CHAPTER XIV.

ELECTRICAL TRANSMISSION UNDER LAND AND WATER.

Energy transmitted over long distances must sometimes pass through

conductors that are underground or beneath water. In some other cases it

is a question of relative advantages merely, whether portions of a

transmission line go under water or overhead. Where the transmitted

energy must enter a sub-station in the heart of a large city, it not

infrequently must go by way of underground conductors without regard to

the voltage employed. In some cities the transmission lines may be

carried overhead, provided that their voltage is within some moderate

figure, but not otherwise. Here it becomes a question whether

transmission lines at high voltage shall be carried underground, or

whether transforming stations shall be established outside of the

restricted area and then low-pressure lines brought into the business

section overhead or underground, as desired. Where a transmission line

must cross a steam railway track it may be required to be underground,

whether the voltage is reduced or not. The distance across a body of

water in the path of a transmission line may be so great that a span is

impossible and a cable under the water therefore necessary. Such a cable

may work at the regular line voltage, or a transformer station may be

established on one side or on each side of the body of water. Even where

it is possible to span a body of water with a transmission line, the

cost of the span and of its supports may be so great that a submarine

cable is more desirable. A moderate increase in the length of a

transmission line in order to avoid the use of a submarine cable is

almost always advisable, but where rivers are in the path of the line it

is generally impossible to avoid crossing them either overhead or

underneath. Thus, St. Paul could only be reached with the 25,000-volt

line from the falls on Apple River by crossing the St. Croix River,

one-half mile wide, on the way. In order to carry out the 40,000-volt

transmission between Colgate and Oakland, the Carquinez Straits, which

intervened with nearly a mile of clear water, were crossed. Sometimes,

as in the former of the two cases just named, an existing bridge may be

utilized to support a transmission line, but more frequently the choice

lies between an overhead span from bank to bank of a river and a

submarine cable between the same points.

The prime advantage of an overhead line at high voltage is its

comparatively small first cost, which is only a fraction of that of an

underground or submarine cable in the great majority of instances. At

very high voltages, like 40,000 to 50,000 or more, the overhead line

must also be given first place on the score of reliability, since the

lasting qualities of underground and submarine cables at such pressures

is as yet an unknown quantity. On the other hand, at voltages in which

cable insulation has been shown by experience to be thoroughly

effective, underground or submarine cables may be more reliable than

overhead lines because of the greater freedom from mechanical

disturbances which these cables enjoy.

In the business portion of many cities a transmission line must go

underground, whether its voltage is high or low. Under these conditions,

it may be desired either to transmit energy to a sub-station for

distribution within the area where conductors must be underground, or to

transmit energy from a generating station there located to outside

points. If the transmitted energy is reduced in pressure before reaching

such a sub-station, a transforming station must be provided, and this

will allow the underground cables to operate at a moderate voltage. For

such a case the advantages as to insulation at the lower voltage should

be compared with the additional weight of conductors in the cable and

the cost of the transforming apparatus and station. If the voltage at

which current is delivered from the transforming station does not

correspond with the required voltage of distribution at the sub-station,

the necessary equipment of step-down transformers is doubled in capacity

by lowering the voltage of the transmitted energy where it passes from

the overhead line to the underground cables. Conditions of just this

sort exist at Buffalo in connection with the delivery of energy from the

power-stations at Niagara Falls. This transmission was first carried out

at 11,000 volts, and a terminal station was located at the Buffalo city

limits where the overhead lines joined underground cables that continued

the transmission at the same voltage to several sub-stations in

different parts of the city. Later the voltage of the overhead

transmission line was raised to 22,000, and it not being thought

advisable to subject the insulation of the underground cables to this

higher pressure, transformers were installed at the terminal station to

lower the line voltage to 11,000 for the underground cables. As the

sub-stations in this case also have transformers, there are two

kilowatts of capacity in step-down transformers for each kilowatt of

delivery capacity at the sub-stations.

[Illustration: FIG. 74.--Cable Terminal House for the 25,000-volt

Chambly Line at Montreal.]

The saving effected in capacity of transformers and in the weight of

cables by continuing the full transmission voltage right up to the

sub-stations whence distribution takes place furnishes a strong motive

to work underground cables at the pressure of the overhead transmission

line of which they form a continuation. Thus, at Hartford, the

10,000-volt overhead lines that bring energy from water-power stations

to the outskirts of the city connect directly in terminal houses there

with underground cables that complete the transmission to the

sub-station at the full line voltage. In Springfield, Mass., the

overhead transmission lines from water-power stations connect directly

with underground cables at a distance of nearly two miles from the

sub-station, and these cables are thus subject to the full line pressure

of 6,000 volts. The overhead line that brings energy at 25,000 volts

from Apple River falls to St. Paul terminates about three miles from the

sub-station there, and the transmission is completed by underground

cables that carry current at the 25,000-volt pressure.

