CHAPTER V

SYSTEM OF ELECTRICAL SUPPLY

[Sidenote: _Energy from

Engine Shaft

to Third Rail_]

The system of electrical supply chosen for the subway comprises

alternating current generation and distribution, and direct current

operation of car motors. Four years ago, when the engineering plans

were under consideration, the single-phase alternating current railway

motor was not even in an embryonic state, and notwithstanding the

marked progress recently made in its development, it can scarcely yet

be considered to have reached a stage that would warrant any

modifications in the plans adopted, even were such modifications

easily possible at the present time. The comparatively limited

headroom available in the subway prohibited the use of an overhead

system of conductors, and this limitation, in conjunction with the

obvious desirability of providing a system permitting interchangeable

operation with the lines of the Manhattan Railway system practically

excluded tri-phase traction systems and led directly to the adoption

of the third-rail direct current system.

[Illustration: SIDE AND END ELEVATIONS OF ALTERNATOR.]

[Illustration: SIDE ELEVATION AND CROSS SECTION OF ALTERNATOR WITH

PART CUT AWAY TO SHOW CONSTRUCTION.]

It being considered impracticable to predict with entire certainty the

ultimate traffic conditions to be met, the generator plant has been

designed to take care of all probable traffic demands expected to

arise within a year or two of the beginning of operation of the

system, while the plans permit convenient and symmetrical increase to

meet the requirements of additional demand which may develop. Each

express train will comprise five motor cars and three trail cars, and

each local train will comprise three motor cars and two trail cars.

The weight of each motor car with maximum live load is 88,000 pounds,

and the weight of each trailer car 66,000 pounds.

The plans adopted provide electric equipment at the outstart capable

of operating express trains at an average speed approximating

twenty-five miles per hour, while the control system and motor units

have been so chosen that higher speeds up to a limit of about thirty

miles per hour can be attained by increasing the number of motor cars

providing experience in operation demonstrates that such higher speeds

can be obtained with safety.

The speed of local trains between City Hall and 96th Street will

average about 15 miles an hour, while north of 96th Street on both the

West side and East side branches their speed will average about 18

miles an hour, owing to the greater average distance between local

stations.

As the result of careful consideration of various plans, the company's

engineers recommended that all the power required for the operation of

the system be generated in a single power house in the form of

three-phase alternating current at 11,000 volts, this current to be

generated at a frequency of 25 cycles per second, and to be delivered

through three-conductor cables to transformers and converters in

sub-stations suitably located with reference to the track system, the

current there to be transformed and converted to direct current for

delivery to the third-rail conductor at a potential of 625 volts.

[Illustration: OPERATING GALLERY IN SUB-STATION]

[Illustration: GENERAL DIAGRAM OF 11,000 VOLT CIRCUITS IN MAIN POWER

STATION]

Calculations based upon contemplated schedules require for traction

purposes and for heating and lighting cars, a maximum delivery of

about 45,000 kilowatts at the third rail. Allowing for losses in the

distributing cables, in transformers and converters, this implies a

total generating capacity of approximately 50,000 kilowatts, and

having in view the possibility of future extensions of the system it

was decided to design and construct the power house building for the

ultimate reception of eleven 5,000-kilowatt units for traction current

in addition to the lighting sets. Each 5,000-kilowatt unit is capable

of delivering during rush hours an output of 7,500 kilowatts or

approximately 10,000 electrical horse power and, setting aside one

unit as a reserve, the contemplated ultimate maximum output of the

power plant, therefore, is 75,000 kilowatts, or approximately 100,000

electrical horse power.

[Sidenote: _Power

House_]

The power house is fully described elsewhere in this publication, but

it is not inappropriate to refer briefly in this place to certain

considerations governing the selection of the generating unit, and the

use of engines rather than steam turbines.

[Illustration: OIL SWITCHES--MAIN POWER STATION]

The 5,000-kilowatt generating unit was chosen because it is

practically as large a unit of the direct-connected type as can be

constructed by the engine builders unless more than two bearings be

used--an alternative deemed inadvisable by the engineers of the

company. The adoption of a smaller unit would be less economical of

floor space and would tend to produce extreme complication in so large

an installation, and, in view of the rapid changes in load which in

urban railway service of this character occur in the morning and again

late in the afternoon, would be extremely difficult to operate.

