CHAPTER XXIII.

STEEL TOWERS.

Steel towers are rapidly coming into use for the support of electric

transmission lines that deliver large units of energy at high voltages

to long distances from water-powers.

One case of this sort is the seventy-five-mile transmission of 24,000

horse-power at 60,000 volts from Niagara Falls to Toronto. Another

example may be seen in the seventy-five-mile line of steel towers which

carries transmission circuits of 60,000 volts to Winnipeg. Guanajuato,

Mexico, which is said to have produced more silver than any other city

in the world, receives some 3,300 electric horse-power over a

60,000-volt transmission line one hundred miles long on steel towers.

Between Niagara Falls and Lockport the electric circuits now being

erected are supported on steel towers. On a transmission line eighty

miles long in northern New York, for which plans are now being made,

steel towers are to support electric conductors that carry current at

60,000 volts.

For the elevations above ground at which it is common to support the

conductors of transmission lines--that is, from twenty-five to fifty

feet--a steel tower will cost from five to twenty times as much as a

wooden pole in various parts of the United States and Canada. It follows

at once from this fact that there must be cogent reasons, apart from the

matter of first cost, if the general substitution of steel towers for

wooden poles on transmission lines is to be justified on economic

grounds. During fifteen years the electric transmission of energy from

distant water-powers to important centres of population has grown from

the most humble beginnings to the delivery of hundreds of thousands of

horse-power in the service of millions of people, and the lines for this

work are supported, with very few exceptions, on wooden poles. Among the

transmissions of large powers over long distances at very high voltages

that have been in successful operation during at least several years

with wooden pole lines are the following: the 60,000-volt circuit that

transmits some 13,000 horse-power from Electra station across the State

of California to San Francisco, a distance of 147 miles, is supported

by wooden poles. In the same State, the transmission line 142 miles

long between Colgate power-house and Oakland, at 60,000 volts, and with

a capacity of about 15,000 horse-power, hangs on wooden poles, save at

the span nearly a mile long over the Straits of Carquinez. Wood is used

to carry the two 55,000-volt circuits that run sixty-five miles from the

10,000-horse-power station at Cañon Ferry on the Missouri River to

Butte. Between Shawinigan Falls and Montreal, a distance of eighty-three

miles, the conductors that operate at about 50,000 volts are carried on

wooden poles. Electrical supply in Buffalo to the amount of 30,000

horse-power depends entirely on circuits from Niagara Falls that operate

at 22,000 volts and are supported on lines of wooden poles.

In the operation of these and many other high-voltage transmissions

during various parts of the past decade some difficulties have been met

with, but they have not been so serious as to prevent satisfactory

service. Nevertheless, it is now being urged that certain impediments

that are met in the operation of transmission systems would be much

reduced by the substitution of steel towers for wooden poles, and it is

even suggested that perhaps the first cost, and probably the last cost,

of a transmission line would be less with steel than with wood for

supports. The argument for steel in the matter of costs is that while a

tower requires a larger investment than a pole, yet the smaller number

of towers as compared with that of poles may reduce the entire outlay

for the former to about that for the latter. More than this, it is said

that the lower depreciation and maintenance charges on steel supports

will make their final cost no greater than that of wooden poles.

In the present state of the market, steel towers can be had at from

three to three and one-half cents per pound, and the cost of a steel

tower or pole will vary nearly as its weight. During the first half of

1904 the quotations on tubular steel poles to the Southside Suburban

Railway Company, of Chicago, were between the limits just stated. That

company ordered some poles built up of steel sections about that time at

a trifle less than three cents per pound. Each of these poles was thirty

feet long and weighed 616 pounds, so that its cost was about eighteen

dollars (xxi, A. I. E. E., 754). For a forty-five-foot steel pole to

carry a pair of 11,000-volt, three-phase circuits along the New York

Central electric road the estimated cost was eighty dollars in the year

last named (xxi, A. I. E. E., 753). On the 100-mile line to Guanajuato,

Mexico, above mentioned, the steel towers were built up of 3″ × 3″ ×

3/16″ angles for legs, and were stayed with smaller angle sections and

rods. Each of these towers has four legs that come together near the

top, is forty feet high, weighs about 1,500 pounds, and carries a

single circuit composed of three No. 1 B. & S. gauge hard-drawn copper

cables. The weight of each of these cables is 1,340 pounds per mile, and

the forty-foot towers are spaced 440 feet apart, or twelve per mile,

over nearly the entire length of line. At three cents per pound, the

lowest figure at which these towers could probably be secured for use in

the United States, the approximate cost of each would be forty-five

dollars. Between Niagara Falls and Lockport each of the steel towers

that is to carry a single three-phase transmission circuit has three

legs built up of tubing that tapers from two and one-half inches to

smaller sizes and is braced at frequent intervals. The height of these

towers is forty-nine feet, and the weight of each is 2,800 pounds. At

three cents per pound the cost of each tower amounts to eighty-four

dollars. For a long transmission line in northern New York bids were

recently had on towers forty-five feet high to carry six wires, and the

resulting prices were $100 to $125 each for a tower weighing about 3,000

pounds. On the line between Niagara Falls and Toronto the standard tower

holds the lowest cables 40 feet above ground at the insulators, has a

weight of 2,360 pounds, and would cost $70.80 at 3 cents per pound.

In January, 1902, four steel towers were purchased to support

transmission circuits for two spans of 132 feet each over the Chambly

Canal, near Chambly Canton, Quebec. Each pair of these towers was

required to support eleven No. 2-0 B. & S. gauge bare copper wires with

the span of 132 feet between them. The vertical height of each of these

four towers is 144 feet above the foundation, and they were designed for

a maximum stress in any member of not more than one-fourth of its

ultimate strength, with wires coated to a diameter of one inch with ice

and under wind pressure. For these four steel towers erected on

foundations supplied by the purchasers the price was $4,670, and the

contract called for a weight in the four towers of not less than 121,000

pounds. On the basis of this weight the cost of the towers erected on

foundations was 3.86 cents per pound.

With these examples of the cost of steel towers a fair idea may be

gotten of the relative cost of wooden poles. For poles of cedar or other

desirable wood thirty-five feet long and with eight-inch tops fitted

with either one or two cross-arms an estimated cost of five dollars each

is ample to cover delivery at railway points over a great part of the

United States and Canada. This size of pole has been much used on the

long, high-voltage transmission systems that involve large power units

and use heavy conductors. Examples of lines where such poles are used

may be seen between Niagara Falls and Buffalo, between Colgate

power-house and Oakland, and between Cañon Ferry and Butte. Of course

some longer poles were used in special locations, like the crossing of

steam railways, but it is also true that on the lines supported by steel

towers such locations make exceptionally high towers necessary. The

thirty-five-foot poles will hold the electric lines about as high above

the ground level as the forty-nine-foot towers on the Niagara Falls and

Toronto transmission, because the former will be set so much closer

together. On the line just named the regular minimum distance of the

electric cables above the ground level at the centres of spans is

twenty-five feet. The standard towers on this line carry the lower

electric cables forty feet above the ground at the insulators, and it

was thought desirable to allow a sag of fifteen feet at the centres of

the regular spans of four hundred feet each. On these towers the

conductors that form each three-phase circuit are six feet apart, and

lines drawn between the three cables form the sides of an equilateral

triangle. With a pin fourteen and three-fourths inches long like that

used on these steel towers, and one conductor at the top of a

thirty-five-foot pole, where the other two are supported by a cross-arm

five feet three inches below, giving six feet between cables, the lower

cables are held by their insulators twenty-six feet above the ground,

when the poles are set five feet deep. Between thirty-five-foot poles

one hundred feet is a very moderate span, and one that is exceeded in a

number of instances. Thus on the 142-mile line from Colgate power-house

to Oakland the thirty-five-foot poles are 132 feet apart, and one line

of these poles carries three conductors of 133,000-circular-mil copper,

while the other pole line has three aluminum cables of 168,000 circular

mils. On the later transmission line from Niagara Falls to Buffalo,

which was designed for three-phase circuits of 500,000-circular-mil

cable, the regular distance between the thirty-five-foot poles is 140

feet.

