LIGHTNING ROD CONFERENCE.

REPORT

OF THE

DELEGATES FROM THE FOLLOWING SOCIETIES, VIZ.:

METEOROLOGICAL SOCIETY.

C. BROOKE, F.R.S., _Past President_ [THE LATE].

E. E. DYMOND, F.M.S., _Vice-President_.

G. J. SYMONS, F.R.S., _President_.

ROYAL INSTITUTE OF BRITISH ARCHITECTS.

PROF. LEWIS, F.S.A., _Vice-President_.

J. WHICHCORD, F.S.A., _Past President_.

SOCIETY OF TELEGRAPH ENGINEERS AND OF ELECTRICIANS.

LATIMER CLARK, M. INST. C.E., _Past President_.

W. H. PREECE, F.R.S., M. INST. C.E., _Past President_.

PHYSICAL SOCIETY.

PROF. W. G. ADAMS, F.R.S., _Past President_.

PROF. G. CAREY FOSTER, F.R.S., _Past President_.

CO-OPTED MEMBERS.

PROF. W. E. AYRTON, F.R.S.

PROF. D. E. HUGHES, F.R.S.

_With a Code of Rules for the Erection of Lightning Conductors; and

various Appendices._

EDITED BY THE SECRETARY, G. J. SYMONS, F.R.S.

LONDON: E. & F. N. SPON, 16, CHARING CROSS.

NEW YORK: 446, BROOME STREET.

1882.

KENNY & CO., PRINTERS, 25, CAMDEN ROAD, N.W.

------------------------------------------------------------------------

CONTENTS.

PAGE

PREFACE v

REPORT 1

Section 1.—The purpose which a lightning conductor is intended

to serve 1

Section 2.—A statement of those features in the Construction

and Erection of Lightning Conductors, respecting which there

has been, or is, a difference of opinion, and the final

decision of the Conference thereupon 3

Points 3

Material for Conductor 5

Size of Rod 6

Shape of Rod (Rod, Tube, Tape, Rope, Plait) 7

Joints 10

Protection of Rod 10

Painting 11

Attachment to Buildings 11

Earth Plates 11

Space Protected 12

Height of Upper Terminal 14

Testing Conductors 14

Internal Masses of Metal 15

External Masses of Metal 16

Section 3.—Code of Rules for the Erection of Lightning

Conductors 16

APPENDICES—

A.—Circular and Questions issued to Manufacturers, and their

Replies (1)

B.—Analysis of, and remarks upon, the views of the

Manufacturers (17)

C.—Reply from Manufacturers received after the completion of

Appendix B. (23)

D.—Report of the Representatives of the Royal Institute of

British Architects (27)

E.—Particulars of Accidents by Lightning, collected 1857–59, by

Mr. Symons, and Report upon the same (43)

F.—Abstracts of Printed Documents (51)

G.—Catalogue of Works upon Lightning Conductors (143)

H.—Application to, and Replies from, the Local Hon. Secretaries

of the Society of Telegraph Engineers and other distinguished

Foreign Authorities (175)

I.—General Correspondence (183)

J.—Data respecting the Sectional Area of Metal requisite for

Lightning Conductors (223)

K.—Notes respecting Lightning Conductors, collected in Paris in

May, 1881, by Messrs. Preece and Symons (225)

L.—On the Lightning Conductors at the Paris International

Electrical Exhibition, by Messrs. Dymond and Symons (229)

M.—Miscellaneous (233)

Index to Appendices (245)

ILLUSTRATIONS.

PAGE

Sketch illustrative of terms employed face x

Sketch illustrative of area of protection 13

Plans and Elevation of Nottingham Castle (25)

(26)

Tower of Church of Week St. Mary, Cornwall (32)

Plan and Elevation of Twyford Moors, Winchester (34)

Plan and Elevation of St. James’ Church, West-End, Hants. (35)

Plan and Elevation of houses at Lewisham, Wandsworth, and Forest (38)

Hill

View of Tower of Holborn Union Infirmary, Holloway (40)

Plan and Elevation of Laundry at Gravesend (41)

Regnier’s System of Lightning Conductors (54)

Joints and Earth Terminals recommended in France in 1807 (55)

Powder Magazine, with oblique as well as vertical rods (57)

Mode of attaching Conductor to Upper Terminal (59)

View and Plan of Bruntcliffe Gunpowder Store (75)

View of Board House, at Purfleet (78)

View and Plan of Heckingham Poorhouse (87)

(88)

Diagrams illustrative of space protected (135)

(136)

Plan and Elevation of Church of Ste. Croix, at Ixelles (141)

Sketch of arrangements for Public Buildings in Denmark (177)

Plan and Elevations of Systems for Powder Magazines in Denmark (178)

Attachment and Earth Terminal used in Italy (180)

Sections of Rods used by the Trinity Board (183)

Eddystone and Spurn Point Lighthouses (184)

South Foreland High Light (185)

Eddystone Lighthouse (191)

Plan and Elevation of house at Trolley Bottom, St. Albans (197)

Plan and Elevation of washhouse of Middlesboro’ Fever Hospital (203)

Plan and Elevation of Indian Pagoda (207)

Plan and Elevation of Upwood Gorse, Caterham (211)

Sections of Rod at Upwood Gorse, Caterham (214)

(215)

Sections of Munson’s Rods (216)

View and Section of Cutting’s Conductor Coupling (217)

Plan and Elevation of Christ Church, Carmarthen (218)

Plan and View of house, and of Bootham Bar, York (220)

(221)

PREFACE.

Although France and other nations have taken active steps to give

official sanction to the best known means of protection from the ill

effects of atmospheric electricity, nothing in this way has ever been

done in England for the public generally.

The enquiries by householders and public bodies for advice and

instruction were so numerous, the absence of authorized or well-matured

directions was so marked, the practice in vogue so varied and anomalous,

that it occurred to the Meteorological Society to take some action in

the matter.

Accordingly, at a Meeting of the Council of the Meteorological Society,

held on 15th of May, 1878, it was resolved—

‘That the House Committee be instructed to address the following

Societies:—

THE ROYAL INSTITUTE OF BRITISH ARCHITECTS,

THE PHYSICAL SOCIETY,

THE SOCIETY OF TELEGRAPH ENGINEERS,

asking them to name delegates to co-operate in considering the

desirability or otherwise of issuing a code of rules for the

erection of lightning conductors, and to proceed in preparing a code

if it is thought desirable.’

In accordance with this resolution the following letter was addressed to

the Secretaries of the above Societies:—

THE METEOROLOGICAL SOCIETY,

30, GREAT GEORGE STREET, WESTMINSTER,

_June 14, 1878_.

SIR,

The Council of the Meteorological Society have had under their

consideration for some time the possibility of formulating the

existing knowledge on the subject of the protection of property from

damage by electricity, and the advisability of preparing and issuing

a general code of rules for the erection of lightning conductors.

They are of opinion that this would best be done by a joint

committee of representative members of those Societies before which

such subjects most naturally come; and they have, therefore, decided

upon inviting the co-operation of your Society by the nomination of

one or more delegates to join a Committee by whom the whole question

should be considered, and to whom also any written communications

would be submitted.

The Council trust that your Society may be represented by delegates;

but if that course be impossible, they invite any written

suggestions which you may have to offer.

A meeting of the delegates will be called for an early date after

the receipt from the Societies consulted, of the names of the

gentlemen nominated by each.

We are, Sir,

Your obedient servants,

G. J. SYMONS, }

JOHN W. TRIPE,} _Hon. Secretaries_.

In reply to this circular all the societies invited nominated delegates,

and the Conference was constituted as follows:—

Meteorological Society. │C. BROOKE, F.R.S., _Past

│ President_.

│E. E. DYMOND, F.M.S.

│G. J. SYMONS, F.R.S., _Secretary_.

Royal Institute of British │PROF. LEWIS, F.S.A.

Architects. │

│J. WHICHCORD, F.S.A., _Vice

│ President_.

Society of Telegraph Engineers and │LATIMER CLARK, M. Inst. C.E., _Past

of Electricians. │ President_.

│W. H. PREECE, F.R.S., M. Inst.

│ C.E., _Vice President_.

Physical Society. │PROF. W. G. ADAMS, F.R.S.,

│ _President_.

│PROF. G. CAREY FOSTER, F.R.S.,

│ _Past President_.

The steps taken by the delegates will be best explained by a short

narrative chiefly formed of extracts from the minute book of the

Conference.

The first meeting was held at the rooms of the Meteorological Society,

on November 14th, 1878, when all the delegates were present. Mr. C.

Brooke, F.R.S., was appointed _President_ of the Conference, and Mr. G.

J. Symons, F.R.S., _Secretary_.

Professor W. E. Ayrton was elected a member.

A circular, which will be found in Appendix A, was drafted for issue to

manufacturers of lightning conductors. This was sent to sixty-five

firms, but only eight replied, and their answers are printed verbatim in

the same Appendix. An analysis of the replies forms Appendix B. Appendix

C is a reply received too late for insertion in Appendix A, and after

Mr. Preece had compiled Appendix B. Another reply from an American firm

will be found in Appendix I, p. (192), making ten in all.

At a subsequent meeting, the delegates from the Royal Institute of

British Architects were requested to ask the Council of that body to

issue a circular to their members inviting them to furnish information

respecting buildings injured by lightning. This circular, together with

abstracts of the replies, and a brief Introductory Summary, by Messrs.

Lewis and Whichcord, will be found in Appendix D.

Mr. Symons submitted to the meeting a mass of statistics respecting

accidents by lightning which he had collected in the years 1857–59; they

were referred to Professor Ayrton, and his note upon them constitutes

Appendix E.

At the meeting on August 5th, 1879, the Secretary announced the death of

the President of the Conference, Mr. C. Brooke, F.R.S., a vote of

condolence was passed unanimously, and ordered to be forwarded to Mrs.

Brooke. The Conference then proceeded to elect a new Chairman, and it

was unanimously resolved that Professor W. G. Adams, F.R.S., be

requested to accept the office.

The following circular was approved and ordered to be forwarded to a

large number of the most important newspapers and periodicals throughout

the United Kingdom.

LIGHTNING CONDUCTORS.

_To the Editor of_ ——

SIR,—

In the summer of 1878 delegates were nominated by the following

Societies, viz., the Royal Institute of British Architects, the

Society of Telegraph Engineers, the Physical Society, and the

Meteorological Society, for the following purpose:—

“To consider the possibility of formulating the existing knowledge

on the subject of the protection of property from damage by

electricity, and the advisability of preparing and issuing a

general code of rules for the erection of Lightning Conductors.”

The delegates have held several meetings, and have already

collected, firstly, from the manufacturers of Lightning Conductors,

and secondly, from the Members of the Royal Institute of British

Architects, a large amount of thoroughly practical information.

Several of their number are also engaged in forming abstracts of the

salient features of the literature of the subject.

The Members of the Conference are, however, most anxious that their

Report should be as trustworthy and as exhaustive as possible, and

they have, therefore, instructed me to ask you to assist them by

publishing this epitome of their proceedings, and allowing them to

invite correspondence upon the points mentioned below.

I am, Sir,

Your obedient servant,

G. J. SYMONS, F.R.S.,

_Secretary to the Conference_.

LIGHTNING ROD CONFERENCE,

30, GREAT GEORGE STREET, S.W.

CLASS OF FACTS MOST REQUIRED.

Full details of accidents by lightning, stating especially whether

the building struck had a conductor or not. If there was a

conductor, state its dimensions—construction—mode of attachment to

building—whether its top was pointed—distance of its upper terminal

from the place struck—nature and extent of the connection between

the conductor and the earth, and whether the earth was dry or

moist—whether the conductor was itself injured—and whether the

conductor or the point struck was the most salient object in the

vicinity. Information is also desired, either verbally or by

sketches, as to the position of metal spouting and lead roofing

relatively to the point struck, and to the conductor.

Details of the thickest piece of metal melted by a flash of

lightning are much needed.

Unimpeachable evidence of the failure of conductors is much desired,

as such failures would be extremely instructive.

The replies were by no means as numerous as was expected: the most

important will be found in Appendix I.

At the meeting, October 27th, 1879, it was resolved “That the members of

the Conference will undertake to prepare abstracts of the principal

English and Foreign books upon Lightning Conductors.” This work became

extremely heavy, and occupied much time, as will be seen from Appendix

F, which contains abstracts of sixty separate treatises, of which 26 are

from English, 17 from French, 6 from Belgian, 5 from American, and 5

from German authors, and one is from the Norwegian.

In order to guard against omitting important works, it was resolved

“That application be made to the Society of Telegraph Engineers for

advance sheets of the Ronalds Catalogue.” From it, supplemented by Mr.

Latimer Clark’s and other lists, the Secretary compiled Appendix G.,

which contains the full titles of no fewer than 704 separate works upon

lightning conductors, or on subjects intimately connected therewith.

At the same meeting it was resolved that efforts be made to obtain a set

of the official instructions issued in all foreign countries. The

circular issued, and an abstract of the information collected, including

replies from America, Belgium, Denmark, Germany, Holland, India, Italy,

and Norway, will be found in Appendix H. Full details respecting the

practice in France will be found in Appendices F, K, and L, and a notice

of Zenger’s Austrian system, on p. (104).

At the meeting, Nov. 20th, 1879, the Secretary was unanimously requested

to act as Editor of the Report.

At the meeting, Jan. 22nd, 1880, a letter was received from Mr. R. H.

Scott, F.R.S., _Secretary to the Meteorological Council_, enclosing a

report respecting the injury to the “Southern Queen,” it was resolved,

“That some of the delegates visit the ship.” The report and a note of

the results of the visit will be found in Appendix I page (205).

At the meeting, April 15th, 1880, Prof. D. E. Hughes was unanimously

elected member of the Conference.

At the meeting, July 6th, 1880, the Secretary handed in a sketch of a

house with various parts of the lightning conductor marked upon it, and

obtained from the delegates definite names for each portion, in order

that in framing the report there might be no uncertainty as to what was

meant by any special term, great confusion in this respect having

previously existed.

The terms adopted have been: _Conductor._—The whole arrangement for the

protection of a building. _Point._—The upper termination of the

conductor, whether blunt or sharp, single or bifurcated. _Upper

terminal._—That portion of the conductor which is between the top of the

edifice and the point. _Joint._—Any connection between any two parts of

the conductor. _Rod._—The main portion of the conductor, whether it

consist of rope, tape, tube or solid rod. _Circuit des Faîtes._—A rod

running round the eaves of a house, the battlements of a tower, &c.

_Earth plate._—The termination of the conductor in the ground, the

pattern being indicated by special terms.

The accompanying lithograph will, it is hoped, supply all additional

necessary particulars.

It is desirable to state that the illustrations in this Report have been

prepared by Mr. E. White Wallis, F.M.S., so as to bring out the various

features distinctly, and as nearly as possible in true proportion, but

without any attempt at artistic finish.

The meetings during the latter part of 1880, and the early part of 1881,

were devoted chiefly to the discussion of various questions as bases for

the report. Much time was also occupied in perfecting the various

appendices, and in compiling an exhaustive index to them.

In May, 1881, Messrs. Preece and Symons, being in Paris, made careful

enquiries as to the existing practice in France respecting lightning

conductors. Their notes form Appendix K.

At the meeting held on May 27th, 1881, the Secretary was instructed to

draw up a draft report, and this having been put in type was sent to all

the delegates; carefully considered, revised, and amended at various

subsequent meetings, and finally adopted.

[Illustration:

INDEX SKETCH OF LIGHTNING CONDUCTOR, ILLUSTRATING THE TERMS EMPLOYED

IN THE REPORT.

]

TERMS APPLIED TO THE VARIOUS

PARTS OF A CONDUCTOR.

_Ⴤ_ _Crutch_

⊞⬜⊞ _Strap_

⋂ _Staple_

⚲ _Wall Eye_

A _Point_

B _Upper Terminal_

c _Joint_

D _Rod_

E _Ridge Rod_

F _Circuit des faîtes_

G _Earth Plates_

G^1 _Earth Plates Sanderson_

G^2 _Earth Plates Borrel_

G^3 _Earth Plates Spang_

REPORT.

The Delegates are of opinion that it will conduce to clearness of

statement if their Report be divided into three sections—

(1) The purpose which a lightning conductor is intended to serve.

(2) A statement of those features in the construction and erection of

lightning conductors respecting which there has been, or is, a

difference of opinion, and the final decision of the Conference

thereupon.

(3) Code of rules for the erection of lightning conductors.

SECTION I.—_The purpose which a Lightning Conductor is intended to

serve._

A flash of lightning is the passage of an electric spark between two

bodies oppositely or unequally electrified, and between which the

difference of electric pressure or potential is sufficiently strong to

break across the air space which separates them, and to produce what is

known as a disruptive discharge. A flash may pass either between one

cloud and another, or between a cloud and the earth. In the former case

damage is not likely to be done, in the latter damage is or is not done,

according to the point at or from which the lightning strikes. The more

any object projects above the general level, the less is the distance

between it and the cloud, and as the less the distance the less the

resistance offered to the discharge, high objects are, _cœteris

paribus_, most frequently struck. Some substances, such as copper or

iron, can conduct a large quantity of electricity with facility, and are

called good conductors. Other substances, such as living vegetable or

animal matter, offer much obstruction, and form only partial conductors;

while dry earth, stone, and wood almost entirely prevent the passage of

electricity, and are very bad conductors—in fact, insulators.

For instance, a man may with perfect impunity clasp a copper rod an inch

in diameter, the bottom of which is well connected with moist earth,

while the top of it receives a violent flash of lightning. But if the

electricity does not find a path prepared for it, it will utilise such

partial conductors as may be reasonably near, for example—the heated air

from a kitchen chimney, the soot inside, and then the metal range at the

bottom; here, however, stone or dry material is generally found, which

will not conduct it, and then it dashes across the kitchen at some gas

or water pipe, or some pump or drain leading to damp earth, doing

serious damage on the way: or it may meet some tree in its course and

rend it from top to bottom, and if the human body intervene life may be

destroyed. Mechanical injury is inflicted only where the conduction for

the discharge is imperfect.

A lightning conductor fulfils two functions: it facilitates the

discharge of the electricity to the earth, so as to carry it off

harmlessly, and it tends to prevent disruptive discharge by silently

neutralising the conditions which determine such discharge in the

neighbourhood of the conductor.

To effect the first object a lightning conductor should offer a line of

discharge more nearly perfect, and more accessible, than any other

offered by the materials or contents of the edifice we wish to protect.

To effect the second object the conductor should be surmounted by a

point or points. Fine points and flames have the property of slowly and

silently dissipating the electrical charges; they, in fact, act as

safety valves.

If all these conditions be fulfilled; if the points be high enough to be

the most salient features of the building no matter from what direction

the storm cloud may come, be of ample dimensions and in thoroughly

perfect electrical connection with the earth, the edifice with all that

it contains will be safe, and the conductor might even be surrounded by

gunpowder in the heaviest storm without risk or danger.

All accidents may be said to be due to a neglect of these simple

elementary principles. The most frequent sources of failure are

conductors deficient either in number, height, or conductivity, bad

joints, or bad earth connections. There is no authentic case on record

where a properly-constructed conductor failed to do its duty.

SECTION II.—_A Statement of those features in the construction and

erection of Lightning Conductors, respecting which there has been, or

is, a difference of opinion, and the final decision of the Conference

thereupon._

Points.

Material for Conductor.

Size of Rod.

Shape of Rod.

(Rods, Tubes, Tape, Rope, Plait.)

Joints.

Protection of Rod.

Attachment to Building.

Earth Plates.

Space Protected.

Height of Upper Terminal.

Testing Conductors.

Internal Masses of Metal.

External Masses of Metal.

=POINTS.=—Starting with the extreme top, we have first to deal with the

question of points. The utility of points was hotly contested rather

more than a century since, and an abstract of the discussion will be

found in Appendix F, page (79), and difference of opinion still exists

as to their precise functions and value. The decision as to the best

form of points is complicated by two opposing requirements (1), the

sharper the point the more rapid the silent discharge of electricity,

and, therefore, the more effective the conductor; but (2) the sharper

the point the more easily is it destroyed by oxidation, or fused, should

a heavy disruptive discharge fall upon it.

Attempts have been made by the use of gold, silver, and platinum, to

obtain a sharp point which should not only be durable, but, owing to its

high melting point, resist fusion by a disruptive discharge. But such

metals are very expensive, and the statements in Appendix F, pages (67,

69, 73, 103, 123, 128, and 139) prove that even platinum points are

often damaged. Copper points whose sectional area is less than ·05 of a

square inch are very liable to be melted. Lightning has even fused a

copper rod ·10 sq. in. in sectional area, _i.e._, 0·35 in. in diameter,

and there are many rods still standing of which the extremity has been

melted into a button or knob.

For these reasons it seems best to separate the double functions of the

point, prolonging the upper terminal to the very summit, and merely

bevelling it off, so that, if a disruptive discharge does take place,

the full conducting power of the rod may be ready to receive it, and,

therefore, that there may be no risk of melted particles of metal

setting fire to the building, as has occurred. [Appendix F, p. (93).]

At the same time, having regard to the importance of silent discharge

from sharp points, we suggest that at one foot below the extreme top of

the upper terminal there be firmly attached, by screws and solder, a

copper ring, bearing three or four copper needles, each 6 inches long

and tapering from ¼ inch diameter to as fine a point as can be made; and

with the object of rendering the sharpness as permanent as possible, we

advise that they be platinized, gilded, or nickel plated.

Vanes, finials, and ornamental ironwork so frequently form the upper

portion of edifices, that it is essential to consider their relation to

the conductor. They should always be in perfect metallic connection with

the conductor. The possibility of such metal work inducing the charge to

desert the conductor for some other path is sometimes suggested, but it

could not happen unless the conductor were out of order, _e.g._, of

inadequate conducting power, or had an imperfect earth-contact.

With respect to factory chimneys, a different practice prevails in

England from that which is nearly universal on the Continent. In this

country one straight rod is usually carried up on one side of the

chimney to a height above the top about equal to the diameter of the

chimney. On the Continent two arches of iron are put crosswise over the

aperture of the chimney, and a vertical rod is carried up from the

intersection. In both systems the upper terminal suffers from the

corroding effect of the fumes from the chimney. Dr. Mann thought,

Appendix F, p. (132), that considering the ready path for lightning

afforded by the heated smoke discharged from chimneys, a coronal

conductor should be placed upon them, as well as a multiple point.

Messrs. Gray say, p. (9): “For high chimney shafts we fit a copper band

round the top, and four points thereon connected to main down rod.” The

Edinburgh Gas Works chimney, 341 feet high and 14 feet across at the

top, was fitted with a conductor under the advice of Faraday, Appendix

F, p. (89). It had an iron plate on the top; Faraday directed that the

rod should be connected with this plate, and the upper terminal should

rise vertically 6 feet above it.

We are of opinion that a coronal or copper band, with stout copper

points, each about 1 ft. long, at intervals of 2 or 3 ft. throughout the

circumference, will make the most durable and generally useful protector

for a factory chimney, but these points should be gilded or otherwise

protected against corrosion.

=MATERIAL FOR CONDUCTOR.=—Iron and copper are practically the only two

metals which need consideration; brass, which has sometimes been used is

so perishable that its employment is a self-evident error. We will

assume the conductivity of equal lengths and weights of iron to be, in

the case of steady currents of electricity, ⅙th that of copper, and the

cost of iron to be ⅑th that of copper, this would make the cost of

copper for equal conducting power ^9⁄_{6}ths, or 50 per cent. dearer

than iron. But there are other matters to be considered: (1) the great

weight and bulk of iron rods; (2) their deterioration by rust; (3) the

serious obstruction offered by a rusty joint; (4) the suddenness of

lightning discharge which modifies the conductivity; and lastly, that

iron is so much more rigid than copper that (except in the form of iron

wire rope, of which we shall speak hereafter) it can rarely be used in

greater lengths than 20 feet, and thus numerous joints become necessary,

whereas every needless joint should be avoided.

As regards galvanizing, we think it scarcely judicious to trust entirely

to it for protection against oxidation, for many instances of imperfect

galvanizing have come to our knowledge.

On the other hand copper becomes brittle, not only when exposed to the

air, but also by the passage through it of powerful charges of

atmospheric electricity. Franklin used iron, and it is employed in

America and on the Continent much more generally than copper, and it is

less tempting to the thief.

Nevertheless, as the cost of erection bears a considerable ratio to the

cost of the rod itself, and as iron possesses the disadvantages above

stated, we think that in all ordinary cases a copper rod will in the end

prove the cheapest, as it will certainly be the most durable.

=SIZE OF ROD.=—This is perhaps the most difficult subject which has to

be determined. We greatly regret the shortness of Table I. in Appendix

K; but we think that it must be assumed from it that lightning has fused

a copper rod ·10 in. (⅒th) in area, _i.e._, weighing 6 ounces to the

foot. We have also the Caterham case, Appendix I, p. (214), where a

copper tube weighing 5¾ ounces per foot was heated to redness.

The saving of cost which might be effected by using, for very low

buildings, rather slighter rods than for ordinary edifices is not worth

considering. In a 30 feet rod it could hardly amount to 10s. We

therefore recommend as the _minimum_ to be used:—

Material. Pattern. Diameter. Sectional Area of Metal. Weight per foot.

in. sq. in.

Copper Rope ½ ·10 6 oz.

Copper Round Rod ⅜ ·11 7 oz.

Copper Tape ¾ × ⅛ ·09 6 oz.

Iron Round Rod 9/10 ·64 35 oz.

=SHAPE OF ROD.=—This depends upon a subject which until lately was

warmly discussed, viz., upon the relative importance of the sectional

area, and of the superficial area of a conductor; a matter which has

been the subject of active discussion among electrical authorities.

Faraday and Sir W. Snow Harris, for example, held diametrically opposite

views respecting it. [Appendix F, p. (89), and I, p. (195).]

There is abundant and conclusive evidence that in the case of steady

electric currents, conductivity depends upon sectional area alone, and

not at all upon extent of surface, and experiments by Mr. Preece and Dr.

Warren De la Rue tend to show that, in the case of sudden discharges

from condensers, to which lightning discharges are probably analogous,

the influence of form is not considerable. On the other hand, there is

equally conclusive evidence that the facility with which currents of

short duration pass through conductors is affected by the form and

arrangement, as well as by the sectional area of the conductors. Upon

the whole we agree with the opinion quoted below, from a writer

recognized in the United States as a high authority on lightning

conductors, who, after describing and engraving more than fifty patterns

of rods, says[1]:—

Footnote 1:

Spang, “A Practical Treatise on Lightning Protection,” p. 121.

“The alleged improvements in the said conductors are, in nearly all

cases, worthless, or of a trifling and unimportant character. The

fact is, the said conductors are quite inferior, and contain no

essential improvement upon the ordinary round iron rod used during

the days of Franklin.”

In Europe the only forms at all generally employed are:—

Rods (round or square); Tubes; Tape; Ropes (wire, or wire with hemp

centres); Plait.

=Rods= (round or square).—The advantages and disadvantages of rods are

easily stated. The advantages are their durability and their rigidity,

the latter being of importance for long upper terminals. The

disadvantages are the necessity for numerous joints, and the difficulty

of avoiding serious disfigurement to the building to which they are

attached.

=Tubes= have much the same merits and demerits, with the additional

objection that they are necessarily of larger diameter than solid rods,

and therefore more conspicuous. They have also an additional

disadvantage in that they are generally joined together by screw

collars. The cutting of the thread in the tube seriously diminishes the

sectional area, and the joint so made is electrically defective. If

tubes are used, the joints should be made as directed in the code of

rules under the head of joints.

=Tape= is a form of rod which is of comparatively recent introduction,

and possesses many advantages. Foremost among these is the length which

can be supplied in a single piece. Where, as at the junction with an

upper terminal, a joint is needed, it is easily made by clamping or

rivetting the two surfaces together and then imbedding the whole in a

mass of solder. No kind of coupling known to us is, in our opinion,

equal to this very simple one. Owing to the flexibility of the tape it

can be made to follow closely the outlines of a building, or may be

countersunk in it, and painted over, but, as stated further on, abrupt

bends should be avoided, and the precautions and instruction set forth

on page 18 should be followed. The objections to tape, Appendix A, pages

(5) and (16) will be found to be objections, not to tape _per se_, but

to bad practice on the part of some persons who have fitted it up and

availed themselves unduly of its flexibility.

=Ropes.=—For many years past rope constructed of twisted strands of

copper or of iron wires has been largely employed for lightning rods.

There is on record a very remarkable case of the complete destruction of

a brass wire rope, an event which, if it had been repeated, might justly

have been regarded as a serious objection to the use of ropes. This case

is fully reported in Appendix F, pages (62–63); and from it some French

electricians have concluded that lightning may single out some wires

from a rope and travel along them in preference to the rest, even when

the whole of them are hardly sufficient to give it a free passage.

Whatever may have been the explanation, this accident seems to be

unique, and even if we accept the explanation given, the only extra

precaution which it calls for, is the soldering of each extremity of the

several wires forming the rod, and at every joint, into a single mass.

We agree with M. Borrel in thinking that serious evil arises from using

wire of too small diameter, which involves an additional number of

interstices for the lodgement of dirt, smoke, and water, and at the same

time renders the wires too thin effectually to resist oxidation. We have

had before us rope ⅜ in. in diameter, composed of 49 strands of a copper

wire about No. 19 B.W.G., say 0·04 in. in diameter. On the contrary, one

firm speaks of employing No. 10 B.W.G., _i.e._ 0·14 in. diameter, and in

special cases Nos. 8 and even 7, which would be about 0·17 in. and 0·19

in. diameter respectively: these would not be open to the objection we

have raised.

The objection to thin wires is necessarily greater with iron ropes, even

if galvanized, than with copper, for irrespective of the doubt as to the

perfect galvanizing of every part, there is the greater brittleness, and

consequent risk of damage from defective continuity.

=Ropes with Hemp Centres.=—One English firm sent us a specimen of

6–strand copper rope with a hemp core, and we understand that the same

pattern is occasionally used both in iron and copper in France. We do

not know the precise object aimed at—probably flexibility—but

considering the perishableness of such a core, its variation in length

with the hygrometric state of the air, and its invariability when the

copper is varying with temperature, we cannot regard it as a wise

construction.