The experience of the Manhattan plant has shown, as was anticipated in

the installation of less output than this, the alternators must be put

in service at intervals of twenty minutes to meet the load upon the

station while it is rising to the maximum attained during rush hours.

After careful consideration of the possible use of steam turbines as

prime-movers to drive the alternators, the company's engineers decided

in favor of reciprocating engines. This decision was made three years

ago and, while the steam turbine since that time has made material

progress, those responsible for the decision are confirmed in their

opinion that it was wise.

[Illustration: PART OF BUS BAR COMPARTMENTS--MAIN POWER STATION]

[Sidenote: _Alternators_]

The alternators closely resemble those installed by the Manhattan

Railway Company (now the Manhattan division of the Interborough Rapid

Transit Company) in its plant on the East River, between 74th Street

and 75th Street. They differ, however, in having the stationary

armature divided into seven castings instead of six, and in respect to

details of the armature winding. They are three-phase machines,

delivering twenty-five cycle alternating currents at an effective

potential of 11,000 volts. They are 42 feet in height, the diameter

of the revolving part is 32 feet, its weight, 332,000 pounds, and the

aggregate weight of the machine, 889,000 pounds. The design of the

engine dynamo unit eliminates the auxiliary fly wheel generally used

in the construction of large direct-connected units prior to the

erection of the Manhattan plant, the weight and dimensions of the

revolving alternator field being such with reference to the turning

moment of the engine as to secure close uniformity of rotation, while

at the same time this construction results in narrowing the engine and

reducing the engine shafts between bearings.

[Illustration: REAR VIEW OF BUS BAR COMPARTMENTS--MAIN POWER STATION]

[Illustration: DUCT LINE ACROSS 58TH STREET 32 DUCTS]

Construction of the revolving parts of the alternators is such as to

secure very great strength and consequent ability to resist the

tendency to burst and fly apart in case of temporary abnormal speed

through accident of any kind. The hub of the revolving field is of

cast steel, and the rim is carried not by the usual spokes but by two

wedges of rolled steel. The construction of the revolving field is

illustrated on pages 91 and 92. The angular velocity of the

revolving field is remarkably uniform. This result is due primarily to

the fact that the turning movement of the four-cylinder engine is far

more uniform than is the case, for example, with an ordinary

two-cylinder engine. The large fly-wheel capacity of the rotating

element of the machine also contributes materially to secure

uniformity of rotation.

[Illustration: MAIN CONTROLLING BOARD IN POWER STATION]

[Illustration: CONTROL AND INSTRUMENT BOARD--MAIN POWER STATION]

The alternators have forty field poles and operates at seventy-five

revolutions per minute. The field magnets constitute the periphery of

the revolving field, the poles and rim of the field being built up by

steel plates which are dovetailed to the driving spider. The heavy

steel end plates are bolted together, the laminations breaking joints

in the middle of the pole. The field coils are secured by copper

wedges, which are subjected to shearing strains only. In the body of

the poles, at intervals of approximately three inches, ventilating

spaces are provided, these spaces registering with corresponding air

ducts in the external armature. The field winding consists of copper

strap on edge, one layer deep, with fibrous material cemented in place

between turns, the edges of the strap being exposed.

[Illustration: DUCTS UNDER PASSENGER STATION PLATFORM

64 DUCTS]

The armature is stationary and exterior to the field. It consists of a

laminated ring with slots on its inner surface and supported by a

massive external cast-iron frame. The armature, as has been noted,

comprises seven segments, the topmost segment being in the form of a

small keystone. This may be removed readily, affording access to any

field coil, which in this way may be easily removed and replaced. The

armature winding consists of U-shaped copper bars in partially closed

slots. There are four bars per slot and three slots per phase per

pole. The bars in any slot may be removed from the armature without

removing the frame. The alternators, of course, are separately

excited, the potential of the exciting current used being 250 volts.

As regards regulation, the manufacturer's guarantee is that at 100 per

cent. power factor if full rated load be thrown off the e. m. f. will

rise 6 per cent. with constant speed and constant excitation. The

guarantee as to efficiency is as follows: On non-inductive load, the

alternators will have an efficiency of not less than 90.5 per cent. at

one-quarter load; 94.75 per cent. at one-half load; 96.25 per cent. at

three-quarters load; 97 per cent. at full load, and 97.25 per cent. at

one and one-quarter load. These figures refer, of course, to

electrical efficiency, and do not include windage and bearing

friction. The machines are designed to operate under their rated full

load with rise of temperature not exceeding 35 degrees C. after

twenty-four hours.