A maximum sag of twenty-four inches between poles 100 feet apart under

the conditions named above brings the lowest points of the wire

twenty-four feet above the ground. The steel towers on the line to

Guanajuato being only forty feet in length, and spaced 440 feet apart,

it seems that the distance of conductors from the ground at the centres

of spans is probably no greater than that just named. Particular

attention is called to this point because it has been suggested that the

use of steel towers would carry cables so high that wires and sticks

could not be thrown onto them. It thus appears that thirty-five-foot

wooden poles set one hundred feet apart will allow as much distance

between conductors, and still keep their lowest points as far above the

ground, as will forty- to forty-nine-foot towers placed four hundred

feet or more apart. The two lines that have their conductors further

apart perhaps than any others in the world are the one from Cañon Ferry

to Butte, on thirty-five-foot wooden poles, and the one to Guanajuato,

on steel towers. In each of these cases the cables are seventy-eight

inches apart at the corners of an equilateral triangle. With steel

towers four hundred feet or wooden poles one hundred feet apart, four of

the latter must be used to one of the former. At $5 per pole this

requires an investment of $20 in poles as compared with at least $45 for

a tower like those on the Guanajuato line, $84 for a tower like those on

the line from Niagara Falls to Lockport, or $70 for one of the towers on

the Niagara and Toronto line. Each of the towers on the line to Toronto

carries two three-phase circuits, and the least distance between cables

is six feet. To reach the same result as to the distance between

conductors with the two circuits on poles, it would be desirable to have

two pole lines, so that $40 would represent the investment in the poles

to displace one tower for two circuits. The older pole line between

Niagara Falls and Buffalo carries two three-phase circuits on two

cross-arms, and the 350,000-circular-mil copper cables of each circuit

are at the angles of an equilateral triangle whose sides are each three

feet long. In this case, however, the electric pressure is only 22,000

volts.

The costs above named for poles and towers include nothing for erection.

Each tower has at least three legs and more commonly four, and owing to

the heights of towers and to the long spans they support it is the usual

practice to give each leg a footing of cement concrete. It thus seems

that the number of holes to be dug for a line of towers is nearly or

quite as great as that for a line of poles, and considering the concrete

footings the cost of erecting the towers is probably greater than that

for the poles. With wooden poles about four times as many pins and

insulators are required as with steel towers, or say twelve pins and

insulators on poles instead of three on a tower. For circuits of 50,000

to 60,000 volts the approximate cost of each insulator with a steel pin

may be taken at $1.50, so that the saving per tower reaches not more

than $13.50 in this respect. In the labor of erecting circuits there may

be a small advantage in favor of the towers, but the weight of the long

spans probably offsets to a large extent any grain of time due to fewer

points of support.

An approximate conclusion from the above facts seems to be that a line

of steel towers will probably cost from 1.5 to twice as much as a line

or lines of wooden poles to support the same number of conductors the

same distance apart, even when the saving of pins and insulators is

credited to the towers. This conclusion applies to construction over a

large part of the United States and Canada. It is known that wooden

poles of good quality retain enough strength to make them reliable as

supports during ten or fifteen years, and it is doubtful whether steel

towers will show enough longer life to more than offset their greater

first cost. It may be noted here that any saving in the cost of

insulators or other advantage that there may be in spans four hundred

feet or more long can be as readily secured with wooden as with steel

supports. With these long spans the requirements are greater height and

strength in the line supports, and these can readily be obtained in

structures each of which is formed of three or four poles with

cross-braces. Such wooden structures have long been in use at certain

points on transmission lines where special long spans were necessary or

where there were large angular changes of direction. In those special

cases where structures 75 to 150 or more feet in height are necessary to

carry a span across a waterway, as at the Chambly Canal above mentioned,

steel is generally more desirable than wood because poles of such

lengths are not readily obtainable. Neither present proposals nor

practice, however, contemplates the use of steel towers having a length

of more than forty to fifty feet on regular spans.

Much the strongest argument in favor of steel towers for transmission

lines is that these towers give a greater reliability of operation than

do wooden poles. It is said that towers will act as lightning-rods and

thus protect line conductors and station apparatus. As to static and

inductive influences from lightning, it is evident that steel towers can

give no protection. If each tower has an especial ground connection it

will probably protect the line to some extent against direct lightning

strokes, but there is no reason to think that this protection will be

any greater than that given by well-grounded guard wires, or even by a

wire run from a ground plate to the top of each pole or wooden tower. If

a direct lightning stroke passes from the line conductors to a wooden

support it frequently breaks the insulator on that support, and the pole

is often shattered or burned. Such a result does not necessarily

interrupt the transmission service, however, as the near-by poles can

usually carry the additional strain of the line until a new pole can be

set. Quite a different result might be reached if lightning or some

other cause broke an insulator on a steel tower, and thus allowed one of

the electric cables to come into contact with the metal structure, as

the conductor would then probably be burned in two. To repair a heavy

cable thus severed where the spans were as much as 400 feet long would

certainly require some little time. Where a conductor in circuits

operating at 20,000 to 35,000 volts has in many cases dropped onto a

wooden cross-arm, it has often remained there without damage until

discovered by the line inspector, but no such result could be expected

with steel towers and cross-arms (xxi, A. I. E. E., 760). Where steel

towers are employed it would seem to be safer to use wooden cross-arms,

for the reasons just stated. This is, in fact, the practice on the steel

towers before named that support 25,000-volt circuits over the Chambly

Canal, and also on the steel towers that carry the 60,000-volt circuits

from Colgate power-house over the mile-wide Straits of Carquinez.

On the 40,000-volt transmission line between Gromo and Nembro, Italy,

where timber is scarce and steel is cheap, both the poles and cross-arms

are of wood. It is thought that the comparatively small number of

insulators used where a line is supported at points about four hundred

feet apart should contribute to reliability in operation, but insulators

now give no more trouble than other parts of the line, and the leakage

of energy over their surfaces is very small in amount, as was shown in

the Telluride tests. Whatever benefits are to be had from long spans are

as available with wooden as with steel supports, and at less cost.