In these and similar cases the relative advantages of underground cables

at the full voltage of transmission and of overhead lines at a much

lower pressure, in the central portions of cities, must be compared. The

overhead lines at moderate voltage will no doubt cost less in almost

every case than underground cables of equal length and at the full

transmission voltage.

As an offset to the lower cost of overhead city lines at moderate

voltage, where they are permitted by local regulations, comes the

increase in weight of conductors due to the low pressure on the overhead

lines, and also the cost of additional transformer capacity, unless the

lines that complete the transmission operate at the voltage of

distribution. The 10,000-volt lines that transmit energy from Great

Falls to Portland, Me., terminate in two transformer houses that are

distant about 0.5 mile and 2.5 miles, respectively, from the sub-station

there. In these transformer houses the voltage is reduced to 2,500, and

the transmission is then continued at this pressure to the sub-station

whence distribution takes place without further transformation.

Where a river or other body of water must be crossed by a transmission

line, either of three plans may be followed. The overhead line may be

continued as such across the water, either by a single span or by two or

more spans supported by one or more piers built for that purpose in the

water. The overhead line may connect directly with a submarine cable,

this cable being thus exposed to the full voltage of the transmission.

As a third expedient, a submarine cable may be laid and connected with

step-down transformers on one bank and with step-up transformers on the

other bank of the river or other body of water to be crossed. The

overhead lines connecting with these transformers can obviously be

operated at any desired voltage, and this is also true of the cable.

Even though the distance across a body of water is not so great that a

transmission line can not be carried over it in a single span, the cost

of such a span may be large. A case in point is that of the Colgate and

Oakland line, where it crosses the Carquinez Straits by a span of 4,427

feet. These straits are about 3,200 feet wide where the transmission

line crosses, and overhead lines were required to be not less than 200

feet above high water so as not to impede navigation. In order to gain

in ground elevation and thus reduce the necessary height of towers, two

points 4,427 feet apart on opposite sides of the straits were selected

for their location. Under these circumstances two steel towers, one

sixty-five feet and the other 225 feet high, were required to support

the four steel cables that act as conductors across the straits. To take

the strain of these four cables, each with a clear span nearly three

times as great as that of the Brooklyn Bridge, eight anchors with housed

strain insulators were constructed, four on the land side of each tower.

On each of these anchors the strain is said to be 24,000 pounds. At each

end of the cables making this span is a switch-house where either of the

two three-phase transmission lines may be connected to any three of the

four steel cables, thus leaving one cable free for repairs. It is not

possible to state here the relative cost of these steel towers and

cables in comparison with that of submarine cables for the same work,

but at first glance the question appears to be an open one. The voltage

of 40,000, at which this transmission is carried out, is probably higher

than that on any submarine cable in use, but it is possible that a

suitable cable can be operated at this voltage. Whatever the limitations

of voltage as applied to submarine cables, it would, of course, have

been practicable to use step-up and step-down transformers at the

switch-houses and thus operate a submarine cable at any voltage desired.

In another case, on a transmission between Portsmouth and Dover, N. H.,

it was necessary to cross an arm of the sea on a line 4,811 feet long

with a three-phase circuit operating at 13,500 volts. It was decided to

avoid the use of either a great span or of raising and lowering

transformers at this crossing, and to complete the line through a

submarine cable operating at the full voltage of transmission. To this

end a brick terminal house six by eight feet inside, and with an

elevation of thirteen feet from the concrete floor to the tile roof, was

erected on each bank of the bay at the point where the submarine cable

came out of the water. The lead-covered cable pierced the foundation of

each of these terminal houses at a point four feet below the floor level

and rose thence on one wall to an elevation eleven feet above the floor

to a point where connection was made with the ends of the overhead

lines. From this connection on each of the three conductors a tap was

carried to a switch and series of lightning arresters. A single

lead-covered cable containing three conductors makes connection between

these two terminal houses. At each end of this cable the lead sheath

joins a terminal bell one foot long and 2.5 inches in outside diameter,

increasing to four inches at the end where the three conductors pass

out. This terminal bell is filled nearly to the flaring upper end with

an insulating compound.

In the instance just named it is possible that the cost of the submarine

cable was less than would have been the outlay for shore supports and a

span nearly a mile long across this body of water.