[Illustration: THREE-CONDUCTOR NO. 000 CABLE FOR 11,000 VOLT

DISTRIBUTION]

[Sidenote: _Exciters_]

To supply exciting current for the fields of the alternators and to

operate motors driving auxiliary apparatus, five 250-kilowatt direct

current dynamos are provided. These deliver their current at a

potential of 250 volts. Two of them are driven by 400 horse-power

engines of the marine type, to which they are direct-connected, while

the remaining three units are direct-connected to 365 horse-power

tri-phase induction motors operating at 400 volts. A storage battery

capable of furnishing 3,000 amperes for one hour is used in

co-operation with the dynamos provided to excite the alternators. The

five direct-current dynamos are connected to the organization of

switching apparatus in such a way that each unit may be connected at

will either to the exciting circuits or to the circuits through which

auxiliary motors are supplied.

The alternators for which the new Interborough Power House are

designed will deliver to the bus bars 100,000 electrical horse power.

The current delivered by these alternators reverses its direction

fifty times per second and in connecting dynamos just coming into

service with those already in operation the allowable difference in

phase relation at the instant the circuit is completed is, of course,

but a fraction of the fiftieth of a second. Where the power to be

controlled is so great, the potential so high, and the speed

requirements in respect to synchronous operation so exacting, it is

obvious that the perfection of control attained in some of our modern

plants is not their least characteristic.

[Sidenote: _Switching

Apparatus_]

The switch used for the 11,000 volt circuits is so constructed that

the circuits are made and broken under oil, the switch being

electrically operated. Two complete and independent sets of bus bars

are used, and the connections are such that each alternator and each

feeder may be connected to either of these sets of bus bars at the

will of the operator. From alternators to bus bars the current passes,

first, through the alternator switch, and then alternatively through

one or the other of two selector switches which are connected,

respectively, to the two sets of bus bars.

[Illustration: INSIDE WALL OF TUNNEL SHOWING 64 DUCTS]

Provision is made for an ultimate total of twelve sub-stations, to

each of which as many as eight feeders may be installed if the

development of the company's business should require that number. But

eight sub-stations are required at present, and to some of these not

more than three feeders each are necessary. The aggregate number of

feeders installed for the initial operation of the subway system is

thirty-four.

Each feeder circuit is provided with a type H-oil switch arranged to

be open and closed at will by the operator, and also to open

automatically in the case of abnormal flow of current through the

feeder. The feeders are arranged in groups, each group being supplied

from a set of auxiliary bus bars, which in turn receives its supply

from one or the other of the two sets of main bus bars; means for

selection being provided as in the case of the alternator circuits by

a pair of selector switches, in this case designated as group

switches. The diagram on page 93 illustrates the essential

features of the organization and connections of the 11,000 volt

circuits in the power house.

[Illustration: MANHOLES IN SIDE WALL OF SUBWAY]

Any and every switch can be opened or closed at will by the operator

standing at the control board described. The alternator switches are

provided also with automatic overload and reversed current relays, and

the feeder switches, as above mentioned, are provided with automatic

overload relays. These overload relays have a time attachment which

can be set to open the switch at the expiration of a predetermined

time ranging from .3 of a second to 5 seconds.

[Illustration: CONVERTER FLOOR PLAN

SUB-STATION NO. 14]

The type H-oil switch is operated by an electric motor through the

intervention of a mechanism comprising powerful springs which open and

close the switch with great speed. This switch when opened introduces

in each of the three sides of the circuit two breaks which are in

series with each other. Each side of the circuit is separated from the

others by its location in an enclosed compartment, the walls of which

are brick and soapstone. The general construction of the switch is

illustrated by the photograph on page 94.

[Illustration: CROSS SECTION SUB-STATION NO. 14]

[Illustration: INTERIOR OF SUB-STATION NO. 11]

[Illustration: LONGITUDINAL SECTION SUB-STATION NO. 14]

Like all current-carrying parts of the switches, the bus bars are

enclosed in separate compartments. These are constructed of brick,

small doors for inspection and maintenance being provided opposite all

points where the bus bars are supported upon insulators. The

photographs on pages 95 and 96 are views of a part of the bus bar

and switch compartments.