One advantage of steel towers over wooden poles or structures is that

the former will not burn and are probably not subject to destruction by

lightning. Where a long line passes over a territory where there is much

brush, timber or long grass, the fact that steel towers will not burn

may make their choice desirable. In tropical countries where insects

rapidly destroy wooden poles the use of steel towers may be highly

desirable even at much greater cost, and such a case was perhaps

presented on the line to Guanajuato, Mexico.

Mechanical failures of wooden insulator pins have been far more common

than those of poles, both as a direct result of the line strains and

because such pins are often charred and weakened by the leakage of

energy from the conductors. For these reasons the general use of iron or

steel pins for the insulators of long lines operating at high voltages

seems desirable. Such pins are now used to support the insulators on a

number of lines with wooden poles and cross-arms, among which may be

mentioned the forty-mile, 30,000-volt transmission between Spier Falls

and Albany and the forty-five-mile 28,000-volt line from Bear River to

Ogden, Utah. Iron or steel pins add very little to the cost of a line,

and materially increase its reliability. One of the cheapest and best

forms of steel pins is that swaged from a steel pipe and having a

straight shank and tapering stem with no shoulder. A pin of this sort

for the 400-foot spans of 190,000-circular-mil copper cable on the line

from Niagara Falls to Toronto measures three and one-quarter inches long

in the shank, eleven and one-half inches in the taper, and has diameters

of two and three-eighths inches at the larger and one and one-eighth

inches at the smaller end. On spans under 150 feet between wooden poles

pins of this type but with a much smaller diameter could be used to

advantage.

On long transmission lines where the amount of power involved is very

large the additional reliability to be had with steel towers is probably

great enough to justify their use. For the great majority of power

transmissions, however, it seems probable that wooden poles or

structures will long continue to be much the cheaper and more

practicable form of support.

The line of steel towers on a private right of way seventy-five miles

long, carrying two circuits for the transmission of 24,000 horse-power

at 60,000 volts from Niagara Falls to Toronto, is one of the most

prominent examples of this type of construction.

Eventually there will be two rows of steel towers along the entire

length of the line.

On the straight portions of the line the steel towers are regularly

erected 400 feet apart, but on curves the distances are less between

towers, so that their total number is about 1,400 for each line.

Standard curving along the line requires towers placed 50 feet apart,

and a change in the direction of not more than ten degrees at each

tower, except at the beginning and end of the curve, where the change in

direction is three degrees. When the change in the direction of the line

is not more than six degrees, the corresponding spans allowed with each

change are as follows:

Degrees Feet of

change. span.

1/2 300

1 286

1-1/2 273

2 259

2-1/2 246

3 232

3-1/2 219

4 205

4-1/2 192

5 178

5-1/2 165

6 151

At some points along the line conditions require a span between towers

of more than 400 feet, the regular distance for straight work. One

example of this sort occurs at Twelve-Mile Creek, where the stream has

cut a wide, deep gorge in the Erie plateau. At this point the lines make

a span of 625 feet between towers.

[Illustration: FIG. 94.--Transposition Tower (Second Tower).]

[Illustration: FIG. 95.--Elevations and Plan of Tower.]

The regular steel tower used in this transmission measures 46 feet in

vertical height from its foot to the tops of the lower insulators, and

51 feet 3 inches to the tops of the higher insulators. The lower six

feet of this tower are embedded in the ground, so that the tops of the

insulators measure about 40 feet and 45 feet 3 inches respectively above

the earth. At the ground the tower measures 14 feet at right angles to

the transmission line and 12 feet parallel with it. The width of each

tower at the top is 12 feet at right angles to the line, and the two

sides having this width come together at points about 40 feet above the

ground. Between the two L bars thus brought nearly together, at each

side of a tower a piece of extra heavy 3-inch steel pipe is bolted so as

to stand in a vertical position. Each piece of this pipe is about 3-1/2

feet long and carries a steel insulator pin at its upper end. The two

pieces of pipe thus fixed on opposite sides of the top of a tower carry

the two highest insulators. For the other four insulators of each tower,

pins are fixed on a piece of standard 4-inch pipe that serves as a

cross-arm, and is bolted in a horizontal position between the two

nearly rectangular sides of each tower, at a point two feet below the

bolts that hold the vertical 3-inch pipes, already named, in position.

Save for the two short vertical and one horizontal pipe, and the pins

they support, each tower is made up of L-shaped angle-bars bolted

together. Each of the two nearly rectangular sides of a tower consists

of two L bars at its two edges, three L bars for cross-braces at right

angles to the edges, and four diagonal braces also formed of L bars. The

lower halves of the L bars at the edges of each side of a tower have

sections of 3″ × 3″ × 1/4″, and the upper halves have sections of 3″ ×

3″ × 3/16″. This last-named cross-brace and the other two cross-braces

have a common section of 2″ × 1-1/2″ × 1/8″. For the lower set of

diagonal braces the common section is 2-1/2″ × 2″ × 1/8″, and the upper

set has a section of 2″ × 1-1/2″ × 1/8″ in each member. At the level of

the lowest cross-braces the two rectangular sides of a tower are tied

together by one member of 2″ × 1-1/2″ × 1/8″ of L section and at right

angles to the sides, and by two diagonal braces of 5/8″ round rod

between the corners of the tower. On each of its two triangular sides a

tower has four horizontal braces and three sets of diagonal braces. The

two upper horizontal braces are of 2″ × 1-1/2″ × 1/8″ L section, and the

lowest is the same, but the remaining horizontal brace has a section of

2-1/2″ × 2″ × 1/8″. Bars of 2″ × 1-1/2″ × 1/8″ L section are used for

the two upper sets of diagonal braces, and bars of 2-1/2″ × 2″ × 1/8″

for the lower set. In addition to the cross-braces named, each

triangular side of a tower near the top of the corner bars has two short

cross-pieces with the common L section of 3-1/2″ × 3-1/2″ × 5/8″, one

just above and the other just below the cross-arm of 4-inch pipe to hold

it in place. At the bottom of each of the four corner bars of a tower a

foot is formed by riveting a piece of 3″ × 1/4″ L section and 15 inches

long at right angles to the corner bar. On one corner bar of each tower

there are two rows of steel studs for steps, one row being located in

each flange of the L section. On the same flange these steps are two

feet apart, but taking both flanges they are only one foot apart. Every

part of each steel tower is heavily galvanized.

[Illustration: FIGS. 96, 97, 98.--Raising Towers on Niagara Transmission

Line.]

[Illustration: FIG. 99.--One of the Towers in Position.]

The labor of erecting these steel towers was reduced to a low figure by

the method employed, as shown in the accompanying illustration. Each

tower was brought to the place where it was to stand with its parts

unassembled. For erecting the towers a four-wheel wagon with a timber

body about thirty feet long was used. When it was desired to raise a

tower, two of the wheels, with their axle, were detached from the timber

body of the wagon, and this body was then stood on end to serve as a

sort of derrick. This derrick was guyed at its top on the side away from

the tower, and a set of blocks and tackle was then connected to the top

of the derrick and to the tower at a point about one-fourth of the

distance from its top. A rope from this set of blocks ran through a

single block fixed to the base of the derrick and then to a team of

horses. On driving these horses away from the derrick the steel tower

was gradually raised on the two legs of one of its rectangular sides

until it came to a vertical position. The next operation was to bring

the legs of the tower into contact with the extension pieces that were

fixed in the earth and then bolt them together.