Underground and submarine cables have been operated at voltages suitable

for transmission during periods sufficiently long to demonstrate their

general reliability. The Ferranti underground cables between Deptford

and London have regularly carried current at 11,000 volts since a date

prior to 1890. During about five years cables with an aggregate length

of sixteen miles have transmitted power from St. Anthony’s Falls to

Minneapolis. At Buffalo, some thirty miles of rubber-insulated cables

have been in use for underground work at 11,000 volts since 1897, and

eighteen miles of paper-insulated cable since the first part of 1901.

These examples are enough to show that transmission through underground

cables at 11,000 to 12,000 volts is entirely practicable. At Reading,

Pa., an underground cable one mile long has carried three-phase current

at 16,000 volts for the Oley Valley Railway since some time in 1902. The

cables in the transmission from Apple River to St. Paul, which carry

three-phase current at 25,000 volts, have a total length of three miles,

and have been in use since 1900. This voltage of 25,000 is probably the

highest in regular use on any underground or submarine cable conveying

energy for light or power. From the experience thus far gained there is

much reason to think that the voltages applied to underground cables may

be very materially increased before a prohibitive cost of insulation is

reached.

On submarine cables the voltage of 13,000 in the Portsmouth and Dover

transmission, above mentioned, is perhaps as great as any in use. It

does not appear, however, that any material difference exists, as to the

strain on its insulation at a given voltage, between a cable when laid

in an underground conduit and when laid under water. In either case the

entire stress of the voltage employed operates on the insulation between

the several conductors in the cable and between each conductor and the

metallic sheath. Underground conduits have little or no value as

insulators of high voltages, because it is practically impossible to

keep them water-tight and prevent absorption or condensation of moisture

therein. For these reasons a cable that gives good results at 25,000

volts in an underground conduit should be available for use at an equal

voltage under water. The standard structure of high-voltage cables for

either underground or submarine work includes a continuous metallic

sheath outside of each conductor or of each group of conductors that

goes to make up a circuit. As most transmissions are now carried out

with three-phase current, the three conductors corresponding to a

three-phase circuit are usually contained in a single cable and covered

by a single sheath. The cables used in transmission systems at

Portsmouth, Buffalo, and St. Paul are of this type. If single-phase or

two-phase current is transmitted, each cable should contain the two

conductors that go to make up a circuit. In work with alternating

currents the use of only one conductor per cable should be avoided

because of the loss of energy that results from the currents induced in

the metallic sheath of such a cable.

[Illustration: FIG. 75.--Cable Terminal House at Piscataqua River

Crossing.]

Where the two, three, or more conductors that form a complete circuit

for alternating current are included in a single metallic sheath, the

inductive effects of currents in the several conductors tend to

neutralize each other and the waste of energy in the sheath is in large

part avoided. To neutralize more completely the tendency to local

currents in their metal sheath, the several insulated conductors of an

alternating circuit are sometimes twisted together, after being

separately insulated, before the sheath is put on. Distribution of power

at Niagara Falls was at first carried out through single-conductor,

lead-covered cables with two-phase current at 2,200 volts. One objection

to this plan was the loss of energy by induced currents in the lead

coverings of the cables. It was later decided to adopt three-phase

distribution at 10,000 volts for points distant more than two miles from

the power-station. Each three-phase circuit for this purpose was made up

of three conductors separately insulated and then covered with a single

lead sheath, so as to avoid losses through induced currents in the

latter. Underground and submarine cables for operation at high voltages

are generally covered with a continuous lead sheath and sometimes with a

spiral layer of galvanized iron wire. For high-voltage work underground

the lead covering is generally preferred without iron wire, but in

submarine work coverings of both sorts are employed. The lead sheath of

a cable being continuous completely protects the insulation from contact

with gases or liquids. As ducts of either tile, wood, or iron form a

good mechanical protection for a cable, the rather small strength of a

lead sheath is not a serious objection in conduit work. Submarine

cables, on the other hand, depend on their own outer coverings for

mechanical protection, and may be exposed to forces that would rapidly

cut through a lead sheath. Cables for operation under water should

usually be covered, therefore, with a layer of galvanized iron wires

outside of the lead sheath. These wires are laid closely about the cable

in spiral form and are usually between 0.12 and 0.25 inch in diameter

each, depending on the size of the cable and its location.

Underground conduits cannot be relied on to exclude moisture and acids

of the soil from the cables which they contain, and either of these

agents may lead to destructive results. If cables insulated with rubber,

but without a protecting covering outside of it, are laid in underground

conduits, the rubber is apt to be rapidly destroyed by fluids and gases

that find their way into the conduit. If a plain lead-covered cable is

employed the acids of the soil attack it, and if stray electric currents

from an electric railway find the lead a convenient conductor it is

rapidly eaten away where they flow out of it. To avoid both of these

results the underground cable should have a lead sheath, and this sheath

may be protected by an outside layer of hemp or jute treated with

asphaltum.