[Illustration: TWO GROUPS OF TRANSFORMERS]

The oil switches and group bus bars are located upon the main floor

and extend along the 59th Street wall of the engine room a distance of

about 600 feet. The main bus bars are arranged in two lines of brick

compartments, which are placed below the engine-room floor. These bus

bars are arranged vertically and are placed directly beneath the rows

of oil switches located upon the main floor of the power house. Above

these rows of oil switches and the group bus bars, galleries are

constructed which extend the entire length of the power house, and

upon the first of these galleries at a point opposite the middle of

the power house are located the control board and instrument board, by

means of which the operator in charge regulates and directs the entire

output of the plant, maintaining a supply of power at all times

adequate to the demands of the transportation service.

[Illustration: MOTOR-GENERATORS AND BATTERY BOARD FOR CONTROL

CIRCUITS--SUB-STATION]

[Illustration: 1,500 K. W. ROTARY CONVERTER]

[Sidenote: _The Control

Board_]

The control board is shown in the photograph on page 97. Every

alternator switch, every selector switch, every group switch, and

every feeder switch upon the main floor is here represented by a small

switch. The small switch is connected into a control circuit which

receives its supply of energy at 110 volts from a small motor

generator set and storage battery. The motors which actuate the large

oil switches upon the main floor are driven by this 110 volt control

current, and thus in the hands of the operator the control switches

make or break the relatively feeble control currents, which, in turn,

close or open the switches in the main power circuits. The control

switches are systematically assembled upon the control bench board in

conjunction with dummy bus bars and other apparent (but not real)

metallic connections, the whole constituting at all times a correct

diagram of the existing connections of the main power circuits. Every

time the operator changes a connection by opening or closing one of

the main switches, he necessarily changes his diagram so that it

represents the new conditions established by opening or closing the

main switch. In connection with each control switch two small

bull's-eye lamps are used, one red, to indicate that the corresponding

main switch is closed, the other green, to indicate that it is open.

These lamps are lighted when the moving part of the main switch

reaches approximately the end of its travel. If for any reason,

therefore, the movement of the control switch should fail to actuate

the main switch, the indicator lamp will not be lighted.

[Illustration: MOTOR-GENERATOR SET SUPPLYING ALTERNATING CURRENT FOR

BLOCK SIGNALS AND MOTOR-GENERATOR STARTING SET]

The control board is divided into two parts--one for the connections

of the alternators to the bus bars and the other for the connection

of feeders to bus bars. The drawing on page 97 shows in plain view

the essential features of the control boards.

[Sidenote: _The

Instrument

Board_]

A front view of the Instrument Board is shown on page 97. This

board contains all indicating instruments for alternators and feeders.

It also carries standardizing instruments and a clock. In the

illustration the alternator panels are shown at the left and the

feeder panels at the right. For the alternator panels, instruments of

the vertical edgewise type are used. Each vertical row comprises the

measuring instruments for an alternator. Beginning at the top and

enumerating them in order these instruments are: Three ammeters, one

for each phase, a volumeter, an indicating wattmeter, a power factor

indicator and a field ammeter. The round dial instrument shown at the

bottom of each row of instruments is a three-phase recording

wattmeter.

A panel located near the center of the board between alternator panels

and feeder panels carries standard instruments used for convenient

calibration of the alternator and feeder instruments. Provision is

made on the back of the board for convenient connection of the

standard instruments in series with the instruments to be compared.

The panel which carries the standard instruments also carries ammeters

used to measure current to auxiliary circuits in the power house.

For the feeder board, instruments of the round dial pattern are used,

and for each feeder a single instrument is provided, viz., an ammeter.

Each vertical row comprises the ammeters belonging to the feeders

which supply a given sub-station, and from left to right these are in

order sub-stations Nos. 11, 12, 13, 14, 15, 16, 17, and 18; blank

spaces are left for four additional sub-stations. Each horizontal row

comprises the ammeter belonging to feeders which are supplied through

a given group switch.

This arrangement in vertical and horizontal lines, indicating

respectively feeders to given sub-stations and feeders connected to

the several group switches, is intended to facilitate the work of the

operator. A glance down a vertical row without stopping to reach the

scales of the instruments will tell him whether the feeders are

dividing with approximate equality the load to a given sub-station.