=Plait.=—This form of rod was probably designed in the belief that the

essential element in a lightning rod was plenty of surface. It is made

in two sizes, with copper wire, about No. 16 B.W.G., plaited into a sort

of ribbon. It invites oxidation as much as is possible, and is in our

opinion neither durable nor trustworthy. The original form of this rod

was ridiculously bad; for it consisted of 13 copper wires and 1 zinc

one. Every time that it became wet, feeble electric action was set up,

and the zinc wire was gradually destroyed, without the slightest benefit

to anybody.

=JOINTS.=—The most fruitful sources of danger in rods are _bad joints_,

not necessarily those that are mechanically bad, but those that are so

electrically. A joint is said to be electrically bad when it offers

resistance to the passage of electricity through it. _There should be no

resistance whatever._ A careful inspection by Capt. Bucknill, R.E.

(Appendix M, p. 243), has proved that bad joints in lightning rods are

very abundant, though they appear perfectly sound; and everyone who has

measured the electrical condition of conductors confirms this fact. Bad

joints have the same effect as lengthening the conductor; and, in one

case, one bad joint was found to have the same effect on a discharge of

electricity as a conductor 1,900 miles long. It is evident that such

rods may be worse than useless, for other parts of the building may

offer easier paths for the discharge to the earth. If the joint be

imperfect, and the rod convey a charge to earth, heat will be generated

at the joint, the rod may be fused, and the discharge be diverted to the

building.

Screwed, scarfed, and rivetted joints, however well they may be made

mechanically, are certain to rust and corrode in time, owing to the

expansions and contractions due to changes of temperature admitting

moisture, and thus causing corrosion and resistance. No joint can

possibly be electrically perfect that is not _metallically continuous_,

and careful soldering, in addition to screwing, scarfing, or rivetting,

is the only certain mode of securing this. Soldering is a method that

has borne the test of experience, and its success as a means of securing

perfect joints leaves no excuse for its omission. The fewer joints the

better, but where there are joints they can only be made electrically

secure by careful soldering.

=PROTECTION OF ROD.=—The lower part of copper rods is sometimes stolen

for the sake of the metal. This can be guarded against by putting it

inside a length of iron gas-barrel, extending from some distance below

ground to 10 ft. above it.

=PAINTING.=—Iron conductors, even if they are galvanized, should be

painted throughout, except at the points, which should be gilded or

nickel-plated.

In France and Belgium painting is resorted to to a considerable extent,

and the practice was recommended by the late Professor Joseph Henry, and

followed very largely in America. [Appendix F, pages (99) and (113).]

=ATTACHMENT TO BUILDINGS.=—The evidence against the use of glass or

other material in order to insulate the conductor, is overwhelming, and

insulation may be regarded as unnecessary and mischievous. The

essentials are (1) that the rod be attached to the building by

fastenings of the same metal as itself, (2) that the fastenings be of

adequate strength, (3) that they be of such form as not to compress or

distort the rod, (4) that they allow play for its expansion and

contraction, (5) that they hold it firmly enough to prevent all the

weight falling on any one bearing.

Where practicable it is well to take the rod down that face of the house

which is most exposed to rain.

=EARTH PLATES.=—This portion of the lightning conductor is of the utmost

importance, but has hitherto been the most neglected. The majority of

cases in which lightning has caused injury very near to or upon

conductors are traceable to those conductors having imperfect earth

terminals. We know of many cases in which the earth terminals have been

miserably imperfect, or entirely neglected, when the above-ground

portion has been perfectly satisfactory. In fact, though it may be

admitted that the case found by Dr. Mann,[2] of the lightning rod of a

church tower, the lower end of which was thrust into an empty glass

bottle, is an exceptionally bad one; yet there are sadly too many, of

which the Middlesboro’ case, Appendix I, page (217) is a perfectly fair

type.

Footnote 2:

Quarterly Journ. Met. Soc., Vol. II., p. 420.

A convenient earth connection is often afforded in towns by the iron

mains for gas and water—arguments both for and against the utilisation

of both water and gas mains will be found in the Appendix—we, therefore,

need only state our opinion in favour of connection with both. But no

connection should ever be made with soft metal pipes, because of the

risk of their fusion; and the conductor should be kept as far as

possible from internal gas pipes on account of the risk of lighting the

gas at an imperfect joint.

As a general rule we advise the soldering of a plate of metal, copper to

copper, iron to iron, to the lower end of the conductor. The earth plate

should always be of the same metal as the rod, otherwise destructive

galvanic action sets in. This plate, which may be flat or cylindrical,

must not have less surface than 18 square feet, _i.e._, 9 square feet on

each face; there is no advantage in notching or pointing it. A hole must

be dug, or well sunk, to receive this plate, and the hole must be so

deep that the earth surrounding the plate shall _never_ be dry. Any

available drain or other water should be allowed to soak into the earth,

over the site of the plate. After the hole has been dug, and the plate

lowered into position, it should be filled with cinders, or coke. In

extremely dry rocky localities, it is sometimes impossible to fulfil

these conditions: then the best thing to do is to bury three or four

hundredweight of iron at the foot of the conductor, still using the

earth plate and the coke, and taking especial care that the rain-water

and sink pipes discharge over it.

All drains, water-courses, in fact, everything which will assist in

distributing the charge over a large extent of moist earth should be

utilized by leading branches from the earth plate to them, or a long

length of the rod may be laid in a drain if it be one which will be

constantly wet.

=SPACE PROTECTED.=—The question as to the extent of the space which will

probably be protected by a lightning rod is one which is of very great

practical importance, because it governs the number and height of the

upper terminals which are required for the protection of any given

building. The index to the Appendix shows that “Protection, Area of,” is

discussed upon twenty-nine pages in different parts of the Appendix. It

has been laid down that the space protected was a cone, having the point

for its apex, and a base whose radius was equal to twice the height of

the point, while the latest French official instructions, Appendix F, p.

(67), state that a point will “effectively protect a cone having the

point for its apex, and a base whose radius is 1·75 of its height.” The

English War Department instructions considerably reduce this space by

asserting, Appendix F, p. (71), that “no precise limit can be fixed to

the protecting power of conductors. In England the base of the protected

cone is usually assumed to have a radius equal to the height from the

ground; but though this may be sufficiently correct for practical

purposes, it cannot always be relied upon.”[3]

Footnote 3:

On page (96) two instances are recorded in which, if the evidence can

be trusted, the stroke fell within a radius equal to the height, but

it is only right to say that the facts are not very clearly recorded.

[Illustration: Sketch illustrative of area of protection]

According to this rule, the church of Ste. Croix (see Appendix F, p.

(141)), would require four upper terminals, one on steeple, one on

chancel, and one in the middle of each half of the transept.

From theoretical considerations stated by Mr. Preece, Appendix F, p.

(137), he arrives at the conclusion that “A lightning rod protects a

conic space whose height is the length of the rod, whose base is a

circle having its radius equal to the height of the rod, and whose side

is the quadrant of a circle, whose radius is equal to the height of the

rod.”

At present we have not sufficient data to enable us theoretically to

calculate the space protected by a lightning rod, and therefore we are

compelled to draw up our rules upon the question entirely from

experience, and here we find, that with the doubtful exceptions already

mentioned, there is no recorded instance of a building being struck by

lightning within a conical space, the radius of whose base was equal to

its height, and we think that the adoption of this rule may reasonably

be expected to yield that security in the future, which as far as we

know, it has done in the past.

=HEIGHT OF UPPER TERMINAL.=—This matter is one which may be left

entirely to the option of individual architects and engineers, subject,

of course, to the opinions expressed under the heading “Space

Protected.” In France extremely long _tiges_, or upper terminals,

generally 33 feet long, are used; but it is obvious that they are

necessarily very strong and heavy, and both by their weight and by the

great leverage which they exert when there is any wind, they must

produce serious vibrations in the roof. In England hitherto the opposite

error is almost universal, and we seldom see a conductor carried high

enough to protect all the building to which it is attached. The question

of appearance comes in here, but concerning it we need only remark that

while in England care seems generally taken to conceal the conductors,

in France they are, to a certain extent, made features of the edifice.

With a proper exercise of taste, the terminals of the lightning

conductors can be made to assist the ornamentation of the building, as

has been done in many cases.

=TESTING CONDUCTORS.=—Periodical examination and careful testing of the

lightning conductor are requisite to maintain the system in efficient

order. Points will corrode from oxidation and fusion; joints will get

loose and bad through the action of weather and workmen; connections

will decay both above and below ground; imperfections will develope

themselves; alterations will be made by landlords and tenants; and, in

spite of every precaution during erection, the conductor will thus lose

its efficiency if it be not _maintained_ in thorough order. For this

purpose inspection should be both visual and electrical. In order to

facilitate the electrical examination of the conductor, some firms have

erected a double rod, connected with one upper terminal, one on each

side of a chimney or shaft; this is a very efficient arrangement, for it

provides a means for testing from the ground. It has also been proposed

to carry an insulated wire alongside or even within the rod, connected

to the terminal at the top, and to the testing apparatus at the bottom.

A testing apparatus has been devised by Mr. Anderson (_Lightning

Conductors_, p. 60). M. Borrell, Appendix K, p. (226), Captain Bucknill,

R.E., Appendix M, p. (244), and Mr. Vyle, Appendix M, p. (244), have

also introduced apparatus for the purpose. The system in use in Paris,

Appendix K, p. (225), and M, p. (245), is perhaps the simplest and

cheapest, and is effective as regards testing the efficiency of the

conductor, but not that of the earth connection.

The efficiency both of the conductor and of its earth terminal should be

annually tested. As this testing involves some skill and familiarity

with electrical apparatus it would be advantageous if some competent

person were officially appointed, either by the government or by some

recognised authority, to perform this duty.

=INTERNAL MASSES OF METAL.=—All large and long masses of metal, such as

beams, girders, pipes, hot water systems, and large ventilators fixed in

the interior of buildings, should be electrically connected with the

earth, or with the conductor; but the soft metal gas pipes should never

be used as conductors. The inlet and outlet pipes of large meters should

always be, independently of the meter, electrically connected with each

other, for two remarkable cases of the explosion of a meter have

occurred through the presence of a joint in the pipe electrically bad

owing to the use of India-rubber packing. Appendix M, p. (239).

=EXTERNAL MASSES OF METAL.=—Large constructive and decorative ironwork,

such as guttering, flashings, railings, finials, vanes, &c., and all

masses of metals used in building, should be connected to each other,

and to the earth direct, or to the conductor. In fact, the gutters and

water pipes are already frequently utilized as a partially protective

system. The ventilators of soil pipes may also be employed in this way,

and even made sightly by the addition of an ornamental finial fitted

with points, but care must be taken that the joints are metallic and not

made with red lead or putty; and it must not be forgotten that the

conductivity of lead is very small, so that undue reliance must not be

placed upon pipes made of that metal.

SECTION III.—_Code of Rules for the Erection of Lightning Conductors._

The following Code of Rules should be carefully attended to in drawing

out a specification for a Lightning Conductor, the reasons for each

being given in the previous Sections and in the Appendix:—

=Points.=—The point of the upper terminal should not be sharp, not

sharper than a cone of which the height is equal to the radius of

its base. But a foot lower down a copper ring should be screwed

and soldered on to the upper terminal, in which ring should be

fixed three or four sharp copper points, each about 6 in. long. It

is desirable that these points be so platinized, gilded, or nickel

plated as to resist oxidation.

=Upper Terminals.=—The number of conductors or points to be specified

will depend upon the size of the building, the material of which

it is constructed, and the comparative height of the several

parts. No general rule can be given for this; but the architect

must be guided by the directions given at pp. 12 to 14. He must,

however, bear in mind that even ordinary chimney stacks, when

exposed, should be protected by short terminals connected to the

nearest rod, inasmuch as accidents often occur owing to the good

conducting power of the heated air and soot in a chimney (p. 2).

=Insulators.=—The rod is not to be kept from the building by glass or

other insulators, but attached to it by metal fastenings. (See p.

11.)

=Fixing.=—Rods should preferentially be taken down the side of the

building which is most exposed to rain. They should be held

firmly, but the holdfasts should not be driven in so tightly as to

pinch the rod, or prevent the contraction and expansion produced

by changes of temperature.

=Factory Chimneys.=—These should have a copper band round the top, and

stout, sharp, copper points, each about 1 ft. long, at intervals

of two or three feet throughout the circumference, and the rod

should be connected with all bands and metallic masses in or near

the chimney. (See p. 5.) Oxidation of the points must be carefully

guarded against.

=Ornamental Ironwork.=—All vanes, finials, ridge ironwork, &c., should

be connected with the conductor, and it is not absolutely

necessary to use any other point than that afforded by such

ornamental ironwork, provided the connection be perfect and the

mass of ironwork considerable. As, however, there is risk of

derangement through repairs, it is safer to have an independent

upper terminal. (See p. 4.)

=Material for Rod.=—Copper, weighing not less than 6 oz. per foot run,

and the conductivity of which is not less than 90 per cent. of

that of pure copper, either in the form of tape or rope of stout

wires—no individual wire being less than No. 12 B. W. G. Iron may

be used, but should not weigh less than 2¼ lbs. per foot run. (See

pp. 5 to 10.)

=Joints.=—Although electricity of high tension will jump across bad

joints, they diminish the efficacy of the conductor; therefore

every joint, besides being well cleaned, screwed, scarfed, or

rivetted, should be thoroughly soldered. (See p. 10.)

=Protection.=—Copper rods to the height of 10 feet above the ground

should be protected from injury and theft, by being enclosed in an

iron pipe reaching some distance into the ground.

=Painting.=—Iron rods, whether galvanized or not, should be painted;

copper ones may be painted or not according to architectural

requirements.

=Curvature.=—The rod should not be bent abruptly round sharp corners.

In no case should the length of the rod between two points be more

than half as long again as the straight line joining them. Where a

string course or other projecting stone work will admit of it, the

rod may be carried straight through, instead of round the

projection. In such a case the hole should be large enough to

allow the conductor to pass freely, and allow for expansion, &c.

=Extensive Masses of Metal.=—As far as practicable it is desirable

that the conductor be connected to extensive masses of metal, such

as hot-water pipes, &c., both internal and external; but it should

be kept away from all soft metal pipes, and from internal

gas-pipes of every kind, respecting which see page 15. Church

Bells inside well protected spires need not be connected.

=Earth Connection.=—It is essential that the lower extremity of the

conductor be buried in permanently damp soil; hence proximity to

rain-water pipes, and to drains, is desirable. It is a very good

plan to make the conductor bifurcate close below the surface of

the ground, and adopt two of the following methods for securing

the escape of the lightning into the earth. A strip of copper tape

may be led from the bottom of the rod to the nearest gas or water

_main_—not merely to a lead pipe—and be soldered to it; or a tape

may be soldered to a sheet of copper 3 ft. × 3 ft. and 1/16 in.

thick, buried in permanently wet earth, and surrounded by cinders

or coke; or many yards of the tape may be laid in a trench filled

with coke, taking care that the surfaces of copper are, as in the

previous cases, not less than 18 square feet. Where iron is used

for the rod, a galvanized iron plate of similar dimensions should

be employed.

=Inspection.=—Before giving his final certificate, the architect

should have the conductor satisfactorily examined and tested by a

qualified person, as injury to it often occurs up to the latest

period of the works from accidental causes, and often from the

carelessness of workmen. (See p. 14.)

=Collieries.=—Undoubted evidence exists of the explosion of firedamp

in collieries through sparks from atmospheric electricity being

led into the mine by the wire ropes of the shaft and the iron

rails of the galleries. Hence the headgear of all shafts should be

protected by proper lightning conductors.

(Signed)

W. GRYLLS ADAMS.

W. E. AYRTON.

LATIMER CLARK.

E. E. DYMOND.

G. CAREY FOSTER.

D. E. HUGHES.

T. HAYTER LEWIS.

W. H. PREECE.

G. J. SYMONS.

JOHN WHICHCORD.

_December 14th, 1881._

APPENDIX A.

CIRCULAR AND QUESTIONS

ISSUED TO

Manufacturers of Lightning Conductors,

AND

THEIR REPLIES THERETO.

NOTE.—There are only two points requiring mention respecting the

following replies. First, that in order to avoid useless

repetition of the questions, the answers are numbered, and the

corresponding question will be found in the following circular.

Secondly, that the replies are verbatim, as received from the

manufacturers, except that frequent entries will be found in

square brackets, _e.g._ [A 0·11 in.] These represent approximately

the sectional area of the conductors, and are given to facilitate

the comparison of the conducting capacities of the very various

patterns submitted to the Conference.

CIRCULAR.

LIGHTNING ROD CONFERENCE.

30, GREAT GEORGE STREET, WESTMINSTER, S.W.

_November 14th, 1878._

At the invitation of the Meteorological Society delegates have been

nominated by the following Societies:

Royal Institute of British Architects,

Society of Telegraph Engineers,

Physical Society,

Meteorological Society,

to consider the present modes of erecting Lightning conductors, and

improvements therein.

At a largely attended meeting held this day I was instructed to

forward to you the questions stated below, and to request you to

forward with your replies any remarks which you may wish to lay

before the Conference.

If you desire any specimens to accompany your remarks, I shall be

glad if, whenever possible, they do not exceed five inches in

length.

I am,

Your obedient Servant,

G. J. SYMONS,

_Secretary to the Conference_.

QUESTIONS.

(_It is requested that the replies be written on foolscap paper, on one

side only, and that they be numbered in accordance with the questions._)

1. Form, dimensions, and material usually adopted by you for upper

terminals.

2. Material and dimensions of conductor.

3. Is any definite proportion between the length and sectional area of

the conductor observed, and if any, what?

4. Joints, how made.

5. Attachment to building, how made.

6. Ground connection, how formed, and of what extent.

7. Extent of area supposed to be protected.

8. If there is more than one terminal, is the size of the conductor

increased?

REPLIES.

39, WAPPING, LONDON, E.

1. The upper terminals are made of a copper tube ⅝ inches in diameter

and 1/16 inches thick [A. 0·11 in.] In the upper end of the tube is

fitted 15 inches of copper rod tapered to a point at the top, into which

is fixed 3 or more smaller rods about ¼ inch in diameter [A. 0·05 in.]

each tapered to a point, and brought into the parent rod in a curve (not

at an angle). The next part of the tube, down to about 9 inches from the

bottom, is filled with a stiff iron rod to strengthen it, the lower end

of the tube being left open to receive the rope. This constitutes what

is called “the point.” These points vary in length from 2 or 3 to 8 or

10 feet when used for buildings. A square-topped tower would require a

much higher point than would be necessary for the top of a spire.

Sometimes the points are tipped with platinum, which we consider to be

altogether superfluous.

2. The conductor is simply a wire rope, varying in size, and mostly

either ⅜, ½, or ⅝ inches in diameter [A. 0·11, 0·20, or 0·31 in.] These

ropes are made in two different forms: the one ⅜ inch diameter [A. 0·11

in.], most suitable for ships’ use, is composed of 49 No. 18 guage

copper wires, each wire having a circumferencial measurement of ·157

inches [A. 0·002 in.]; the circumferencial or surface measurement of the

whole of the 49 wires is equal to 5·693 inches [A. 0·11 in.], or say,

equal to the surface of a copper band 2·846 inches wide—_i.e._,

measuring both sides of the band.

The other make, say ½ inch diameter [A. 0·20 in.], much used for lofty

buildings, is composed of 7 No. 7 guage copper wires, each wire having a

circumferencial measurement of ·581 inches [A. 0·027 in.]; the

circumferencial or surface measurement of the 7 wires is equal to 4·067

inches [A. 0·19 in.], or say equal to the surface of a copper band 2·033

inches wide.

3. There is no definite proportion observed between the length and

sectional area of the conductor. We take it that the sectional area

should be the same, irrespective of length, as we do not trace that

lightning varies in intensity while passing through a conductor of

greater or less length. The rather prevalent idea that a smaller

conductor is sufficient for a low building is, we think, erroneous, as

we do not find any data to show that lightning in its descent loses any

portion of its force until it actually enters the earth.

4. The copper rope is joined to the upper terminal by passing the end of

the rope into the tube at the lower end of the terminal for the space of

about 9 inches, and fixing it with 3 copper rivets. There is no other

join in the conductor whatever—a feature of much greater importance than

is sometimes admitted.

5. The upper terminal is passed through two strong earthenware

insulators which are usually fixed to the building by two strong

galvanized iron staples. Other modes of fixing the terminal must

sometimes be resorted to, as some factory chimneys are capped with iron,

and buildings of varied forms must be treated with according to

circumstances. Having fixed the terminal, the rope may then be led down

the building on the most convenient side for the purpose, and fixed at

intervals of 6 or 8 ft., according to circumstances, with glass

insulators supported by copper brackets. The rope should be given the

straightest course practicable from the upper point down to the earth,

carefully avoiding all angles, specially an acute angle, as much as

possible, and in its passage it should be kept clear from any other

metal in the building.

There are three matters to which we would call special attention, viz.:

_Insulators, Angles and Joints, Metal in Building._

_Insulators._—When copper rope lightning conductors were first

introduced, about the year 1837, a circumstance occurred which at once

proved the efficiency of the conductor, and suggested the use of

insulators. The late Mr. Andrew Smith, C.E., had fitted a factory

chimney in the East of London with a rope conductor, which was fixed to

the chimney by iron staples. In a violent storm which occurred soon

afterwards, the lightning was seen to pass down the conductor, which

remained unaltered in any way; but on examining the chimney it was found

that the brickwork had received a concussion at most, if not all, of the

staples, showing that the lightning in passing had expended part of its

force on the iron staples. It is probable that, if the staples had been

made of thicker iron, and had been so placed as to lead off from the

conductor with easy curves inwards, instead of being driven into the

wall at right angles with the conductor, the concussions would have been

much more violent than was the case.

_Angles and Joints._—It must be obvious to any one that lightning, as

well as any other matter or thing which travels at high speed, would be

greatly obstructed in having to turn corners. It must also be borne in

mind that lightning is of intense heat, and while passing in a straight

line the effect of its heat is lost in the velocity of its motion; but

in passing an angle its momentary pause (much too brief to be

calculated) is sometimes enough to create sufficient heat to fuse the

conductor at the angle. For this reason all angles must be avoided, and

easy curves having a downward tendency substituted.

The angles in copper tube conductors are doubly objectionable, for,

having joins as well as angles, they are liable, by the effect of heat,

to become disjointed. It would be difficult, if not impossible, to fit a

tubular conductor, except in a straight line from end to end, without

this double objection. Similar objections apply also, in a greater or

less extent, to the copper band conductors, as they are made with joins,

and, when fixed up, are usually carried into and over as many angles as

come in their way. They do not so readily follow all the sinuosities of

a building as a rope does on the curve principle.

The flat band conductors, which are composed of a number of galvanized

iron and copper wires combined, are simply a frivolity.

_Metal in Buildings._—Taking the conductivity of copper as from 7 to 10

times greater than that of iron, it would probably follow, that if two

rods, the one of copper the other of iron, in these proportionate sizes,

were brought together in one common terminal or point, and led by the

same course to the earth, as much of the fluid would possibly pass down

the one as the other. On this principle, we avoid contiguity with any

metal in a building, especially if in large masses, such as machinery,

&c.

_Ships’ Conductors._—In fitting the rope conductor to a ship’s rigging

it is only necessary to pass it through a hole in the truck, so that the

end may stand about 6 inches above the truck. It may be held up by a pin

or key passed through the rope close over the truck, and then carried

down the topgallant backstay (to which it should be tied at intervals

with yarn) to the gunwale, where a sufficient length of the conductor

should be kept in a coil to reach well down into the sea in any position

of the ship. In stormy weather the coil may be untied, and by its own

weight the end will drop down into the sea as required. Sometimes the

rope is shackled at the gunwale to a strip of sheet copper about 3

inches wide, which is nailed down the ship’s side till it meets the

sheathing at the bottom. The strip of copper should _overlay_ the

sheathing for a few inches. It may be noticed that this kind of

conductor, fitted with a coil at the gunwale, is without any join

whatever, and that it takes almost a straight course direct from the

truck into the water.

The copper band conductors let into the mast and carried through the

hull of the ship are objectionable and unsafe, as, in passing from each

portion of the mast, they require moveable joints, so as to admit the

several parts of the mast being run up or down as required. These joints

present angular interruptions which may become out of order, and, in

passing through the hull, any rupture of the band in that part, or the

contiguity of other metals, may cause serious consequences. Certainly,

there can be no necessity for carrying the lightning through the ship

when, by a safer and much more simple method, it may be kept altogether

outside.

In the smaller vessels, where the mainmast is well above the other

masts, it may be sufficient for that mast only to be fitted with a

conductor, but in larger ships, particularly long steam-ships, where the

masts are a considerable distance apart, each mast should have a

conductor.

We do not, either in theory or in practice, know any necessity for

protecting the yards with conductors, though it is not altogether

improbable that, in the absence of conductors on the masts, the yards

might get damaged while the masts remain uninjured.

6. The end of the rope should be buried in moist earth, and carried in a

curve to 5 or 6 feet from the foundation. In clay ground and on the

shady side of a building about 3 feet below the surface would be deep

enough; but in lighter ground, and particularly on the sunny side, it

should be buried 6 or 7 feet deep, to ensure sufficient moisture at all

times of the year.

7. As the course by which lightning approaches the earth is very

devious, it would be difficult to determine with certainty the extent of

area protected; but, viewing the absence of damage to the most remote

parts of the roofs of buildings which have been properly fitted with

conductors within the last 40 years, we should think the area protected

may be taken as equal to from 3 to 5 or 6 times the height of the

conductor.

8. When two or more terminals are used, the main rope should be somewhat

enlarged; otherwise, the collective quantity of fluid received on the

several points may be too great for the common channel.

WILKINS & WEATHERBY.

* * * * *

DORA STREET, LIMEHOUSE, E.

We have to own receipt of your valued communication of the 14th ult.,

and with great pleasure to submit for the consideration of the

Conference the following replies to their questions. We have endeavoured

to make them as explicit as possible, but it is difficult adequately to

describe our system on paper, and we suggest for the consideration of

the Conference the advisability of showing any Committee they may

appoint one or two of the numerous public buildings fitted by us.

Any further particulars or drawings you may require we shall be glad to

send you; and it is with great pleasure that we add that any services we

can render you in your valuable investigations are at your disposal.

1. A five-pointed copper spindle, the sharp points of which are

silvered, and single points on high chimney shafts to the number of four

or five.

2. Copper solid bands, or tubes, “as samples sent,” being simple,

durable, cheap, and the most capacious form for the safe conduction of a

heavy stroke of lightning, the bands being from 1 inch to 3 inches in

width and ⅛ inch thick [A. 0·12 to 0·37 in.], and the tubes from ¾ to 1½

inches in diameter and ⅛ inch thick [A. 0·24 to 0·54 in.].

3. Yes; experience has proved that nothing less than 1½ inch bands [A.

0·18 in.] should be used for the main conductor to ordinary houses, with

¾ [A. 0·09 in.] to 1 inch [A. 0·12 in.] bands for branches, and from 2

to 3 inches [A. 0·24 to 0·37 in.] bands as main conductor to buildings

of large area, with 1 to 1½ inch [A. 0·12 to 0·18 in.] for branches; or,

in the case of chimney shafts, ¾ inch to 1½ inch tube [A. 0·24 to O·54

in.] for main conductor, and 2 to 3 inches flat band [A. 0·24 to 0·37

in.] for tops of same.

4. The bands are in long lengths, are lapped, closely rivetted and

soldered, to form a continuous band; while the tubes have patent

insertion joints, the upper end being turned and fitted into the lower

end, which is bored, and the tube then forms a continuous line

externally and internally.

5. Copper holdfasts to suit shape and size of conductor.

6. Not less than 30 feet of 1½ inch to 2 inch copper bands [A. O·18 to

0·24 in.] in two or three branches, with forks at end of each band, and,

if water is not near, the trenches half filled with carbonaceous

materials and well watered, as this material will readily absorb the

least moisture and retain it, while being in itself the best conductor.

But much will depend upon the nature of the ground; for if chalk or rock

foundation and water cannot be got at, the ground branches must be at

least doubled, and the trenches deeper and made up of carbonaceous

materials and earth.

7. Our experience is that no appreciable extent is protected by a single

rod conductor in the presence of other influences. The chimney-stacks,

lined with carbon in the shape of soot, with the heated gases, cause a

rarefaction in the atmosphere, and form an easier passage for the

electric fluid. Roofs and buildings having large masses of metals will

be more likely to influence lightning than the single line of copper rod

generally fitted. Many cases have occurred of chimney-stacks 4 feet to 9

feet across being struck opposite the conductor, and lead roofs,

gutters, lead ridges, &c., from 10 feet to 20 feet from the rod

conductor.

8. No; the system of conduction used by us does away with this, the

lines of conduction being ample.

REMARKS.

From our close connection with the late Sir William Snow Harris, adviser

to the Crown for upwards of twenty-five years in regard to lightning

conductors for the navy, and having made lightning conductors our

especial practical study for thirty-five years, we may be pardoned for

making a few remarks on the protection of buildings from lightning.

We would, firstly, say that the system of conductors now fitted by us is

based upon these past years of experience, and upon facts collected

during this period, of accidents to buildings having the ordinary single

line of conduction, as also from the practical success of the conductors

in the navy.

The form of conductors used by us has been adopted after considerable

experience, as being the most simple, solid, durable, and capacious form

of conductor for the safe conduction of heavy strokes of lightning.

In place of insulators as fastenings, we use copper holdfasts, as we

found the former dangerous and useless, as the glass, being

non-conductive, the expansion and heat of the electric fluid, being

confined, broke them, and caused an unsafe concussion; and it is also a

disadvantage for a conductor to be away from the building, as nearly

every material in nature assists, without detracting from, the safe

discharge of the electric fluid through a good copper conductor. We find

that the copper wire rope conductor, usually applied, is seldom more

than ⅜th of an inch in diameter; but we did once remove, from the tower

of St. Mary’s Church, Taunton, a copper wire rope conductor of ⅞th of an

inch in diameter [A. 0·60 in.], said to be especially made to

order—certainly the largest we ever came across; but it failed to give

the necessary protection in a lightning storm, which did much damage to

the tower and roof of the church. As capacity or weight of copper is the

most important for safe conduction, copper wire rope is very deceptive

in this respect, as will be seen by the following comparisons, viz.:—A

copper wire rope conductor of ⅜ inch diameter [A. 0·11 in.] weighs 2¾

ounces per foot, not equal to a plain solid band ⅜ inch wide and ⅛ inch

thick [A. 0·046 in.], which weighs 2·907 ounces per foot. A copper wire

rope conductor of ½ inch diameter [A. 0·20 in.] weighs 5 ounces per

foot, not equal to a solid band of ¾ inch wide and ⅛ inch thick [A.