[Illustration: FIG. 100.--Steel Tower for Transmission Line.]

The tops of the three pins that carry the insulators for each

three-phase circuit are at the corners of an equilateral triangle (Fig.

100), each of whose sides measures six feet. The six steel insulator

pins used on each tower are exactly alike, and each is swaged from extra

heavy pipe. Each finished pin is 2-3/8 inches in diameter for a length

of 3-1/4 inches, and then tapers uniformly to a diameter of 1-1/8 inch

at the top through a length of 11-1/2 inches. This gives the pin a total

length of 14-3/4 inches. In the larger part there are two 9/16-inch

holes from side to side, and within two inches of the top there are

three circular grooves each 3/16 inch wide and 1/16 inch deep. Forged

steel sockets of two types are employed to attach the steel pins with

the pipes. Each socket is made in halves, and these halves are secured

to both the pipe and the pin by through bolts. Like all other parts of

the towers, these steel pins and sockets are heavily galvanized. On

each of the four corner bars of a tower the lower six feet of its length

is secured to the upper part by bolts or rivets. This lower six feet of

each corner bar is embedded in the earth, and the construction just

named makes it easy to replace the bars in the earth when corrosion

makes it necessary.

Footings for each tower are provided by digging four nearly square holes

with their sides at approximately 45 degrees with the direction of the

transmission line, and the shortest side of each hole at least two feet

long. Centres of these holes are 14 feet 3 inches apart in a direction

at right angles to the line, and 13 feet 9 inches apart parallel with

the line. In hard-pan each one of the holes was filled to within 2 feet

6 inches of the top with stones, after the leg of the tower was in

position, and then the remainder of the hole was filled with cement

grouting mixed four to one.

At the bottom of each hole in marsh land a wooden footing 3 feet × 6

inches × 24 inches was laid flat beneath the leg of the tower, and then

the hole was filled to within 2-1/2 feet of the surface with the

excavated material. Next above this filling comes a galvanized iron

gutter-pipe, four inches in diameter, and filled with cement about the

leg of the tower for a length of two feet. Outside of this pipe the hole

is made rounding full of cement grouting.

[Illustration: FIG. 101.--Transmission Line at Welland Canal.]

At some points along the transmission line exceptionally high towers are

necessary, a notable instance being found at the crossing over the

Welland Canal, where the lowest part of each span must not be less than

150 feet above the water. For this crossing two towers 135 feet high

above ground are used, as seen in Fig. 101. Each of these towers is

designed to carry all four of the three-phase power circuits that are

eventually to be erected between Niagara Falls and Toronto. For this

purpose there was used a special design of tower with a width of about

48 feet at right angles to the direction of the line below the top

truss, and a width of about 68.5 feet at that truss where the two lower

conductors of each circuit are attached.

With all spans longer than 400 feet, a tower of heavier construction

than the standard type is used, and this tower provides three insulators

for the support of each conductor. A tower of this type that supports

the lowest conductors about 40 feet above the ground level has its

corner bars made up of 4″ × 4″ × 3/8″ and 4″ × 4″ × 5/16″ L sections,

has three cross-arms of extra heavy 4-inch pipe, and a 6-inch vertical

standard pipe to support each group of three insulators for the highest

conductor of each circuit. Each of the lower conductors of a circuit on

this tower is supported by an insulator on each of the three parallel

cross-arms. On some of these towers, for long spans, the two outside

insulators for the support of each conductor are set a little lower than

the insulator between them.

[Illustration: FIG. 102.--Heavy Tower at Credit River.]

[Illustration: FIG. 103.--Angle Tower Near Bronte.]

Angle towers, used where the line makes a large change in direction at a

single point, have three legs on each rectangular side, a width of 20

feet on each of these sides for some distance above the ground, and a

width of 27 feet 2 inches at the top. In these towers the two legs on

the triangular side that is in compression are each made up of four 3″ ×

3″ × 1/4″ L sections joined by 1-1/2″ × 1/4″ lattices and rivets. Towers

of this sort are used near the Toronto terminal-station, where the line

changes 35 degrees at a single point, and near the crossing of

Twelve-Mile Creek, where the angular change of the line on a tower is 45

degrees. Close to each terminal-station and division-house the

transmission line is supported by terminal towers. These towers differ

from the others in that each carries insulators for only three

conductors, and these insulators are all at the same level. Each

terminal tower has nine insulators, arranged in three parallel rows of

three each for the conductors of a single circuit, and each conductor

thus has its strain distributed between three pins. All three wires of a

circuit are held 40 feet above the ground by a terminal tower, and pass

to their entries in the wall of a station at the same level. As these

terminal towers must resist the end strain of the line, they are made

extra heavy, the four legs each being made up of 4″ × 4″ × 5/16″ and 4″

× 4″ × 3/8″ L sections. For the three cross-arms on one of these towers

three pieces of 4-inch pipe, each 15 feet 9 inches long, are secured at

its top with their parallel centre lines 30 inches apart in the same

plane. Each of these pipes carries three insulator pins with their

centres 7 feet 4-1/2 inches apart. On the bottom of each leg of a

terminal tower there is a foot, formed by riveting on bent plates, that

measure 15 and 18 inches, respectively, on the two longer sides. Each

foot of this tower is set in a block of concrete 5 feet square that

extends from 3.5 feet to 7.5 feet below the ground level.

Insulators for the transmission line, which are illustrated in Fig. 104,

are of brown, glazed porcelain, made in three parts, and cemented

together. The three parts consist of three petticoats or thimbles, each

of which slips over or into one of the others, so that there are three

outside surfaces and three interior or protected surfaces between the

top of an insulator and its pin.

From top to bottom the height of each insulator is 14 inches, and this

is also the diameter of the highest and largest petticoat. The next or

middle petticoat has a maximum diameter of 10 inches and the lowest

petticoat one of 8 inches. Cement holds the lowest petticoat of the

insulator on one of the steel pins previously described, and in this

position the edge of the lowest petticoat is about 2-1/2 inches from the

steel support. At the top of each insulator the transmission conductor

is secured, and the shortest distance from this conductor to any of the

steel parts through the air is about 17 inches.

From the step-up transformer house at Niagara Falls to the

terminal-station at Toronto, a distance of seventy-five miles, each

three-phase, 60,000-volt, 25-cycle circuit on the steel towers is made

up of three hard-drawn copper cables with a cross section of 190,000

circular mils each, and is designed to deliver 12,000 electric

horse-power with a loss of ten per cent, on a basis of 100 per cent

power factor. Six equal strands of copper make up each cable, and this

wire has been specially drawn with an elastic limit of more than 35,000

pounds and a tensile strength of over 55,000 pounds per square inch.

This cable is made in uniform lengths of 3,000 feet, and these lengths

are joined by twisting their ends together in copper sleeves, and no

solder is used. No insulation is used on these cables.