Feeders to different sub-stations usually carry different loads and,

generally speaking, a glance along a horizontal row will convey no

information of especial importance. If, however, for any reason the

operator should desire to know the approximate aggregate load upon a

group of feeders this systematic arrangement of the instruments is of

use.

[Illustration: SWITCHBOARD FOR ALTERNATING CURRENT BLOCK SIGNAL

CIRCUITS--IN SUB-STATION]

[Illustration: EXTERIOR OF SUB-STATION NO. 18]

[Sidenote: _Alternating

Current

Distribution

to Sub-Stations

Power House

Ducts and

Cables_]

From alternators to alternator switches the 11,000 volt alternating

currents are conveyed through single conductor cables, insulated by

oil cambric, the thickness of the wall being 12/32 of an inch. These

conductors are installed in vitrified clay ducts. From dynamo switches

to bus bars and from bus bars to group and feeder switches, vulcanized

rubber insulation containing 30 per cent. pure Para rubber is

employed. The thickness of insulating wall is 9/32 of an inch and the

conductors are supported upon porcelain insulators.

[Sidenote: _Conduit

System for

Distribution_]

From the power house to the subway at 58th Street and Broadway two

lines of conduit, each comprising thirty-two ducts, have been

constructed. These conduits are located on opposite sides of the

street. The arrangement of ducts is 8 x 4, as shown in the section on

page 96.

[Illustration: EXTERIOR OF SUB-STATION NO. 11]

The location and arrangement of ducts along the line of the subway are

illustrated in photographs on pages 98 and 99, which show

respectively a section of ducts on one side of the subway, between

passenger stations, and a section of ducts and one side of the subway,

beneath the platform of a passenger station. From City Hall to 96th

Street (except through the Park Avenue Tunnel) sixty-four ducts are

provided on each side of the subway. North of 96th Street sixty-four

ducts are provided for the West-side lines and an equal number for the

East-side lines. Between passenger stations these ducts help to form

the side walls of the subway, and are arranged thirty-two ducts high

and two ducts wide. Beneath the platform of passenger stations the

arrangement is somewhat varied because of local obstructions, such as

pipes, sewers, etc., of which it was necessary to take account in the

construction of the stations. The plan shown on page 98, however,

is typical.

The necessity of passing the cables from the 32 x 2 arrangement of

ducts along the side of the tunnel to 8 x 8 and 16 x 4 arrangements of

ducts beneath the passenger platforms involves serious difficulties in

the proper support and protection of cables in manholes at the ends of

the station platforms. In order to minimize the risk of interruption

of service due to possible damage to a considerable number of cables

in one of these manholes, resulting from short circuit in a single

cable, all cables except at the joints are covered with two layers of

asbestos aggregating a full 1/4-inch in thickness. This asbestos is

specially prepared and is applied by wrapping the cable with two

strips each 3 inches in width, the outer strip covering the line of

junction between adjacent spirals of the inner strip, the whole when

in place being impregnated with a solution of silicate of soda. The

joints themselves are covered with two layers of asbestos held in

place by steel tape applied spirally. To distribute the strains upon

the cables in manholes, radical supports of various curvatures, and

made of malleable cast iron, are used. The photograph on page 100

illustrates the arrangement of cables in one of these manholes.

[Illustration: OPERATING BOARD--SUB-STATION NO. 11]

In order to further diminish the risk of interruption of the service

due to failure of power supply, each sub-station south of 96th Street

receives its alternating current from the power house through cables

carried on opposite sides of the subway. To protect the lead sheaths

of the cables against damage by electrolysis, rubber insulating pieces

1/6 of an inch in thickness are placed between the sheaths and the

iron bracket supports in the manholes.

