CHAPTER XXX

COUPLING OF DYNAMOS

Series and Parallel Connections.--When it is necessary to generate a

large and variable amount of electrical energy, as must be done in central

generating stations, apart from the question of liability to breakdown, it

is neither economical nor desirable that the whole of the energy should

be furnished from a single dynamo. Since the efficiency of a dynamo is

dependent upon its output at any moment, or the load at which it is worked

(the efficiency varying from about 95 per cent. at full load to 80 per

cent. at half load), it is advisable in order to secure the greatest

economy in working, to operate any dynamo as near full load as possible.

Under the above circumstances, when the whole of the output is

generated by a single dynamo this can evidently not be effected, for

the load will naturally fluctuate up and down during the working

hours, as the lamps, motors, etc., are switched into and out of

circuit; hence, although the dynamo may be working at full load

during a certain portion of the day, at other times it may probably

be working below half load, and therefore the efficiency and economy

in working in such an arrangement is very low.

Ques. How is maximum efficiency secured with variable load?

Ans. It is usual to divide up the generating plant into a number of units,

varying in size, so that as the load increases, it can either be shifted

to machines of larger size, or when it exceeds the capacity of the largest

dynamo, the output of one can be added to that of another, and thus

the dynamos actually at work at any moment can be operated as nearly as

possible at full load.

Ques. What should be noted with respect to connecting one dynamo to

another?

Ans. It is necessary to take certain precautions (as later explained) in

order that the other dynamos may not be affected by the change, and that

they may work satisfactorily together.

Ques. What are the two methods of coupling dynamos?

Ans. They are connected in series, or in parallel.

In coupling dynamos in series, the current capacity of the plant is

kept at a constant value, while the output is increased in proportion

to the pressures of the machines in circuit.

When connected in parallel, the pressures of all the machines are kept

at a constant value, while the output of the plant is increased in

proportion to the current capacities of the machines in circuit.

Coupling Series Dynamos in Series.--Series wound dynamos will run

satisfactorily together without special precautions when coupled in

series, if the connections be arranged as in fig. 685.

The positive terminal of one dynamo is connected to the negative

terminal of the other, and the two outer terminals are connected

directly to the two main conductors or bus bars through the ammeter

A, fuse F, and switch S. If it be desired to regulate the pressure

and output of the machines, variable resistances, or hand regulators

R, R^1, may be arranged as shunts to the series coils as shown, so as

to divert a portion or the whole of the current therefrom.

Series Dynamos in Parallel.--Simple series wound dynamos not being

well adapted for the purpose of maintaining a constant pressure, are in

practice seldom coupled in parallel; the conditions or working, however,

derive importance from the fact that compound dynamos, being provided with

series coils, are subject to similar conditions when working in parallel,

which is frequently the case.

Ques. What may be said with respect to coupling two or more plain series

dynamos in parallel?

Ans. The same procedure cannot be followed as in the case of plain shunt

dynamos, for the reason that if the voltage of the dynamo to be coupled

be exactly equal to that of the bus bars when connected in parallel, the

combination will be unstable.

[Illustration: Fig. 685.--Diagram showing method of coupling series

dynamos in series. R and R' are two hand regulators which are placed in

shunt across the coil terminals to regulate the pressure and output of

the machine.]

Ques. Why is this?

Ans. If, from any cause, the pressure at the terminals of one of the

dynamos fall below that of the others, it immediately takes a smaller

proportion of the load; as a consequence, the current in its field coils

is reduced, and a further fall of pressure immediately takes place. This

again causes the dynamo to relinquish a portion of its load, and again

occurs a further fall of pressure. Thus the process goes on, until finally

the dynamo ceases to supply current, and the current from the other

dynamos flowing in its field coils in the reverse direction reverses its

magnetism, and causes it to run as a motor against the driving power in

the opposite direction to that in which it previously ran as a dynamo.

Under such circumstances the armature is liable to be destroyed if

the fuse be not immediately blown, and in any case it is subjected to

a very detrimental shock. This tendency to reverse in series dynamos

can be effectually prevented by connecting the field coils of all the

dynamos in parallel.

[Illustration: Fig. 686.--Diagram showing method of coupling series

dynamos in parallel. In the diagram A, A', are ammeters; F, F', fuses; S,

S', switches.]

Ques. How are the field coils of all the dynamos connected in parallel?

