ELECTRICAL CODE REVISIONS.

At the recent meeting of the Underwriters’ National Electric Association

it was decided that Cooper Hewitt lamps must have a cut-out for each

lamp or series, except when contained in a single frame and lighted

by a single operation, in which case not more than five lamps shall

be dependent on a single cut-out. The regulators must be enclosed

in non-combustible cases, and where subject to flyings of lint or

combustible material, all openings through the casings must be protected

by a fine wire gauze. Moore electric light tubes must be installed so

as to be free from liability to mechanical injury or of contact with

inflammable material. The high-potential coils and regulating apparatus

must be installed in an approved steel cabinet, which shall be ventilated

in such a manner as to prevent the escape of flame or sparks in case of

burn-out. The apparatus in this box must be mounted on slate, and the

enclosing case positively grounded. The supply conductors must comply

with the rules governing low-potential systems where such wires do not

carry current having a potential of over 300 volts.

Rule 8, section _d_, was amended to apply to auto-starters only, and

a new section was added to rule 60 governing the details of rheostat

construction. New rules regarding low-potential transformers follow: Oil

transformers must not be placed inside of any building except central

stations and sub-stations, unless by special permission of the inspection

department. Air-cooled transformers must not be placed inside of any

building excepting central stations and sub-stations, unless the highest

voltage of either primary or secondary does not exceed 550 volts, and

must be so mounted that the case shall be one foot from combustible

material or separated therefrom by non-combustible, non-absorptive,

insulating material, such as slate or marble. Where transformers are

placed at a lesser distance, a slab of slate or marble somewhat larger

than the transformer must be used, and where the transformer is mounted

on a side wall, the slate or marble must be secured independent of

the transformer supports, the transformer being supported by bolts

countersunk at least one-eighth inch below the surface of the back of the

slab and filled.

For wiring electric cranes the following rules were adopted: All wires

except bare collector wires, those between resistances and contact

plates of rheostats and those subjected to severe external heat, must

be approved, rubber-covered and not smaller in size than No. 12 B. & S.

Wires between resistances and contact plates of rheostats must conform

to No. 4-c, unless the wires are exposed to moisture, in which case

the insulation must also be rubber. Wires subjected to severe external

heat must have approved slow-burning insulation. All wires, excepting

collector wires and those run in metal conduit or armored cable, must be

supported by knobs or cleats which separate them at least one inch from

the surface wired over, but in dry places where space is limited and the

distance between wires as required by Rule 24-h cannot be obtained, each

wire must be separately encased in approved flexible tubing securely

fastened in place. Collector wires must be supported by approved

insulators so mounted that even with the extreme movement permitted the

wires will be separated at all times at least one and one-half inches

from the surface wired over. Collector wires must be held at the ends by

approved strain insulators.

Where the wires are arranged in a horizontal plane above the crane,

they must be supported at least every twenty feet if practicable, and

separated at least six inches, but if longer spans are necessary, the

distance between wires must be increased proportionately, the span in

no case to exceed forty feet. If not arranged in a horizontal plane,

they must be carried along the runways and must be rigidly and securely

attached to their insulating supports at least every twenty feet, and

if not arranged in a vertical plane, must be separated at least eight

inches.

Where bridge collector wires are over eighty feet long, insulating

supports on which the wires may loosely lie must be provided at least

every fifty feet. Bridge collector wires must be kept at least two and

one-half inches apart, but a greater spacing should be used whenever

it may be obtained. Collector wires must not be smaller in size than

specified in the following table for the various spans:

Distance between Size wire

rigid supports. required.

Feet. B. & S.

0 to 30 6

31 to 60 4

Over 60 2

Collectors must be so designed that sparking will be reduced to a minimum

between them and collector wires. The main collector wires must be

protected by a cut-out and the circuit controlled by a switch, cut-out

and switch to be so located as to be easy of access from the floor.

Cranes operated from cabs must have a cut-out and switch connected into

the leads from the main collector wires and so located in the cab as to

be readily accessible to the operator. Where there is more than one motor

on a single crane, each motor lead must be protected by a cut-out located

in the cab if there is one.

Controllers must be installed according to No. 4, except that if the

crane is located outdoors the wires between resistances and contact

plates of rheostats may be rubber-covered or bare or slow-burning if

properly supported. If the crane operates over readily combustible

material, the resistances must be placed in a fire-resisting enclosure;

or, if located in a cab, the cab must be constructed of non-combustible

material and sides provided which enclose the cab from its floor to a

height at least six inches above the top of the resistance.

The motor frames, the entire frame of the crane and the tracks must be

permanently and effectively grounded.

A number of recommendations were made calling for conductive coatings on

cables, outlet boxes and fittings in order to secure better electrical

contact at all points throughout systems in which they are used.

The following suggested changes in the rules were adopted: The fine print

note under rule 2, section a, was amended to read as follows: “Wires from

generator to switchboard may, however, be placed in conduit, provided

that proper precautions are taken to protect them against moisture and

mechanical injury. If lead-covered cable is used no further protection

against moisture will be required, etc.” Section c of the same rule

was amended by inserting the words, “where not in conduit,” after the

first word. The last sentence of the fine print note in rule 12, section

g, was amended to read: “The outer or weather end of conduit is to be

provided with approved devices having wires separated and bushed through

porcelain.”

A number of changes were made in rule 24. Section a, with fine-print

note, was stricken from the Code; section o was amended by making the

first recommendation “a turn of 90 deg., etc.”; section p was amended so

as to restrict the number of different circuits in the same conduit to

four two-wire or three three-wire; section x was changed by substituting

the word _or_ after the word _fastenings_ for _of_. Rule 24A was also

changed somewhat. Section d was amended so as not to prohibit the

installation of armored cable without the lead covering in buildings

of fireproof construction in locations free from moisture; the word

“underground” was omitted from the first line of the fine-print note

under section a. A new section was added as follows: “All bends must

be so made that the armor of the cable will not be injured. The radius

of the curve of the inner edge of any bend not to be less than one and

one-half inches.”

Rule 28, section e, was amended so as to exclude flexible cord from

show cases as well as show windows; the fine-print note under section g

was omitted. A number of minor changes were made in the rules governing

the wiring of theaters, principally in inserting the words, “or armored

cable,” so as to permit the use of the latter as an alternative to rigid

conduit. The other changes have to do with the details of construction,

fitting, etc. Among the miscellaneous suggestions adopted were the

following: All self-fastening knobs, cleats and supports must be secured

by suitable screws; wires in molding must be in continuous lengths from

outlet to outlet or from fitting to fitting; sockets or rosettes cannot

be used to dead-end a circuit; soap-stone can be used as an alternative

for slate or marble; and ends of flexible wire need not be soldered

before insertion under binding posts, as called for in rule 14, section c.

The Journal of Electricity, Power and Gas, Volume XX, No. 18, May 2, 1908 Devoted to the Conversion, Transmission and Distribution of Energy · 第 5 / 37 题