0·092 in.], which weighs 5·814 ounces per foot. A copper wire rope

conductor of ⅝ inch [A. 0·31 in.] weighs 9½ ounces per foot, not equal

to a solid band of 1¼ inch and ⅛ inch thick [A. 0·153 in.], which weighs

9·690 ounces per foot. This is the largest size of wire rope conductor

made or used.

From the above will be seen what protection can be given by conductors

of such small capacities; and we may add that solid band conductors of

the same weight, and superior in every way, can be fixed at less than

half the cost of the wire rope, _foot_ for _foot_.

Copper chains and copper wire bands, as conductors, answer in so

uncertain a manner with the galvanometer, that they should never be

used.

Iron in any form should be avoided, from its lower conducting power, and

its utter uselessness when in a rusty and decayed state.

With regard to testing with the galvanometer, the mere testing of the

conductors is no proof of the security of the building itself. We not

only test the conductors, but also the building, to prove that it is

under safe conduction in lightning storms.

In conclusion, we beg to state that our patent system of protection is

the application of one or more main down and ground copper conductors

and sizes, according to the height and area of the building, the fitting

of the copper bands to each chimney-stack, and connecting the same, and

the connecting of all the metals on the roofs thereto and to the main

conductor, so that there shall be no circuit by which the lightning

fluid would be likely to attack without having its exit to the main

conductor.

For high working chimney-shafts we fit a copper band round the top, and

four points thereon connected to main down conductor.

For further information, we earnestly solicit the careful perusal of our

pamphlet and papers herewith.

J. W. GRAY & SON.

* * * * *

CHIPPENDALE MEWS, HARROW ROAD.

1. Upper terminals pointed with one or more points, according to the

nature of the building to be protected. Dimensions vary in like manner.

Material—copper or brass, with electro-gilded points.

2. Conductor composed of copper or galvanized rope, according to height,

&c., of building, &c., dimensions varying with resistance of the

circuit.

3. The sectional area varies with the length.

4. Joints made, as far as possible metallically; where solder cannot be

used, screw joints are made use of.

5. Attachment to building direct by metallic ties of requisite form.

6. Ground connection—When practicable, the end of conductor is

metallically connected with gas or water _main_, otherwise a hole is dug

deep enough to meet always moist earth. The end of conductor is either

attached to an earth plate, or coiled up in a bundle and surrounded by

coke.

7. The area protected is supposed to be a radius equal to the height of

conductor.

8. If more than one terminal is attached to one conductor, the size of

the latter is increased, except under certain conditions.

F. RUSSELL & CO.

* * * * *

137, PRINCESS STREET, MANCHESTER.

1. A copper tube 1¼ inch diameter or 1 inch diameter, finished at the

upper end, with a forged copper point or cone, connected with the tube

by a cast copper (or gun-metal) coupling, into which coupling are also

screwed three or more smaller points round the larger central one. At

the lower end the tube is screwed into a somewhat similar coupling, to

receive also the brazed and screwed end of the conductor. Or a solid

copper rod ½ inch diameter [A. 0·20 in.], or _wrought_ iron rod 1 inch

diameter [A. 0·79 in.] (where iron conductors are used) the rod in

either case forged to a blunt point, and screwed at the lower end, like

the tube first described, to fit the coupling.

2. (_a_). Copper wire rope of 7 strands each, No. 10 Birmingham wire

gauge, or in specified cases of No. 8 or 7 wire gauge, making, when

spun, a rope with a sectional area varying from 7/16 to 11/16.

(_b_). Solid copper rods ½ inch diameter [A. 0·20 in.].

Solid iron rods 1 inch diameter [A. 0·79 in.].

(_c_). Copper band or “tape” of sizes from ¾ × ⅛ to 2 or 3 × 3/16

inches [A. 0·09 to 0·38 or 0·56 in.].

(_d_). Copper tube ⅝ inch diameter outside, and ⅛ inch thick [A. 0·20

in.]

3. Although no definite rule exists for the proportional sizes of the

conductor, it is usual and prudent in a large building to employ for the

main conductors, which should come from the highest and most exposed

points to the earth in the most direct way, a larger conductor than

would be required for a small building, and the branches or connections

to this main conductor may be smaller in sectional area than the

principal one. Thus, a church tower with four angle pinnacles may be

protected by four finials or points, one to each pinnacle, and these

four parts fitted to rope of 7 wires No. 10 gauge [A. 0·10 in.], to be

united to a continuous band round the parapet, from whence a rope of 7

wires No. 8 gauge [A. 0·15 in.] should descend into the earth; or an

infirmary or workhouse built with wings would have, perhaps, three

direct rod conductors, one to each chimney stack, and connections with

the water spouts, or lead flashing made of small copper tape ¾ × ⅛ [A.

0·09 in.] _soldered_ to the lead and worked round the rods.

4. The fewer joints the safer, and for this reason—the copper _rope_ or

_tape_ is better than the rod or tube, as the former is made

conveniently any required length, and the danger of a fault or break in

the continuity is avoided. Of the necessary joints the rope requires one

at its junction with the top rod or tube; this is made by brazing a

small ring of brass (or copper) round the rope; the solid end thus

formed being chased with a deep male thread, which fits the prepared

base of the rod. The branch conductors or connections, with adjacent

constructive or decorative iron work—as beams, girders; cresting, vanes,

&c., are made by threading a bead with a similar ring to receive the

branch, as that already described. Where the branch reaches its object a

ring or solid coupling should be “tapped” into the girder or cresting,

to ensure thorough metallic connection, if the destination of the branch

be the lead flashing, the seven wires must be opened like a fan, and

_each wire_ strongly soldered with common plumbers’ solder to the lead—

(_b_). Copper or iron rods are made continuous by couplings of either

metal, as the case may be, which should exceed the diameter of

the rods by enough metal to allow of a good thread. These

couplings should be hexagonal or octagonal in plan, to allow the

workman a certain grip; and the thread should be of the kind

called right and left, so that while screwing one length he may

not unscrew the other. These conductors require very careful,

steady workmen, as a great element of danger exists in these

numerous joints.

5. The various natures of the buildings provided with conductors require

separate, and often different treatment: but the principle in all cases

is the same, viz., to attach the conductor closely to the fabric, and

the more the conductor is made an integral part, as it were, the more

efficacious it will be. Any attempts at so called isolation are opposed

to the theory of protection by conductors. The mechanical means of

fixing are best illustrated by diagrams, the chief objects to be

considered are—

(_e_). Permanence or strength and durability.

(_f_). Room for expansion of the conductor.

(_g_). Facility in fixing without cutting or breaking the conductor.

(_h_). Neatness in appearance.

These objects are gained by a careful consideration of the materials to

which the conductors are fixed by “holdfasts,” for stone, slate or

tiles, wood, and iron. It is important that _sharp_ bends be avoided. A

string course, for instance, should be drilled, and the rod or rope

passed straight through. Also, that any metal bodies in the line of the

conductor should be connected with it by staples screwed into such

bodies. It is most necessary that the ends of vane bolts or rods should

be joined to the conductor, or, where this is impossible, should be

fitted with an independent wire or rod to the earth.

6. The connection with the ground is of special importance, as the

object of the conductor is to provide a free passage between the two

currents, and if this be not done, a lateral discharge is pretty sure to

result. A building provided with suitable conductors, properly fixed,

should at all conditions of the atmosphere, allow a free course to the

electricity, and be in all its parts electrically equivalent, and with

this intention the several parts (as mentioned in answer to question 3)

are brought into connection with each other or with the ground. The

actual length of the ground conductor is fixed by the nature of the

subsoil, as it is obvious that dry sandy soil is unsuitable for a

termination. We therefore continue the rope or tape until a good damp

earth is reached, if possible, a spring or open water—generally

speaking, about 5 to 10 yards will be sufficient in most localities. The

conductor is then buried 5 to 10 feet, or upwards, in the damp earth or

water. If a rope, the several strands are unravelled and opened out: if

a rod or tape, a discharging fork is usually attached to the end to

promote the easy discharge, for which purpose it is also usual to fill

the trench with charcoal. The trench must be dug with a slight fall from

the building downward.

7. The extent of area supposed to be protected by the conductor is

estimated by many as included in a radius of double the height of the

conductor from the base line; but the immunity from accident enjoyed by

many buildings situated at a greater distance from a number of tall

factory chimneys; or to take an opposite example, in a city where there

are many lofty spires or towers, would go to show that a number of

conductors attached to tail objects, serve to obviate the dangers

arising from lightning by providing, at many different points, a direct

communication between the positive and negative currents which exist in

the clouds and earth. We have never known a church spire, when the

conductor was fixed in accordance with ordinary skill, injured by

lightning; and the tall factory chimneys of our manufacturing towns

afford strong corroborative evidence of the value of conductors, and

this in two ways—first, because those to which conductors are fixed, do

not get struck; and, second, because those unprovided with conductors,

_do_ get destroyed from time to time.

8. A reference to the answer to No. 3 question, will show that we

consider that when several terminals are used, an increased diameter is

advisable in the main or principal conductor; but it must be remembered

that either of the conductors referred to in the answer to question 2,

is greatly in excess of what many eminent electricians consider

necessary. A single wire being thought sufficient of 3/32 inch diameter

(A. 0·06 in.) for any ordinary current of electricity. But both the

English and French Governments have thought it prudent to specify a

copper body, with a sectional area of ½ inch in English, or 1 centimetre

in French (0·40 in.)—partly to provide against corrosion, which would

rapidly deteriorate a thin wire, and partly to obviate the danger of the

melting of the smaller conductor under the continued force of an

unusually strong shock of lightning. We, therefore, respectfully follow

the decision of such experts as have, by careful experiment and

considerable diligence, acquired the knowledge they possess—both as to

the substance, the form, and the treatment of this subject; and have

only to add the fact, that any small experience we have practically had,

goes to support the conclusions already arrived at by these authorities.

FREEMAN & COLLIER.

* * * * *

24 & 26, LEVER STREET, MANCHESTER.

1. Our upper terminals are made of copper or brass, plain spike or ball

with spike at top, and three radiating from it, or four or five spikes

radiating from the ball. Attached to the ball (screwed into it) is a

solid rod of copper, to which the conductor is fastened, as explained

below.

2. Conductor is made of good quality copper wire strand 7 ply: ⅜ inch

[A. 0·11 in.] to 7/16 inch [A. 0·15 in.] diameter.

4. Joints of the strand not usually permitted, as we spin it any

reasonable length.

The end of the conductor is knotted and drawn through a cup-shaped ring

of metal one end, the top of which is screwed into the bottom of the

solid rod of the terminal. This makes a good connection.

5. Copper holdfasts fasten the rod to the building.

6. Ground end is coiled loosely in damp earth or a well.

RICHARD JOHNSON, CLAPHAM, & MORRIS.

* * * * *

180, ROTTEMORE, GLASGOW.

We beg to reply to your queries on the material, system, and fitting of

lightning conductors, as practiced by us for over 25 years, during which

time we have never had a building injured in which we have been engaged,

and have fitted from 15,000 to 20,000 feet a year, without

advertisement.

1. Uniformly solid copper, consisting of 1 centre concave point, about

14 inches long, presenting 8 sharp angles = 3½ inch surface; this is

surrounded by 4 smaller points of same construction. These all terminate

or spring out of a hollow copper ball, which is screwed on a copper tube

¾ inch diameter inside, and from 4 inches to 5 inches long, according to

requirement. The copper cable is passed through this tube, is knotted

inside of the ball, and the points are all screwed against it, which

forms the point of contact, and thoroughly fixes the cable at the top;

but the fixing of the top or terminal rod is fashioned in accordance

with the requirements of the building or material to be fixed to.

2. Uniformly copper cable constructed of 49 strands, _hard drawn square_

copper wire Nos. 17, 18, or 19 w.g.

3. We never use less than 6–inch surface, _i.e._, measuring the

circumference of each wire, we contending that surface is the only power

of the conductor. Up to 150 ft. we use No. 19 (= ½ inch diam.) [A. 0·20

in.], ¾ inch for a longer length of cable (_i.e._, 17 or 18) [A. 0·44

in.].

4. Usually with a gun-metal screwed coupler.

5. With brass holdfasts, lined with porcelain, glass, or guttapercha.

6. Spread out end of strands of cable like a fan, and bury it in the

moist earth a few feet deep, in an oblique way tending from building.

7. 30 to 40 yards.

8. We invariably run one cable from each terminal or top rod: but in

spires we commonly take a connection from the _bottom_ of the vane rod,

and connect it to the main conductor, which goes to the highest point of

vane or final: if the former, we fix a copper bush or disc to the vane

rod at foot of vane, which is fast to cable, and a corresponding one on

vane, with cable at highest point, when the cable is fringed out,

presenting its 49 points, and by these discs the vane revolves with that

portion of the conductor attached, and the point of contact is given by

the discs.

C. H. PENNYCOOK & CO.

* * * * *

ALL SAINTS’ WORKS, DERBY.

1. Form for upper terminals:—A straight copper tube, ¾ inch diameter;

thickness of metal, 15 B.W.G. [A. 0·15 in.], with solid copper point (no

branches); the point is soldered and rivetted into the tube; or a solid

copper rod, ½ inch diameter [A. 0·20 in.], tapering towards the top.

2. Material and dimensions of conductor:—Either a copper band of 2½

inches wide and No. 16 B.W.G. thickness [A. 0·16 in.]; or a copper wire

rope, ½ inch diameter, of 6 strands, each strand containing 6 wires [A.

0·20 in.].

3. Proportion between length and sectional area of conductor:—The ½ inch

copper rope [A. 0·20 in.], or 2½ × 16 B.W.G. band [A. 0·16 in.], is used

for heights not over 120 feet; for higher buildings, a ¾ inch rope [A.

0·44 in.] or band, 2½ × 12 B.W.G. [A. 0·27 in.] should be used.

4. Joint, how made:—Joint is made between band and copper rod with a

brass screwed socket, the rod is soldered and rivetted into socket, and

the band is soldered round socket, then soldered and rivetted. When the

copper rope is used, a hole is drilled into socket, same diameter as

rope, at the lower end, and turned out conical shape; the rope is then

passed through the socket, the ends spread out, and the spaces filled up

with solder.

5. Attachment to building:—The conductor is fixed close to building

_without_ insulators, and is brought into close contact with the

spouting; is closely attached to chimney and walls by means of copper

straps and copper nails driven into the masonry.

6. Ground connection:—Should a good, permanent drain be near, the

conductor is brought to it and bound round and firmly fixed.

If there should be an open drain or brook, the conductor is brought

under it at _sufficient_ depth that if the stream be dry at any time

there will be sufficient moisture to carry away the charge without

disruption. Should there be neither drain pipes nor brook sufficiently

near, the conductor is taken from 12 to 20 feet below the surface to the

clay, where it is certain to be always damp, even in seasons of the

greatest drought ever known.

In no case should the earth connection be taken into a closed tank or

well.

If a band be used, it should be cut into strips about 18 inches long and

laid in different directions; rope should be unwrapped and spread in a

similar manner.

7. Supposed area protected:—It is impossible to determine exactly the

area the conductor protects. It is erroneously supposed that the rod

will protect buildings within its radius, but experience will not bear

out this axiom. Many instances may be related of buildings being struck

much within the radius of well-protected churches or chimneys.

The protection a conductor affords depends to a great extent on the

relative positions of the electric discharge and the objects that it may

meet in its course. As a general rule, a church with a high spire with a

proper conductor may be considered to protect the remainder of the

edifice; but a low, straggling building should have several conductors

at the _outside_ highest points.

8. If there is more than one terminal is the size of conductor

increased?—No; as sufficient material should always be used to carry off

without disruption the heaviest known charge, it is unnecessary to

increase the size of conductor. Should two or more upper terminals be

connected with the main conductor, the size of material need not be

increased; for if two or more terminals receive the charge

simultaneously it necessarily follows that it is sub-divided; therefore

the conductor will have no more work than if one point only had been

struck.

_Note._—We quite agree with Snow Harris regarding insulators, that if

there be anything in insulators they are a disadvantage, for if the

building be struck in any other part than the conductor, the current

cannot easily find its way to the conductor. The current will take the

line of least resistance; therefore it is reasonable to assume that the

building is more certain to escape the disruptive force of lighting when

the conductor is in close proximity with the building.

JOHN DAVIS & SON.

* * * * *

BIGG MARKET, NEWCASTLE-ON-TYNE.

1. For upper terminals I generally use ½ inch diameter solid copper rod

[A. 0·20 in.], or ¾ inch diameter tube [A. 0·24] with four points, and I

fix them 4 or 6 feet above the building they are intended to protect. I

always endeavour to get the upper terminal as near the size of the

conductor as is consistent with strength. I make my points of the best

copper tipped with platinum.

2. For the conductor I use ½ inch diameter copper wire rope [A. 0·20

in.], which is (in my opinion) the best and most applicable conductor

used, as it appears to be an open question, at present, whether it is

surface or mass which conducts. If it is mass, then a tube conductor is

insufficient. If it is surface, then a solid rod is superfluous. The

copper tape conductor I consider the worst form of any, as it bends too

easily round sharp corners, projections, &c., of buildings, which is a

thing to be avoided as much as possible. A conductor should be brought

to earth as direct as possible, and with no bends if they can be

avoided. The copper wire rope conductor has both surface and mass

conduction, and can be led about roofs and other difficult places better

than any other form of conductor that I know of.

3. None; I imagine it is not necessary.

4. I avoid joints as much as possible; but, when they must be made, I

scrape the ends of my wire bright, and then splice or interlace them

together, covering the whole with thin sheet lead—I object to solder, as

I think it must interfere with surface conduction; the wire is fastened

to the upper terminal, with a Matthew Walker knot let into a hollow cup,

and the terminal screwed down on it.

5. I attach my wire to the building with a brass or gun-metal holdfast 4

inches long, having a ⅝ hole, the inner edge being flush with the wall

of the building, so as to allow the conductor to touch the wall of the

building all the way up, and still allow plenty of room for the free

passage of the electric fluid. I do not approve of insulators, nor yet

of that kind of holdfast that is driven in tight on to the wire, for I

think that must interfere with the clear passage of the electric fluid.

6. I cut a trench some 15 or 20 feet long, gradually deepening from 1

foot at the commencement to 4 ft. at the termination, which I fill with

pounded charcoal and bury the wire in it. Earth-plates are not necessary

when this is done.

7. It is calculated that a conductor will protect a surface in the shape

of a cone, the diameter of the base of which is equal to the height of

the conductor. Thus, if a conductor were 100 feet high, the space

protected would be represented by a straight line drawn from a radius of

50 feet from the base of conductor, to a radius of 8 or 10 feet from its

highest point.

8. I consider, if there are two terminals, there should also be two

wires, or the wire should be of sufficient capacity to carry off a

double charge, in case both terminals should be struck at one time. I

think the conductors should certainly be of sufficient capacity to carry

off any charge that might be received by the terminals, be they few or

many.

T. MASSINGHAM.

APPENDIX B.

ANALYSIS OF, AND REMARKS UPON,

THE VIEWS OF MANUFACTURERS.

On Nov. 14th, 1878, a circular was issued to the principal lightning-rod

manufacturers in this country, inviting their replies to various

questions that were submitted to them, and also any remarks that they

might wish to lay before the Conference.

Replies have been received from—

Messrs. WILKINS & WEATHERBY, of London.

Messrs. GRAY & SON, of London.

Messrs. F. RUSSELL & CO., of London.

Messrs. JOHNSON, CLAPHAM, & MORRIS, of Manchester.

Messrs. FREEMAN & COLLIER, of Manchester.

Messrs. PENNYCOOK & CO., of Glasgow.

Messrs. DAVIS & SON, of Derby.

Messrs. MASSINGHAM, of Newcastle-on-Tyne.

All well-known firms, who have written fully and freely, and whose

experience is very extensive.

It is impossible to read these replies without feeling the absolute need

of such a Conference as that which has been formed, to collect facts, to

digest opinions, and to endeavour to formulate some guiding principles

for uniformity in practice—for here we have the most diverse modes of

execution detailed, the most opposite views expressed, and the most

varied experience narrated. In fact, some ideas enunciated are quite

opposed to the teachings of science. Where practice is so opposite,

error must abound: and, therefore, there must be great need for an

effort to reduce the system of constructing lightning conductors in this

country to some uniform basis. On no one single point, except in the use

of copper and the necessity for reaching damp earth, do any two

manufacturers agree in adopting similar measures.

I will take each question submitted _seriatim_.

1. _Form, dimensions, and material usually adopted for upper terminals._

There are single points and branching points, fine points and blunt

points, cones, spikes, balls with spikes on top, and balls with

radiating spikes.

The dimensions vary with each form, and they are made of solid copper

and copper tube, of brass, of iron, and of gun-metal. The ends are

sometimes silvered, sometimes gilt, and sometimes tipped with platinum.

But there is no rule or uniformity; and one manufacturer acknowledges

that, while he sometimes tips the points with platinum, he considers the

practice to be altogether superfluous.

Now it is clear that if there be any electrical efficacy in points _as

points_, they should be made in such a form, and of such a material, as

to maintain their efficiency permanently. The writer is very strongly of

opinion that the efficiency of lightning conductors is due principally

to the peculiar electrical action of their points. He sees no advantage

whatever in multiplying these points. In his opinion each conductor

should end in one fine platinum point. It would thus act as a dissipator

of the electric charge in its immediate neighbourhood, and would then

_prevent_, and not favour discharge. Moreover, points demand frequent

inspection, attention, and renewal. He thinks that one function of the

Conference should be to examine some of these points _in situ_, if

possible. At present they are erected and left to their fate.

2. _The Material and Dimensions of the Conductor._

The use of copper is almost universal, but two manufacturers

occasionally use iron. The form varies. The majority use wire rope, but

some use rods, others bands or tapes, others tubes. One firm uses a

cable “constructed of 49 strands of hard-drawn _square_ copper wire.”

Another firm uses a wire rope, simply because “it appears to be an open

question, at present, whether it is surface or mass which conducts.” The

dimensions are as varied as the form, from a wire rope ⅜th of an inch in

diameter to a copper band 3 inches wide and ⅛th thick.

The only point worthy of note is, that no one uses a smaller conductor

than a copper rope ⅜th in diameter (_i.e._ 4 oz. of copper per foot

run).

Leaving the dimensions as a question for future investigation, the

points submitted for the consideration of the Conference under this head

are—

1. Is conduction a question of surface or of mass?

2. Is copper alone to be used?

3. Is the conductor to be in the form of a rope, a rod, a tube, or a

band?

Now, on the first point the writer entertains no doubt whatever that the

conduction of atmospheric electricity is simply a question of mass, and

that the lightning protector acts simply as a conductor obeying the laws

of Ohm.

On the second point he sees no objection whatever to the use of iron,

when properly galvanized, in situations free from chemical impurities.

The reasons urged against its adoption are extremely weak. First, it is

said to decay rapidly; and, secondly, it is said to be a very much worse

conductor than copper.

The rusting of iron is almost entirely checked, in pure air, by

galvanising or coating with zinc. It is used for nearly every other

purpose in connection with building, and it is difficult to understand

why it should be discarded on account of its liability to decay for this

particular purpose, where it is always under supervision.

Again, pure copper conducts about six times better than pure iron: but

we never get pure copper in lightning conductors. Moreover, the

manufacture of iron wire for telegraphic purposes has increased so

enormously during the last two or three years, that the wire now

supplied conducts 50 per cent. better than it used to. Hence the

difference between the two in this respect is not so great as theory

indicates; and it would be well for the Conference to satisfy itself on

this point by having similar sized wires made of the two materials, and

having them measured electrically for their resistance.

But it has been pointed out by the late Mr. Brough (_Phil. Mag._, May,

1879), that by regarding (1) the influence of the rise of temperature,

(2) the difference between the specific heats, and (3) the relative

dimensions, iron conductors can be made much smaller than was formerly

supposed: and, that as iron is so much cheaper, iron rods can be made

equally efficient for a much less sum than copper. Moreover, the use of

iron enables the architect to use one kind of metal throughout his

structure, and thus avoid anywhere the contact of dissimilar metals,

which always results in decay.

On the third point, the writer is clearly of opinion that a galvanized

iron _rope_ is amply sufficient for country residences and buildings

free from chemical actions. In such places, and in towns, copper should

be used. A rope, whether of iron or copper, is easily handled, it can be

made of any size, it can be led in any direction without bends or

angles, it is neat and easily jointed, diverted, or lengthened.

The writer refrains from expressing any opinion on its dimensions here,

for this is a point that will require most careful examination by the

Conference.

3. _Is there any definite proportion between the length and sectional

area of the conductor?_

The majority of the manufacturers increase the size of the conductors

for high buildings—one making the limit 120 feet, another 150 feet,

while a third “varies the sectional area with the length.” One firm does

not consider any difference necessary, while another takes it that the

sectional area should be the same irrespective of length, for “lightning

does not vary in intensity while passing through a conductor of greater

or less length.”

Now, the laws of electricity clearly show that to maintain equal

efficiency we must vary the sectional area as we increase the length of

the conductor; but it is a question for the Conference to decide whether

we should not recommend a rope of uniform dimensions that would be

equally applicable for high and low buildings. Within ordinary limits

the necessity for increased thickness for increased height is scarcely

evident, but the remedy of an increased sectional area, with the number

of separate points erected, is very clear. Indeed, each point should be

the terminal of a conductor, whose sectional area should be uniform to

the earth. For if it be not so, and each conductor be fully charged with

electricity, then when the sectional area diminishes there will be

congestion, resulting in heat and discharge to the building. Hence the

thickness of the main conductor must increase with the number of

separate points erected.

4. _Joints, how made._

Some are rivetted, others are screwed, others are coupled by right and

left-handed screws. Tubes are socketed into each other. In one case “the

end of the conductor is knotted and drawn through a cup-shaped ring of

metal.”

There can be no doubt that joints are the greatest source of danger in

lightning conductors. If a joint be imperfect, and the conductor be

conveying a charge to earth, heat will be generated there, the conductor

may be fused and rendered useless, and the discharge will be diverted to

the building. Or the joint may be so bad—that is, its resistance may be

so great—that it renders the conductor practically useless, for other

parts of the building will offer easier paths to the earth. Though the

use of solder is pretty general, it is not universal. Indeed, one

manufacturer objects to it because “it must interfere with surface

conduction!” It certainly should be imperatively used. No joint can

possibly be perfect that is not metallically continuous. Careful

soldering is the only certain mode of securing this, and that this is

practicable is evident from the millions of perfect joints in telegraph

wires. To scrape the ends of wire bright, and cover the whole with thin

sheet lead, as is done by one firm, is simply to court danger. The

absence of joints in wire rope is one great element in its favour.

5. _Attachment to building, how made._

Some attach the conductor to the building by copper straps and nails;

some use holdfasts, either of copper wire or gun metal; others use

staples; one uses metallic ties. Several pass the conductor through

insulators of glass, porcelain, or earthenware. But the majority discard

insulators as useless.

In the opinion of the writer they are quite right, for it is difficult

to understand what useful function the insulator performs. One fact that

occurred in 1837 is given as a reason for their use, but the fact

militates against the efficiency of the conductor rather than the

absence of insulators. If the conductor were perfect there could have

been no concussion at the point of attachment. If it were imperfect

there may have been, for the discharge would seek other paths to earth.

Some manufacturers use holdfasts of a different metal to that of the

conductor. This is wrong, for where different metals are used galvanic

action sets in, tending to decay and rupture. The attachments for this

reason should always be of the same metal as the conductor.

6. _Ground connection, how formed, and of what extent._

The necessity for reaching moist ground is generally recognised, but

various curious ways for making earth connection are suggested. One firm

considers that a band cut into strips 18 inches long would suffice,

while another says that not less than 30 feet, in two or three branches,

with fork at the end of each band, should be used. One firm is very

brief: “Ground end is coiled loosely in damp earth or a well.” The use

of coke, powdered charcoal, or carbonaceous materials, is insisted upon

by others.

It is questionable whether the difficulty of fitting a good connection

with the earth is fully realized. None but telegraphists know the great

difficulty there is in doing this. The first object to be secured is a

good damp soil, and the next as large a conducting surface as possible.

Metal pumps, iron, gas, or water pipes, wells in which plates of metal 2

or 3 feet square are placed, or similar plates may be buried in

perpetually damp ground, or in holes well filled with powdered coke.

Moisture in some form is essential, and without it a lightning protector

is of small service.

7. _Extent of area supposed to be protected._

The majority of the firms consider that the area protected has a radius

equal to the height of the conductor; but one firm considers that this

should be multiplied by five or six times; while another asserts, “that

no appreciable extent is protected by a single rod conductor;” and

another, that “many instances may be related of buildings being struck

much within the radius of well protected churches or chimneys.”

We have no experience at present to enable us to form a definite opinion

on this point. The Committee of the French Academy, gave the radius as

equal to twice the height of the conductor from the ground, but

buildings have undoubtedly been injured within this limit. The writer

does not think that a greater radius than the height should be taken:

but thinks that this is one of the most important questions that the

Conference could determine. Calculation might, to a certain extent,

settle the point: but it is more a case for experience.

8. _If there is more than one terminal, is the size of the conductor

increased?_

This question has been partially considered. (See No. 3.)

* * * * *

Some firms do not consider any increase necessary: others think that

when two or more terminals are used, the main rope should be somewhat

enlarged; while others run one cable from each terminal, or make the

conductor of sufficient capacity to carry off the double charge.

The writer considers that every conductor should be complete in itself:

or, if this is inconvenient, then the size of the main conductor should

be enlarged in proportion. It does not at all follow, as one firm

implies, that if two or more terminals receive the charge

simultaneously, it is necessarily sub-divided. Each charge may be full

and complete in itself, and be sufficient to fill the wire; and,

therefore, if the main conductor be not increased, accident may result.