[Sidenote: _Cable

Conveying

Energy from

Power House to

Sub-Stations_]

The cables used for conveying energy from the power house to the

several sub-stations aggregate approximately 150 miles in length. The

cable used for this purpose comprises three stranded copper conductors

each of which contains nineteen wires, and the diameter of the

stranded conductor thus formed is 2/5 of an inch. Paper insulation is

employed and the triple cable is enclosed in a lead sheath 9/64 of an

inch thick. Each conductor is separated from its neighbors and from

the lead sheath by insulation of treated paper 7/16 of an inch in

thickness. The outside diameter of the cables is 2-5/8 inches, and the

weight 8-1/2 pounds per lineal foot. In the factories the cable as

manufactured was cut into lengths corresponding to the distance

between manholes, and each length subjected to severe tests including

application to the insulation of an alternating current potential of

30,000 volts for a period of thirty minutes. These cables were

installed under the supervision of the Interborough Company's

engineers, and after jointing, each complete cable from power house to

sub-station was tested by applying an alternating potential of 30,000

volts for thirty minutes between each conductor and its neighbors, and

between each conductor and the lead sheath. The photographs on

page 98 illustrates the construction of this cable.

[Sidenote: _Sub-Station_]

The tri-phase alternating current generated at the power house is

conveyed through the high potential cable system to eight sub-stations

containing the necessary transforming and converting machinery. These

sub-stations are designed and located as follows:

[Illustration: DIAGRAMS OF DIRECT CURRENT FEEDER AND RETURN CIRCUITS]

Sub-station No. 11--29-33 City Hall Place.

Sub-station No. 12--108-110 East 19th Street.

Sub-station No. 13--225-227 West 53d Street.

Sub-station No. 14--264-266 West 96th Street.

Sub-station No. 15--606-608 West 143d Street.

Sub-station No. 16--73-77 West 132d Street.

Sub-station No. 17--Hillside Avenue, 301 feet West of

Eleventh Avenue.

Sub-station No. 18--South side of Fox Street (Simpson

Street), 60 feet north of Westchester Avenue.

[Illustration: SWITCH CONNECTING FEEDER TO CONTACT RAIL]

[Illustration: CONTACT RAIL JOINT WITH FISH PLATE]

The converter unit selected to receive the alternating current and

deliver direct current to the track, etc., has an output of 1,500

kilowatts with ability to carry 50 per cent. overload for three hours.

The average area of a city lot is 25 x 100 feet, and a sub-station

site comprising two adjacent lots of this approximate size permits the

installation of a maximum of eight 1,500 kilowatts converters with

necessary transformers, switchboard and other auxiliary apparatus. In

designing the sub-stations, a type of building with a central air-well

was selected. The typical organization of apparatus is illustrated in

the ground plan and vertical section on pages 101, 102 and 103 and

provides, as shown, for two lines of converters, the three

transformers which supply each converter being located between it and

the adjacent side wall. The switchboard is located at the rear of the

station. The central shaft affords excellent light and ventilation for

the operating room. The steel work of the sub-stations is designed

with a view to the addition of two storage battery floors, should it

be decided at some future time that the addition of such an auxiliary

is advisable.

[Illustration: CONTACT RAIL BANDS]

The necessary equipment of the sub-stations implies sites

approximately 50 x 100 feet in dimensions; and sub-stations Nos. 14,

15, 17, and 18 are practically all this size. Sub-stations Nos. 11 and

16 are 100 feet in length, but the lots acquired in these instances

being of unusual width, these sub-stations are approximately 60 feet

wide. Sub-station No. 12, on account of limited ground space, is but

48 feet wide and 92 feet long. In each of the sub-stations, except No.

13, foundations are provided for eight converters; sub-station No. 13

contains foundations for the ultimate installation of ten converters.

[Illustration: DIRECT CURRENT FEEDERS FROM MANHOLE TO CONTACT RAIL]

The function of the electrical apparatus in sub-stations, as has been

stated, is the conversion of the high potential alternating current

energy delivered from the power house through the tri-phase cables

into direct current adapted to operate the motors with which the

rolling stock is equipped. This apparatus comprises transformers,

converters, and certain minor auxiliaries. The transformers, which are

arranged in groups of three, receive the tri-phase alternating current

at a potential approximating 10,500 volts, and deliver equivalent

energy (less the loss of about 2 per cent. in the transformation) to

the converters at a potential of about 390 volts. The converters

receiving this energy from their respective groups of transformers in

turn deliver it (less a loss approximating 4 per cent. at full load)

in the form of direct current at a potential of 625 volts to the bus

bars of the direct current switchboards, from which it is conveyed by

insulated cables to the contact rails. The photograph on page 102

is a general view of the interior of one of the sub-stations. The

exterior of sub-stations Nos. 11 and 18 are shown on page 107.