[Illustration: FIG. 104.--Insulators.]

Instead of a tie-wire, a novel clamp is employed to secure the copper

cable on each insulator. This complete clamp is made up of two separate

clamps that grasp the cable at opposite sides of each insulator and of

two half-circles of hard-drawn copper wire of 0.187 inch diameter. Each

half-circle of this wire joins one-half of each of the opposite clamps,

and fits about the neck of the insulator just below its head. Two bronze

castings, one of which has a bolt extension that passes through the

other, and a nut, make up each separate clamp. When the combined clamp

is to be applied, the sides are separated by removing the nut that holds

them together, the half-circles are brought around the neck of the

insulator, and each of the side clamps is then tightened on to the cable

by turning the nut that draws its halves together. This complete clamp

can be applied as quickly as a tie-wire, is very strong, and does not

cut into the cable.

Each of the regular steel towers is designed to withstand safely a side

strain of 10,000 pounds at the insulators, or an average of 1,666 pounds

per cable. With the 190,000-mil cable coated to a depth of 1/2 inch with

ice and exposed to a wind blowing 100 miles per hour, the estimated

strains on each steel pin for different spans and angular changes in the

direction of the line are given in the accompanying table:

POUNDS STRAIN ON PINS, 1/2-INCH SLEET, 100 MILES WIND.

=====+=========================================

| Degrees and Minutes.

Span,+-----+-----+-----+-----+-----+-----+-----

feet.| 0 | 0.30| 1 | 1.30| 2 | 2.30| 3

-----+-----+-----+-----+-----+-----+-----+-----

0| 0| 35| 69 | 104| 138| 173| 207

100| 256| 291| 325| 360| 394| 429| 463

200| 512| 547| 581| 616| 650| 685| 719

300| 768| 803| 837| 872| 906| 941| 975

400|1,024|1,059|1,093|1,128|1,162|1,197|1,231

500|1,280|1,315|1,349|1,384|1,418|1,453|1,487

600|1,536|1,571|1,605|1,640|1,674|1,709|1,743

700|1,792|1,827|1,861|1,896|1,930|1,965|1,999

800|2,048|2,083|2,117|2,152|2,186|2,221|2,255

900|2,304|2,339|2,373|2,408|2,442|2,477|2,511

1,000|2,560|2,595|2,629|2,664|2,698|2,733|2,767

-----+-----+-----+-----+-----+-----+-----+-----

=====+===================================

| Degrees and Minutes.

Span,+-----+-----+-----+-----+-----+-----

feet.| 3.30| 4 | 4.30| 5 | 5.30| 6

-----+-----+-----+-----+-----+-----+-----

0| 242| 276| 311| 345| 380| 414

100| 498| 532| 567| 601| 636| 670

200| 754| 788| 823| 857| 892| 926

300|1,010|1,044|1,079|1,113|1,148|1,182

400|1,266|1,300|1,335|1,369|1,404|1,438

500|1,522|1,556|1,591|1,625|1,660|1,694

600|1,778|1,812|1,847|1,881|1,916|1,950

700|2,034|2,068|2,103|2,137|2,172|2,206

800|2,290|2,324|2,359|2,393|2,428|2,462

900|2,546|2,580|2,615|2,649|2,684|2,718

1,000|2,802|2,836|2,871|2,905|2,940|2,974

-----+-----+-----+-----+-----+-----+-----

The copper cables were so strung as to have a minimum distance from the

ground of 25 feet at the lowest points of the spans. In order to do this

the standard steel towers that hold the lower cables 40 feet above the

ground level at the insulators are spaced at varying distances apart,

according to the nature of the ground between them. At each tower the

upper cable of each circuit is 5 feet 3 inches higher than the two lower

cables, and this distance between the elevations of the upper and the

lower cables is maintained whatever the amount of sag at the centre of

each span. If there is a depression between two standard towers on a

straight portion of the line, the sag in the centre of a span 400 feet

long may be as much as 18 feet. Where a rise and fall in the ground

between towers make it necessary to limit the sag to 14 feet in order to

keep the lowest cables 25 feet above the highest point of earth, the

length of span is limited to 350 feet. If the rise and fall of ground

level between towers allow a sag of only 11 feet with the lowest cable

25 feet above the earth, the length of span with 40-foot towers is

reduced to 300 feet; and if for a like reason the sag is limited to 8

feet, the span may only be 250 feet.

[Illustration: FIG. 105.--Take-up Arrangement on Terminal Tower.]

At each terminal tower, where the cables are secured before they pass

into a terminal-station, the three insulators for each cable are in a

straight line with their centres, 30 inches apart. When a line cable

reaches the first insulator of the three to which it is to be attached

on one of these towers, it is passed around the neck of this insulator

and then secured on itself by means of two clamps that are tightened

with bolts and nuts. See Fig. 105. The cable thus secured turns up and

back over the tops of the three insulators and goes to the

terminal-station. Around the neck of the insulator to which the line

cable has been secured in the way just outlined a short detached length

of the regular copper cable with the parts of a turnbuckle at each end

is passed, and this same piece of cable also passes around the neck of

the next insulator in the series of three. By joining the ends of the

turnbuckle and tightening it, a part of the strain of the line cable in

question is transferred from the first to the second insulator of the

series. In the same way a part of the strain of this same line cable is

transferred from the second insulator of the series to the third, or one

nearest to the terminal-station.

INDEX.