* * * * *

There is no doubt whatever that great consideration should always be

given to the lessons of experience, and the opinions of those who have

made the erection of lightning conductors for 35 years their especial

practical study, are much entitled to weight; but such practice may have

originally been based on error, and the teachings may not have been

guided by science. Where such variety of practice abounds, there must be

fallacy somewhere, and, therefore, danger; and not the least of the

beneficial labours of the Conference will be to point out to these

different practical men, where their faults and their departures from

truth exist.

W. H. PREECE.

_August 8th, 1879._

APPENDIX C.

REPLY FROM MANUFACTURERS, RECEIVED AFTER THE COMPLETION OF THE ANALYSIS

WHICH FORMS APPENDIX B.

FARADAY STEAM WORKS,

ST. JOHN’S ROAD, HUDDERSFIELD.

_11th November, 1879._

SIR,

Enclosed we have pleasure in handing you our replies to the eight

questions which you ask lightning rod manufacturers and erectors,

together with three tracings, showing our system of protection under

different conditions. In the case of Nottingham Castle we considered

it necessary, on account of the rock on which the castle was built,

to adopt an extensive system of lateral points in earth termination,

by running all the main conductors from the building down the

shrubbery into the moat, where we formed the flat copper band into

the form of gridirons, in which several hundred feet of the copper

band has been used, and the termini of the ribs pointed, and the

whole being sunk eight feet, and two cart-loads of gas carbon laid

over each grid.

Yours obediently,

SANDERSON & CO.

REPLIES TO THE QUESTIONS OF THE LIGHTNING-ROD CONFERENCE.

I.—Usually a length of copper tube 5 feet long 1 inch diameter × No. 8

B.W.G., which is termed the elevation rod, surmounted by a solid copper

point, forged from ⅞th of an inch round bar, wrought three parts of its

length to a square tapering point, the said elevation rod and point are

screwed together by a copper ball-shaped union, into which are screwed

four smaller points at an angle of 45 degrees. When fixing lightning

conductors on church spires and turrets we usually run the copper tape a

few inches above the vane or finial, having previously prepared and

pointed the tape; by this system all joints are avoided.

II.—We, the sole inventors, manufacture the solid copper tape lightning

conductors of the following sizes:—

Nos. │ 1 │ 2 │ 3 │ 4 │ 5 │ 21 │ 22 │ 23

│ in. │ in. │ in. │ in. │ in. │ in. │ in. │ in.

│⅝×1/12 │ ¾×⅛ │ 1×⅛ │ 1½×⅛ │ 2×⅛ │1×1/16 │1½×1/16│2×1/16

[A │ ·05 │ ·09 │ ·13 │ ·19 │ ·25 │ ·06 │ ·09 │ ·13]

and in continuous lengths up to 500 and 600 feet.

III.—Yes. For heights of say 50 feet we recommend our No. 2 (¾ in. × ⅛

in.) size; for 100 feet our No. 3 (1 in. × ⅛ in.) size; and for 200 feet

or over, our No. 4 (1½ in. × ⅛ in.) size; or our Nos. 21 (1 in. × 1/16

in.), 22 (1½ in. × 1/16 in.), or 23 (2 in. × 1/16 in.) according to

position and circumstances.

IV.—In the case of church spire or turret conductors we have no joints

whatever, as described in Answer I., but where elevation rods and points

are used we make a copper coupling, screwed at one end to receive the

elevation rod, and at the other end to receive the copper tape, which is

firmly rivetted into the coupling, and thence soldered or brazed. But

when a complete system is employed with branches or tributaries, running

from several points on to the main conductors, we make the joint by

means of copper rivets, and then solder.

V.—By means of gun metal clips, or holdfasts, let into the building,

which secures the copper tape in close contact with the face of the

building. Under no circumstances do we use glass, ebonite, or other

insulators.

VI.—In good moist earth 5 feet or 6 feet deep we simply run the copper

tape out from the building some 20 feet, and then rivet a copper earth

plate on to same, or sometimes employ a large gridiron made of copper

tape, using as much as 200 lineal feet in its construction. Wherever we

make earth terminations in rocky, dry, or gravelly soil, we always fill

in with a load of small coke, charcoal, or other carbonaceous matter,

and also divert the rain fall-pipe system over the termination so

formed; also, wherever possible, we connect the conductor with the gas

and water systems outside the building. In all cases of earth

terminations, the size of earth-plate is in proportion to the size of

conductor employed, and other circumstances.

VII.—We are unable to come to any conclusion as to any definite area

which one lightning conductor will effectively protect, and no two

writers appear to agree on the subject; but from actual practical

experience of 30 years, combined with the closest observance and

research, we are in the position to say, emphatically, that a conductor

on one prominent elevation—for example, a turret will not protect a

similar elevation, be it only 1 yard, or 50 yards distant; but that

providing that two prominent features be provided with a conductor point

on each, then on the same foundation, we say that both of them would be

effectively protected. But for the purpose of simplifying and

practically illustrating our views on this subject, we enclose you

tracings and particulars of several buildings for which we have designed

the system of lightning conductors, and which we believe to be perfect.

VIII.—Yes,—always, and in proportion to the number of extra terminals

adopted.

SANDERSON & CO.

DETAILS OF LIGHTNING CONDUCTORS APPLIED TO NOTTINGHAM CASTLE.

The following three engravings render very few verbal details necessary.

Fig. 1 gives the east elevation of the castle, it shows part of a

flag-staff 115 feet high, which has a conductor, also three of the

principal terminals, and twenty-six minor points upon the building, and

by two dotted lines the position of two of the main conductors to earth.

The principal terminals are tapered iron tubes, 13 feet long, carrying

copper tapes 1 inch × 1/16th and terminating with copper points tipped

with platinum; the minor points are of solid copper 9 inches long. The

main conductors to earth are copper tapes 2½ in. × 1/16th.

[Illustration:

FIG. 1.

]

Fig. 2 give a plan of the roof, much of which is of glass with wooden

rafters. The twelve principal terminals are shown by small rings, the

ninety-four minor points by round dots, the horizontal copper tape (2

inches × 1/16th), uniting all the upper terminals, by a pecked line, and

the position of the main conductors to earth by dotted crosses. All the

gutters are metallically connected with the conductors.

[Illustration:

FIG. 2.

]

Fig. 3 gives a general plan (for which we are indebted to the

architects, Messrs. T. C. Hine & Sons) of the castle and grounds, and

also a little section indicative of the precipitous eminence on which

the castle stands. From these it will be seen that two of the main

conductors to earth are carried underground at a depth of about 4 feet,

under the terrace and down the slope and terminate in trellis-work,

about 14 feet square, of 2½ inches × 1/16th copper tape rivetted at

every intersection. The other earth contact is obtained by bolting the

terminal on to the town water-main. The total length of tape used in the

earth connections was about 500 feet.

SANDERSON & CO.

[Illustration:

FIG. 3.

]

APPENDIX D.

REPORT OF THE REPRESENTATIVES

OF THE

ROYAL INSTITUTE OF BRITISH ARCHITECTS

TO THE

LIGHTNING ROD CONFERENCE.

The Council of the Royal Institute of British Architects sent out

upwards of 600 circulars (a copy of which follows this Report) to their

Architectural Members requesting information as to injury by lightning

to any buildings known to them.

The Council also requested the same information from their Honorary

Associates (upwards of 100 in number), who are chiefly men eminent in

the Scientific, Literary, and Artistic world.

The Council have received up to this date only 35 answers from

Architects, and 1 from the Honorary Associates.

Of these answers many are to the effect that no case of injury has

arisen to works under their direction. The remainder give 33 instances

of damage, and enter, in many cases, very fully into the details of

them.

The instances given may be roughly classified thus:—

There are 26 of buildings injured where there were no conductors.

In 9 of these the lightning did some injury to the chimneys and other

exposed parts, and was then conducted safely to the ground through the

metal gutters and rain water pipes.

In three other instances the lightning appears, from the statement of

persons in the building struck, to have dispersed and passed out by open

doors, &c.

We give no opinion as to this, but the facts are distinctly stated. In

several other cases the lightning passed off in several distinct

directions and currents.

There are 6 cases of buildings being injured although protected by

lightning conductors. In one of them (No. 14) the failure is clearly

explained by the fact that the lower part of the conductor had been

stolen, leaving only two or three feet of it in the ground. The

lightning in this case broke through a wall 4 feet 6 inches thick, at a

height of 6 feet from the floor to a gas pipe.

In another case (No. 3) a gable was struck, although close to a spire

and turret which had a lightning conductor.

In another (No. 7) the part struck (a chimney) was 64 feet away from a

tower, in the same building having a lightning conductor.

In No. 24 the conductor was sufficient protection until it passed at a

sharp bend round some mouldings; these it injured, but did no further

damage.

In two cases (Nos. 21 and 23) the discharge injured some gas tubing near

it, and set fire to the gas, and by its means to the building.

We beg finally to call attention to the drawings attached to No. 7 (Mr.

Colson, of Winchester), showing the injury to trees 130 feet away in a

direct line from a spire which was destroyed, it having no conductor.

T. HAYTER LEWIS, V.P.

JOHN WHICHCORD, V.P.

CIRCULAR.

LIGHTNING ROD CONFERENCE.

SIR,

I beg leave to inform you that the Council have appointed two of

their members to meet delegates from several scientific societies in

order to confer as to the best methods of protecting buildings from

lightning; and in accordance with a resolution of that conference I

have the honour to forward to you, by the desire of the Council, the

questions appended below.

I shall be much obliged if you will return me this paper, with any

answer you may be in a position to make to the questions, on or

before Monday the 20th of January, 1879; and

I remain, Sir,

Your faithful servant,

WILLIAM H. WHITE,

_Secretary_.

9, CONDUIT STREET, HANOVER STREET, W.

_19th December, 1878._

QUESTIONS.

1. Have any buildings, in the construction of which you have been

professionally engaged, or which are otherwise well known to you, been

struck by lightning?

2. If so, state briefly the damage done to them, describing their

general plan and construction by sketches or otherwise, particularly

noting the position of any metal work to roofs, pipes, &c.

3. Were the buildings furnished with lightning conductors? If so,

describe them in relation to the following heads:—

(_a_). Their materials and dimensions.

(_b_). Their attachment to building.

(_c_). Their connection with the ground.

(_d_). Their upper terminals.

(_e_). The height of conductor above chimney or other adjacent part of

the building.

(_f_). If there existed more than one conductor state the distance from

one another.

4. What was the distance of the point struck, horizontally and

vertically from the conductor?

5. Was any damage done, and if so how much, to the conductor, and in

what manner?

6. Give particulars as to any trees within a short distance of the

building struck.

* * * * *

The replies received to this Circular are too long to be printed in

full, they have therefore had to be epitomised in the following

list, and consequently cannot be given as separate answers to each

question.

The replies were all numbered consecutively, so that the numbers

omitted in the list refer to circulars returned by members who had

no information to give on the subject.

REPLIES TO CIRCULAR.

2. _St. Aubyn, J. P. Week St. Mary, North Cornwall._—The tower of this

church stands on very elevated ground, and has lofty pinnacles, three of

which have been struck at different times, on each occasion one of these

pinnacles was shattered, and had to be taken down and rebuilt. Some of

the stones are held by iron cramps, but no iron or other metal spindles.

The roof of the tower, as well as that of the church, is slate, without

spouts, and there are no lightning conductors to the building. There is

open country all round the church, and no tree of any size within a mile

of the tower.

The following detailed report was received direct from the Rev. G. H.

Hopkins, the rector of the parish:—

_An Account of the position of the Church of Week St. Mary, in the

County of Cornwall, and the effect of Lightning upon the Pinnacle

and Tower when struck for the fourth time this century on November

8th, 1878._

_Situation of the building._—The situation of the church is at the

northern angle of an extensive triangular plateau, which towards the

south is much broken by small valleys and low hills, while the high

land is for the most part moor, broken in places by cultivated

ground and small plantations. Within a quarter of a mile from the

church, on three sides, the ground commences to fall very rapidly to

a depth of 200 or 250 feet; it is three miles from, and nearly 500

feet above, the sea; to the N.W. lies Widemouth Bay, one of the very

few breaks in the cliff along the coast of North Cornwall; the

entire extent of this break is quite a mile-and-a-half; between the

Bay and the extremity of the plateau, at which the church is built,

the surface is broken by low hills, only one of which exceeds 250

feet above the sea level, and this exception is separated by one

valley from the church hill; half a mile south of the church is the

highest ground in the parish, but neither this nor any hill for

several miles exceeds in height the pinnacles of the tower. The

elevation of the building above the surrounding country can be

better understood from a local rumour that 28 churches are visible

from the battlements of the tower, and the average size of a parish

attached to each church is 6000 acres. The highest point of the

pinnacle is 90 feet above the ground.

_No mines or spring of water beneath it._—There is no evidence of

the existence of any metalliferous lode in the parish, and certainly

no such attractor of electricity lies beneath the church, nor is

there any spring of water near the foundations; but as the surface

soil is clay, the rain water has no means of flowing away, except

over the surface, and a few hours of moist weather make the soil

like a wet sponge.

_Circumstances._—The tower was struck at 6.45 a.m. on November 8th,

1878, the weather having previously been gusty, with sudden storms

of hail and rain as each heavy cloud came up from the sea: many

times during the night the downfall of hail was very violent, and it

was during one of these storms that the single electrical discharge

took place; the hailstones were considerable, both in number and

size, when the flash occurred, and they certainly commenced falling

before the shock took place.

_Brightness of the flash._—The brightness of the lightning was

intense, and I have been at some trouble to inquire into the effect

which it had upon those who saw it. I was awake, and the lightning

illuminated the room through double chintz curtains and dark-green

blinds, the windows looking away from the church, and being more

than a quarter of a mile from it; during the storm a farmer took

refuge in a closed cattle shed, 200 yards from the church, and he

spoke afterwards of his impression that he was surrounded by fire;

two farmers going to Camelford fair, were at the time waiting on the

road, a mile-and-a-half from the church, and their impression was

that they were enveloped in flame, and the flame came between them;

these experiences were given to me at different times, and were

independent evidences of individual opinion. At Holsworthy, eight

miles away, in a direct line, two ladies were attending their sick

mother, and the vividness of the lightning obscured the brightness

of the light of two candles and a paraffin lamp.

_The loudness of the thunder._—The loudness of the clap of thunder

was very great; of course it shook my house; and a neighbouring

rector, who lives three miles away, in an adjoining parish, felt the

effect of the clap to an extent which was very unusual; at

Camelford, lying W.S.W., and distant about twelve miles, with a

considerable range of hills between, the thunder was not heard; but

two miles nearer, and in the same line, it was just heard: this

latter station being on the summit of the range; at Holsworthy,

lying E.N.E., it was heard as an awful peal; at Kilkhampton, which

lies directly N., and separated by a broad broken valley, the

thunder was blamed with causing colts to break through a fence from

terror, and the distance is ten miles. I am unable to give any

further account either of the distance the thunder was heard, or of

the intensity of the light of the flash. As the wind was blowing

from the west, with a slight bearing towards north, the effect of

the wind upon the sound is evident.

_Effect upon the pinnacle._—The S.W. pinnacle (A) was struck, and

apparently the effect of the lightning was not felt upon the two

uppermost stones, namely a small cross and a truncated cone, which

supports it at the summit, both of granite. It may be remarked that

the entire facing of the tower is granite, the interior masonry

being made up of small stones of different kinds, which exceeds 3

feet in thickness, while the blocks of granite which face the tower

vary from 10 to 12 inches in thickness, and in some cases are of

immense size and weight. As soon as the current could reach that

part of the pinnacle which is made up of courses of separate stones,

the mischief commenced, and the effect was to force the stones out

all round the axis of the pinnacle, so that in the same course many

of the stones were separated by intervals of from 1 to 5 inches; one

great block, measuring 2 feet in length, was thrown right out, but

fortunately fell outside the tower walls, and left a gap in the

pinnacle opening towards that quarter from which the storm came. The

entire pinnacle was shattered, and all the courses of stones which

make it up dislocated, as well as the two courses of stones which

lie beneath it. The fierce rain storms had long ago washed away all

the mortar from between the stones which compose the outside of the

tower, and probably every shower wets the interior of the masonry;

and this was especially the case at one part where there is a

considerable leak of drainage from the roof of the tower.

[Illustration: Tower of Church of Week St. Mary, Cornwall]

_Effect upon the tower._—The course of action of the current was

from the pinnacle to this leakage, where a stream of water was

running down the wall and between the granite facing and interior

masonry; the downward course of the water was arrested by the belfry

light, and then has to fall to the masonry below the window; just

above the window a large block of granite C (outside measurement 2

feet by 14 inches), was thrown out in such a way that it hangs like

a halfopen door, the projecting edge being that which lies just

below the leakage, and standing out about 10 inches from the wall;

across the belfry window runs an horizontal iron bar, and at the

bottom of the window lies an old iron bar; the stonework beneath

this bar was much knocked about. From that spot the effect of the

lightning disappears, until it reached an immense carved granite

block D, which lies on the south side of the tower, and very near

its south-east corner; and a few feet below this the leaden gutter E

(through which part of the roof drainage is poured to the ground),

runs some feet down the wall towards the earth, but does not reach

the earth by 12 feet. The immense carved granite block is broken

into two almost equal parts by a line parallel to its vertical

edges, and the two parts are separated by quite half an inch; the

fracture of the stone is not quite straight nor clean, and the parts

of the stone do not project beyond the surface of the tower. I have

been unable to trace the course farther; it may have passed along 70

feet of leaden gutter, between the nave and south aisle (F) to the

east end of the church, or gone to ground at the base of the tower.

Three or four days later, during a very high wind, a second stone

fell from the pinnacle; this same stone had been partially thrust

out on a previous occasion in 1865. Upon examination the pinnacle

was found to be in such a precarious condition that a single blow

with a hammer on one small stone would have endangered the whole.

_Previous injuries._—On October 19th, 1843, at 10 p.m., the S.E.

pinnacle (B) was completely torn down, and two courses of stones

just beneath it were greatly damaged. The line of action of the

current was to the north-east edge of the tower, towards the leaden

gutter, between the nave and north aisle, over this it threw out a

great block of granite; from that point it passed along the leaden

gutter and across the roof at the north aisle, to a strong iron bar

running vertically down the third out of the four north windows;

this window was considerably damaged, and still bears marks of rough

usage; how it happened that two other windows near the tower, and

similarly fitted up with iron bars, were passed untouched is a

mystery; to some extent all the windows in the church were somewhat

damaged, the framework being of wood they were much shaken, and

partially separated from the masonry. This was probably caused by

the effect of the current upon the air in the building: the

direction of the damage being due to the outward pressure.

In 1812 the north-east pinnacle was struck, and also some little

time before 1688, as there is a stone engraved with that date upon

it, and the date of the tower is the close of the fifteenth century.

The dates of these misfortunes have been as follows:—

About 1688 N.E. pinnacle.

1812 N.E. pinnacle.

1843 S.E. pinnacle.

1865 S.W. pinnacle.

1878 S.W. pinnacle.

The north-west pinnacle appears to have escaped, and it stands just

over the tower stairs. The south-east pinnacle, which was struck in

1843, was at that time surmounted by a weathercock.

_There never has been a lightning conductor to any part of the

church._

One word further. I have been the holder of the benefice since the

autumn of 1876; last summer the specifications for the complete

restoration of the church, at a cost of £2000, were sent to me by

the architect; before forwarding the same to the Bishop of the

Diocese I supplied the omission of a lightning rod in the

specification.

_Meteorological Notes._—It is a noteworthy fact that on each

occasion during this century when a pinnacle has been struck, the

season has been between November and March, with _one_ electrical

discharge during the storm. It is also remarkable (an experience

founded certainly on only two summers, but during that time the rule

has been invariable) that all round the neighbourhood summer

thunderstorms may be passing in their usual fitful manner of storm

and sunshine, but immediately a summer thunderstorm passes over this

village there is a complete break in the weather for eight or ten

days.

_Rainfall._—1877: 49·11 in., 213 wet days; 1878: 48·03 in., 212 wet

days.

3. _Baker, A. J. Rosherville Church, near Gravesend._—The west gable

of the south aisle was struck by lightning, although close to the

tower and spire which were provided with a lightning conductor, and

received no injury.

5. _D. Brandon. St. Ann’s Hotel, Buxton._—In 1875 a chimney-stack

was shattered by lightning, the concussion in the flue drove fire

and smoke into the drawing-room, displaced the mantle-piece, and

broke many panes of glass. The hotel occupies half a crescent, the

stack being in the middle of the crescent. The building had no

lightning conductor, and there were no trees nearer than five or six

hundred feet.

7. _J. Colson. Twyford Moors, near Winchester._—Struck by lightning

in June, 1878. This building (of which a plan is given) was provided

with one lightning conductor fixed to the tower. The upper terminal

branched into five points, about four feet above tower roof; the

conductor, which was ⅜-inch copper wire-rope, was attached to the

upper part of the tower, with glass insulators, and in the middle

nailed to the wall through lead flashing, then carried down

rain-water pipe into cesspit. The point of the building struck by

the lightning was distant about sixty-four feet horizontally and

sixteen feet vertically from the upper terminal of the conductor.

Damage done was very slight, tiles and laths being knocked off, but

no sign of scorching. The conductor was not injured; there are no

trees near the building.

[Illustration: Plan and Elevation of Twyford Moors, Winchester]

C Conductor.

* Point struck.

P Rain-water pipes attached to iron gutters.

7_a_. _St. James’ Church, West End, Hants._—Struck by lightning at 5

p.m., on June 12th, 1875. The church stands on the top of a hill

with many trees near, it is built of brick with a lead ridge to

roof, iron and lead gutters, iron rain-water pipes P, and two iron

chimneys. The spire is of brick, with stone angles fixed by iron

cramps; the spire was finished by an iron bar at the top, but was

not provided with a lightning conductor. The damage done to the

spire was considerable, as shewn in the engraving, making it

necessary to pull it down, but the tower was not injured. Stones

from the spire were thrown through the trees at B, which are 126

feet distant from the church, cutting off some of the boughs. The

tree at A was untouched.

[Illustration:

St. James Church, West End, Hants.

]

12. _T. Hawksley._ Several Steam Chimneys not provided with

lightning conductors; upper portions knocked down, chimney split or

often skinned by the lightning, _i.e._, the four and a half inches

of brickwork taken off; details not given. Now uses Gray’s system of

lightning conductors for such buildings, which is found successful.

13. _A. Hill._ In South Africa houses are generally roofed with

corrugated iron, and protected from lightning by planting a circle

of high trees round them.

14. _G. J. Hine. All Saints’ Church, Nottingham._—Struck about

twelve years ago; tower and spire 150 feet high, with one conductor

of half-inch copper wire-rope, with platinum terminal, and secured

by insulated brackets, but earth contact only two feet long at time

of accident the rest having been stolen. The lightning passed down

the conductor till within six feet from the ground, where it passed

through a wall of solid masonry four feet six inches thick,

displacing some of the stones, to an inch-iron gas pipe inside the

church. In passing off along the gas pipes under the floor, it so

far disarranged them as to cause a considerable leakage of gas,

which was set fire to by a candle some hours after the accident and

exploded. There were no trees, only a few shrubs near.

16. _J. Jerman. Alphington Church, near Exeter._—Tower struck about

March, 1828; the church had no lightning conductor. The tower was

rent through the masonry vertically, damaging parapet and ungearing

and injuring bells, which were being rung at the time; one ringer

was killed, and some of the others had the heel-plates melted off

their boots. There are few trees of any size near the tower, which

surmounts all adjacent buildings; it had pinnacles and a weathercock

on the top, and a lead roof with spouts, no down pipe. Very few

casualties from lightning occur in Devonshire.

18. _E. J. Law._—The tower, surmounted by a cast iron vane, of a

house built under my superintendence, was struck; the slates

stripped from the roof, and the charge apparently escaped down the

rain-water pipe; it divided, however, and passed to an adjoining

ridge, chipped a piece off the iron cresting and hurled it some

twenty yards from the building. Lightning conductor ordered, but not

erected; cast iron ridges to all the roofs. Large infirmary within

two hundred yards and high church tower within three hundred yards,

and houses nearer, of equal height to the one struck, and with cast

iron crestings, none of these were injured.

18_a_. _St. Sepulchre’s Church, Northampton._—Vane on top of spire

struck by lightning, passed down the rod, then to frame of one of

the spire windows, and thence to clock face, from clock face it

passed down the gas pipe, leaving no further trace.

19. _T. Hayter Lewis. Lewisham, 1872._—Zinc chimney of house struck;

lightning went down flue A, thence to a gasalier (glass) B, broke it

to pieces and passed harmlessly to the other end of the house where

the pipe ended at C, broke through a partition there and the window

D, and passed down the rain-water pipe E to the earth.

[Illustration:

SECTION.

]

19_a_. _Wandsworth, 1875._—Chimney of house struck and damaged as

shown in sketch, lightning then passed along eaves gutter F, and

down the iron water-pipe G, doing no further injury.

[Illustration:

PLAN AND ELEVATION. PLAN.

]

19_b_. _Addiscombe, 1878._—Chimney struck above H, the lightning

passed down flue, slightly injured the chimney-pieces, and

apparently passed through the two open doors to the road, as the

tenant standing at J distinctly felt a shock.

19_c_. _Forest Hill._—Chimney (K) struck, lightning followed gutters

shown by dotted line in sketch, part no doubt escaped by pipe L, but

some passed along gutter to M doing slight injury to brickwork

there, the window N was broken, and the gilt bead under cornice in

rooms K and O was blackened.

[Illustration:

PLAN AND ELEVATION.

]

19_d_. _University College, London._—A chimney has been struck on

two occasions, but little damage done; the lightning passed off by

gutters and rain pipes which enter the drains; the top of the dome,

which is of stone, has escaped.

21. _J. Murgatroyd. St. Mary’s, Crumpsall, near Manchester._—A

lightning conductor from spire touched the eaves gutter, and a gas

pipe touched the end of this gutter. The lightning passed from the

conductor along the gutter to the gas pipe, melted it, and set the

church on fire by igniting the gas.

22. _T. Oliver._—Never had a building damaged during thirty years

practice; uses ½ inch copper rope for lightning conductors, in

contact with any iron work near, and buried 8 feet in ground in

ashes.

23. _Wyatt Papworth._—Tall spire struck. The church stands in an

open position with no large trees near. It was provided with an iron

lightning conductor ¾ in. diam., fixed with iron holdfasts, and

carried down inside the spire and tower into ground; the top of it

was said to be attached to a bold copper finial on the spire about

150 feet from the ground, and 50 feet above ridge of roof; the

lightning is supposed to have first struck the finial, it slightly

deranged some beds of masonry in upper part of spire, then descended

by iron rod to belfry, melted a gas tube in the floor, and set fire

to the belfry by igniting the gas.

23_a_. House in country road. The lightning struck chimney-pot,

descended flue to fire-grate and there divided, one part passed to

fire-grate below and damaged the gasalier, another part destroyed a

box of clothes near grate, then passed out of door into another

room, struck the grate and passed into room below doing no further

damage.

23_b_. Another house situated at the corner of country road with

high trees near, lightning followed bell wires, stripping paper, &c.

23_c_. At a third house, chimney pot struck, shaft and eaves gutters

damaged.

24. _J. L. Pearson._—Weathercock of a tall spire in an exposed

situation struck.—There was a wire rope conductor attached to the

bar carrying the vane and passing down inside the spire and out at

the belfry window, the bells being connected with it; it was

attached to the tower by ordinary metal hooks, and was carried 6 or

8 feet into the ground, and about 10 feet from the base of the

tower, the strands being spread out. The conductor was bent about

very awkwardly under copings, and in some places, at right angles,

the damage was very slight, and was limited to projections of

mouldings close to a bend in the conductor about 20 feet above

ground. The conductor itself was uninjured. Some insignificant trees

100 yards distant.

26. _E. C. Robins. St. Matthias’s Church, Brixton._—No conductor,

although the church had previously been struck. I have now put one

up, leading its lower end into a cistern of water. The portland

stone terminal cross was shattered, and the stones of the cornice of

the two topmost stages were displaced.

28. _H. S. Snell. The Holborn Union Infirmary, Upper Holloway, in

course of erection._—Conductor not fixed. Apex of tower roof, 160

feet from ground, having only roof timbers, some lead-work A at

apex, and vane (gilded iron) fixed. The damage commenced just below

lead-work on apex, and three out of four hips were much torn and

shattered, necessitating taking down and rebuilding; the hips were

each framed in three sections, bolted together with iron bolts, and

in nearly every case the bolts seem to have specially attracted the

fluid causing slight charring. One of the dormer windows B was also

separated from the spire. The fluid appeared eventually to have been

attracted by the water-pipes, which rise to top story of building,

and so passed away. It will be noted as peculiar that the iron vane

was not touched, and that the damage commenced immediately below it.

[The damage evidently occurred _only_ where the conducting materials

were absent, the iron vane and the lead would naturally bear no

trace of injury.—ED.] No trees nearer than 150 feet, and these much

below the top of tower.

[Illustration: View of Tower of Holborn Union Infirmary, Holloway]

32. _J. B. M. Withers._ Detached house, near Sheffield, in course of

construction.—No conductor; the top of a chimney fifty-two feet six

inches above the ground was struck and deranged but not thrown down.

The nearest ironwork was an ordinary cast gutter, twenty feet from

the top of the chimney. No trees within sixty yards of the building.

34. _G. Wrottesley (Col. R.E.)._ Chimney shaft of a laundry at the

Barracks at Gravesend.—No conductor. The chimney shaft, forty feet

high, was entirely destroyed by a heavy charge of electricity as low

down as the eaves of the building—at this point iron gutters went

round the building and outside the chimney shaft, and the charge

passed harmlessly away to the earth by the rain water pipes P. Not a

brick was left in place above and not one disturbed below the

gutter; the shaft appeared as if cut off by a knife at this point.

No trees within 100 or 150 yards. The disruptive force was so great

that the bricks were scattered over a radius of 200 feet, and the

slate roof was riddled like a colander by the brickbats.

[Illustration:

ELEVATION AND PLAN.

]

36. _E. N. Clifton. Bethnal Green_—A four-roomed house, one of a

row, with a V shaped roof, was cut in two by lightning; a fissure

was made in the front and back walls, and also in the middle plaster

partition. The fluid entered the house between the front windows and

passed through the partition and back wall, rather to the side of an

iron pipe at the back which was the only metal near. No trees in the

neighbourhood.

APPENDIX E.