Rubber, paper, and cotton are extensively used as insulation for

underground and submarine cables, but the three are not usually employed

together. As a rule, the insulation is applied separately to each

conductor, and then an additional layer of insulation may be located

about the group of conductors that go to make up the cable. Where rubber

insulation is employed, a lead sheath may or may not be added, but where

insulation depends on cotton or paper the outer covering of lead is

absolutely necessary to keep out moisture. The radial thickness of

insulation on each conductor and of that about the group of conductors

in a cable should vary according to the voltage of operation.

Cables employed between the generating and sub-stations of the Manhattan

Elevated Railway, to distribute three-phase current at 11,000 volts, are

of the three-conductor type, rubber insulated, lead covered, and laid in

tile conduits. Each cable contains three No. 000 stranded conductors,

and each conductor has its own insulation of rubber. Jute is laid on to

give the group of conductors an outer circular form, and outside of the

group a layer of insulation and then a lead sheath is placed. Outside

diameter of this cable is nearly three inches, and the weight nine

pounds per linear foot.

The 11,000-volt, three-phase current from Niagara Falls is distributed

from the terminal house to seven sub-stations in Buffalo through about

30 miles of rubber-insulated and 18 miles of paper-insulated,

three-conductor, lead-covered cables, all in tile conduits. In each

cable the three No. 000 stranded conductors are separately insulated and

then twisted into a rope with jute yarn laid in to give an even round

surface for the lead sheath to rest on. A part of the rubber-insulated

cables have each conductor covered with 9/32-inch of 30 per cent pure

rubber compound, and the remaining rubber cables have 8/32-inch

covering on each conductor of 40 per cent pure rubber compound. The

paper-insulated cable has 13/64-inch of paper around each conductor, and

also another 13/64-inch of paper covering about the group of three

conductors and next to the lead sheath. In outside diameter the

rubber-insulated cable is 2-3/8 inches, and of the paper-insulated cable

2-5/8 inches, the radial thickness of the lead sheath being 1/8-inch in

each case. It is reported that the cables insulated with 9/32-inch of

the mixture, said to be 30 per cent pure rubber, have proved to be more

reliable than the cables insulated with 8/32-inch of a mixture said to

be 40 per cent pure rubber. Vol. xviii., A. I. E. E., 136, 836.

The six miles of underground cables that carry three-phase, 25,000-volt

current in St. Paul are of the three-conductor type, lead covered, and

laid in a tile conduit. One of the two three-mile cables is insulated

with rubber and the other with paper. In the former cable each conductor

is separately insulated with a compound containing about 35 per cent of

pure rubber and having a radial thickness of 7/32-inch. The three

conductors after being insulated are laid up with jute to give a round

surface, tape being used to hold them together, and then a rubber cover

5/32-inch thick is placed about the group, after which comes the lead

sheath over all. In the three miles of paper-insulated cable each

conductor is separately covered with paper to a thickness of 9/32-inch,

then the three conductors are laid together with jute and taped, and

next a layer of paper 4/32-inch thick is put on over the group. Outside

of all comes the lead sheath, which has an outer coating of tin. The

paper insulation in these cables was saturated with a secret insulating

compound. The lead sheath on both the rubber and paper insulated cables

is 1/8-inch thick and the sheath of the former contains 3 per cent of

tin. Each of the three conductors in each cable consists of 7 copper

strands and has an area of 66,000 circular mils. Outside of the lead

sheath each of these cables has a diameter of about 2-1/4 inches. By the

manufacturer’s contract these cables were tested up to 40,000 volts

before shipment, and might be tested up to 30,000 volts in their

conduits during any time within five years from their purchase. In first

cost the cable with rubber insulation was said to be about 50 per cent

more expensive than the cable in which paper was used. Vol. xvii., A. I.

E. E., 650.

Underground cables in which the separate conductors are covered with

cotton braid treated with an insulating compound, and then the group of

conductors going to make up the cable enclosed in a lead sheath, are

extensively used in Austria and Germany. For cables that operate at

10,000 to 12,000 volts the radial thickness of cotton insulation on each

conductor is said to be within 3/16-inch, and these cables are tested up

to 25,000 volts by placing all of the cable except its ends in water,

and then connecting one end of the 25,000-volt circuit to the water and

the other end to the conductors of the cable.

A test on the paper-insulated cable at St. Paul showed its charging

current to be 1.1 amperes at 25,000 volts for each mile of its length.