Air-blast cooled transformers, 129

Air-gap data, 183

Air gaps, number in series to stand given voltage, 183

Albany-Hudson Ry. Plant, 121

Alternating currents, 227

Alternator voltage, 118

Alternators, 103

data, 118

for high voltage, 120

inductor, 112

types of, 111

Aluminum as a conductor, 200, 209

cables in use, 213

conductor joints, 206

conductors, 27, 28

corrosion of, 211

properties of, 212

soldered joints, 206

_vs._ copper, 209

wire, cost of, 29

Amoskeag Mfg. Co. plant, 51, 52

Amsterdam (N. Y.) plant, 121

Anchor ice, 59

Anderson (S. C.) plant, 121

Apple River (Minn.) plant, 1, 26, 27, 28, 71, 97, 98, 99, 102, 118,

119, 124, 126, 127, 134, 174, 187, 190, 192, 208, 245, 264, 294

Arc lighting, 167

Arcing, 46

Automatic regulators, 162

Barbed wire, 169, 175

Belt drive, 83, 107

Bienne plant (Switzerland), 42

Birchem Bend, 57, 67, 79, 95, 97, 98, 102

Blower capacity necessary to cool transformers, 130

Boosters, 133

Boston-Worcester Ry. plants, 121

Braces for cross-arms, 259

Bronze conductors, 200

Brush discharge, 281

Buchanan (Mich.) plant, 88

Building materials, 95

Bulls Bridge plant, 63

Burrard Inlet (B. C.) plant, 111, 112

Bus-bars, 142, 147

dummy, 145

Cable insulation, 195

sheaths, 194

ways, 140

Cables, aluminum, 212

aluminum, in use, 213

charging current, 197

cost of, 188, 196

for alternating current, 194

high-voltage, 191

paper insulated, 196

protection against electrolysis, 195

rubber-covered, 195

submarine, 192

temperature of, 198

voltage in, 190, 196

Canadian-Niagara Falls Power Co., 121

Canals, 51, 53

long, 68

Cañon City plant, 26, 27, 28, 117, 118, 127, 208

Cañon Ferry plant, 1, 3, 26, 27, 28, 46, 49, 53, 62, 68, 69, 83, 89,

94, 95, 97, 102, 105, 112, 113, 118, 119, 124, 125, 126, 127, 130,

132, 134, 174, 208, 233, 234, 245, 246, 249, 254, 257, 259, 268, 272,

280, 282, 294, 295, 302

Cedar Lake plant, 90

Chambly plant, 96, 110, 149, 156, 172, 189, 249, 255, 256, 257, 267,

272, 287, 294, 295, 311, 312

Charging current for cable, 197

Charring of pins, 276, 278

Chaudière Falls plant, 118

Choke-coil used with lightning arresters, 180

Circuit breakers, 135, 150

breakers, time limit, 152

Circuits, selection of, 233

Coal, price of, in Salt Lake City, 8

Colgate plant, 1, 3, 26, 27, 28, 74, 82, 83, 90, 94, 97, 98, 99, 101,

102, 108, 112, 113, 118, 127, 130, 132, 134, 187, 190, 201, 206, 208,

213, 245, 246, 250, 254, 257, 272, 277, 280, 282, 294, 295, 304, 309

Columbus (Ga.) plant, 83, 115

Compounding, 160

Compressive strength of woods, 302

Conductivity of the conductor metals, 201

Conductors, 200

aluminum, 27, 28, 206

aluminum, properties of, 212

coefficients of expansion, 200

corrosion of, 211

cost of, 22, 29, 203, 204, 205

cost of aluminum, 29

cost of per k. w., 28

cost of copper, 29

data, 204

data from representative transmission plants, 208

expansion of aluminum and copper, 211

melting points, 200

minimum size for transmission line, 202

properties of ideal, 200

relative conductivity, 201

relative cost of, 20

relative properties for equal lengths and resistances, 204

relative strengths for given area, 203

relative weight for given conductivity, 202

relative weight of, 202

relative weights of three-phase, two-phase, and single-phase lines,

220

resistance of, 225

skin effect, 206, 233

weight per k. w., 27

Conduits, 195

radiation loss in, 198

temperature rise in, 198

Constant current regulator, 167

transformer, 167

Control equipment for d. c. and a. c. plants, 35

Copper conductors, 200

cost of, 22

_vs._ aluminum, 209

wire, cost of, 29

Corrosion of conductors, 211

Cross-arm braces, 258

iron, 284

location of, 257

material, 258

Cross-arms, 49, 256

Crossings, 187

Dales plant (White River), 26, 27, 28, 71, 134, 208

Dams, 62

Delta connection, 131

Depreciation, 11

Design of power-plant, 83

Dike, 60

Direct connection, 84

Discharge, static, 170

Distribution system, 158

Draught tubes, 79

Dummy bus-bars, 145

Easton (Pa.) plant, 121

Edison Co. (Los Angeles) plant, 118

Efficiency constant-current transmission, 216

curves, motor-generator set, 117

of constant-voltage transmission, 217

of transformers, 133

relative, of a. c. and d. c. transmission, 35

Electra plant, 1, 3, 74, 82, 83, 92, 94, 97, 98, 101, 102, 108, 112,

113, 118, 127, 174, 206, 208, 212, 213, 233, 235, 236, 245, 248, 253,

254, 256, 259, 272, 275, 277, 280, 281, 282, 294, 295

Electric power, market for, 7

Electrical Development Co., Niagara plant, 120

Electricity _vs._ gas, 6

Electrolysis, 195

Energy curves of hydro-electric stations, 13

electrical, cost of at switchboard, 23

Entrance end strain, 261, 325

insulating discs, 262

into buildings, 179

of lines, 179, 261, 265

through roof, 269

wall openings, 262

Entries for transmission lines, 261

Expansion, coefficient of, for copper and aluminum, 211

coefficients of, for various conductor metals, 200

Farmington River (Conn.) plant, 26, 27, 28, 58, 118, 125, 134, 208,

212, 213,

245

Feeders, 143

Ferranti cables, 192

Fire-proofing, 95

Floor, distance from roof to, 95

location of, 79

space, 12, 101, 102

space per k. w. of generators, 12

Floors, 95

Fog, 46, 277

Fore-bay, 59, 60

Foundations, 95

Frequency, 113, 127

effect on transformer cost, 116

Fuel, price of, in Salt Lake City, 8

Fuses, 135, 150

Garvins Falls plant, 56, 60, 79, 80, 94, 96, 97, 102, 113, 145, 240,

294

Gas _vs._ electricity, 6

Gears, 84, 108

Generators (a. c.), 103

d. c. _vs._ a. c., 31

Generators, belt-driven, 107

capacity of, 32

compounding of, 160

cost of, 40

(a. c.) cost, 32

(a. c.) data, 118

direct-connected to horizontal turbines, 89

to impulse wheels, 90

connection to vertical shafts, 84

(d. c.) field excitation of, 41

floor space, 101

per k. w., 12

gear-driven, 108

(a. c.) high-voltage, 120

(d. c.) in series, 31

(d. c.) installation of, 41

insulation of, 39, 45

lightning protection, 34

limiting voltage of, 44

(a. c.) limiting voltage of, 32

(d. c.) limiting voltage of, 31

overload capacity, 103

relation between voltage and capacity, 127

revolving armatures, 112

fields, 112

series-wound, 41

speed regulation, 38

Glass _vs._ porcelain insulators, 288

Great Falls plant, 54, 60, 61, 64, 67, 78, 92, 93, 102, 114, 118

Greggs Falls plant, 54, 56, 64, 240

Ground connections, 178

for guard wires, 171, 172

Grounded guard wires, 168

Guard wires, 168

installation of, 175

Guying of poles, 255

Hagneck (Switzerland) plant, 86

Hooksett Falls plant, 56, 131

Hydro-electric plants, 1

built at the dam, 64-67

canals, long, 68-73

long and short, 58

short, 53-56

capacity and weight of conductors per k. w. for various plants, 27

(800 k. w.) cost of, 10

(1500 k. w.) cost of, 11

cost of labor, 12

cost of operation, 12, 77

design of, 83

floor, 79

space per k. w., 101

interest and depreciation, 11

linked together, 56-58

load factors, 14, 15

location of, 64

model design, 12

operation, 59

_vs._ steam plant, 5, 12

with pipe-lines, 73-77

with steam auxiliary, 84

Ice, 59

Impulse wheel speed, 108

wheels, 82, 90

location of, 99

Indian Orchard plant, 57, 84

Inductance, 206, 230

Induction, electro-magnetic, electrostatic, 168

on lines, 206

regulator, 162

Inductor alternators, 112

Insulation, as affected by ozone, 197

cost of paper _vs._ rubber, 196

of a. c. and d. c. lines, 34

of apparatus, 142

of cables, 195

of electrical machines, 45

of generators, 39

protection against ozone, 198

Insulator arc-over test, 291

-pins, 270 (see Pins)