[Illustration: CONTACT RAILS, SHOWING END INCLINES]

The illustration on page 108 is from a photograph taken on one of

the switchboard galleries. In the sub-stations, as in the power house,

the high potential alternating current circuits are opened and closed

by oil switches, which are electrically operated by motors, these in

turn being controlled by 110 volt direct current circuits. Diagramatic

bench boards are used, as at the power house, but in the sub-stations

they are of course relatively small and free from complication.

The instrument board is supported by iron columns and is carried at a

sufficient height above the bench board to enable the operator, while

facing the bench board and the instruments, to look out over the floor

of the sub-station without turning his head. The switches of the

direct current circuits are hand-operated and are located upon boards

at the right and left of the control board.

A novel and important feature introduced (it is believed for the first

time) in these sub-stations, is the location in separate brick

compartments of the automatic circuit breakers in the direct current

feeder circuits. These circuit breaker compartments are shown in the

photograph on page 93, and are in a line facing the boards which

carry the direct feeder switches, each circuit breaker being located

in a compartment directly opposite the panel which carries the switch

belonging to the corresponding circuit. This plan will effectually

prevent damage to other parts of the switchboard equipment when

circuit-breakers open automatically under conditions of short-circuit.

It also tends to eliminate risk to the operator, and, therefore, to

increase his confidence and accuracy in manipulating the hand-operated

switches.

[Illustration: ASSEMBLY OF CONTACT RAIL AND PROTECTION]

The three conductor cables which convey tri-phase currents from the

power house are carried through tile ducts from the manholes located

in the street directly in front of each sub-station to the back of the

station where the end of the cable is connected directly beneath its

oil switch. The three conductors, now well separated, extend

vertically to the fixed terminals of the switch. In each sub-station

but one set of high-potential alternating current bus bars is

installed and between each incoming cable and these bus bars is

connected an oil switch. In like manner, between each converter unit

and the bus bars an oil switch is connected into the high potential

circuit. The bus bars are so arranged that they may be divided into

any number of sections not exceeding the number of converter units, by

means of movable links which, in their normal condition, constitute a

part of the bus bars.

Each of the oil switches between incoming circuits and bus bars is

arranged for automatic operation and is equipped with a reversed

current relay, which, in the case of a short-circuit in its

alternating current feeder cable opens the switch and so disconnects

the cable from the sub-station without interference with the operation

of the other cables or the converting machinery.

[Illustration: CONTACT RAIL INSULATOR]

[Sidenote: _Direct Current

Distribution

from

Sub-Stations_]

The organization of electrical conductors provided to convey direct

current from the sub-stations to the moving trains can be described

most conveniently by beginning with the contact, or so-called third

rail. South of 96th Street the average distance between sub-stations

approximates 12,000 feet, and north of 96th Street the average

distance is about 15,000 feet. Each track, of course, is provided with

a contact rail. There are four tracks and consequently four contact

rails from City Hall to 96th Street, three from 96th Street to 145th

Street on the West Side, two from 145th Street to Dyckman Street, and

three from Dyckman Street to the northern terminal of the West Side

extension of the system. From 96th Street, the East Side has two

tracks and two contact rails to Mott Avenue, and from that point to

the terminal at 182d Street three tracks and three contact rails.

[Illustration: CONTACT SHOE AND FUSE]

Contact rails south of Reade Street are supplied from sub-station No.

11; from Reade Street to 19th Street they are supplied from

sub-stations Nos. 11 and 12; from 19th Street they are supplied from

sub-stations Nos. 12 and 13; from the point last named to 96th Street

they are supplied from sub-stations Nos. 13 and 14; from 96th Street

to 143d Street, on the West Side, they are supplied from sub-stations

Nos. 14 and 15; from 143d Street to Dyckman Street they are supplied

from sub-stations Nos. 15 and 17; and from that point to the terminal

they are supplied from sub-station No. 17. On the East Side branch

contact rails from 96th Street to 132d Street are supplied from

sub-stations Nos. 14 and 16; from 132d to 165th Street they are

supplied from sub-stations Nos. 16 and 18; and from 165th Street to

182d Street they are supplied from sub-station No. 18.