PARTICULARS OF ACCIDENTS BY LIGHTNING COLLECTED IN THE YEARS 1857, 1858

AND 1859 BY MR. SYMONS, AND REPORT UPON THE SAME BY PROF. W. E. AYRTON.

_Selected accidents._

I.

About a quarter past ten p.m. on Aug. 14, 1857, an occurrence took place

at the Brick-lane station of the Chartered Gas Company, St. Luke’s,

which caused some alarm. It appears that the lightning struck one of the

iron columns which supported one side of a gasometer, or gas holder,

situate on the right hand side of the yard. Owing to the column having

been thus struck by lightning, the gas, comprising many hundred thousand

feet, became ignited. Fortunately, the services of the firemen were not

required, for, owing to the admirable directions given by Mr. Upward,

the superintendent of the works, and the exertions of the men under him,

the flames were subdued in a comparatively short period. Fortunately no

person was injured, and no damage was done to any of the surrounding

property.

II.

At half-past eleven on Aug. 14, 1857, there was a terrific discharge of

lightning, by which the south-east pinnacle of St. Michael’s Church,

Stamford, was instantaneously struck down. The Church of St. Michael is

a modern structure, erected in 1832. It is situate in the centre of the

town. The south-east pinnacle, which received the electric fluid, was

composed of a mass of masonry, weighing about fifteen hundred weight;

the iron clamps or ties by which the work was bound together served as

partial conductors. At every break in their arrangement a series of

disruptive discharges of the electric fluid took place in lateral

directions, driving out large masses of the stonework, spreading them

over the roof of the nave and churchyard, doing considerable damage to

the roofing and tombstones. The effect of the fluid when it reached the

base of the pinnacle, from not meeting with a ready conducting medium,

was to uplift the whole mass imparting to it at the same time a kind of

circular motion to the southward, the apex of the pinnacle falling in a

line with its original base; and the base having traversed about the

eighth part of the circle, fell into the roof of the tower. Immediately

at the base of the pinnacle there is a three-inch iron spout or tube

erected to convey the water from the tower roof. This iron tube the

electric fluid entered, and, finding through it an unopposed channel,

passed down the tower, and finally into the earth, without doing more

damage. The iron tube or spouting in this instance, and by mere

accident, acted the part of a lightning conductor, and served to protect

the other parts of the tower from most serious injury, if not entire

destruction.

III.

At Walthamstow, at 7.30 a.m., on June 5th, 1858, the flag staff of the

church was shivered, the gutters were torn up, the robing room and

various parts of the exterior injured, and the gas pipes torn open.

IV.

_Effects of lightning on a chimney stalk 240 feet high._—Facts collected

by Alexander Cruickshank, 28th June, 1859:

During the thunder storm at Aberdeen, between 8 and 9 a.m., 26th June,

1859, the lightning struck Messrs. Richard & Co’s chimney, 240 feet

high, at Rubislaw, Bleachfield, one mile west of the city. At the height

of 120 to 140 feet three patches of surface bricks were torn off. By the

aid of a telescope and knowing the size of the bricks and the thickness

of the mortar between them, the two largest patches of denuded bricks

were 7 feet by 3 feet and 4½ feet by 3 feet—the longest measurements are

vertical. These patches were visible to the naked eye at least two miles

off. The parts denuded were 4½ inches thick, or the breadth of a brick

when placed with its largest surface horizontal and its sides external

and internal. Every fourth layer, however, of the bricks have their ends

placed external and internal with respect to the axis of the chimney,

and these bricks are broken across at the depth of 4½ inches, or midway

between their internal and external ends, the latter being at the

surface of the chimney. Thus three-fourths of the bricks of the denuded

patches were torn off through the lime seam parallel to the surface of

the chimney, while a fourth of the number has been broken across in the

same vertical plane. Another portion of the surface bricks, 10 feet

(vertical) by 3 feet, has not been entirely detached from the side of

the chimney but forms a bulging of 1 foot at its greatest projection,

and is visible in profile half a mile off. The lightning on striking the

chimney appeared like a cricket ball, of the brightness of iron at a

white heat. This instantaneously passed into a bluish flame a little

darker than that of common salt when thrown on the fire. A momentary

flicker and a hard crack were perceived. The lightning seems to have

struck the chimney 20 feet above the uttermost denuded patch at a small

abraded spot occupying a few bricks, and reddish when seen from the

ground. The chimney has no lightning conductor and the damage done has

not affected its stability and draught.

_Additional remarks_, by Alexander D. Milne, chemist, of Rubislaw Works.

6th December, 1859.—Half the lower bulging part, where the force of the

electric fluid seems to have become diffused or spent, fell during the

gale of 3rd and 4th December. The 3rd inst. had been frosty, followed by

thaw, rain, and wind from S.W. The part newly exposed is 10 feet in

vertical height and 2 feet across, and the first mortar joint forms also

the plane of separation, the radial bricks being cut right across. The

lower edge of the patch is 100 feet from the ground, and the four

patches extend upwards in an irregular line for 40 feet, not vertically,

but in a spiral of about one-third round the circumference of the

chimney. The abraded spot through which the fluid seems to have

penetrated is 20 feet farther up in the same oblique direction. It seems

to be about 6 inches in diameter, and the part appears as if broken by a

hammer from the outside, instead of being forced out from within, as in

the denuded parts below. We may form a conception of the immense

disruptive force exercised, thus: 105 bricks are torn off, area of each

14⅞ths square inches; total area, 1562 square inches. Force or dead

weight required to tear asunder: 1 square inch of brick has been found

to be 300 lbs. Total disruptive force 468,600 lbs., or 209 tons, and

this on the bricks cut across alone. In addition we have a mortar joint

three times the above area, which at a moderate estimate of one-third

the strength, or 100 lbs. per square inch, gives 209 tons more, or 418

tons in all, the approximate dead weight required to tear off what has

fallen. Allowing for what is damaged but has not fallen, the electric

fluid must have had a momentary disruptive force of 500 tons.

V.

_Gloucester, July 2nd, 1859._—Two clumps of objects were struck, two elm

trees in the Spa walks and Rycroft Chapel—with the adjoining elm. This

shows the lightning to have been forked, as they were both struck at the

same time, and there was a double explosion of thunder; the extremities

of the fork were 1480 feet from each other. The trees in the Spa

standing close to each other were stripped from a great height, of six

or seven inches width of bark, which, with the branches, was strewed to

the distance of several yards. The elm at California had a large bough

struck off; the lightning then ran along another branch, struck the

stone edging of the roof of the chapel, scorching the end of the bough

and chipping great pieces off the stone; it then ran along the metallic

gutter to the end of the roof near the schoolroom, where it descended

the iron spouting to the ground, bursting the spouting at the joints,

where it was a quarter of an inch thick, and in one place knocked a hole

in the wall ten inches deep, as if some superior conductor had attracted

it inside.

VI.

I delayed answering your note until I could give you a correct

description of the damage done to the chimney by examination from the

scaffolding (which we were erecting at the time of its receipt.)

The chimney is a portion of some additions made to my manure works only

last November. It was struck during a fearful thunderstorm on Tuesday

the 19th of July, about three o’clock in the afternoon. The electric

fluid detached about one-third of the topmost stonework, which fell with

great violence through the roof of the buildings below; it then

displaced and passed through the joints of the remainder of the

stonework to the brick shaft. This octagonal brick shaft it split and

shattered in all directions on three of its sides, for a space of about

twenty-five feet, completely detaching portions of the brickwork several

feet in length, both inside and out; after which it split the remainder

of the shaft asunder in a straight line through a further space of about

fifteen feet to the stone base. This stone base it also displaced

(passing through the joinings,) and through seven feet more solid

brickwork, to an open ventilator placed under the roof of a building at

the foot of the chimney.

Through the ventilator a portion of the electric fluid seems to have

escaped from the chimney into the interior of a large warehouse, some of

the main timbers of the roof of which it has split and shattered very

much. A portion only of the fluid seems to have escaped in this way, as

the chimney is split below the ventilator for a further space of about

ten feet.

Several persons were at work in the warehouse at the time, none of whom

were injured in any way (although they felt benumbed.) Two strong horses

standing in a cart were, however, struck down by the lightning on its

escape from the warehouse.

The greater portion of the chimney must come down; in fact, we are now

taking it down.

JOHN STERRIKER.

Driffield, _August 8th, 1859_.

P.S.—In the construction of the chimney, hoop iron was imbedded in the

body of the brickwork every five or six courses, to bind it together;

and this, I think, prevented the whole of the upper shaft from being

thrown down, although in many places the iron has been completely fused.

The total height of the chimney was 85 feet.

_Extract from Mr. Symons’s report on Thunderstorms in 1857–58 and 1859._

[Read at the Oxford Meeting of the British Association, 1860.]

_Lightning Conductors._—No building provided with a conductor is

recorded to have been injured during the three years; in a few cases

bars or pipes of metal acted as such, so far as they extended. The first

instance was at Wibsey School, where the charge, which killed one boy

and injured eight others, had passed safely down an iron pendant from

the roof—in fact, an iron rod of, I believe, small diameter.

In the case of a house in Camden Square, the charge which overturned one

end of a stack of chimneys, passed safely down the iron water-pipe at

the back of the house.

The flash which injured Ryecroft Chapel, Gloucester, first struck an

elm-tree close to the chapel and broke off a large bough, it then darted

to the roof, ran along the metallic gutter to the end of the roof, where

it descended the iron spouting to the ground, bursting the spouting at

the joints, where it was a quarter of an inch thick, and in one place

knocked a hole in the wall ten inches deep, as if some superior

conductor had attracted it inside.

I presume few persons will now oppose the results obtained by the

elaborate investigations of Sir W. Snow Harris, either as to the

_utility_ of conductors, or their best form and distribution. These

points being admitted, it remains to ascertain why they are not more

generally used—why, in short, the accidents I have enumerated (with,

perhaps, as many more of which I have not heard) are allowed to

occur—that they are preventible there is no reasonable doubt. I believe

that the reason that conductors are so comparatively seldom used may be

expressed by one word—expense; a remark made by Professor W. Thomson, at

the Aberdeen meeting, was a strong illustration of this point, “If I

urge our manufacturers to put up lightning conductors they say, ‘It is

cheaper to insure than to put up conductors.’”

But as no insurance nor ought else can compensate for loss of life, it

becomes important to consider if any cheap and effectual substitute for

a regular conductor can be found.

One plan for effecting this, as far as private dwellings are concerned,

is that of connecting the lead gutters of the roof with the rain water

pipe, and with a rod projecting a few feet above the chimneys; it is

obvious that both gutters and pipe would derive additional conducting

power from the water which (at such times as the conductor is required)

is usually flowing along them.

I am not sufficiently acquainted with the laws of electric action to

offer an opinion on this plan; as far as my own limited experience goes,

I think it would be decidedly better than the entire neglect which now

so largely prevails, for it would probably induce the shock to pass down

the outside of the house instead of down the chimney inside, which has

hitherto been its most frequent course.

I much wish that those who have turned their attention to electric

action would express a decided opinion on the matter. In one of the

foregoing cases the iron pipe was perfectly competent and effectual in

conveying the charge; and in the other the damage (limited, be it

remembered, to bursting the joints) doubtless arose from the

intervention of the _lead_ between the two lengths of pipe—considering

the somewhat low conducting power of the lead, such a result might

almost have been anticipated.

_Kind of Trees Struck._—In sixteen cases the class of tree struck has

been mentioned; of these one-third were elms. The next in order of this

unenviable distinction are the oak, ash, and poplar; instances also

occurred of the crab, the lime, and the willow being injured by

lightning.

It is satisfactory to find that as far as so short a series is

competent, it corroborates previous opinions on the subject. I may

perhaps be permitted to quote one of the earliest with which I am

acquainted. In the year 1787 Mr. Hugh Maxwell wrote to the American

Academy that he thought he might state from his own experience that the

elm, chestnut, oak, and pine, are _often_; ash _rarely_; and beech,

birch, and maple _never_ struck.

A communication with which I have been favoured by Mr. Ingram, of

Belvoir Castle, bears closely on this subject, and is, I think, worthy

of consideration. He says, “I filed your letter, resolving to keep a

sharp look out in my rides about the neighbourhood for all the

thunder-blasted trees. It is of course difficult to obtain perfectly

accurate information, because trees are taken away after their

destruction; but I have ascertained that within the area of Croxton

Park, twenty per cent. of the trees (oaks) have been struck by

lightning. The park is situated on high ground; the substratum is rock

(limestone), which has more or less iron in it. The oaks, where the soil

is strongly ferruginous, are useless as timber trees; the wood, when

sawn, splits and rives in every direction, possibly from the quantity of

iron.”

* * * * *

The accounts given in the notes supplied to me by Mr. Symons are of

great interest, but as the majority of the buildings struck had no

lightning rods the details of the destructions do not bear

immediately on the object of our Conference. There are, however,

some few facts which may probably be of interest.

1.—_Damp air although not a conductor for ordinary electricity (see the

writings of Sir Wm. Thomson) may be a conductor for lightning_:—

For there are many instances of sheep and horses being killed in open

fields. This may have been due to the sheep collecting together in a

flock, and the air above them becoming moist from the perspiration

arising from the flock.

2.—_Certain coincidences of earthquake waves and atmospheric electrical

storms have been observed._—The following may, perhaps, be one:—

June 5th, 1858.—During thunderstorm at Pegwell Bay the water in the Bay,

the tide being then about two hours past flood, suddenly receded about

200 yards, and returned to its former position within the space of about

twenty minutes.

3.—_Open doors allow lightning to pass through._

August 12th, 1858, Bedford.—The lightning passed through five open doors

in its way from a chimney, which was originally struck, to an open

window, by which it went out, all the doors being on the ground floor.

4.—_Difficulty of making lightning conductors to protect buildings._

August 18th, 1858. Neighbourhood of Norwich—A boy riding on a pony

escaped unhurt, while the pony was killed by lightning.

St. Peter’s Church, Brighton.—The tower was provided with a lightning

conductor, but it was only carried up one of the pinnacles, hence one of

the other pinnacles of the tower was struck—the distance between the

pinnacles being scarcely ten feet.

Sometimes trees are struck in the middle, and not at the top.

New Kent Road.—While a man was sawing wood, the lightning entered by the

window, struck the blade of the saw, burnt the handle, but did not

injure the man.

5. _A small body perfectly insulated from the ground is not safe from

lightning._

October 11th, 1858. Kilham, Yorkshire.—Two sea gulls, while flying, were

killed by lightning.

6. _Advantages of lightning conductors._

During 1857, –58, –59 almost the whole of the buildings reported as

damaged by lightning were unprovided with lightning conductors. Among

those struck but not damaged were buildings on which metal bars or pipes

acted as conductors as far as they went, proved by the lightning having

burst the metallic spouting at the joints.

7. _Expense of Conductors._

Sir W. Snow Harris’ rule:—

Copper solid 0·5 in. in diameter

tube 1·5 in. in diameter ¼ in. thick.

Iron solid 0·75 in. in diameter

tube 2·00 in. in diameter ¼ in. thick.

Minimum cost one shilling per foot, not including cost of carriage and

fixing.

* * * * *

Sir William Thomson, at the meeting of the British Association at

Aberdeen, said “If I urge on Glasgow manufacturers to put up lightning

conductors they say it is cheaper to insure than to do so.”

This shows the importance of economy in the construction of conductors,

and consequently of the determination of the least expensive conductor,

which will be safe for any special building. One of the most important

points to determine, it appears to me, is whether an electric current,

when the electro motive force is very high, passes along the surface or

through the body of a conductor, since on the result of this must depend

whether we give a lightning conductor large surface, or large sectional

area—in fact, whether a tube of large diameter, but with comparatively

thin walls, is better than a solid rod of much smaller diameter.

In the May number for this year of the Philosophical Magazine, there

appeared an interesting article, by the late Mr. Brough, “On the proper

Relative Sectional Areas for Copper and Iron Lightning Rods,” in which

Mr. Brough arrived at the result that the sectional area of an iron rod

conductor should be to the sectional area of a copper rod in the ratio

of 8 to 3; from which he concludes that an iron rod will be the cheaper

conductor. But this result is obtained on the assumption that the

resistance of rods of the same length, and of the same material for

lightning, are inversely as their sectional areas, a result about which

I think there may well be doubt.

W. E. AYRTON.

APPENDIX F.

ABSTRACTS OF PRINTED DOCUMENTS.

FRENCH OFFICIAL PUBLICATIONS.

_Preliminary Note._

In 1784, the attention of the French Government having been directed to

the desirability of protecting the powder magazines of the kingdom from

damage by lightning by the employment of conductors, a system of

construction was proposed by two officers of the Engineers and

Artillery. This system was referred by the Minister of War to the

Academy of Sciences for consideration and report. From time to time

subsequently other proposals of a like nature, and other inventions and

improvements in the construction of lightning rods were considered by

the Academy, and reported upon by various Committees.

At the request of the Conference, I have endeavoured, in the following

pages, to give in as condensed a form as possible an accurate abstract

of their contents, and to avoid, in all cases, the expression of any

opinion, either adverse or concurrent, upon the principles or

suggestions contained in them.

E. E. DYMOND.

REPORT _made to the_ ACADEMY OF SCIENCES, _by_ FRANKLIN, LEROY, COULOMB,

DE LA PLACE, _and_ ROCHON.

_24th April, 1784._

Certain proposals for erecting lightning rods for protecting the powder

magazines at Marseilles having been submitted to the Academy for their

opinion, a committee, consisting of the above-named, was appointed to

examine and report.

They begin by enunciating the theory which should regulate the erection

of conductors, and they lay down the following rules:—

1. The extent of the building should first be ascertained to decide

whether one or more conductors should be used. Electrical experiments

had not yet made known anything of the extent to which the action of the

point of the conductor reached. But since buildings had been supplied

with conductors many observations had shown that those parts of them

which were more than 45 feet French (48 English) from the point of the

conductor had been struck by lightning.

2. When there are many points or arrows on the building they should be

connected together and also connected with all parts of the roof which

are covered with lead, and also connected with the weathercocks or

ornamental metal points so as to form one metallic system with the

conducting bars.

3. It is not less important that these bars should be thoroughly joined

together; for a solution of continuity in them produces a resistance to

the passage of the electricity according to the extent of their

separation.

4. It is necessary that the bars should communicate thoroughly with

moist earth or, better still, with water.

As to the height of the points they should be at least 12 or 15 feet (13

to 16 feet English), or even more if the building is a large one. It is

certain that the higher they are the wider the extent of their action.

They should be 2 inches (2·2 English) square at the base and greater in

proportion as their height exceeds 15 feet (16 English). If the

conducting bars are 8 or 10 lines (or, say 1 inch) square, it will be

more than enough. No case had occurred in which iron bars of this size

had been in any way damaged or altered by the passage of lightning.

The reporters then proceed to examine the two proposals for protecting

the powder magazines at Marseilles, sent in by M. Ravel de Puy Contal

and M. Pierron. They were both for the same building which was 31 toises

long and 8 toises wide (about 198 by 51 English feet). The first

provided for the erection of three points on the ridge of the roof, and

of four others, one at each angle of the building; the second had also

three points on the ridge, but the other four were alternated on the two

sides of the roof, and iron bars were carried all along and connected

with all the points. The manner in which the terminals were fastened to

the roof and the conducting bars fastened together and led to the water

was the same in each proposal.

The reporters remark concerning the second that the conducting bars laid

horizontally along the roof would involve a great and unnecessary

expense, but the points should be retained, only instead of placing them

alternately they should be set up so that each of them was half way

between the middle and the end of the roof, and instead of connecting

these points by bars along the length of the roof, they should be

connected with the one connecting the three points on the ridge by bars

joining it perpendicularly.

As to the method proposed for joining the several parts together the

reporters cannot help thinking that in their desire to make thoroughly

good connections MM. Pierron and de Ravel had proposed a plan involving

too much difficulty and superfluous expense [It seems to have been

proposed to screw the bars into each other], and they recommend instead

of this to make at the base of each point, immediately above its

insertion into the roof, a circular flange about 2 inches in diameter

and 2 lines thick, with a hole half an inch in diameter in the middle

and at the ends of each conducting bar to make a similar flange and to

bolt the flanges together with a sheet of lead between them. Crutches

should be fixed on the roof to carry the conducting bars. The points

should be fixed three on the ridge and two on each side of the roof half

way between the point in the middle and that at each end. These four

should be connected with the conducting rods running along the ridge and

should overtop the ridge by at least 6 feet (6 feet 5 inches English).

By this arrangement all parts of the roof would be well protected.

The reporters highly approve of the way in which the conducting bars are

connected with water by being led into the sea, but if at the other end

of the building there is sufficient earth on the surface, and the soil

is not entirely rock the conductor from the point placed at that end

might be led into it. It is recommended that the points of copper should

be screwed to the terminals for convenience of removal when necessary.

REPORT _made to the_ NATIONAL INSTITUTE, _by_ LEROY, LA PLACE, _and_

COULOMB, _on a Lightning Rod for Powder Magazines proposed by_ REGNIER.

_6 Nivose, Year 8_ (_23rd December, 1789._)

The reporters think it desirable to make some general observations on

lightning rods, the rather that it appears that some persons have had

fears as to the certainty of their effect.

It is impossible to reject the theory upon which Franklin had proceeded

in providing lightning rods for the purpose of protecting buildings from

damage by lightning. Still, as the theory needed to be confirmed by

facts, it might at first have been doubted whether the lightning rods

were really effectual; but now that observation, and experiment had

proved the truth of the theory there was no longer any room to question

their utility. It may even be remarked that observations had not only

proved that they were effective when well constructed, but that they

conducted the lightning down without accidents, even when they had some

defects, which might have caused one to doubt their efficacy. The

defects alluded to were a blunted point and a break in the continuity of

the conductor. With reference to these two cases observations have

shown—1st. That although the points have been blunted, they still

attract the lightning from the clouds to themselves in preference to the

surrounding objects. 2nd. That although the several parts of the

conductor are not thoroughly joined together, the lightning will still,

if the break be not too considerable, pass along the conductor without

accident.

In support of the first proposition they quote the observations of

Doctor Rittenhouse, of Philadelphia, who had examined several of the

points in that city, and had found them melted, showing clearly that

they had been struck by lightning, and probably more than once, as it

had been shown by many observations that where, from local circumstances

(not then fully ascertained,) lightning had struck in certain places or

on certain buildings, it was not uncommon to see it strike again; and a

number of observations of a different sort had shown that lightning was

attracted by metals on buildings even when they were but slightly

pointed, such as tin weathercocks, or iron crosses, and even plain

sheets of iron.

One of the most striking examples in support of the second proposition,

was the case of an American ship, reported in the Phil. Trans. for 1770.

During the night, in the midst of a storm, the crew reported that there

was a stream of fire in the rigging, just above the middle of the

lightning conductor. The captain saw a stream of fire, sometimes in

sparks, and sometimes only a steady light; and on examining the

conductor next morning, found that one of the links of its chain was

broken. Fortunately the two pieces, being kept in place by the fastening

to the shrouds, were only about three quarters of an inch apart. These

two broken ends formed a sort of points, and on its passage between them

the lightning had become visible. But this was all; no shock was felt,

nor anything which caused any suspicion that the fracture of the

conductor had in any way hindered the passage of the lightning. Franklin

also had shown by experiment that in a lightning rod where the upper end

was only connected with the part entering the ground by a very fine

brass wire, although the wire was melted by the passage of the

lightning, it still was conducted from top to bottom without any damage

to the house; and in other instances metallic wires, though partly

melted by the lightning, had still served as conductors. But it is not

contended from these examples that a very exact and continuous

connection of all the different parts should be dispensed with.

The lightning rod proposed by Regnier consisted of a piece of wood,

coated with resin, rising 2 metres (6 feet 7 inches) above the roof, and

having fixed on its top a sort of inverted funnel of copper, at the

upper end of which was fixed the point. To the lower edge of the funnel

were fastened ropes formed of twenty-seven annealed iron wires well

bound together, which were, at a suitable distance, connected with iron

bars, fastened to masts, and leading to moist earth. The point had a

small piece of platinum at its upper end.

[Illustration: Regnier’s System of Lightning Conductors]

The reporters observe that the wooden support may be employed by way of

extra precaution, though there was no known instance of lightning

leaving metal for wood; but it should be strong enough to resist the

wind. They approve of the method proposed for connecting the point with

the metal bars, metallic ropes being very suitable for this purpose, and

keeping them well away from the building was quite right; but they add

that the metallic bars should not only communicate with moist earth, but

also with water in wells or otherwise.

INSTRUCTIONS FOR ERECTING LIGHTNING RODS FOR POWDER MAGAZINES, _adopted

by the_ FORTIFICATIONS COMMITTEE.

_25th August, 1807._

A lightning rod is an electrical conductor terminating in a point and

carried down to the common receiver. It may be regarded as a metallic

tree, and divided into (1) the upper terminal, (2) the trunk, and (3)

the roots.

1. The upper terminal is a very pointed, conical or pyramidal spike of

metal having a base 3 or 4 centimetres (1½ inches) in radius. The point

is of gold or platinum, soldered to a copper rod 1 or 2 metres long (3

feet 3 inches to 6 feet 7 inches). This rod is joined to the rest of the

upper terminal, which is of iron, either by solder, a screw, or a pin.

It is important that all the parts of the upper terminal should be

joined with care so as to prevent fracture; at the bottom of the

terminal are several feet by which it can be leaded to the vault or

bolted to the framing of the roof. Several devices for giving some play

to the terminal so as to diminish the effect of vibration have been

proposed, but it is better to make the terminal strong enough to resist.

At the bottom of the terminal is joined the piece connecting with the

conductor; this ought to be very complete and continuous, especially at

the point of junction with the terminal. Frequently the terminal is

enlarged at this point to facilitate the passage of the lightning. To

preserve the terminal from rust it is sometimes gilded—it has been

proposed to tin it—more frequently it is merely painted; experience

shows that this is sufficient. Instead of making the whole terminal

conical or pyramidal, a square bar of iron, finished with a point of

copper tipped with gold or platinum, is sometimes used. This plan may

usually be adopted without danger, but they are more liable to be broken

or bent by vibration.

[Illustration:

FIG: 1.

]

[Illustration:

FIG: 2.

]

[Illustration:

FIG: 3.

]

[Illustration:

FIG: 4.

]

2. The trunk or conductor is made of iron bars 13 to 20 millimetres

square (½ to ¾ inch) notched at the ends and bolted together with a

plate of lead between the two (Fig. 1). For powder magazines a bar of 27

millimetres (1 inch) square is recommended. They follow the outline of

the roof, cornice, and wall, and each bar is fixed by a half collar

(Fig. 2) or cramp placed in the middle of the bar or as far as possible

from the junction of two bars. Instead of the iron bars ropes of copper

or iron wire, or even of hemp, may be used; these last may be used

provisionally, but for permanent conductors they have no advantage

either in economy or conductivity. The copper rope conducts the

lightning better, but its smaller size and cylindrical form, by

diminishing its absolute and relative surface, counterbalances its

superior conductivity. The great and real advantage of metallic, and

especially of copper ropes, is in their continuity and their

flexibility. The conductor is led down to the surface of the ground

where it is bent and led parallel to the surface towards a pit full of

water, or deep enough to allow the end of the conductor to rest in damp

earth; from 2 metres (6 feet 6 inches) above the ground to the pits the

conductor is enclosed in a channel or trough like the fuse of a mine,

the object of this is to protect the conductor from the dampness of the

soil and from contacts. These would be unimportant so long as there is a

perfect connection between the point of the conductor and the common

reservoir, but this continuity may be destroyed by degradation of the

conductor, and it is chiefly at the joints that this discontinuity is to

be feared. When the conductor has to be buried it should be in an oaken

trough, well put together and tarred or charred or surrounded by

powdered charcoal so that the metal cannot be rusted by infiltrations or

humidity; in some soils it is better to make the subterranean part of

the conductor of lead, taking care by increasing the surface to make up

for its inferior conductivity. Sometimes water pipes may be made use of,

but only when they serve to lead water away and when they terminate in

an isolated reservoir. It is important to lead the conductor far away

from water pipes carrying water to public fountains or into the interior

of houses.

3. If the conductor leads to a well full of water the roots (Fig. 3)

need not be more than a few spindles terminated in points and long

enough to be always immersed. When the conductor only leads to a bed of

earth it is supplied with a system of roots (Fig. 4), having for its

object the multiplication of the points for the escape of the lightning,

and these are increased in number according as the soil is a less good

conductor. The pits should be some distance from the foundations of the

building, so that the lightning may not damage them, and it is

important, by all possible means, to increase the natural humidity of

the soil. When the wells cannot be closed it is necessary that the

conductor should be insulated and plunged deeply in the water for fear

that the communication of the electricity to the well-chains or

pump-rods might cause accidents or alarm. After some other instructions

it is added that the dispersal of the electricity in the common

reservoir is, next to the continuity of the conductor, that which most

deserves the attention of the physicist and the engineer.

It has been remarked that a point extended its sphere of activity as far

as 10 metres (32 feet 9 inches), that beyond this distance its effect

became less sensible, and that when the points were too near together

they neutralised one another. So upon a building of a given size it is

necessary to set up so many that all parts shall be covered by their

spheres of attraction, which should meet and not overlap each other.

Lightning in passing from a cloud to the earth does not always take a

vertical direction, it sometimes follows the path of the rain drops,

which is inclined by the wind, so when a magazine is very lofty, or on

an elevated spot it is not useless to fix horizontal or inclined points

on the gables or angles. In some places the magazines are dominated by

other buildings; in these cases the neighbouring buildings should be

protected, or the magazines should have horizontal points towards them.

If the ramparts dominate the magazine it will be prudent to set upon

them a lightning rod on a mast. Trees are only struck by lightning

because their tops serve as points but their trunks are bad conductors,

hence it is prudent not to have plantations, especially of lofty trees

near magazines. However many points may be set up on a magazine they

should all be connected together, and all joined to the principal

conductor, and it would be well to have more than one principal

conductor so that if one loses its continuity the lightning may have a

path by the other. Stone, wood, and gunpowder are bad conductors, and

pieces of metal may without danger be used in the inside of magazines,

provided they are connected with the principal conductor by branch

conductors of suitable size: still it is prudent to keep the metal

outside.

