CHAPTER VII

LIGHTING SYSTEM FOR PASSENGER STATIONS AND TUNNEL

In the initial preparation of plans, and more than a year before the

accident which occurred in the subway system of Paris in August, 1903,

the engineers of the Interborough Company realized the importance of

maintaining lights in the subway independent of any temporary

interruption of the power used for lighting the cars, and, in

preparing their plans, they provided for lighting the subway

throughout its length from a source independent of the main power

supply. For this purpose three 1,250-kilowatt alternators

direct-driven by steam turbines are installed in the power house, from

which point a system of primary cables, transformers and secondary

conductors convey current to the incandescent lamps used solely to

light the subway. The alternators are of the three-phase type, making

1,200 revolutions per minute and delivering current at a frequency of

60 cycles per second at a potential of 11,000 volts. In the boiler

plant and system of steam piping installed in connection with these

turbine-driven units, provision is made for separation of the steam

supply from the general supply for the 5,000 kilowatt units and for

furnishing the steam for the turbine units through either of two

alternative lines of pipe.

The 11,000-volt primary current is conveyed through paper insulated

lead-sheathed cables to transformers, located in fireproof

compartments adjacent to the platforms of the passenger stations.

These transformers deliver current to two separate systems of

secondary wiring, one of which is supplied at a potential of 120 volts

and the other at 600 volts.

The general lighting of the passenger station platforms is effected by

incandescent lamps supplied from the 120-volt secondary wiring

circuits, while the lighting of the subway sections between adjacent

stations is accomplished by incandescent lamps connected in series

groups of five each and connected to the 600-volt lighting circuits.

Recognizing the fact that in view of the precautions taken it is

probable that interruptions of the alternating current lighting

service will be infrequent, the possibility of such interruption is

nevertheless provided for by installing upon the stairways leading to

passenger station platforms, at the ticket booths and over the tracks

in front of the platforms, a number of lamps which are connected to

the contact rail circuit. This will provide light sufficient to enable

passengers to see stairways and the edges of the station platforms in

case of temporary failure of the general lighting system.

The general illumination of the passenger stations is effected by

means of 32 c. p. incandescent lamps, placed in recessed domes in the

ceiling. These are reinforced by 14 c. p. and 32 c. p. lamps, carried

by brackets of ornate design where the construction of the station

does not conveniently permit the use of ceiling lights. The lamps are

enclosed in sand-blasted glass globes, and excellent distribution is

secured by the use of reflectors.

The illustration on page 122 is produced from a photograph of the

interior of one of the transformer cupboards and shows the transformer

in place with the end bell of the high potential cable and the primary

switchboard containing switches and enclosed fuses. The illustration

on page 123 shows one of the secondary distributing switchboards

which are located immediately behind the ticket booths, where they are

under the control of the ticket seller.

[Illustration: TRANSFORMER COMPARTMENT IN PASSENGER STATION]

In lighting the subway between passenger stations, it is desirable, on

the one hand, to provide sufficient light for track inspection and to

permit employees passing along the subway to see their way clearly and

avoid obstructions; but, on the other hand, the lighting must not be

so brilliant as to interfere with easy sight and recognition of the

red, yellow, and green signal lamps of the block signal system. It is

necessary also that the lights for general illumination be so placed

that their rays shall not fall directly upon the eyes of approaching

motormen at the head of trains nor annoy passengers who may be reading

their papers inside the cars. The conditions imposed by these

considerations are met in the four-track sections of the subway by

placing a row of incandescent lamps between the north-bound local and

express tracks and a similar row between the southbound local and

express tracks. The lamps are carried upon brackets supported upon the

iron columns of the subway structure, successive lamps in each row

being 60 feet apart. They are located a few inches above the tops of

the car windows and with reference to the direction of approaching

trains the lamps in each row are carried upon the far side of the iron

columns, by which expedient the eyes of the approaching motormen are

sufficiently protected against their direct rays.

[Sidenote: _Lighting of

the Power

House_]

For the general illumination of the engine room, clusters of Nernst

lamps are supported from the roof trusses and a row of single lamps

of the same type is carried on the lower gallery about 25 feet from

the floor. This is the first power house in America to be illuminated

by these lamps. The quality of the light is unsurpassed and the

general effect of the illumination most satisfactory and agreeable to

the eye. In addition to the Nernst lamps, 16 c. p. incandescent lamps

are placed upon the engines and along the galleries in places not

conveniently reached by the general illumination. The basement also is

lighted by incandescent lamps.

[Illustration: SECONDARY DISTRIBUTING SWITCHBOARD AT PASSENGER

STATION]

For the boiler room, a row of Nernst lamps in front of the batteries

of boilers is provided, and, in addition to these, incandescent lamps

are used in the passageways around the boilers, at gauges and at water

columns. The basement of the boiler room, the pump room, the

economizer floor, coal bunkers, and coal conveyers are lighted by

incandescent lamps, while arc lamps are used around the coal tower and

dock. The lights on the engines and those at gauge glasses and water

columns and at the pumps are supplied by direct current from the

250-volt circuits. All other incandescent lamps and the Nernst lamps

are supplied through transformers from the 60-cycle lighting system.

[Sidenote: _Emergency

Signal System

and Provision

for Cutting Off

Power from

Contact Rail_]

In the booth of each ticket seller and at every manhole along the west

side of the subway and its branches is placed a glass-covered box of

the kind generally used in large American cities for fire alarm

purposes. In case of accident in the subway which may render it

desirable to cut off power from the contact rails, this result can be

accomplished by breaking the glass front of the emergency box and

pulling the hook provided. Special emergency circuits are so arranged

that pulling the hook will instantly open all the circuit-breakers at

adjacent sub-stations through which the contact rails in the section

affected receive their supply of power. It will also instantly report

the location of the trouble, annunciator gongs being located in the

sub-stations from which power is supplied to the section, in the train

dispatchers' offices and in the office of the General Superintendent,

instantly intimating the number of the box which has been pulled.

Automatic recording devices in train dispatchers' offices and in the

office of the General Superintendent also note the number of the box

pulled.

The photograph on page 120 shows a typical fire alarm box.

The New York Subway, Its Construction and Equipment · 第 7 / 12 章