For the cable with rubber insulation the charging current per mile of

length was found to be about twice as great as the like current for the

paper-insulated cable. Each of the two overhead transmission lines

connected with these cables consisted of three solid copper wires with

an area of 66,000 circular mils each, and all three so mounted on the

poles as to form the corners of an equilateral triangle twenty-four

inches apart. The charging current of one of these three-wire, overhead

circuits was found to be about 0.103 ampere per mile, at 25,000 volts,

or a little less than one-tenth of the like current for the paper cable.

These tests were made with three-phase current of sixty cycles per

second.

Where overhead transmission lines join underground or submarine cables,

either with or without the intervention of transformers, lightning

arresters should be provided to intercept discharges of this sort that

come over the overhead wires. Lightning arresters were provided in the

terminal house at Buffalo, where the 22,000-volt overhead lines feed the

11,000-volt cables through transformers, also at the terminal house in

St. Paul, where the 25,000-volt overhead lines are electrically

connected to the underground cables. If an underground or submarine

cable connects two portions of an overhead line, as in the Portsmouth

and Dover transmission above mentioned, lightning arresters should be

provided at each end of the cable, as was done in that case. One

advantage of a high rather than a low voltage on underground cables,

where power is to be transmitted at any given rate, lies in the fact

that the amperes flowing at a fault in the cable determine the

destructive effect there, rather than the voltage of the transmission.

It is reported that a fault or short-circuit in one of the 11,000-volt

cables at Buffalo usually melts off but little lead at the sheath and

does not have enough explosive force to injure the cable or its duct.

Ozone seems to destroy the insulating properties of rubber very rapidly,

and as it is well known that the silent electric discharge from

conductors at high voltages develops ozone, care should be taken to

protect rubber insulation from its action. This is especially true at

the ends of cables where connections are made with switches or other

apparatus, and the rubber insulation is exposed. To protect the rubber

at such points it is the practice to solder a brass cable head or

terminal bell to the lead sheath near its end, this head having a

diameter perhaps twice as great as that of the sheath, and then to fill

the space about the cable conductors in this head with an insulating

compound. Heads of this sort were used on the 11,000-volt cables at

Buffalo as well as on the 13,500-volt cable in the Portsmouth and Dover

transmission.

As insulating materials, whether rubber, cotton, or paper, may be

impaired or destroyed by heat, it is necessary that the temperature of

underground cables under full load be kept within safe limits. Rubber

insulation can probably be raised to 125° or 150° Fahrenheit without

injury, and paper and cotton may go a little higher. For a given size

and make of leaded cable the rise of temperature in its conductors above

that of the surrounding air, for a given loss in watts per foot of the

cable, may be determined by computation or experiment. The next step is

to find out how much the temperature of the air in the conduits where

the cable is to be used will rise above the temperature of the earth in

which the conduits are laid, with the given watt loss per foot of cable.

On this point there are but little experimental data. Obviously, the

material of which ducts are made, the number of ducts grouped together

with cables operating at the same time, and the extent to which ducts

are ventilated must have an important bearing on this question. At

Niagara Falls some tests were made to show the rise of air temperature

in a section of thirty-six-duct conduit lying between two manholes about

140 feet apart. For the purpose of this test twenty-four of the

thirty-six ducts in the conduit had one No. 6 drawing-in wire passed

through each of them. These twenty-four wires were connected into three

groups of eight wires each, so that one group was all in ducts next to

the surrounding earth, another group was one-half in ducts next to the

earth and the other half in ducts separated from the earth by at least

one duct, while the third group of wires was entirely in ducts separated

from the earth by at least one duct. It was found that when enough

current was sent through these wires to represent a loss of 5.5 watts

per foot of ducts in which they were located, the rise of temperature in

the air of the ducts next to the earth was about 108° Fahrenheit above

that of the earth. For the ducts separated from the earth by at least

one other duct the rise in temperature of contained air was 144°

Fahrenheit above the earth. If the earth about the ducts reached 70° in

hot weather, the temperature of air in the inner ducts, with a loss of

5.5 watts per duct foot, would thus be 214°. This temperature is too

high for either rubber, cotton, or paper insulation, to say nothing of

the amount by which the temperature of the conductors and insulation of

a cable in operation must exceed that of the surrounding air in its

duct. The cables actually installed in the ducts just considered were

designed for a loss of 2.34 watts per foot. As the No. 6 wire used in

the test did not nearly fill each duct as a cable would do, it would be

very interesting to know how much ventilation took place while the test

was going on. Unfortunately, this point was not reported. Vol. xviii.,

A. I. E. E., 508.

Electric Transmission of Water Power · 第 14 / 23 章