[Illustration: Powder Magazine, with oblique as well as vertical rods]

Reference is then made to “Regnier’s System of Lightning Rods,” Appendix

F., p. 53, which is thought to be much too expensive.

REPORT _on the foregoing Instructions made by_ LA PLACE, ROCHON,

CHARLES, MONTGOLFIER, _and_ GAY LUSSAC _to the_ NATIONAL INSTITUTE.

_2nd November, 1807._

The reporters say that experience has taught that the point of a

lightning rod 4 or 5 metres (13 to 16⅓ feet) does not effectually

protect a space round it greater than one having a radius of 10 to 12

metres (32¾ to 39¼ feet). That when there are points or considerable

masses of metal on a building having a lightning rod it is absolutely

necessary to connect them by branches with the principal conductor. That

it is not less important that the metallic bars should be thoroughly

well connected together so that the electricity may find no resistance

in its path from the point to the common receiver. And lastly, that it

is necessary that the conductor should have a perfect communication with

moist earth, or better, with water. They then proceed to discuss the

instructions, or that part of them which relates to the construction of

the lightning rods. They recommend the use of gilded copper points,

notwithstanding the doubt concerning them which had been raised in

consequence of their deterioration by oxidation, and their being blunted

by lightning. They say that experience has shown that an iron rod 20

millimetres (·8 inch) square is more than sufficient to carry the most

violent discharge of lightning, and that it is consequently needless to

make them larger, as recommended in the Instructions; that it is only at

the joints that there is any cause for fear because, in spite of the

insertion of the piece of lead, the contact is not perfect; that it

would be easy by enlarging the bars at their junctions to increase the

number of points of contact, and by lengthening the bars to make fewer

joints. That in this respect the use of iron wire ropes would be very

advantageous, but they fear that the ropes would be easily destroyed,

and that the use of copper wire rope instead of iron would be too

expensive.

When the conductor reaches the ground too much care cannot be exercised

in making a free communication between it and the soil. It is upon this

that its good effect principally depends, for houses have been struck

although provided with a conductor, because it only communicated with a

very dry soil. M. Patterson, of Philadelphia, in the fourth volume of

the American Phil. Trans., has published a means of making a good

contact which seems useful. He proposes to lay the conductor in a bed of

galena worked into a paste with melted sulphur. The galena is a good

conductor, and would have the advantage of protecting the iron from the

damp. He has also proposed a simple means of providing for the easy

dispersion of the electric fluid in cases where the soil is not very

damp, which consists in making a hole in the ground and filling it with

charcoal, into which the conductor is plunged. But M. Guyton used the

conducting power of charcoal for this purpose more than thirty years

ago, and it has been applied in many ways. Charcoal, like galena, is a

good conductor, and this property renders its employment desirable in

cases where the soil is dry.

Upon the proposal to fix inclined or horizontal points they think that

vertical points will suffice; and with reference to the Regnier system,

they remark that it would certainly be very expensive, and that it would

not be necessary to adopt it until the usual system had been found

insufficient.

INSTRUCTIONS _about_ LIGHTNING RODS _adopted by the_ ACADEMY OF

SCIENCES.

_First Part, 23rd April, 1823._

PREPARED BY A COMMITTEE CONSISTING OF MM. POISSON, LEFEVRE-GINEAU,

GIRARD, DULONG, FRESNEL, AND GAY LUSSAC.

[Illustration: Mode of attaching Conductor to Upper Terminal]

After some theoretical remarks the Committee describe the conductor they

recommend, giving the name of _tige_ (upper terminal) to the part rising

into the air above the roof, and that of conductor to that part

extending from the upper terminal to the ground. The upper terminal is a

square or round bar of iron tapering from base to summit. If from 7 to 9

metres (23 feet to 29 feet 6 inches) high, which is the smallest height

to be used on large buildings, it should be 54 to 60 millimetres (2·1 to

2·3 inches) square or diameter at the base, if 10 metres (32 feet 9

inches) high, it should be 63 millimetres (2·5 inches). About fifty-five

centimetres (1 foot 9½ inches) of the upper end is cut off and replaced

by a point of copper either gilded at the end or tipped with a little

piece of platinum. At the lower end of the terminal (A), 8 centimetres

(3·15 inches) above the roof, is fixed a base (B) to throw off the rain

which would run down the terminal, and above this base the terminal is

clasped by a collar (C), as shown in the drawing, to which is bolted the

conductor (D). The engraving shows the modification of the arrangement

as adapted to both round and square terminals. The conductor is a bar of

iron 15 to 20 millimetres (·59 to ·79 inches) square, joined firmly to

the upper terminal by bolting it tightly between the two ears of the

collar. The best way of joining the bars together is shown in figure 1,

p. 55. It is to be held up at a distance of 12 to 15 centimetres (4·7 to

5·9 inches) from the roof by crutches, and to be kept at a like distance

from the walls of the building. At 50 or 55 centimetres (19·6 to 21·6

inches) below the surface it is turned away perpendicularly from the

wall for a distance of 4 or 5 metres (13 feet 1 inch to 16 feet 5

inches) if it does not sooner meet with water. To avoid rusting the rod

is carried in a trench filled with charcoal, and then turned down a well

so as to have at least 65 centimetres (25·7 inches) in the water when at

its lowest level, where it terminates in three or four branches to

facilitate the exit of the electricity from the conductor.

If there is no well convenient, a pit should be made 13 to 16

centimetres (5·1 to 6·3 inches) in diameter, and 3 to 5 metres (9 feet

10 inches to 16 feet 4 inches) deep, down the middle of which the

conductor should be led and the hole filled with charcoal tightly

rammed. As the iron bars forming the conductor are not easily bent to

follow the lines of the building a metallic rope may be used. It is made

of four strands, each composed of 15 iron wires, and forming a rope of

16 or 18 millimetres (·62 to ·7 inches) in diameter. Each strand is

tarred separately, and the whole also well tarred when put together. It

is attached to the upper terminal in the same way as the bars by

pinching between the ears of the collar (c). At 2 metres (6 feet 7

inches) above the ground it is joined to the bars which form the earth

connection by being pinned into a socket formed at the end of the first

bar. Ropes of copper or brass wire may be used, and they need not be

more than 16 millimetres (·62 inches) in diameter.

It is necessary to connect any considerable metallic masses (lead roofs,

metal gutters, or tie rods) with the conductor, because if this be not

done, and the conductor be broken, or have a bad earth connection, the

lightning may leave the conductor for the metallic mass.

Modifications of this form of conductor for use on churches, ships, and

powder magazines (for the latter carrying the conductors on masts is

recommended) are then described.

The report says that the terminal of a conductor protects efficiently a

circular space round its base, having a radius equal to twice its

height; but that it is prudent to estimate that a conductor on a church

spire only protects a circle having a radius equal to the height of the

conductor.

The conductor should go the shortest way to earth. It should be on the

side most exposed to the weather, especially on spires.

_Second Part, 18th December, 1854._

PREPARED BY A COMMITTEE CONSISTING OF MM. BECQUEREL, BABINET, DUHAMEL,

DESPRETZ, CAGNARD DE LATOUR, AND POUILLET.

Notwithstanding the considerable advance in knowledge since 1823, the

instructions of that date have no need to be altered, at least in their

essential principles; but the methods of construction of buildings

having materially altered, and metal having largely replaced wood and

stone, buildings had, so to speak, become metallic masses, which would

have incomparably greater attraction for thunder clouds. The Palais

d’industrie in the Champs Elysees, for example, nearly 3 hectares (7·4

acres) in extent, and 40 metres (131 feet) in height had everywhere

enormous masses of iron, brass, and zinc.

The company undertaking the building had sought the advice of the

Academy as to the means to be employed to protect it from lightning, and

it had been found necessary to revise the instructions of 1823, in order

to introduce such modifications as were necessary.

Quoting the passage referring to the connecting of metallic masses with

the conductor, the Committee think that the time had come to enter into

fuller details on this point.

Formerly the use of metal was almost restricted to ridges, gutters, and

tie rods; now metal was used everywhere, and what is important, in large

surfaces and great masses; and this new system realised on a large scale

the first objection to lightning rods—it attracts the lightning.

When this objection was applied to lightning rods, it had only the

appearance of truth, but when applied to the masses of metal then used

in buildings, it was not only specious, but true, and founded upon well

established laws; these buildings do attract the lightning, and render

its effects more disastrous.

In the case of two buildings alike in size and shape, situated on the

same soil, one made of wood and stone as formerly, the other with much

metal as now, and both without lightning rods—if the conditions are such

that the lightning must discharge itself, it will always strike the

latter, and never the former; in the same way as on bringing to the

conductor of an electrical machine a ball of wood or stone, and one of

metal, it is always the latter which will receive the spark. Lightning

rods, therefore, are so much the more indispensable as the buildings

contain greater surfaces and greater masses of metal.

The nature of the soil must be taken into account, as well as the

buildings and other objects upon it. A dry soil, with a subsoil of dry

sand, chalk, or granite, does not attract the lightning, because it is a

bad conductor. Unless when accidentally wetted the buildings on it

participate to some extent in this immunity, at least if they are not

built in the modern style, and are not very large. But if there are at a

moderate depth underneath this dry ground, large metallic veins, vast

caverns, sheets of water, or only abundant springs—these will attract

the lightning, which will destroy everything in its path unless

protected. If the wet or metallic strata are very deep, the danger of an

explosion is diminished by the difficulty of passing the intervening

envelope, and by the weakening of the action of the cloud by the

increase of distance.

On the 19th April, 1827, the packet boat _New York_ was twice struck by

lightning. On the first occasion, having no conductor, it received

considerable damage; on the second, the conductor was fixed; it was made

of a pointed bar of iron, 1·2 metre (about 4 feet) long, and 11

millimetres (·43 inch) diameter at the base, and a surveyor’s chain

about 40 metres (131 feet) long, forming a connection between the foot

of the rod and the sea; the chain was made of iron wire 6 millimetres

(·24 inch) in diameter; the links were 45 centimetres (17·7 inches)

long, ending in loops, and joined together by two round rings. When

struck the chain was dispersed in burning fragments and globules, which

set the deck on fire in many places, notwithstanding the hail upon it

and the rain which fell heavily; the bar at the top was melted for a

length of 30 centimetres (11·8 inches) from the point, and down to a

diameter of 6 millimetres (·2 inches). The rest of the rod remained with

about 8 centimetres (3·1 inches) of the chain attached to it, the

longest piece of chain found was less than 1 metre (3 feet 3 inches)

long, and was blistered as by fire.

On the 13th June, 1854, the _Jupiter_ was struck by lightning. The

conductors were in place; that of the mainmast which was struck went 2

metres (6 feet 6 inches) into the sea, and had at its end a ball 2 kilos

in weight. After being struck the conductor had disappeared and the

pieces of it were scattered everywhere. The conductor, about 70 metres

(230 feet) long, was a cable of three strands formed of sixty brass

wires, each one half or two-thirds of a millimetre (·019 or ·026 inches)

thick. The cable was mostly in bits no bigger than pins, but there were

some pieces a few decimetres long, these had been turned violet colour

as by fire, and those first touched were still burning hot.

These two examples show that a conductor may be destroyed, but they also

show that it is not useless even then, since it will have received the

discharge and directed it, and so prevented greater mischief. The

_Jupiter_ received no damage; whilst not far off, a Turkish vessel,

which also had a conductor (but the chain of which did not reach the

water) having been struck by lightning in the same storm, had a hole

more than 30 centimetres (11·8 inches) deep, and almost such as would

have been made by a cannon ball, in her side just above the copper, and

near the water line.

The question is, are such accidents to conductors inevitable, or are

they the result of faulty construction? All the facts established in the

accounts of lightning and its phenomena, leave no doubt on this point.

All the lightning rods which have been destroyed were of bad materials,

insufficient, badly constructed, not in accordance with the principles

which theory has deduced from experience.

The conductor of the _New York_ had several faults; its upper terminal

was too small, and too much drawn out; its conductor had much too small

a sectional area; and the use of a chain in such cases should be

strictly excluded.

There is no example known in which lightning has been able to melt iron

rods 2 centimetres (·78 inch) in diameter, or 3 square centimetres (1·18

inch) in section; and copper may be used in still smaller sizes.

The conductor of the _Jupiter_, although better than the former, had

also a radical defect. The fragments of the conductor which were

examined bore but few traces of fusion, and none of these traces

extended to the entire thickness of the cable; they were also limited to

a group of some of the sixty wires of which it was composed. This seemed

to show that the discharge was not carried equally by all the wires, and

that those wires which it followed being insufficient to carry it, were

the ones melted, and the others were broken or volatilised with

explosion. Hence the breaking of the cable and dispersion of fragments

of some decimetres in length, which, though too hot to be touched, were

not hot enough to set wood on fire. This explanation, however, raises a

singular question, whether, in a cable of similar wires twisted and

bound together, the lightning can choose some wires in preference to the

rest, even when the whole of them are hardly sufficient to give it a

free passage.

Undoubtedly, yes; at any rate under certain conditions. No doubt if at

both ends of the cable, for the length of a decimetre, the wires first

tinned separately are afterwards soldered together, so as to make a sort

of metallic cylinder, electricity, whether natural or artificial, having

to pass along the cable, will not show a preference for one wire over

another; but where this is not done—if at the two ends, or, more

generally, at the two points of junction with other conductors, the

wires are isolated by layers of dust or oxide—if, in addition, the cable

only touches the terminals by its outside wires, then things happen very

differently. The electricity takes those wires that are in contact with

the terminal; these reduced to few in number become incapable of

carrying it; and the whole cable broken by the explosion exhibits the

phenomena shown in the case of the _Jupiter_.

The deficiency in each case was due to one cause—insufficiency of

sectional area. In the first case the insufficiency is apparent, the

iron wires 6 millimetres (·24 inch) thick were nine or ten times too

small; in the second, the insufficiency is more hidden, it results from

badly made junctions.

The two most fundamental rules for the construction of the rod and

conductors are—1st. That they shall have a sufficient sectional area.

2nd. That they shall be continuous and without a break from the point of

the upper terminal to the common receiver (the earth). But this

continuity may in strictness be interpreted in two ways: it may be said

that two pieces of metal in contact form a sufficiently continuous

connection; and it may be said, on the other hand, that most frequently

this simple contact is no more than a break in consequence of oxidation

and the interposition of foreign bodies.

The instruction of 1823, without adopting the first interpretation, does

not appear to have sufficiently recommended the second, which should

exclusively regulate all construction of lightning rods. No doubt it is

possible, by taking great care, to join and bolt together two pieces of

iron or copper closely enough to make a practically continuous

conductor, but when there are many joints we fear that evil might arise

from the negligence of workmen, and still more from the chemical

alteration of the surfaces, the deposition of foreign matter, and the

mechanical dislocation produced by time and repeated shocks.

Hence, the three following practical rules should always be observed:—1.

To reduce as much as possible the number of the joints. 2. To make all

the joints with hard solder, and they should be upon surfaces of at

least 10 centimetres (3·9 inches) square, and further strengthened by

straps and bolts. 3. Not to make the upper terminal so gradually pointed

as usual. The upper terminal of iron should be not less than 2

centimetres (·78 inch) diameter, the end should be filed down and a

screw tapped 1 centimetre (·39 inch) high and 1 centimetre diameter, and

to this a cone of platinum 2 centimetres diameter and 4 centimetres (1·5

inch) high, and consequently having an angle at the point of 28° or 30°

should be fitted, screwed, and carefully soldered.

In other respects the instructions of 1823 should be followed; no fact

which leads to a modification of the general rules there proposed 1, for

the sectional area of the conductors; 2, for the method of fastening to

buildings; 3, for the method of making the earth connection, has since

come to light.

The subject, however, is not exhausted, there still remains the

important and difficult question: what is the circle of protection

afforded by a well constructed lightning rod? The opinion generally

received at the end of the last century was that the circle of

protection had a radius of twice the height of the terminal, and the

instruction of 1823 adopted this opinion, but with some restrictions as

in the case of spires. It is important to remember that these rules rest

upon a more or less arbitrary basis, and this is said not to condemn

them, but only to prevent there being attached to them a value which

they do not possess.

More observations are required, and it is only with reserve that these

rules are admitted. They are neither general nor absolute, they depend

upon a variety of circumstances, and especially on the materials of the

buildings. For example, the radius of the circle of protection, which

would be sufficient for a building having only wood tiles or slate on

its upper portion, would not be sufficient for a building in which the

covering or the framing of the roof was of metal. In the former case the

active portion of the thunder cloud, although further from the lightning

rod than from the roof, would exert a greater action on the rod, whilst

in the latter the action on the rod and on the roof would be almost

equal at an equal distance.

A special note upon ships, and another on the Palais de l’Exposition

close the report.

SPECIAL REPORT FOR THE NEW BUILDINGS OF THE LOUVRE, 18 DECEMBER, 1854,

BY THE SAME COMMITTEE.

Referring to the subject of the earth connection the Committee say; in

the earliest instructions, it is said that the conductors should

communicate with the water in a river, a pond, or wells, or at least

with moist earth. This rule, although quite correct in itself,

frequently leads to erroneous practice. It is sometimes thought that

lightning is extinguished by water, as fire is; and when water is scarce

the conductors are plunged into a well-cemented cistern. This is a most

dangerous mistake; the conductor should be in connection with the common

receiver, that is, the great water-bearing strata (nappes d’eau,) of

much greater extent than the thunder cloud. At other times where wells

are possible but costly, advantage is taken of the alternative allowed

by the instructions. Instead of wells the conductors are put in

connection with the earth, without being careful to see that it

preserves sufficient moisture in times of drought when storms are most

to be expected, and without being careful to see that the moist

connection is sufficiently large. They specially note this latter error,

as it appears to be still more common than the former. They do not

hesitate to say that recourse should never be had to this method of

connection with the common receiver. They recommend that in default of

rivers or very large ponds, the conductor should always be connected by

large surfaces with the inexhaustible subterranean water-bearing strata.

Secondly, where these strata are at a moderate depth below the surface,

the Committee consider it necessary to make use of a conductor with two

branches, the principal to descend to the subterranean water; the

secondary, leaving it at the ground level, is put in connection with the

surface. And for this reason; after great droughts thunder clouds exert

but a feeble influence upon a dry, badly conducting soil. All their

energy is felt by the subterranean waters; and the electricity will be

carried by the principal branch. On the other hand, after a summer

shower, when the surface soil gets moist, it is at once made a good

conductor. It is that which is affected by the thunder cloud: while, at

the same time, it screens the subterranean water from electrical

influence. In such a case it is indispensable that the surface of the

ground should be in direct connection with the conductor; and this the

secondary branch supplies.

There is a final question how the conductors should be connected with

the various metallic portions of the building. The ridges are throughout

of iron; but the interior arrangements require that, in some portions of

the building, there should be, properly speaking, only one floor, whilst

in other parts there are six. Each floor may be regarded as a great

metallic network, composed of several strong plate girders, crossed by

numerous joists analagous to rails, while these are, in their turn,

crossed by a multitude of smaller iron rods; and the meshes of this

network are filled with tiles. In enquiring into the effect of a thunder

storm upon those portions where there are six such floors one above the

other, it is easy to see that if the roof were a great continuous sheet

of metal, it would take up the whole electrical energy of the cloud, at

any rate, as far as the floors underneath it are concerned. In this case

it would be amply sufficient if the covering were well connected with

the lightning rods. But in this case the roof is metallic, only in a

very small portion; it may be said that the ridges only form a network

with very large meshes, and, consequently, is an insufficient shield,

through which the upper floor may still receive a considerable shock.

Therefore the Committee propose the following arrangements:—1st. The

principal pieces of each floor should be put in connection with the

conductor. 2nd. It is very desirable that all the joists of the upper

floors should be connected together by a rod bolted, and, if possible,

soldered to each, which rod should be connected with the conductors.

3rd. It seems probable that, in general, the roof frames are in good

connection with each other, and, consequently, it would suffice if all

the upper terminals are connected with them. If, however, it happens

either by changes of level in the gutters, or from other causes that the

connections become doubtful special iron connections must be made. 4th.

The zinc gutters and ridges should be connected with the lightning rods.

REPORT _on the points of upper terminals made by Messrs. Delieul, by a

Committee consisting of_ MM. BECQUEREL, BABINET, DUHAMEL, DESPRETZ,

CAGNIARD DE LATOUR, REGNAULT, DE SENARMONT, _and_ POUILLET.

_5th March, 1855._

The committee examined the points presented by Messrs. Delieul, one of

platinum, made exactly as described in the report of the previous 18th

December; the other, a cone similar in form, size, and external

appearance, but rather less costly, being made of a cap of platinum,

fixed with hard solder upon the conical end of the iron rod. It was

thought that this second arrangement would not practically be inferior

to the other; but it must be made by a skilful workman, who knows how to

insure that the solder should take to the whole of the surfaces brought

together. They see no objection to the substitution of palladium, or

gold or silver of a standard of ·950 for the platinum. But all these

metals are costly; few workmen know how to work in them, or at least to

employ that precision, and take that minute care, which are

indispensable to success. These reasons have raised again a proposition

that was discussed in the former commission, which consists in making

the points of copper. The copper point is 2 centimetres (·78 inch) in

diameter, like the upper part of the iron rod, to which it is screwed

and brazed; its length is about 20 centimetres (7·87 inches), and it

terminates in a cone 3 or 4 centimetres (1·1 or 1·5 inches) high.

They see no reason why this should not be used with almost the same

confidence as the preceding forms. If there is ground to fear that it

may undergo changes from atmospheric influences, this is counterbalanced

by certain advantages. 1st, copper is with palladium, gold, and silver,

among the best conductors of heat and electricity; and the point of the

cone will be much less heated than the platinum point; and 2nd, the

terminal, with a copper point, is much less expensive, and can be made

everywhere.

On the report being put to the vote M. Despretz could not approve the

proposal to employ copper points, fearing that the deposition of

carbonate or some other badly conducting matter would diminish the

efficacy of the lightning rod.

INSTRUCTIONS _upon_ LIGHTNING RODS _for_ POWDER MAGAZINES, _by a

Committee consisting of_ MM. BECQUEREL, BABINET, DUHAMEL, FIZEAU, EDM

BECQUEREL, REGNAULT, _le Maréchal_ VAILLANT, _and_ POUILLET.

_14th January, 1867._

After referring to some general principles, and to the construction of

lightning rods recommended in the reports of the earlier Committees: the

Committee recommend, that the upper terminal including the copper point

should be from 3 to 5 metres (9 feet 10 inches to 16 feet 5 inches)

high; that the junction of the conductor and the upper terminal, and

also the several joints of the conductor, should be covered with solder,

and insist very strongly upon the necessity of communication with the

_nappe d’eau souterraine_, which they define as “the water level in

neighbouring wells which never dry up, and which retain at least 50

centimetres (19·68 inches) in depth of water in the most unfavourable

seasons.”

The special arrangements to be adopted in setting up lightning rods for

powder magazines are: not to fix them on the building itself but outside

the surrounding walls. For each large sized magazine (27·89 metres, by

20 metres, and 11 metres high, equal to 91 feet 6 inches by 65 feet 7

inches, and 36 feet high) there should be three conductors—two near the

ends of the long side of the enclosing wall most exposed to storms, and

the third in the middle of the opposite side. The upper terminals should

be only 5 metres (16 feet 5 inches) high, and should be raised on a

pier, a mast, or other support 15 metres (49 feet 2 inches) high, down

which the conductor should be led to the ground. There should be a

circuit which the Committee call _circuit de ceinture_ carried entirely

round the enclosing wall to which each conductor should be joined, and a

conductor should be carried from the most convenient point of this

circuit to the underground water. For middle sized magazines two

terminals and supports, and for small magazines one terminal and support

will suffice; but in all cases there should be a _circuit de ceinture_.

This need not be deep below the surface, nor covered over; it may even

be in an open gutter, but a conductor must be led from it to the

underground water, even if in order to do this it is necessary to carry

the conductor several hundred metres or several kilometres. It need not,

however, be made of bars and carried all the way in a trench, but it may

be made of six wires 6 or 7 millimetres (about ·25 inches) in diameter,

and carried on posts like telegraph wires, except that they need not be

insulated.

INSTRUCTIONS _by the Committee consisting of_ MM. ALPHAND, BELGRAND,

FIZEAU, _Comte du_ MONCEL, ED. BECQUEREL, DESAINS, CH. SAINTE

CLAIRE-DEVILLE, DUC, BALLU, MAGNE, DAVIOUD, FELIX LUCAS, _and_ R.

FRANCISQUE MICHEL, _appointed to inspect the_ LIGHTNING RODS _on the_

MUNICIPAL BUILDINGS _of_ PARIS.

_20th May, 1875._

The Committee find that platinum tips are useless, and recommend instead

that the point of the terminal should be made of pure copper, 50

centimetres (19·7 inches) long, and terminating in a cone, forming an

angle of 30°. This should be scarfed, pinned, and soldered to the end of

the terminal. The terminal should be of wrought iron in one length, and

where possible galvanized; but on no account painted. The connection

with the conductor should be by a piece fitted and bolted; and, lastly,

the whole joint should be well covered with solder.

The Committee consider that on an ordinary building a terminal will

effectively protect a cone, having the point for its apex, and a base

whose radius is 1·75 of its height. But in practice the terminals may be

much farther apart, if there is a _circuit des faites_. This is defined

as a metallic conductor, which extends without break over the ridges of

all the buildings which it is intended to protect, and which is joined

by metallic contact to all the upper terminals and to the conductor, and

consequently to the underground water which alone forms the common

reservoir. All pieces of metal of any considerable size should be

connected with the conductor.

If the conductor is made of iron bars, they should be galvanized if

possible, and the joints should be fitted, bolted, and finally covered

with solder. If the bars cannot be galvanized, they should be well

painted. The Committee recommend the employment, especially in the

_circuit des faites_, of an arrangement for compensating for the

lengthening and shortening of the bars by the variations of temperature.

This is made by inserting in the circuit a curved band of copper which

will yield to the movement of the rods. If the conductor is made of

galvanized iron wire rope, each wire should be 2·5 or 3 millimetres (·09

to ·11 inch) in diameter, and there should be such a number of them that

the sum of their sectional areas shall be equal to one-fifth more than

that of a bar of iron 20 millimetres (·78 inch) square. The rope should

be all in one piece, and the joints with the terminal and earth

connection should be covered with solder.

The supports should not be insulated, and there should be as few as

possible of them. At the underground end of the conductor should be

fixed a large sheet or hollow cylinder of metal, and this should be

always, even in the greatest droughts, plunged at least 1 metre (3 feet

3 inches) into the subterranean water. If from any cause this water

cannot be reached, the conductor may be joined to one of the main

water-pipes of the city; but if the conductor cannot be led either to

the subterranean water or to a main water-pipe, no lightning-rod should

be erected. It would do more harm than good.

In the case of buildings of any importance, two or more conductors

leading to the subterranean water should be employed. It should be so

arranged that the underground part and the earth connection may be

easily inspected and cleaned from rust, and the whole should be

inspected and cleaned at least once a year, at the end of the autumn.

The Committee is of opinion that it would be better to put all the

lightning-rod work in the hands of special workmen, under the control of

an agent appointed by the administration, and not to trust it to the

blacksmiths and locksmiths usually employed. The Committee lastly

recommend that they should be permanently appointed, and meet every year

after the inspection, to report and decide upon the steps to be taken to

remedy any defects that may be discovered.

REPORT _by the joint Secretary_ (FRANCISQUE MICHEL) _of the Lightning

Rod Committee to the Prefect of the Department of the Seine_.

This report gives a detailed description of the state of the lightning

rods attached to the public buildings of Paris.

In most cases the upper terminals were of great length, some of them as

much as 9 metres (nearly 30 feet) in height; the conductors were in

almost all cases of iron, either in bars or wire rope; the earth

connections were of various kinds and extent.

The report frequently states that the points were blunted; that the

upper terminals and the conducting rods were deeply rusted; that

especially at the joints the conductors were seriously deficient; and

that the underground portion was greatly deteriorated by rust.

A description is given of an accident from lightning to the church of

St. Sulpice; but this building had no lightning rod. In the case of the

church of St. Clotilde there are five upper terminals, two on the two

spires, the remaining three along the ridge of the main roof. The

building was amply protected as far as its length was concerned, but the

transept was not so thoroughly protected. The five terminals were joined

to a conductor which went round the building, and was connected with the

ground. A second conductor led from one of the terminals to the ground,

where it terminated in a second pit. The conductors were made of iron

rods 18 millimetres (·71 inch) in diameter, joined by collars and pinned

and the whole covered with paint. They terminated in distributors

plunged in the underground water in walled pits. They were supported by

insulated collars. The building has an iron roof. The church had been

struck by lightning at least four times since the lightning rods had

been erected. The first time, twelve years ago, the lightning struck the

rod placed on the transept, and carried away the platinum tip of the

copper point. Since then the rod has received another discharge, and the

copper point is bent to the S.W. In January, 1872 or 1873, the lightning

struck the western tower, and shattered one of the stones above one of

the windows of the staircase.

“One of the platinum tips is gone, and many are blunted. The

conductivity of the conductor is very bad, and the joints are very much

damaged: hence the accident to the tower. The greater number of the

glass insulators are broken, or gone altogether.”

In the case of the church of St. Eloi, which had one terminal on the

spire, one conductor, formed of iron wire rope 2 centimetres (·78 inch)

in diameter, joined at 3 metres (9 feet 10 inches) above the ground to

an iron rod 25 millimetres (·97 inch) in diameter, which entered the

ground and ended without branches in a pit filled with charcoal. The

soil was dry and calcareous. The conductor was made up of many lengths

of rope, old pieces apparently having been used; the joints were in bad

condition, and needed soldering. The underground part was deeply rusted.

“In September, 1874, lightning struck the spire, twisted the conductor,

broke the terminal, threw down the part above the cross, and made great

cracks in the apse.”

During the building of the Mairie of the 20th Arrondissement, the

lightning struck a fir-pole in the scaffolding. It did not do any

damage, being carried away by the chain attached to the pole, from which

it took all the rust, and being thence conducted by some pieces of iron

roof framing lying on the ground.

There are several other accounts of accidents, but they are mostly

represented by the foregoing examples.

INSTRUCTIONS _as to the application of_ LIGHTNING CONDUCTORS _for

protection of_ POWDER MAGAZINES, ETC.

Issued with Army Circulars, dated May 1st, 1875.