Ans. This is effected in practice by connecting the ends of all the series

coils where they join on to the armature circuit by a third connection,

called the "equalizing connection," or "equalizer," as shown in fig. 686.

Ques. What is the effect of the equalizer?

Ans. The immediate effect is to cause the whole of the current generated

by the plant to be divided among the series coils of the several dynamos

in the inverse ratio of their resistance, without any regard as to whether

this current comes from one armature, or is divided among the whole. The

fields of the several dynamos being thus maintained constant, or at any

rate being caused to vary equally, the tendency for the pressure of one

dynamo to fall below that of the others is diminished.

Shunt Dynamos in Series.--The simplest operation in connection with the

coupling of dynamos, and the one used probably more frequently in practice

than any other, is the coupling of two or more shunt dynamos to run either

in series or in parallel. When connected in series, the positive terminal

of one machine is joined to the negative of the other, and the two outer

terminals are connected through the ammeter A, fuses F, F', and switch S,

to the two main conductors or omnibus bars as represented in fig. 687. The

machine will operate when the connections are arranged in this manner,

if the ends of the shunt coils be connected to the terminals of their

respective machines.

Shunt Dynamos in Parallel.--The coupling of two or more shunt dynamos

to run in parallel is effected without any difficulty. This method of

coupling dynamos is one that is very frequently used. Fig. 688 illustrates

diagrammatically the method of arranging the connections. The positive

and negative terminals of each machine are connected respectively to two

massive insulated copper bars, shown at the top of the diagram, called

_omnibus bars_, through the double pole switches, S, S', and the double

pole fuses F, F'. Ammeters, A, A' are inserted in the main circuit of each

machine, and serve to indicate the amount of current generated by each.

An automatic switch or cutout, Ac, Ac', is also shown as being included

in the main circuit of each of the machines, although this appliance

is sometimes dispensed with. The pressure of each of the machines is

regulated independently by means of the hand regulators R, R', inserted

in series with the shunt circuit.

The shunt circuits are represented as being connected to the positive

and negative terminals of the respective machines, but in many cases

where the load is subjected to sudden variations, and when a large

number of machines is connected to the bus bars, the shunt coils

are frequently connected direct to these. In such circumstances

this method is preferable, as by means of it the fields of the idle

dynamos can be excited almost at once direct from the bus bars by

the current from the working dynamos; hence, if a heavy load come on

suddenly, no time need be lost in building up a new machine previous

to switching it into parallel. The pressure of the lamp circuit is

given by a voltmeter whose terminals are placed across the bus bars;

and the pressure at the terminals of each of the machines is indicated

by separate voltmeters or pilot lamps, the terminals of which are

connected to those of the respective machines.

[Illustration: Fig. 687.--Diagram showing method of coupling shunt dynamos

in series. The ends of the shunt coils may be connected to the terminals

of their respective machine, or they may be connected in series as shown.]

Ques. Describe a better method of parallel connection.

Ans. Better results are obtained by connecting both the shunt coils in

series with one another, so that they form one long shunt between the two

main conductors, the same as in fig. 687.

When arranged in this way, the regulation of both machines may be

effected simultaneously by inserting a hand regulator (R) in series

with the shunt circuit as represented.

[Illustration: Fig. 688.--Diagram showing method of coupling shunt dynamos

in parallel.]

Switching Dynamo Into and Out of Parallel.--In order to put an additional

dynamo in parallel with those already working, it is necessary to run

the new dynamo up to full speed, and, when it excites, regulate the

pressure by means of a hand regulator until the voltmeter connected to

the terminals of the machines registers one or two volts more than the

voltmeter connected to the lamp circuit, and then close the switch. The

load upon the machine can then be adjusted to correspond with that upon

the other machines by means of the hand regulator.

Ques. In connecting a shunt dynamo to the bus bars, must the voltage be

carefully adjusted?

Ans. There is little danger in overloading the armature in making the

connection hence the pressure need not be accurately adjusted.

It is, in fact, common practice in central stations to judge the

voltage of the new dynamo merely by the appearance of its pilot lamp.

Ques. How is a machine cut out of the circuit?

Ans. When shutting down a machine, the load or current must first be

reduced, by gradually closing the stop valve of the engine, or inserting

resistance into the shunt circuit by means of the hand regulator; then

when the ammeter indicates nine or ten amperes, the main switch is opened,

and the engine stopped.