Insulators, 277, 282, 287, 322

and pins, data from various plants, 280

defective, 288

glass _vs._ porcelain, 288

in snow, 293

method of fastening to iron pins, 271

novel clamp, 323

on various transmission lines, 294

petticoats, 294

testing of, 288

tests, 290

test voltage, 289

with oil, 287

Iron conductors, 200

Kelley’s Falls plant, 56

Kelvin’s law, 219

Labor, cost of, 12

in hydro-electric stations, 12

Leakage, 275, 287

line, 207, 214

Lewiston (Me.) plant, 118, 120, 122, 167, 213

Lighting, incandescent, minimum frequency, 116

series distribution, 167

Lightning arrester, effect of series resistance, 185

arresters, 168, 176

ground connection, 178

multiple air-gap, 176, 183

non-arcing metals in, 184

series connection of, 180

shunted air-gaps, 185

with choke coil, 180

protection, 34

Line calculations, 221-232

charging current, 197

conductors, 200

conductors, cost of, 22

weight of, 21

construction, 222

cost, 310

cross-arms, 49

spacing of wires, 46

(a. c.) transmission, 34

(d. c.) transmission, 33

end strain, 325

leakage, 47

loss, 39

losses due to grounded guard wires, 176

Lines, sag, 309

transposition of, 314

Line voltages, 45

Load factors, 14, 15

lighting, 61

maximum, 60

motor, 160

railway, 164

Loss in conduits, 198

relation to weight of conductors, 215

Losses due to grounded guard wire, 176

on transmission lines, 215

Ludlow Mills plant, 26, 27, 28, 57, 79, 100, 121, 208, 213

Madrid (N. M.) plant, 26, 27, 28, 118, 208

Manchester (N. H.) plants, 120

Market for electric power, 7

Materials, building, 95

for line-conductors, 200

Mechanicsville plant, 58, 67, 109, 121, 174

Melting points of conductor metals, 200

Montmorency Falls plant, 26, 27, 28, 240

Motor load, 160

Motor-generator set efficiency curve, 117

Motors, series-wound, 41

(d. c.) speed regulation, 38

synchronous, 241

Multiple air-gap arrester, 176

Needle-point spark-gap for measuring pressure, 290

Neversink River plant, 75, 179

Niagara Falls Power Co., 3, 59, 81, 86, 87, 93, 94, 95, 97, 101, 102,

105, 106, 107, 108, 112, 113, 117, 118, 119, 127, 133, 137, 140, 143,

145, 151, 153, 161, 165, 170, 181, 188, 194, 195, 208, 211, 240, 245,

246, 257, 272, 273, 275, 280, 287, 289, 294, 295, 297

Nitric acid from air, 281

Non-arcing metals, 184

North Gorham (Me.) plant, 120

Ogden (Utah) plant, 26, 27, 28, 118, 120, 132, 134, 208, 245

Ohm’s law, 223

Oil switches, 136

Ontario Power Co., 121

Operating expenses, 59

Operation, cost of, 12, 77

Operations, reliability of, 311

Ouray (Col.) plant, 121

Overhead line connection to underground, 197

Overload capacity of generators, 103

Ozone, 197

Painting of poles, 255

Paper insulated cables, 196

_vs._ rubber insulation, 196

Payette River (Idaho) plant, 73, 101

Penstocks, 59, 98

Phase, 113

Pike’s Peak plant, 77

Pilot wires, 161

Pins, 259, 270

and insulators, data from various plants, 280

burning of, 270, 276, 278

charring of, 276, 278

composite, 281

compressive strength of woods, 302

design of, 298

dimensions of, 301

formula for diameter of, 299

iron, 275, 285, 286

expansion of, 290

method of fastening insulators, 271

method of fastening to cross-arms, 271

metal, 271, 275, 282, 285, 286

of uniform strength, 300, 302

proportions, 301

relative cost of metal and wooden, 284

shank, 274

shoulder, 275, 299, 305

softening of threads, 280

steel, 275, 312

strain with 1/2-inch sleet and 100-mile wind for different spans,

324

strains on, 270, 298

strength of, 303

table of standard, 301

treatment of, 259, 275

weakest point, 298

wooden, data from various plants, 272

dimensions of, 272

dimensions of standard, 273

Pipe-lines, 73

Pittsfield (Mass.) plant, 121

Pole line, cost of, 21

lightning arresters, 179

relative cost of, 20

lines, 246

Poles, cost, 310

depth in ground, 254

diameter of, 254

dimensions of, 254

guying of, 255

iron, 284

length of, 253, 309

life of, 255

setting of, 252

spacing of, 249

steel, cost of, 307

treatment of, 255

woods for, 252

Porcelain _vs._ glass insulators, 288

Portland (Me.) plant, 120, 166, 239

Portsmouth, N. H. plant (steam), 102, 118, 119, 120, 121, 144, 194,

264, 294

Power plant, relative cost of a. c. and d. c., 36

transmitted, total cost of, 24

Radiation loss in conduits, 198

Railway crossing, 187, 252

service, 164

Red Bridge plant, 53, 60, 79, 93, 94, 96, 97, 99, 101, 102

Regulation, 155, 239

as effected by synchronous motors, 165

at receiving end, 162

hand, 161

Regulator, automatic, 162

constant-current, 167

induction, 162

Relay-switches, 145

Resistance, 225

in series with lightning arrester, 185

Revolving armature alternators, 112

field alternator, 112

River crossings, 187, 190, 249

Roof, distance from floor, 95

Roofs, 95

Rope-drive, 83

Rotaries, cost of, 117

suitable frequency for, 115

Rubber-covered cables, 195

maximum temperature, 198

protection against ozone, 198

Sag in lines, 309

St. Hyacinthe (Que.) plant, 118

St. Joseph plant, 66

St. Maurice plant (Switzerland), 31

Salem (N. C.) plant, 121, 122

San Gabriel Cañon plant, 26, 27, 28, 208

Santa Ana plant, 1, 26, 27, 28, 74, 76, 82, 83, 92, 94, 95, 96, 97,

98, 99, 101, 102, 208, 245, 263, 280, 281, 294, 295, 296

Sault Ste. Marie plant, 72, 83, 85, 89, 97, 102, 104, 105, 112, 113,

117, 118, 120, 127

Scott system, 132

Series distribution, 167

machines, 41

Sewall’s Falls plant, 26, 27, 28, 155

Shawinigan Falls plant, 1, 70, 71, 107, 116, 117, 163, 164, 166, 209,

212, 213, 235, 236, 242, 245, 267, 272, 273, 280, 282, 294, 295, 296

Sheaths for cables, 194

Shunted air-gaps, 185

Skin effect, 206, 232

Snoqualmie Falls plant, 3, 4

map of transmission lines, 4

Snow, 293

Soldered joints, 206

Spacing of poles, 249

of wire, 234

Spans, long, 190, 250

strains for different lengths, 324

Sparking distances, 182

voltages, 182

Speed, peripheral, of impulse wheels, 108

peripheral of turbines, 85, 103

regulation, 38, 42

d. c. motors, 38

Spier Falls plant, 1, 2, 3, 54, 58, 61, 62, 68, 91, 94, 98, 124, 126,

127, 130, 141, 142, 146, 161, 174, 236, 237, 243, 244, 245, 250, 253,

266, 280, 285, 287, 289, 291, 294, 295, 296, 312

Star connection, 131

Static discharges, 170

Steam and water-power station combined, 84

electric plant, cost of labor, 12

cost of operation, 12

floor area per k. w., 102

