supposing it struck by lightning. It is quite

sufficient to enclose the building with a network of a good conducting

substance. For instance, if a copper wire, say No. 4, B. W. G. (0·238

inch diameter) were carried round the foundation of the house, up each

of the corners and gables, and along the ridges, this would probably

be a sufficient protection for an ordinary building against any

thunderstorm in this climate. The copper wire may be built into the

wall to prevent theft, but should be connected to any outside metal,

such as lead or zinc on the roof, and to metal rain-water pipes. In the

case of a powder-mill, it might be advisable to make the network closer

by carrying one or two additional wires over the roof and down the

walls to the wire of the foundation. If there are water or gas-pipes

which enter the building from without, these must be connected with

the system of conducting wires; but if there are no such metallic

connections with distant points, it is not necessary to take any pains

to facilitate the escape of the electricity into the earth; still less

is it advisable to erect a tall conductor with a sharp point in order

to relieve the thunder-clouds of their charge.

[Illustration: Fig. 38. ARRANGEMENT OF PROFESSOR CLERK MAXWELL’S

LIGHTNING CONDUCTORS.]

‘It is hardly necessary to add, that it is not advisable, during a

thunderstorm, to stand on the roof of a house so protected, or to stand

on the ground outside, and lean against the wall.’

Prof. Clerk Maxwell, in a letter to Mr. Charles Tomlinson, F.R.S., the

author of ‘The Thunderstorm,’ says: ‘My plan is to convert a building

into a closed conducting vessel by a sufficient number of wires

enclosing it. For an ordinary house, a skeleton of its edge is quite

enough. A _a_ may be a zinc ridge, B _b_ and C _c_ water-gutters of

zinc or iron; but the pieces A B D, A C E, _a b d_, _a c e_, and the

circuit D E _e d_ should be of stout copper wire or rope, built into

the wall as a security against theft, but connected to every other

piece of metal on the outer surface of the house, and to every gas or

water-pipe which enters the house from without, but _not_ to any masses

of metal wholly within the whole, unless this is desirable for other

purposes.’

[Illustration: Fig. 39.]

Lightning Conductors: Their History, Nature, and Mode of Application · 第 13 / 16 章