Each contact rail is insulated from all contact rails belonging to

adjacent tracks. This is done in order that in case of derailment or

other accident necessitating interruption of service on a given track,

trains may be operated upon the other tracks having their separate and

independent channels of electrical supply. To make this clear, we may

consider that section of the subway which lies between Reade Street

and 19th Street. This section is equipped with four tracks, and the

contact rail for each track, together with the direct current feeders

which supply it from sub-stations Nos. 11 and 12, are electrically

insulated from all other circuits. Of each pair of track rails one is

used for the automatic block signaling system, and, therefore, is not

used as a part of the negative or return side of the direct current

system. The other four track rails, however, are bonded, and together

with the negative feeders constitute the track return or negative side

of the direct current system.

The diagram on page 109 illustrates the connections of the contact

rails, track rails and the positive and negative feeders. All negative

as well as positive feeders are cables of 2,000,000 c. m. section and

lead sheathed. In emergency, as, for example, in the case of the

destruction of a number of the cables in a manhole, they are,

therefore, interchangeable. The connections are such as to minimize

"track drop," as will be evident upon examination of the diagram. The

electrical separation of the several contact rails and the positive

feeders connected thereto secures a further important advantage in

permitting the use at sub-stations of direct-current circuit-breakers

of moderate size and capacity, which can be set to open automatically

at much lower currents than would be practicable were all contact

rails electrically connected, thus reducing the limiting current and

consequently the intensity of the arcs which might occur in the subway

in case of short-circuit between contact rail and earth.

The contact rail itself is of special soft steel, to secure high

conductivity. Its composition, as shown by tests, is as follows:

Carbon, .08 to .15; silicon, .05; phosphorus, .10; manganese, .50 to

.70; and sulphur, .05. Its resistance is not more than eight times the

resistance of pure copper of equal cross-section. The section chosen

weighs 75 pounds per yard. The length used in general is 60 feet, but

in some cases 40 feet lengths are substituted. The contact rails are

bounded by four bonds, aggregating 1,200,000 c. m. section. The bonds

are of flexible copper and their terminals are riveted to the steel by

hydraulic presses, producing a pressure of 35 tons. The bonds when in

use are covered by special malleable iron fish-plates which insure

alignment of rail. Each length of rail is anchored at its middle point

and a small clearance is allowed between ends of adjacent rails for

expansion and contraction, which in the subway, owing to the

relatively small change of temperature, will be reduced to a minimum.

The photographs on pages 110 and 111 illustrate the method of

bonding the rail, and show the bonded joint completed by the addition

of the fish-plates.

The contact rail is carried upon block insulators supported upon

malleable iron castings. Castings of the same material are used to

secure the contact rail in position upon the insulators. A photograph

of the insulator with its castings is shown on page 113.

[Sidenote: _Track

Bonding_]

The track rails are 33 feet long, of Standard American Society Civil

Engineers' section, weighing 100 pounds a yard. As has been stated,

one rail in each track is used for signal purposes and the other is

utilized as a part of the negative return of the power system.

Adjacent rails to be used for the latter purpose are bonded with two

copper bonds having an aggregate section of 400,000 c. m. These bonds

are firmly riveted into the web of the rail by screw bonding presses.

They are covered by splice bars, designed to leave sufficient

clearance for the bond.

The return rails are cross-sectioned at frequent intervals for the

purpose of equalizing currents which traverse them.

[Sidenote: _Contact Rail

Guard and

Collector Shoe_]

The Interborough Company has provided a guard in the form of a plank

8-1/2 inches wide and 1-1/2 inches thick, which is supported in a

horizontal position directly above the rail, as shown in the

illustration on page 113. This guard is carried by the contact

rail to which it is secured by supports, the construction of which is

sufficiently shown in the illustration. This type of guard has been in

successful use upon the Wilkesbarre and Hazleton Railway for nearly

two years. It practically eliminates the danger from the third rail,

even should passengers leave the trains and walk through a section of

the tunnel while the rails are charged.

Its adoption necessitates the use of a collecting shoe differing

radically from that used upon the Manhattan division and upon the

elevated railways employing the third rail system in Chicago, Boston,

Brooklyn, and elsewhere. The shoe is shown in the photograph on

page 114. The shoe is held in contact with the third rail by

gravity reinforced by pressure from two spiral springs. The support

for the shoe includes provision for vertical adjustment to compensate

for wear of car wheels, etc.