_vs._ water-power, 5

Steel towers, 306

Storage capacity, 15

Strains on insulation as affected by resistance in series with

arrester, 185

Stray currents, protection against, 195

Submarine cables, 187, 192, 194

Sub-station, arrangement of apparatus, 128

Sub-stations, 157, 237

Surges, 136

Switchboard, 156

wiring, 146, 148, 149

Switches, 135, 244

arcing of, 135

electrically operated, 140

long break, 135

oil, 136

open-air, 136

pneumatically operated, 140

power operated, 138

relay, 145

Switch-houses, 141, 142, 238, 244

Switching, 146

high-tension, 147

Synchronous converters, 115

cost, 117

motors, 165, 241

Tail-race, 96

Telephone, 161

Telluride plant, 47, 160, 169, 181

Temperature of cables, 198

rise in conduits, 198

Tensile strength of conductor metals, 201

Time-limit circuit-breaker, 152

Time relays, 152, 153

Towers, 250, 306

angle, 320

cost, 310

dimensions, 314

erection of, 316-319

heavy, 320

reliability of operation, 311

spans, 313

steel, cost, 307, 308

steel pins, 312

strain on, 324

Transformers, 122

air-blast _vs._ water-cooled, 129

artificially cooled, 129

at sub-stations, 125

blower capacity necessary to cool, 130

constant-current, 167

cooling, quantity of water necessary, 129

cost, 21, 116, 124, 134

cost of operation, 129

cost of, relative, 20

delta and star connections, 131

efficiency, 133

frequency, effect of, 116

insulation, 45

in transmission systems, 134

limiting voltage for, 32

location of, 97

polyphase, 124

regulation, 125

reserve, 149

secondary, in series, 131

single-phase, 124

two- to three-phase, 132

used to compensate drop, 133

used to regulate voltage, 162

voltages, 45

when to use, 122

Transmission, constant-current, 38, 216

constant-voltage, 40, 217

continuous-current, 31, 32

control equipment, 35

cost of, 19, 40, 222

(d. c.) cost of, 40

efficiency, 35, 41

first long line, 37

frequency, 113

generator end, 103

lightning protection, 34

limiting voltage, 44

lines, arcing, 46

calculation of, 221-232

charging current, 197

construction, 222

cost, 310

cross-arms, 49, 256

crossings, 187, 190

data from various plants, 245

effect of length on cost, 20

effect of length on cost of power, 24

efficiency, 22, 24

end strain at entries, 325

entrance to buildings, 179, 261

inductance, 206

induction, 168

insulation, 34

insulators (see Insulators), 287

insulator-pins (see Pins), 270

interest, maintenance and depreciation, 22

leakage, 47, 207, 214

length of, capacity of, population supplied, 8

lightning arresters (see Lightning Arresters), 179

lightning protection, 118

long spans, 190

loss, 22, 39

losses, 215

maximum investment in, 220

method of fastening conductors to insulators, 323

operation, 311

pole spacing, 249

regulation with synchronous motors, 241

relative weights of three-phase, two-phase, and single-phase, 228

right-of-way, 246

sag in, 309

spacing of wire, 234

steel towers (see Towers), 306

switch-houses, 238

switches, fuses, and circuit-breakers, 135

take up, arrangement for, 325

total cost of, 22

total cost of operation, 23

transposition of wires, 206, 314

voltage, 21, 215

in cables, 190

regulation, 130

wind pressure, 210

long line, 221

minimum-sized wire, 202

physical limits of, 44

a. c. pole line construction, 34

d. c. pole line construction, 33

pole lines, 246

problems, 19

regulation, 155, 239

selection of circuits, 233

single _vs._ parallel circuits, 241

spacing of conductors, 46

submarine, 187

three-phase, 113

three-phase and two-phase, 228

two-phase, 113

underground, 187

without step-up transformers, 120

Transposition of wires, 206

Turbines, high-speed, 107

horizontal, 79, 83, 89, 97

impulse, 82, 90, 99

speed of, 108

low-head good speed, 105

peripheral, speed of, 85, 103

pressure, 79

several on same shaft, 85, 105

vertical, 79, 84, 85, 86, 97

Underground cable connected to overhead line, 197

cables, 187

Victor (Colo.) plant, 26, 27, 28, 208

Virginia City plant, 118

Voltage drop compensation, 133

fluctuations, 218

high, alternators, 120

measurements, 290

in cables, 190, 196

limiting, 44

for a. c. machines, 32

for d. c. machines, 31

of transmission lines, 21, 215

regulation, 130, 155

sparking, 182

test for insulators, 289

Volts per mile, 26

Wages paid attendants, 12

Walls, 95

Washington & Baltimore Ry., 121

Washouts, 81

Water-cooled transformers, 129

Water-power, development of, 51

high head, 74-77

low head, 51-74

per cent. of energy available, 16

pure hydraulic development, 51

stations (see Hydro-electric Stations)

storage capacity, 15, 61

utilization of, 10

_vs._ steam, 5

Water, storage of, 15, 61

Weight of the conductor metals, 202

Welland Canal plant, 1, 26, 27, 28, 208, 245, 248

Westbrook (Me.) plant, 120

White River to Dales plant, 26, 27, 28, 71, 134

Wind, 324

pressure on lines, 210

Winooski River plant, 64

Wire room, 139

Wood, compressive strength of, 302

Woods for poles, 252

Yadkin River (N. C.) plant, 26, 27, 28, 118, 208

Transcriber’s Notes

This transcription uses the text of the original work.

Inconsistencies (e.g., per cent. and per cent; Chambly and Chamblay;

Garvin’s and Garvins Falls; 1-0 and 1/0 B. & S. gauge; hyphenation;

capitalisation; use of italics, etc.) have been retained, except as

mentioned below. Some of the calculations in the book give different

results to the ones provided; these have not been corrected.

In this book, “cm.” stands for circular mils, not for centimeters.

Page 76, Fig. 16: the text in the centre of the illustration

probably reads 1200 feet Pipe Line.

Page 111: between figures 44 and 46 the original book has figure

51_a_; the numbering has not been changed.

Changes made:

Obvious minor typographical and punctuation errors have been

corrected silently.

Fractions have been standardised to x/y; all occurrences of _vs._

have been italicised.

In-line multi-line formulas have been changed to single-line

formulas.

Table of Contents: the Index has been added.

page 15: table header changed to small caps as others

page 31: Electrical transmission changed to Electrical transmissions

page 56: Canon changed to Cañon

page 77: Tlaluepantla changed to Tlalnepantla

page 312: Teluride changed to Telluride

page 332: Canon changed to Cañon.

Electric Transmission of Water Power · 第 23 / 23 章