By following this plan, the heavy sparking at the switch contacts is

avoided, and the tendency for the engine to race, reduced.

Ques. What precaution must be taken in reducing the current?

Ans. Care must be taken not to reduce the current too much.

Ques. Why is this necessary?

Ans. There is danger that the machine may receive a reverse current from

the other dynamos, resulting in heavy sparking at the commutator, and in

the machine being driven as a motor.

Ques. What provision is made to obviate this danger?

Ans. Dynamos that are to be run in parallel are frequently provided with

automatic cutouts, set so as to automatically switch out the machine when

the current falls below a certain minimum value.

Dividing the Load.--If a plant, composed of shunt dynamos running in

parallel, be subjected to variations of load, gradual or instantaneous,

the dynamos will, if they all have similar characteristics, each take up

an equal share of the load. If, however, as is sometimes the case, the

characteristics of the dynamos be dissimilar, the load will not be shared

equally, the dynamos with the most drooping characteristics taking less

than their share with an increase of load, and more than their share

with a decrease of load. If the difference be slight, it may be readily

compensated by means of the hand regulator increasing or decreasing

the pressures of the machines, as the load varies. If, however, the

difference be considerable, and the fluctuations of load rapid, it becomes

practically impossible to evenly divide the load by this means.

Under such circumstances, the pressure at the bus bars is liable to

great variations, and there is also liability of blowing the fuses

of the overloaded dynamos, thus precipitating a general breakdown. To

cause an equal division of the load among all the dynamos, under such

circumstances, it is needful to insert a small resistance in the armature

circuits of such dynamos as possess the straightest characteristics, or

of such dynamos as take more than their share of an increase of load.

By suitably adjusting or proportioning the resistances, the pressures at

the terminals of all the machines may be made to vary equally under all

variations of load, and each of the machines will then take up its proper

share of the load.

Coupling Compound Dynamos in Series.--Since compound dynamos may be

regarded as a combination of the shunt and series wound machines, and

as no special difficulties are encountered in running these latter in

series, analogy at once leads to the conclusion that compound dynamos

under similar circumstances may be coupled together with equal facility.

Ques. How are compound dynamos connected to operate in series?

Ans. The series coils of each are connected as in fig. 685, and the shunt

coils are connected as a single shunt as in fig. 687, which may either

extend simply across the outer brushes of the machines, so as to form a

double short shunt, or may be a shunt to the bus bars of external circuit,

so as to form a double long shunt.

[Illustration: Fig. 689.--Coupling compound dynamos in series; short shunt

connection. The dotted lines indicate the changes that would be made for

long shunt connection.]

Compound Dynamos in Parallel.--Machines of this type will not run

satisfactorily together in parallel unless all the series coils are

connected together by an equalizing connection, as in series dynamos.

The method of arranging the connections as adopted in practice, being

illustrated in fig. 690. By means of it idle machines are completely

disconnected from those at work.

Ques. How is the equalizer connected?

Ans. The equalizer is connected direct to the positive brushes of all the

dynamos, a three pole switch being fitted for disconnecting it from the

circuit when the machine to which it is connected is not working. The

two contacts of the switch are respectively connected to the positive

and negative conductors, while the central contact is connected to the

equalizer.

[Illustration: Fig. 690.--Diagram showing method of coupling compound

dynamos in parallel.]

Switching a Compound Dynamo Into and Out of Parallel.--If the

characteristics of all the dynamos be similar, and the connections

arranged as in figs. 690, or 691, the only precaution to be observed in

switching a new machine into parallel is to have its voltage equal, or

nearly equal to that of the bus bars previous to closing the switch. If

this be the case, the new machine will take up its due share of the load

without any shock.

[Illustration: Fig. 691.--Diagram showing another and better method

of coupling compound dynamos in parallel. With this arrangement the

idle machines are completely disconnected from those at work. The same

reference letters are common in both diagrams. S, S' are switches; F,

F' fuses; A, A' ammeters, which indicate the total amount of current

generated by each of the machines; AC, AC', automatic switches, arranged

for automatically switching out a machine in the event of the pressure at

its terminals being reduced through any cause; R, R,' are hand regulators,

inserted in the shunt circuits of each of the machines, by means of which

the pressures of the individual machines may be varied and the load upon

each adjusted. The pressure at the bus bars is given by the voltmeter V,

one terminal of which is connected to each of the bars; a second voltmeter

may be used, to give the pressure of any individual machine, by connecting

"voltmeter keys" to the terminals of each of the machines, or a separate

voltmeter may be used for each individual machine. The only essential

difference between figs. 690 and 691 is, that in fig. 690 the equalizer

is connected direct to the positive brushes of all the dynamos, while

in fig. 691 the equalizer is brought up to the switchboard and arranged

between the two bus bars, a switch being fitted for disconnecting it from

the circuit when the machine to which it is connected is not working.]