(_Abstracted by Prof. T. Hayter Lewis, F.S.A._)

1. The principles adopted by Sir W. S. Harris, as shown in the

Appendices A and B, to this paper, still held to be sound.

2. The terminating plane of action of lightning is sometimes beneath the

surface of earth, which, if moist, forms good medium for diffusion of

electricity.

3. Dry soil is to be regarded as non-conducting matter.

4. Therefore conductor to be taken into soil permanently damp.

5–6. Underground magazines are usually in dry soil, and should

therefore be fitted with conductors as in the case of similar magazines

above ground.

8–9. Casemated batteries of modern construction, with magazines in

basement should have conductors on the parapet or terreplein from end to

end of battery, attached to vertical conductor into earth. Flagstaff

should have conductor. In large works there should be several points 5

feet above top of building. Iron verandahs and railings are good

conductors when with good earth connections.

10. Iron buildings are good conductors. But if covered with asphalte,

concrete, &c., rods or points must be provided projecting above

asphalte, &c., and with good earth connections. Iron shields should be

connected with conductors.

11. Copper is recommended as best conductor; it is not liable to

corrosion, and very durable.

12. But if exposed to injury, or likely to be stolen or corroded, copper

may be replaced by iron, provision being made for its smaller

conductivity—viz., ⅕th that of copper.

13. Copper rods to be ½ inch diameter; copper tubes to be ⅝ × ⅛ inch

thick; copper bands to be 1½ × ⅛ inch thick.

14. If the conductor be of iron, solid rods to be 1 inch diameter; solid

bands to be 2 inches wide × ⅜ inch.

15–16. The fusing temperature of copper is 1994° Faht.; whereas that of

iron is 2786° Faht. So far there is a marked advantage over copper. But

it rusts easily, and then the electrical resistance is immensely

increased. Roughly speaking, an equal conducting power may be obtained

either in iron or copper for the same cost, the number of iron

conductors being greater in proportion to the less cost, and the more

conductors being the better.

17–19. Expansion and contraction are to be carefully provided against;

_e.g._ by suitable bends at intervals in long lines of horizontal

conductors and by bearing collars, allowing of slip in vertical lines.

20. Soldered or welded joints are desirable, but not absolutely

necessary.

21. Gives engravings of connections recommended by Sir W. S. Harris,

where soldered joints cannot be used, and which fulfil the conditions

specified in sections 17–19.

22. Soldered or welded joints to be used where discharge is possible

with unsoldered joints, and likely to ignite dust or inflammable

substances near.

23. Iron may be connected by similar joints as for copper, or by screw

joints as for gas pipes. No white lead to be used, it being a bad

conductor.

24. Iron flat bands may be connected by rivets or screws, working in

slots, to provide for expansion, each surface in contact being at least

six times the sectional area of band.

25. Copper bands to be similarly connected. Joints between different

metals may be soldered, screwed, or rivetted, the extent of surface in

contact being regulated by the dimensions of the metal of the least

conducting power. Access of moisture to surfaces in contact must be

prevented, on account of local galvanic action and decomposition.

26. No precise limit can be fixed to protecting power of conductors. In

England the limit is usually assumed as being the radius of the height

from ground. It may be sufficiently correct for practical purposes, but

cannot always be relied upon.

27. Conductors do not attract lightning; they only diminish the

resistance due to the air. Even a change in the nature of the soil -over

which a cloud passes may produce a discharge.

28. One angle of a building may receive a discharge, though another

angle have a conductor. So every prominent part of a building containing

explosive material should have a conductor.

29. In buildings of uniform height, provide a solid rod 5 feet above it

at each end, and at each 45 feet in length; if the conductor be of iron

the top should be gilt.

30. Buildings not over 20 feet long to have one vertical conductor at

end, and a horizontal conductor on ridge.

31. If 20 to 40 feet long to have one vertical conductor in centre, and

one along ridge, as last.

32. If 40 feet long to have two vertical conductors; if 100 feet long

three conductors; in both cases with conductor along ridge.

33. Similar principles to be adopted in larger and more complicated

buildings.

34. Each prominent part should have a conductor. The value of three or

four points to terminals is not apparent unless the points are widely

separated.

35. Conductors are to be connected horizontally, _e.g._, by ridge or

eaves, which, when of metal, should be invariably connected with

conductor. All metal surfaces whatever to be also so connected.

36. Sir W. S. Harris considers the relative conductivity of the several

metals as being—of lead 1, tin 2, iron 2½, zinc 4, copper 12. So lead

cannot be altogether depended on.

37. Avoid long lengths of horizontal conductors without earth contacts,

as the currents might leave the conductor, and pass to earth, causing

danger. Avoid sharp angles.

38. Good earth connections most important. Conductors are to be led into

springs or wells or earth permanently wet. Not into watertight tanks.

Shingle, dry sand, or dry mould are not sufficient. Provide several

earth connections in all large systems of conductors as a precaution.

39. Lead conductors into ground in trenches 18 inches deep. Not less

than 30 feet of metal to be in contact with moist earth.

40. Lead a flow of water over trenches if possible, _e.g._, from rain

water pipes.

41. Trenches in rocky or dry soil to be 30 to 120 feet long, so as to

obtain all moisture possible.

42. Connections in trenches may be of old iron, forming continuous

metallic surface, the trenches to be filled with cinders or coal ashes.

Water pipes form excellent earth connections, but gas pipes are

dangerous.

43–44. Frequently inspect conductors, especially as to joints connecting

different metals and defects in iron from rust.

45–46. Galvanize iron, care being taken that the coating is good.

47. Great care to be taken in case of contact of zinc coating with other

metals, especially copper.

_April 8th, 1875._

FRED. E. CHAPMAN.

_Inspector General of Fortifications._

APPENDIX A.—BY THE LATE SIR W. SNOW HARRIS, F.R.S.

1. The earth’s surface and clouds are the terminating surfaces of

electric actions, and buildings, &c., are only points, as it were, of

earth’s surface in which the whole action vanishes.

2. Electricity when confined to substances resisting its progress, as

air, glass, dry wood, stones, &c., exerts a terribly explosive power.

3. But when confined to bodies, such as metals, offering small

resistance, its violent expansion or disruptive action is greatly

reduced or avoided altogether, and becomes a continuous current

comparatively quiescent. But if body be small, as wire, it may be heated

or fused. Resistance is so small that a shock has traversed copper wire

at the rate of 576,000 miles a second; resistance increases with length

and diminishes with area of section of conductor.

4. So a building metallic in all its parts, or a man in armour is safe.

5. So endeavour to bring buildings into the same passive or

non-resisting state as if of metal.

6. So conducting channels of copper should be systematically applied to

walls, either in plates united in series one over another, not less than

3½ inches wide and 1/16th and ⅛th of an inch thick, or of stout copper

pipe not less than 3/16ths of an inch thick, and 1½ to 2 inches

diameter, fixed to building by braces or copper nails or clamps.

Terminals to be solid metal rods, projecting above to a moderate and

convenient height. Earth connections to be by one or two branches,

leading out about a foot below ground—if possible into moist ground, but

if dry, use old iron or other metallic chains so as to expose a large

metallic surface.

7. All metals in roof, &c., of building to be connected with main

conductors; any prominent chimney to have a pointed conductor taken

along it to metals of roof.

8. An electrical discharge never leaves a perfect conductor to pass to a

very bad one, so the apprehension of lateral discharge is absurd.

Furious discharges have fallen on the conductors to the masts of H.M.

ships, and passed through copper bolts in bottom without injury even to

persons leaning against the conductors.

9. Metallic bodies have no specific attraction for electricity more than

wood or stone have; all matter is indifferent so far as regards a

specific attraction. Lightning falls indiscriminately upon trees, rocks

and buildings, whether with metals about them or not; _e.g._, at

Plymouth Dockyard in May, 1841, a granite chimney, 120 feet high,

without any metal in it, was struck, and yet it was within 300 feet of a

clock-tower of equal height, having metal weathercock, a dome covered

with metal and large conductor along it to ground. The damage ceased

where the chimney passed through a massive metallic roof, having a

conductor from it to the ground. Here the lightning fell on a building,

which, according to the popular idea, held no “invitation” in preference

to a structure which _did_ hold such “invitation.”

10. If efficient conductors provide free and uninterrupted course for

electrical discharge, it will follow that course without danger to

general structure; if _not_, then this irresistible agency will find a

course for itself and shake all imperfect conducting matter in pieces in

doing so. The great object is to provide a line or lines of small

resistance in given directions, less than the resistance in any other

line of the building. The conductor no more attracts lightning than a

gutter or water pipe attracts a flow of water.

11. It follows that a magazine if of metal would be safer than if built

in the usual way. Metallic gutters and ridges, with continuous metallic

communications to earth, are unobjectionable.

NOTE.—It is as wrong to isolate conductors from buildings by glass or

resin, as it would be to place rain water pipes 10 feet from the

building from which they should carry off the water.

An instance is given of an iron conductor which was placed 10 feet from

a house, the latter being, notwithstanding, struck at the point nearest

to the conductor, which was untouched.

12. Pointed terminations tend to break the force of lightning when it

falls on them. Before explosion a large amount of discharge passes off

through pointed conductors.

Pointed conductors should be solid copper rods, about ¾ inch diameter,

and a foot long, united by brazing to the conducting tube. It is not

necessary to gild the points, or form them of platinum. Sometimes even,

this would be detrimental, as platinum has only half the conducting

power of copper. The oxidations of the surface of conductor is of little

moment; and in case of copper very trifling. In any case the conducting

surface is better than the bad—or non-conducting air. The electric

telegraph wires work well, though enclosed by gutta percha or other

non-conducting matter. It is sufficient if the terminal solid rod be

even roughly pointed. But even a ball, a foot diameter, would be a point

as opposed to 1,000 acres of charged clouds.

NOTE.—Experience contradicts the idea that the conductor protects a

certain area. The foremast of a ship has been struck, though the

mainmast has been protected by conductor.

13. Copper linings to doors and windows of magazines, are not

objectionable, but useless for keeping out lightning. They should be

connected with the general system of conductors.

APPENDIX B.—AS TO SOLID OR HOLLOW CONDUCTORS. BY SIR W. SNOW HARRIS,

F.R.S.

1. A given quantity of electricity melts the same quantity of metal,

whether in a solid or hollow form. So far it is immaterial which form

the conductor has. But supposing the mass of metal to be so large that

the heating effect may be neglected. It is proved that the greater the

surface, the less is its intensity or power at any point, the intensity

approaching the second power or square of the surface inversely. It is

important to give the charge free room of expansion by increasing the

surface of conductor, so as to reduce the mechanical activity of shock

to the least possible. Rectangular flat bars may be employed.

2. A rain water pipe communicating with main conductor, should have

earth connection. All imperfect substances, as masonry, and ship masts,

transmit a certain portion of electricity without explosive action. One

great use of the conductor is to relieve the wood or masonry of the

quantity it cannot discharge without explosion.

3. Conductors of small iron rod or wire are very objectionable. They

commonly rust at the joints, and have fallen to pieces, and often been

knocked to pieces by lightning. Iron may, certainly, be employed with

advantage, but should be galvanized. Zinc is an even better conductor

than iron; and being spread over the surface is not open to the

objection of making a conductor of two metals of unequal conducting

power. A good and efficient conductor might be formed of galvanized

iron. It should be of wrought iron, galvanized, of 2 inches diameter,

with screwed joints of _extra_ thickness. Copper tubing is, however,

always to be preferred.

4. In dry or rocky soil, complete the conductor by leading old iron

chains out from the walls in several directions, or by leading a flow of

water over them. Fortunately a thunder storm is usually attended by

heavy rains. The iron chains should extend 30 to 50 feet, and be a foot

or 18 inches under ground. The termination in a large surface of moist

earth would be preferable to that in a well, as the action is a

superficial one of expansion in all directions. In the _tin_ leaf

coatings of the electrical jar, the charge is not influenced by the

thickness of metal.

W. SNOW HARRIS.

REPORT ON THE DESTRUCTION BY LIGHTNING OF A GUNPOWDER STORE AT

BRUNTCLIFFE, YORKSHIRE. BY MAJOR Y. D. MAJENDIE, R.A.

(_Abstracted by G. J. Symons, F.R.S._)

The Gunpowder exploded at 4.30 p.m. on August 6th, 1878, during the

greatest intensity of a violent thunderstorm. The building, was brick,

with brick arched roof, length 9 feet, width 5 feet, height 6 feet

(internal dimensions). The store had a uniform thickness of three

bricks, and was furnished at the one end with an iron door, at the other

end with a lightning conductor. The conductor consisted of a copper wire

rope, 10 gauge copper wire, the rope being 7/16 inch thick, having four

points at the top (one large one in the centre, and three smaller ones

round it), it extended to about 13 feet above the top of the building,

and about the same length was carried into the ground and terminated in

a drain. The conductor had been erected in 1876, by Mr. John Bisby, of

Leeds, and was fixed to a pole distant about 2 inches from the end of

the building opposite to that in which the iron door was fixed, it was

not connected with the iron door in any way. No one was near the store

when the powder exploded, and it seems probable that the earth

connection of the conductor was bad, that the mass of iron in the door

offered at least an equally good path—and that the gunpowder was ignited

by a flash passing between, the two imperfect conductors.

[Illustration: View and Plan of Bruntcliffe Gunpowder Store]

“The only structural damage effected was produced by the impingement of

bricks, which striking with great force, had in a few instances,

partially penetrated or displaced brick work in the dwelling-houses and

buildings, and a portion of the iron of an iron church was broken by a

piece of projected _débris_. A brick was driven through a window in one

of the houses at three hundred yards, and broke a bedstead. As far as I

have been able to discover no other structural injury was occasioned.”

This accident appears to suggest several conclusions:—

“In the first place it appears to me to afford a striking confirmation

of the principle which has been repeatedly and emphatically enunciated

by Sir William Snow Harris and other authorities on the subject of

lightning conductors, that in order to secure an efficient protection

for a given building, all the metal of the building, and as far as

possible the whole of the structure itself, should be brought into

actual connection with the system of conduction; in other words, that

the general conducting power of the mass of the edifice should be

completed, and all attractive and prominent parts allied in one

protective combination, so as to “bring the whole” (as it has been

expressed by Sir William Snow Harris) “as nearly as may be into that

passive or non-resisting state which it would assume, supposing the

whole were a mass of metal.” In the present case, assuming the conductor

itself to have been efficient, a point which there seems no sufficient

reason for doubting, the system of conduction was obviously defective.

Not only was the whole length of the building left unprotected, the

conductor having been on a pole at one end, and carefully insulated from

the building, but the iron door which was at the opposite end, was

absolutely unconnected therewith, and was not itself supplied with any

earth connection.”

“It appears clear, therefore, that even what may be deemed _per se_ an

efficient lightning conductor, _i.e._ a conductor, which considered

alone, offers a path of little or no resistance even to a powerful

electric current, does not afford a reliable protection to a building

unless it be scientifically applied, and with due regard to those

principles upon which the more eminent authorities on electrical science

are agreed. To a disregard of these principles, especially in respect of

the iron door being left out of the system of conduction, and

unconnected therewith, I believe the present accident may be

attributed.”

REPORTS OF COMMITTEES ON THE POWDER MAGAZINES AT PURFLEET.

(Phil. Trans., 1773, p. 42, and 1778, Part I., p. 232.)

(_Abstracted by Prof. W. G. Adams, F.R.S._)

Report of a Committee consisting of the Hon. Henry Cavendish, Dr.

Watson, Dr. Franklin, Mr. J. Robertson, Mr. Wilson, and Mr. Delaval,

appointed by the Royal Society, “to consider of a method for securing

the powder magazine at Purfleet.”

A powder mill at Brescia having blown up in consequence of being struck

by lightning, the Board of Ordnance applied to Mr. B. Wilson to know in

what way the powder magazine could be protected. He recommended that a

blunt conductor should be employed, whereas Dr. Franklin recommended a

pointed conductor. The Committee met and Dr. Franklin read a paper on

the subject, and the report of the Committee was in conformity with Dr.

Franklin’s views.

The Committee went to Purfleet and examined the buildings. They found

that the barrels of powder, when the magazines were full, lay piled on

each other up to the spring of the arches; on each barrel were four

copper hoops, which with vertical iron bars formed broken conductors

within the building. These iron bars were ordered to be removed.

The Committee advised that at _each end_ of each magazine a well should

be dug in or through the chalk, so deep as to have in it at least four

feet of standing water. From the bottom of this water should arise a

piece of leaden pipe to or near to the surface of the ground, where it

should be strongly joined to the end of an upright iron bar, an _inch

and a half_ in diameter, fastened to the wall by leaden straps, and

extending ten feet above the ridge of the building, tapering from the

ridge upwards to a sharp point, the upper twelve inches of copper, the

iron to be painted.

Lead was mentioned for the underground part as less liable to rust, in

the form of a pipe as giving greater stiffness for the substance, and

iron for the part above ground as stronger, and less likely to be cut

away. The pieces of which the bar may be composed should be screwed

strongly into each other by a close joint with a thin plate of lead

between the shoulders. Each rod in passing above the ridge should be

strongly and closely connected by iron or lead, _or both_, with the

leaden coping of the roof, so making metallic communication between the

two bars of each building.

It was also advised that two wells be dug within twelve feet of the

doors, one to the north of the north building and the other to the south

of the south building, and that metallic communications be made between

the water in them and the leaden coping of the roof.

The Board house stood 150 yards from the magazines, on elevated ground,

and was a “lofty building with a pointed hip-roof, the copings of lead

down to the gutters, from which leaden pipes descend at each end of the

building into the water of wells of forty feet deep, for the purpose of

conveying water forced up by engines to a cistern in the roof.”

As to the Board-house, they thought it already well furnished with

conductors by the several leaden communications above-mentioned from the

point of the roof down into the water, and that by its height and

proximity it may be some security to the building below it; they

therefore proposed no other conductor for that building, and only

advised erecting _a pointed iron rod_ on the summit, similar to those

before described and communicating with those conductors.

Mr. Wilson dissented from that part of the Report which recommended that

each conductor should be pointed, because, _he says_, “by points we

solicit the lightning, and may promote the mischief by drawing the

charges from charged clouds, which would not discharge at all on the

building if there were no points on the conductors.” By experiments made

and appealed to at the Committee the difference in the effects between

pointed and blunted conductors is as twelve to one. Mr. Wilson states

that, “A thunder cloud, therefore, if it acted at 1200 yards distance

upon a point, would require a blunted end to be brought within the

distance of 100 yards, and beyond those limits would pass over it

without affecting it at all.” He also says, “The _longer_ the conductors

are above the building, the more danger is to be apprehended from them.

I have always considered pointed conductors as being unsafe by their

great readiness to collect the lightning in too powerful a manner.”

Mr. Wilson adds an account of an accident to St. Paul’s Church, and some

curious reasoning on it in support of his own views. (See Phil. Trans.

1773, p. 59–61.)

* * * * *

On the 15th of May, 1777, the Board House at Purfleet was struck by

lightning, and some of the brickwork damaged (See Phil. Tran., 1778, Pt.

I., p. 232). About 6 p.m., after heavy rain through the day, a heavy

cloud hung over the house for some time, and Mr. Nickson, who watched it

from the house and gives the account, says he suspected that some of the

conductors might find employment from it. He had not been long at the

window before a violent flash of lightning and clap of thunder came

together. The lightning struck one of the iron cramps that hold the

coping, and made a dent in the lead of the cramp and the stone adjoining

it, throwing some stone down and slightly disturbing about a cubic foot

of brickwork at A. The iron cramp was situated over a plate of lead, and

the ends of it, inserted in the stone, came within 7 inches of that

plate, which communicated with the gutter, and served as a fillet to it;

this gutter was part of the main conductor of the building. The

lightning struck through the stone, &c., to the corner of the plate,

fusing a very small portion of it. From this point no farther effect of

the lightning could be traced. At the distance of seven feet and a-half

from the place struck, a large leaden pipe went down from the gutter to

a cistern of water in the yard. It is remarkable that the surface of one

of the hip-rafters, four inches and a-half in diameter, covered with

lead (communicating with the gutter), and _reaching within twenty-eight

inches_ of the place struck, seems not to have been at all affected. The

distance from the point of the conductor on the house to the part struck

was forty-six feet.

[Illustration: View of Board House, at Purfleet]

A fresh Committee of the Royal Society, consisting of Mr. Henly, Mr.

Lane, Mr. Nairne, and Mr. Planta, recommended a channel to be made from

cramp to cramp round the parapet, filled with lead, and connected in

four places with the main conductor on the roof of the building.

Mr. Wilson again dissented from their report, and attributed the hanging

of a heavy cloud over the house (it being calm at the time) to the

presence of the pointed lightning conductor.

An account of Mr. Wilson’s elaborate series of experiments at the

Pantheon on a long cylinder to illustrate the effects of pointed and

rounded conductors occupies seventy pages of the Philosophical

Transactions; and another Committee of the Royal Society, consisting of

Sir John Pringle, Dr. Watson, Henry Cavendish, W. Henly, Bishop Horsley,

T. Lane, Lord Mahon, E. Nairne, and Dr. Priestley, report in favour of

having additional conductors ten feet high, with copper eighteen inches

long, finely tapered and acutely pointed placed upon the magazines. They

conclude that “elevated rods are preferable to low conductors terminated

in rounded ends, knobs, or balls of metal,” conceiving that, the

experiments and reasons, made and alleged to the contrary by Mr. Wilson,

are inconclusive.

Mr. Wilson’s objections are again urged by Dr. Musgrave, but called in

question by Mr. Nairne (see Phil. Trans., 1778, Pt. 2, p. 823), who

makes a series of experiments to illustrate the advantage of pointed

conductors.

Both Mr. Wilson’s and Mr. Nairne’s experiments agree in showing that

“pointed conductors draw off the electricity from a cloud at a much

greater distance than those which are blunted.” Mr. Wilson objecting

that this draws the charged cloud from a greater distance; and Mr.

Nairne concluding that “a charged body is exhausted of more of the fluid

by a pointed than by a blunted conductor,” and so is not likely to cause

so much damage since it discharges itself more gradually.

EXPERIMENTS AND OBSERVATIONS ON ELECTRICITY.

BY BENJAMIN FRANKLIN. Fifth edition. London, 1774.

(_Abstracted by Prof. T. Hayter Lewis, F.S.A._)

The author shows that pointed bodies draw off electricity much more

effectually than blunt ones.

When the land is hot, “the lower air is rarified and rises; the cooler,

denser air above, descends.”

The clouds meet over the heated place, “and if some are electrified and

others not, lightning and thunder succeed, and showers fall.”

“As electrified clouds pass over a country, high hills and trees,

towers, spires, masts, chimneys, &c., as so many points, draw the

electrical fire and the whole cloud discharges there.”

Therefore it is dangerous to take shelter under a tree. It is safer to

be in the open fields, especially if the clothes are wet.

Metals are fused, possibly without heat; the lightning creating a

violent repulsion of the particles of the metal it passes through.

[He afterwards admits this opinion to be erroneous.]

Describes experiments with sharp-pointed metallic bodies, and says: “May

not the knowledge of this power of points be of use to mankind in

preserving houses, churches, ships, &c., from the stroke of lightning,

by fixing on their highest parts upright rods of iron, made sharp as a

needle, and gilt, to prevent rusting; and from the feet of these rods

lead iron wire down the outside of the building into the ground; or down

one of the shrouds of a ship and her side till it reaches the water.”

“Would not pointed rods probably draw the electrical fire silently out

of a cloud before it came nigh enough to strike, and thereby secure us

from that most sudden and terrible mischief?”

He mentions the case of the topmast heads of a ship being struck, but

having flames upon them like very large torches before the stroke.

He thinks that if there had been a good wire conductor from the heads to

the sea there would have been no stroke or damage.

He records the experiments on the 10th of May, 1752, at Marly, of M.

D’Alibard, who placed upon an electrical body a pointed bar of iron 40

feet high. In a thunder storm sparks of fire were attracted from it.

Again, at Paris, on the 18th of May, with the same result, by M. de Lor,

with a bar of iron 99 feet high upon a cake of resin 3 inches thick and

2 feet square.

Similarly in London in July, 1752, by Mr. Canton.

He refers to other experiments.

He experimented in 1752 with a kite of thin silk (as being able to bear

the wet), having a very sharp-pointed wire fixed to its top, above which

it rose about a foot. The kite was raised by twine, the part in the hand

being made of silk and kept quite dry.

The pointed wire will draw the electric fire from thunder clouds, and

when the rain has wet (_sic_) the kite and twine, so that it conducts

the electric fire freely, they will be electrified, and the electric

fire will stream out plentifully on the approach of the knuckle.

“Spirits may be kindled, &c., as with a rubbed glass or tube, and

thereby the sameness of the electric matter with that of the lightning

be completely demonstrated.”

September, 1752. He erected “an iron rod to draw the lightning into his

house in order to experiment on it.”

After many experiments, he concluded that “the clouds of a thunderstorm

are most commonly in a negative state of electricity, but sometimes in a

positive state.” The latter, he believed, rare.

“So that, for the most part, in thunderstrokes, it is the earth that

strikes into the clouds, and not the clouds into the earth.”

In the contrary (rare) case the cloud was, “I conjecture, compressed by

the driving winds or some other means, so that part of what it had

absorbed was forced out, and formed an electric atmosphere round it in

its denser state, so communicated positive electricity to my rod.”

“The electric fluid, moving to restore the equilibrium between the cloud

and the earth, takes, in its way, all the conductors it can find (_v._

page 132 of Franklin’s book)—as metals, damp walls, moist wood, &c.—and

will go considerably out of a direct course for the sake of the

assistance of a good conductor.”

“Explosions only happen when the conductors cannot discharge it as fast

as they receive it, by reason of their being incomplete, disunited, or

too small, or not of the best materials for conducting.”

He supposes that a wire ¼ inch diameter will conduct the electricity of

any one stroke of lightning ever known.

Iron is the best material, as least liable to fuse.

“Pointed rods erected on buildings and communicating with moist earth

would either prevent a stroke, or, if not prevented, would conduct it so

that the building should suffer no damage.

He gives instances of a small wire acting as conductor and saving the

building, though the wire, being too small, was utterly destroyed.

His theory as to the crooked course of lightning is as follows:

“Who knows but that there may be, as the ancients thought, a region of

this fire (electric) above our atmosphere, prevented by our air and its

own too great distance of attraction from joining our earth. Yet some of

it be low enough to attach itself to our highest clouds,” which thence

become electrified, &c.

“I am still at a loss about the manner in which clouds become charged

with electricity, no hypothesis I have yet formed perfectly satisfying

me.”

He describes how he and others have been struck down by electric shocks

without feeling pain or sustaining permanent injury.

For protecting powder magazines, erect a mast not far from it, and 15 or

20 feet above the top of it, with a thick iron rod fastened to it,

reaching down till it comes to water.

“In buildings the rod may be fastened to the walls, chimneys, &c., with

staples of iron. The lightning will not leave the rod (a good conductor)

to pass into the wall (a bad conductor) through these staples. It would

rather, if anywhere in the wall, pass out of it into the rod to get more

readily into the earth.”

If the building be very extensive, two or more rods may be placed at

different parts for greater security.

It is well not to sit near the chimney, or gilt objects, during a

thunderstorm.

AN ESSAY ON THE CAUSE OF LIGHTNING, _and the manner by which the thunder

clouds become possessed of their electricity, deduced from known facts

and properties of that matter, to which are added plain directions for

constructing and erecting safe conductors. By_ JOHN SIMMONS. 8vo. 1775.

(_Abstracted by Prof. T. Hayter Lewis, F.S.A._)

“As on the earth the operation necessary for the excitation and

collection of the electric fluid is attrition.” ... “So we may

rationally conclude that attrition is the means of excitation and

collection of electric matter in the clouds as well as on the earth.”

By metallic conductors buildings may be preserved from the effects of

lightning

Electricity ascends from the earth to the clouds by means of moist air.

“A conductor is a continuation of metal from a certain height above the

highest part of a building to moist earth or water” ... “for easy and

safe passage of lightning.”

Metal is the best of all conductors.

The author quotes from Franklin “buildings that have their roofs covered

with lead and spouts of lead continued from roof into ground to carry

off the water, are never hurt by lightning when it falls on such a

building.”

The conductor may be made of any metal, and flat or round.

But nowhere less than ¾ inch diameter except at terminal.

But iron rusts, so copper or lead should be used. Lead is best, used in

strips 4 inches wide and ⅒th inch thick.

Good earth contact required in moist earth (going therein at least 5

feet) or water.

The several lengths of the conductor must be well in contact by being

screwed, if of iron; soldered, if of lead.

The upper terminal to be iron or copper rod 9 or 10 feet long, ¾ inch

diameter, and 2 to 5 feet above top of highest chimney or other part of

building.

It should be pointed as this attracts electricity better.

Lead roofs to be connected with conductor. (Examples given of house and

ship struck.)

No building or object is known to have been struck by lightning within

50 feet of a proper conductor. But a tree has been shivered within 52

feet, so we may conclude that protecting influence extends to 50 feet

horizontally in every direction from the point of conductor.

In gunpowder stores, conductors are not to be fixed to the buildings,

but at (say) 12 feet away, fastened to a standard, the top being as high

above the building as it can be conveniently.

No metal on sides or roof of the building is to be exposed to the

lightning so as to attract it.

A TREATISE on ATMOSPHERIC ELECTRICITY.

BY JOHN MURRAY. 1830.

(_Abstracted by Prof. W. G. Adams, F.R.S._)

In Chapter V., on lightning identified with electricity, the author

speaks of fire-balls and the Aurora Borealis, and ascribes the formation

of shooting stars to electrical action. He does not believe they come

from distant space into our atmosphere, but regards them as concretions

formed by a flash of lightning darting through gaseous media and

atmospheric air _expanded by heat_, carrying metallic dust and earthy

particles ejected from volcanoes, or carried up by _evaporation_ or

other causes, and diffused over an immense surface in the upper regions

of the air. “The lightning carries, like a _ploughshare_, the

accumulated matter in its progress, and, by the powerful electrical

attraction thus excited, these particles will be drawn into the vortex

of the lightning instantaneously; for, the lightning finally

encountering an electricity of an opposite kind, an explosion ensues,

and the collected mass is instantaneously fused and agglutinated, while

the meteorite thus formed tumbles to the ground.... We therefore do not

see the necessity of considering meteoric stones _extra atmospheric_.”