Ques. How is a compound dynamo, running in parallel, cut out of circuit?

Ans. The load is first reduced to a few amperes, as in the case of shunt

dynamos, either by easing down the engine, or by cutting resistance into

the shunt circuit by means of the hand regulator, and then opening the

switch. Previous to this, however, it is advisable to increase the voltage

at the bus bars to a slight extent, as while slowing down the engine

the load upon the outgoing dynamo is transferred to the other dynamo

armatures, and the current in their series coils not being increased in

proportion, the voltage at the bus bars is consequently reduced somewhat.

Equalizing the Load.--When a number of compound dynamos of various output,

size, or make, are running together in parallel, it frequently happens

that all their characteristics are not exactly similar, and therefore the

load is unequally distributed, some being overloaded, while others do not

take up their proper share of the work.

NOTE.--The action of an equalizing bar in equalizing the load on

compound dynamos run in parallel may be explained as follows: The

compound winding of a dynamo raises the pressure in proportion to

the current flowing through it, and if, in a system of parallel

operated compound dynamos without the equalizing connection, the

current given by one machine were slightly greater than the currents

from the others, the pressure of that machine would increase. With

this increase in pressure above the other machines, a still greater

current would flow, and so raise the pressure further. The effect is

therefore cumulative, and in time the one dynamo would be carrying

too great a proportion of the whole current of the system. With the

equalizing connection, whatever the current flowing from each machine,

the currents in the various compound windings are all equal, and so

the added pressure due to the compound winding is practically the

same in each machine. Any inequality in output from the machines is

readily eliminated by adjusting the shunt currents by means of the

shunt rheostats. When compound wound dynamos are operated in parallel,

the equalizer bar insures uniform distribution among the series coils

of the machines.

NOTE.--To secure the best results in parallel operation, dynamos

should be of the same design and construction and should possess as

nearly as possible the same characteristics; that is, each should

respond with the same readiness, and to the same extent, to any change

in its field excitation. Any number of such machines may be operated

in parallel. The usual practice is to connect the equalizer and the

series field to the positive terminal, though if desired, they may be

connected to the negative terminal; both however, must be connected to

the same terminal. The resistance of the equalizer should be as low

as possible, and it must never be greater than the resistance of any

of the leads from the dynamos to the bus bar. Sometimes a third wire

is run to the switchboard from each dynamo and there connected to an

equalizer bar, but the usual practice is to run the equalizer directly

between the dynamos and to place the equalizer switches on pedestals

near the machines. This shortens the connections and leads to better

regulation. The positive and equalizer switches of each machine

differ in pressure only by the slight drop in the series coil, and in

some large stations these two switches are placed side by side on a

pedestal near the machine. In such cases, the equalizer and positive

bus bars are often placed under the floor near the machines, so that

all leads may be as short as possible. If all the dynamos be of equal

capacity, all the leads to bus bars should be of the same length, and

it is sometimes necessary to loop some of them.

If the difference be small, it may be compensated by means of the hand

regulator; if large, however, other means must be taken to cause the

machines to take up their due proportion of the load.

If the series coils of the several dynamos be provided with small

adjustable resistances, in the form of German silver or copper ribbon

inserted in series with the coils, the distribution of the current in the

latter may be altered by varying the resistance attached to the individual

coils. The effect of the series coils upon the individual armatures in

raising the pressure may be adjusted, and the load thus evenly divided

among the machines.

Shunt and Compound Dynamos in Parallel.--It is not practicable to run

a compound dynamo and a shunt dynamo in parallel, for, unless the field

rheostat of the shunt machine be adjusted continually, the compound dynamo

will take more than its share of the load.

Hawkins Electrical Guide v. 03 (of 10) Questions, Answers, & Illustrations, A progressive course of study for engineers, electricians, students and those desiring to acquire a working knowledge of electricity and its applications · 第 5 / 10 章