In this way John Murray goes on page after page, but the above will

probably be sufficient notice of his work.

The following are the conditions he lays down for a good conductor:—

1. A finely pointed summit to offer an unresisting entrance.

2. A sufficient length to anticipate, as it were, the descending

electricity, and receive it on its summit before it could reach any part

of the building.

3. A superior conducting power in the material of the rod to facilitate

its passage to the earth.

4. A sufficient thickness to prevent its fusion, which, however, will

greatly depend on the resistance it has encountered in entering the

conductor. And, finally

5. A safe conduction to a well or moist surface below ground.

He says: “Let the wires below ground in contact with moisture pass

through a cylinder of zinc before they diverge to form the root, the

copper wires will in this case always remain free from any oxidation.”

HARRIS’S LIGHTNING CONDUCTORS. REPORT _to the Committee upon_ MR. SNOW

HARRIS's _and other_ LIGHTNING CONDUCTORS.

(February 11th, 1840. Parliamentary Paper. Fcap. folio).

(_Abstracted by Professor W. E. Ayrton_).

Instances are given of ships not provided with lightning conductors

being struck and damaged, whilst others lying near, and provided with

conductors, were not injured. The question of lightning conductors

attracting lightning considered, and evidence shown to the contrary.

Lateral discharge from a lightning conductor considered. Evidence

against it, if only the conductor were continuous and of sufficient

size. Faraday considered that a man leaning against one of Harris’s

conductors when the electricity descended would not be hurt. Proposition

to place a globe of glass on the head of the mast in place of a

lightning conductor considered, and the conclusion arrived at that it

would do harm.

Wheatstone stated that “in the Report of the Committee of the Academy of

Sciences of Paris, appointed to investigate the utility of lightning

conductors, there is no instance on record of an iron rod of ½ inch in

diameter being fused or even made red-hot by a flash.”

Mechanical objections to lightning conductors on ships considered and

discussed. Decided that the application of Mr. Harris’s conductor tended

rather to strengthen than weaken the mast and spars. Then follows a

large number of letters, giving accounts of accidents from lightning to

ships, &c.

Decision arrived at that on the whole Mr. Harris’s conductor is the best

of those examined.

THE DIFFERENCE BETWEEN LEYDEN DISCHARGES AND LIGHTNING FLASHES. BY C. V.

WALKER, Hon. Sec. Lon. Electrical Soc. London. 1842.

(_Abstracted by Prof. T. Hayter Lewis, F.S.A._)

The author alludes to the experiments of Franklin, &c.

The distance to the lower surface of clouds, observed by Le Gentil and

others, shows an average of 1000 to 2000 feet, whereas the greatest

length of spark with a large machine is 3 to 4 feet.

The inductive action bears some inverse ratio to the distance.

Leaves of trees have a remarkable property of silently drawing off

electricity.

He gives the particulars of a large number of experiments, with

arguments thereon, to prove the theory of the difference between Leyden

discharges and lightning.

Quotes examples of lightning on conductors and buildings to show that

the conductor takes part only of the charge, the remainder taking other

paths. Contiguous semi-insulated bodies must not be left unconnected

with the lightning rod.

He quotes, with approval, the advice of Faraday, viz., to tie together

with a metallic connection all contiguous readily-conducting bodies.

Cites numerous other opinions to the same effect, viz., that all

metallic parts of a building should be connected with the conductor.

He sums up by stating “that the Leyden charge differs considerably not

so much in _nature_ as in _degree_ from that of the cloud, inasmuch as

the proximity of the coatings in the one case is infinitely small

compared with the distance in the other,” &c.

He expresses great confidence in Sir W. S. Harris’s system for

protecting ships.

THE EFFECT OF A LIGHTNING FLASH ON THE STEEPLE OF BRIXTON CHURCH, AND

OBSERVATIONS ON LIGHTNING CONDUCTORS GENERALLY. BY C. V. WALKER. London.

1842.

(_Abstracted by Prof. T. Hayter Lewis, F.S.A._)

The author refers to Faraday’s experiments, as shewing instances of

lateral discharge, and says, “unless precautions are taken to prevent

its proceeding from a lightning conductor, that instrument literally

invites the enemy within doors.”

He gives detail of the accident at Brixton, there being no lightning

conductor.

The stroke did much damage to the steeple and then passed off harmlessly

by the metal gutters and rain-water pipes.

One side of the steeple was drenched with wet and carried off part of

the stroke.

He quotes examples of the apparently protective action of high trees.

Lofty trees near lofty buildings would materially mitigate, if not

prevent, the violence of the stroke.

The accident at Brixton shows that the lightning takes not simply the

_shortest_, but, in addition, the _largest_ path.

Had the steeple been provided with a lightning conductor outside,

passing near the clock face or the bells, or water pipe, it is more than

probable that a flash would pass from it to these vicinal conductors.

If _outside_ the tower the danger would be greater. He recommends that

the _metal_ cross on the steeple be _replaced_ by a _stone_ one, and

that the present iron rain water-pipes be connected by copper rods or

plates, which are also to be connected with the lead work of roof.

The bells are also to be connected with each other and with the

conductor.

Every bolt-clamp or other piece of metal within “striking distance” of

the conductor, unless in direct communication with it, is liable to

cause lateral discharge.

The odour developed by lightning was, at Brixton, decidedly sulphurous,

as a piece of stone which was shattered by the stroke retained the odour

of sulphur distinctly for several hours.

ON THE NATURE OF THUNDERSTORMS; AND ON THE MEANS OF PROTECTING BUILDINGS

AND SHIPPING AGAINST THE DESTRUCTIVE EFFECTS OF LIGHTNING. BY W. SNOW

HARRIS, F.R.S. 1843.

(_Abstracted by Prof. Ayrton._)

_The backstroke may do injury_, that is, a person may be killed in

consequence of a flash of lightning passing between the clouds and the

earth at some distance from the person.

In the Phil. Trans. for 1787, Mr. Brydone writes to the President of the

Royal Society, and mentions the case of two men riding in two carts, the

front one drawn by two horses, these horses and the man driving them

were killed;, the man on the hinder cart and a shepherd at a distance,

saw the occurrence and heard a report but observed no lightning.

_A metallic screen appears to protect the interior from the action of a

current, as well as from static induction._

Dr. Franklin found he could not destroy a wet rat by artificial

electricity, although he could a dry one.

The first lightning conductor was erected in England at Payneshill, by

Dr. Watson, in 1762.

The lightning conductor should expose a large surface, and should be

united with all the great masses of metal in its vicinity. For

stationary elevations the conductor should consist of solid or tubular

rods or flat plates of metal. We must consider the _mechanical_ action

the lightning may produce on the conductor, as well as any possible

heating action. Sir W. Snow Harris mentions that there were no signs of

fusion in the fragments of the linked brass rod, at Charles Church,

Plymouth, torn to pieces in 1824, or in the small pieces of the

conductor at the Hotel des Invalides, at Paris, consisting of a strand

of twenty iron wires, and which was smashed in 1839.

He says the benefical effect of _superficial_ conductors appears to

depend on the removal of the electrical particles further out of the

sphere of each other’s influences.

“Thus we find,” says Sir W. Snow Harris, “in a variety of cases of

damage by lightning that the passing charge, in striking on large

expanded sheets of metal has become comparatively tranquil, and has been

traced no further, whilst in striking on large masses of metal exposing

but a small surface, it has assumed an intensely active state.”

He goes on to state that the resistance of the conductor must be kept as

low as possible, and as neither the resistance nor the heat developed is

increased by rolling the wire out into a flat surface, he argues that

“there is, consequently, no disadvantage in giving a lightning rod as

much superficial capacity as possible, as regards conducting power,

whilst, on the contrary, the diminished intensity attendant on it is

very advantageous: this effect of superficial conductors appears to

depend on the removal of the electrical particles further out of the

sphere of each other’s influence.”

_What quantity of metal is requisite for a lightning rod?_ He concludes

from the results of a number of accidents that “a copper rod ¾ inch

diameter, or an equal quantity of copper under any other form, would

withstand the heating effect of any discharge of lightning which has yet

come within the experience of mankind.”

_Practical deductions._—“From the various enquiries contained in the

first 123 pages of this book, we arrive at the following deductions:—

“1st. Copper is the best kind of metal for a conductor.

“2nd. The quantity of metal should not be less than that represented by

the section of a solid cylinder ½ inch diameter.

“3rd. The metal should be placed under as great an extent of surface as

is consistent with strength, and should be perfectly continuous.

“4th. The conductor should involve in its course the principal detached

masses of metal in the building.

“5th. It should be placed as close as possible to the walls which are to

be defended, and not at a distance from them, and be carried at once

directly into the ground.

“6th. It should be attached to the most prominent points of the

building, and if the length be very considerable its dimensions should

be increased.

“Lastly. In extensive ranges of buildings, all the most prominent parts

should have long pointed rods projecting freely into the air, and the

greater the range of building the higher they should be.

“In particular cases, in which expense must necessarily be considered,

wrought iron tubing may be employed; it should not, however, be less

than 2 inches in diameter, and 3/10ths of an inch in thickness.”

Insulating the lightning conductor from the building is quite valueless.

The method of fixing lightning conductors to ships is explained at

considerable length.

_Range over which the protecting power of the lightning rod

extends._—Great doubts exists as to the answer to this question, since

in many cases one portion of a building has been struck while a

lightning rod in good condition existed close by.

For example, the powder magazine at Bayonne was 56 feet long, 36 feet

wide, covered with thick vaulted masonry and a sloping roof with gable

ends, protected by plates of lead; the gutters were also of lead, and

there were the usual spouts for discharging the rain. The lightning rod

projected about 20 feet above the building, and was attached to the lead

of the roof by a metallic socket through which it passed, and which was

soldered to one of the lead coverings. Instead of being carried,

however, directly into the earth at the foot of the wall, it was turned

outward at about 2 feet from the ground, and being bent at right angles,

was continued on semi-insulating posts of wood into a trench filled with

charcoal, distant 33 feet from the wall.

On the 23rd of February, 1829, the building was struck, the point of the

conductor melted, and the leaden plates by which it was attached to the

wood posts at the foot of the wall, were more or less torn and

perforated by holes. No damage, however, ensued to the building in the

course of the conductor. At the south-west corner, a sheet of lead

covering the gable end was torn out immediately over a point where two

stones of the cornice were united by an iron cramp.

Sir W. Snow Harris considers the possibility of this damage having

arisen “from the conductor (in consequence of being continued at so

great a distance from the building) not offering a sufficiently easy

line of transit for the discharge to the earth,” but he rejects this

explanation and concludes that the damage arose from the lightning

striking the building in two points.

Again, the Heckingham poorhouse, although armed with eight pointed

lightning rods, was struck, in 1787, at a point _m_, 70 feet from the

nearest conductor _c_.

[Illustration: View and Plan of Heckingham Poorhouse]

[Illustration: View and Plan of Heckingham Poorhouse]

The squares at _a_, _b_, _c_, _d_, _e_, _f_, _g_, _h_, indicate chimneys

to which lightning conductors were attached. The centre range was 108

feet long, the flanks each about 160 feet long: the details of the

lightning conductors are not given. One portion of the lightning

discharge struck one of the conductors and was carried off by it without

damage to the building, one portion struck the building at the point _m_

and also the shed at _s_, doing some damage, and a third portion struck

the ground immediately in front of the building near a gate, G.

The ship _Ætna_ was struck in 1830 by several heavy electrical

discharges when at Corfu. These for the most part passed down a chain

conductor attached to the mainmast. One of the discharges, however,

struck the ship near the bow, and exploded about 12 feet above the

forecastle close to the foremast, knocking people down, &c.

The Board-house at Purfleet was a lofty building with a pointed roof,

well leaded and connected by lead gutters and pipes with the earth, and

with wells 40 feet deep for the purpose of conveying water forced up to

a cistern on the roof. It was, therefore, only thought necessary to add

an iron spike about 10 feet long to the middle of the highest part of

the roof. The building, however, in 1777, was struck and slightly

damaged at a point 46 feet from the conductor.

Several other examples illustrating how small an area a lightning rod

protects follow.

Sir W. Snow Harris further concludes that experience shows that

lightning will not leap from a lightning rod to a piece of insulated or

semi-insulated metal near it, although a discharge may take place

between the rod and a distant metallic mass in connection with the

earth, but not otherwise in connection with the rod.

He lastly considers the question, formerly much debated as to whether a

lightning rod attached to a house will attract to the house a discharge

that otherwise would not have struck it, and he concludes that there is

no foundation for the erroneous impression that the existence of a

lightning conductor can ever cause damage.

AN ACCOUNT OF THE CHIMNEY OF THE EDINBURGH GAS WORKS. BY G. BUCHANAN,

C.E., F.R.S.E.

[Proceedings of the Royal Scottish Society of Arts, 1850–51.]

(_Abstracted by G. J. Symons, F.R.S._)

This chimney has a total height of 341½ feet (329 feet above ground), it

is circular; at the top the internal diameter is 11 feet 4 inches, and

the external 13 feet 10 inches; and at the bottom, internal diameter 20

feet, external 26 feet 3 inches.

Respecting the conductor Faraday was consulted, and replied as follows:—

“The conductor should be of ½ _inch copper rod_, and should rise above

the top of the chimney by a quantity equal to the width of the chimney

at the top. The lengths of rod should be well joined _metallically_ to

each other, and this is perhaps best done by screwing the ends into a

copper socket. The connection at the bottom should be good; if there are

any pump pipes at hand going into a well they would be useful in that

respect. As respects electrical conduction, no advantage is gained by

expanding the rod horizontally into a strap or tube—surface does

nothing, the solid section is the essential element.[4] There is no

occasion for insulation (of the conductor) for this reason. A flash of

lightning has an intensity that enables it to break through many hundred

yards (perhaps miles) of air, and therefore an insulation of six inches

or one foot in length could have no power in preventing its leap to the

brickwork, supposing that the conductor were not able to carry it away.

Again, six inches or one foot is so little that it is equivalent almost

to nothing. A very feeble electricity could break through that barrier,

and a flash that could not break through five or ten feet could do no

harm to the chimney.

Footnote 4:

The very reverse of what was formerly held by high authorities.—[Note

by Editor of Proc. Roy. Scot. Soc. of Arts.]

“A very great point is to have no insulated masses of metal. If,

therefore, hoops are put round the chimney, each should be connected

metallically with the conductor, otherwise a flash might strike a hoop

at a corner on the opposite side to the conductor, and then on the other

side on passing to the conductor, from the nearest part of the hoop

there might be an explosion, and the chimney injured there or even

broken through. Again, no rods or ties of metal should be wrought into

the chimney parallel to its length, and therefore to the conductor, and

then be left unconnected with it.”

In answer to some further inquiry, Professor Faraday again wrote:—

“The rod may be close along the brick or stone, it makes no difference.

There will be no need of rod on each side of the building, but let the

cast-iron hoop and the others you speak of be connected with the rod,

and it will be in those places at least, as if there were rods on every

side of the chimney.

“¾ rod is no doubt better than ½ inch, and except for expense I like it

better. But ½ inch has never yet failed. A rod at Coutt’s brewery has

been put up at 1½ inch diameter—but they did not mind expense. The

Nelson column in London has ½ inch rod, ¾ is better.

“I do not know of any case of harm from hoop-iron inclosed in the

building, but if not in connection with the conductor, I should not like

it; even then it might cause harm if the lightning took the end furthest

from the conductor.”

The following paragraph states what was done:—

“The electric conductor stands 6 feet above the iron top-plate, ⅝-inch

round copper, made fast to stone and brickwork with 7⅞-inch copper

holdfasts let 4 inches into the masonry or brickwork, with a head on the

inside and an eye on the outside to receive the rod as it was carried

up. By these holdfasts an ascent can easily be made to the top by a

small tackle suspended to the holdfasts. The conductor is metallically

connected to all the ironwork on the stalk—the plate on the top,

projecting cope, malleable iron hoops, bolts on the top of stone

pedestal, and also the ascending chain. The rod descends into a well

about 10 feet from the foundation, and is immersed about 8 feet deep in

water, and the end turned up 2 feet in a horizontal direction, and

flattened.”

PAPERS _relative to_ SHIPWRECKS BY LIGHTNING, _as prepared by_ SIR SNOW

HARRIS, _and presented by him to the Admiralty_.

(August 5th, 1854. Parliamentary Paper. Fcap. folio).

(_Abstracted by Professor W. E. Ayrton_).

Number of merchant ships destroyed by lightning, loss to the country.

Application of lightning conductors to ships in 1820. Mode of applying

them. Mechanical difficulties; how overcome. The saving to the Exchequer

which has resulted.

Long account of various ships in the Royal Navy not provided with

lightning conductors, struck by lightning and damaged. Loss of life and

injury that has resulted. Long account of ships provided with lightning

conductors, and so preserved.

Sir Snow Harris states that “although his system of lightning conductors

ought to guard against all those violent and regular shocks of lightning

falling within the ordinary experience of mankind, it is not to be

expected that the system could guard against every possible kind of

atmospheric electrical discharge, be the circumstances what they may,

such as thunderbolts, fire-balls; nor is it expected that it should

guard against meteorolites, or against sweeping electrical action mixed

up with convulsions of nature; nor can it quiet those minor electrical

effects producing electric glow; nor can it always obviate that

tremendous concussion and expansion of the atmosphere in cases in which

a thunder-cloud discharges its lightning in a dense explosion on the

masts, and which may rupture, or mechanically tear to pieces, frangible

matter.”

STATISTICS OF BUILDINGS AND SHIPS STRUCK BY LIGHTNING. BY F. DUPREZ,

MEMBER OF THE ACADEMY.

[Académie Royale de Belgique, Extrait du Tome 31 des Mémoires, 5th

December, 1857.]

(_Abstracted by Professor T. Hayter Lewis, F.S.A._)

M. Duprez refers to the Report of a Committee of the Institute of

France. (Vide _Comptes rendus_, 1852–6.)

He divides the subject into the following heads:—

1. The frequency with which lightning rods are struck.

2. Their terminal points and the effects of the stroke on them.

3. The conductors and their ground connections.

4. The protective power of the lightning rods.

1. _Concerning the frequency with which lightning conductors are struck

by lightning._

The author cites 144 cases of lightning rods having been struck. Of

these seventeen were struck two or three times, so that the total number

of electric discharges on them was 168, as far as recorded.

But very many cases are not recorded at all, _e.g._, from 1793 to 1813

only two cases were noted. The great number of lightning rods struck

would seem at first to support the idea that they attract lightning.

But we must compare the number of rods struck with those fixed, and we

find from a communication made in 1777 to the Academy of Berlin, that,

even then, a large number were fixed to the most important edifices of

N. Italy and England.

The same in 1784 to those in the ports of France and to the ships in the

said ports.

In 1794 the fortresses of Russia were ordered to be so protected.

In 1769 there were 166 edifices in Hamburg alone, and 104 in its

environs, with conductors.

If the number of conductors were so great in the last century, we must

conclude that the number of those struck must be very inconsiderable as

compared with those fixed.

In Hamburg, _e.g._, not one rod is recorded as having been struck.

In 1785, Ingen-Housz reports that of all the lightning rods placed by

his direction on the Austrian powder magazines and other buildings only

one had been struck.

In 1772, Franklin wrote, that during the twenty years in the course of

which lightning rods had been fixed in America he knew of five cases

only in which these rods had been struck.

Sir W. S. Harris reports in 1854, as the results of twenty-two years’

experience, that the number of vessels struck unprotected by lightning

rods, as compared with that of vessels protected by his plan, was as

three to two.

The above show that the idea of danger from lightning rods is not well

founded.

Besides which it must be remembered that they are frequently placed in

the most exposed positions, _e.g._, of the 144 rods struck, seventy-four

were on ships, and fifteen others on buildings which had been struck

before.

One would think that the number of terminals placed on a building would

diminish the chances of their being struck, but it does not seem to be

so; _e.g._, twelve buildings in the first list had many terminals

communicating with a common conductor or different conductors.

Yet the lightning struck, with explosive effect, one or other of the

rods of these buildings.

And in each of two cases the lightning struck at once the three rods

fixed to a building.

Of the 144 cases above cited:—

74 were to lightning rods fixed on ships

30 were to lightning rods fixed on towers

9 were to lightning rods fixed on powder magazines

31 were to lightning rods fixed on ordinary buildings.

———

144

In forty-four cases where one of Sir W. S. Harris’ conductors was fixed

to each mast of a ship, the mainmast was struck twenty-seven times; the

foremast was struck fourteen times; the mizen was struck twice; both the

main and foremast twice.

2. _As to the points of the lightning rods struck, and the effect

produced on them._

(Sir W. Snow Harris’s system as adopted in the British Royal Navy since

1830 is described. They are formed of bands of copper let into the

masts. They have no upper terminals or points, and fifty-five are

included in the list already quoted of 144 lightning rods struck.)

Of the eighty-nine cases remaining in the list, only fifty-one are

recorded as having their upper terminals ended with points.

Of these, thirty had their points melted to a greater or less extent;

six of them were of copper or brass; five were of copper gilt or iron

gilt; one was of brass silvered; and four were of platinum. The others

are not distinctly described, and the sizes seldom given.

One of brass was 25·4 centimetres (c. 10 inches) long, and 5 millimetres

(⅕th inch) diameter at its base, and was melted for ¼th of its length.

One of copper was 24 centimetres (c. 9½ inches) long, and 9 millimetres

(c. ⅓rd inch) diameter at base, and was almost all melted.

One of platinum was 8 centimetres (c. 3 inches) long, and 1 centimetre

(c. ⅓rd inch) diameter at base. This was melted for a length of 5 or 6

millimetres (c. ⅕th inch.)

It results from the above facts that the points of the lightning rods

have been much too slender.

The Institute of France recommends, therefore, for the points 2

centimetres diameter (c. ¼th inch) at base, and only 4 centimetres (c.

1½ inches) high, with an angle of opening of 28 to 30 degrees.

It has been urged, especially in Germany, against the employment of

pointed upper terminals that these points are fused by the lightning,

this fusion being regarded as dangerous on account of its action on

inflammable substances near.

As to this, the author cites three cases of buildings set on fire,

though protected by lightning rods. But the precise cause of the fire

was not ascertained.

Several observations show that the melted metal trickled down the side

of the lightning rod.

At Strasbourg the metal was pressed down on one side, and had bent like

wax softened by heat. At other times the lightning disperses the melted

metal in all directions. (Examples quoted.)

With these facts before us we cannot altogether deny that some danger

may arise from the fusion of the metal at the point of the terminal. But

this danger can be much lessened, if not removed, by adopting the size,

etc., of the lightning rods recommended by the Institute of France.

Besides fusion, the points sometimes show distinct traces of mechanical

action caused by lightning.

The author quotes six examples of this where the points had been curved.

This shows the necessity of strengthening the points of the upper

terminals. The curvature arises, probably, from the points being much

heated by the lightning, and acted on by the wind.

One case is noted of a point which had the appearance of having been

struck violently by a hammer.

Also of one in which the base of a point, where it was screwed to the

rest of the upper terminal, was split for a length of 11 millimetres (c.

½ inch).

Also of a platinum point screwed on the upper terminal (copper), and

retained by a pin, where the stroke tore away the pin, the point falling

intact at the foot of the lightning rod.

3. _Of Conductors of lightning rods struck, and their contact with the

ground._

The author refers to forty-one cases of lightning rods struck when not

on Harris’s principle.

Of these, 5 were of copper bands soldered together; 5 were of copper

wire either as rope or chain; 1 was made of bands of sheet iron; 11 were

of bars of iron joined by screws or by solder; 3 had pieces of lead

between the parts where they were screwed together; 3 were of simple

iron wire, or of rope or chain of iron wire; 3 were of iron joined

together by hooks; 12 are described as chains (metal not specified); 1

is described merely as a conductor.

The dimensions of the above are seldom given.

The largest bands reported are 16 centimetres (c. 6¼ inches) in width.

The largest bars reported are 55 centimetres (c. 2¼ inches) in width and

15 centimetres (c. ½ inch) in thickness.

The description of the earth connection is also imperfect.

Of eighty-nine lightning rods described as struck, only twelve are noted

as having their ends in running water or wells, and one in damp soil.

Fifteen simply entered the ground, it being noted expressly of six of

these that it was dry.

In three cases were the lightning rods were struck the author found that

the part at the base and in the damp earth had terminated in a plate of

lead, protected above the ground by a wooden enclosure.

Three conductors of ships did not communicate with the sea.

Twenty-three cases are noted of ordinary conductors (not on Sir W. S.

Harris’s principle).

The lightning melted, or reduced almost to powder, three.

The first was on a house, and was of copper wire, the diameter not

known, ending with a chain of iron buried in the earth.

The second was on a ship’s mainmast, and was of iron wire 6 millimetres

(c. ¼ inch), diameter, 46 centimetres (c. 18 inches) long, folded at

their extremities, and united by rings.

The third (also to a ship) was a rope of three strands formed in the

whole of 60 brass wires, each being one half to two-thirds of a

millimetre thick.

The two last conductors had their ends in the sea.

The parts of these conductors, in place of being soldered or screwed

together, were joined merely by hooks and rings like a surveyor’s chain.

Evidently a bad form as their contact is imperfect.

In three other conductors, whose different parts were screwed together

with lead between them, the stroke melted the lead.

This shows the danger of lead from its fusibility, in addition to its

less conducting power.

The author gives examples of this, wherein a leaden pipe, 8 centimetres

(c. 3¼ inches) external diameter, and 13 millimetres (c. ½ inch) thick,

was melted.

He quotes Arago as calling attention to the importance of the form of

the bends in conductors, abrupt bends being dangerous.

Two examples are quoted to prove this, the conductors having been broken

by the lightning stroke at a sudden bend.

To provide lest the lightning, after having struck the lightning rods,

should abandon them for larger masses of metal near them, these masses

should be made to communicate with the conductors.

Cases are cited where the lightning quitted the conductor and struck

metallic bodies near. Also, in respect of painting conductors, the

author quotes a case where part of a bell wire adjoined a lead pipe

which communicated with the conductor. Part of the wire was painted in

oil colour, the other part not. The latter was melted, the first not,

but the paint (though otherwise uninjured) had ceased to adhere to it.

Three examples are cited of danger from conductors ending in watertight

tanks.

In one case the stroke broke the conductor.

In another it left the conductor and injured the building.

In the third it merely melted the point of the upper terminal.

Nevertheless, it often happens that the lightning, in spite of imperfect

communication with the earth, disperses itself inoffensively.

Out of fifteen cases of lightning rods struck, in which the conductors

were simply buried, more or less, in the soil, they carried off the

stroke in eleven without the buildings being injured, or any trace being

left of it, except that the ground was upheaved where the latter was too

dry.

The French Institute, in their report on the protection of the Louvre,

considered it necessary to employ, under certain circumstances, a

conductor with two branches, the one descending into a subterranean

source of water, the other communicating simply with the surface of the

earth.

On the other hand, Arago thought that conductors need not enter the

ground, but communicate only with a metallic surface lying on the

ground.

This view is confirmed by the cases which the author mentions where the

surface of the earth being wetted by rain formed a conductor.

Nevertheless, the two branches are desirable, in case one should fail.

Fifty-five conductors on Sir W. S. Harris’s system are recorded as

having been struck, but the damage was quite trivial.

Two electrical phenomena are to be noted as sometimes occurring when a

lightning rod is struck.

First, when a conductor is formed of metallic plates a peculiar noise is

heard like water pouring on a fire.

Second (independently of the form of the conductor), electric sparks are

emitted from bodies near. The author cites example at Berne, 1815.

4. _Protective agency of lightning rods._

Out of 168 cases of lightning rods struck (_vide_ page 91) there are

only twenty-seven (c. ⅙th) in which the buildings or ships have not been

preserved, and of this sixth many of the conductors were imperfect;

_e.g._, four terminated in earth which was unusually dry, and two of

them were of insufficient size.

Another was formed of pieces having their ends hooked.

Two conductors ended in watertight tanks.

Another was in the form of a surveyor’s chain, the parts not being,

consequently, in close contact.

Others were badly jointed, or had imperfect communication with the

ground or with the sea.

In two cases the stroke broke the conductor at points where its

direction was abruptly changed.

In two other cases the lightning left the conductors struck, and fell

upon buildings near without causing damage to those on which the rods

were fixed.

In the instance of a lightning rod fixed to the mainmast of the

_Jupiter_ (1854), the conductor was made of sixty brass wires, one half

to two-thirds of a millimetre (0·02 inch) thick, and was broken by the

stroke into thousands of pieces. The Institute Committee concluded that

the lightning was not conducted by all the wires of the conductor. Those

which it followed were insufficient to transmit it; some were melted,

some broken. The Committee recommended, therefore, that each metallic

wire be tinned separately at the extremity of the conductor, and

soldered thereto for a length of about a decimeter (c. 0·4 inch), so as

to form a metallic cylinder.

In the last six cases the particulars of the lightning rods are not

given sufficiently to show the cause of their failure, but five are

described as being of chain or ropes of metal wire.

It results from the above facts that when the lightning rods have proved

insufficient protection, their failure has been owing to defects in

their construction; it is rather surprising to find how well buildings

and ships have been protected, even when the lightning rods have not

been well constructed.

In every one of the fifty-five cases where Sir W. S. Harris’s rods were

fixed they have protected the ships, except that not having points some

slight damage has sometimes occurred to the tops of the masts.

This shows their superiority over ropes or chains.

Arago thought that lightning rods were protection against ordinary

lightning, but not when it assumed the form of fire-balls. The author

cites several examples to show that this opinion was not well founded.

He considers a perfectly constructed lightning rod to be a perfect

safeguard.

But he adds that the lightning stroke produces electric disturbances in

its vicinity, although the building be intact.

He cites an example of this in respect of a prison whose inmates (300)

experienced a great enfeebling of their muscular power during some

seconds.

Very few records exist relating to the area of action of lightning rods,

and the elements for determining their protective power are slight. The

author gives a table showing the heights of points, horizontal

distances, &c., in certain cases, and cites four instances of ships

whose foremasts were struck although the mainmasts had lightning rods,

and one where the mizen was struck though the fore and mainmasts were

protected.

TABLE GIVEN BY M. DUPREZ.

┌─────────────────────┬───────────────────────┬───────────────────────┐

│ │ IN METRES. │ IN ENGLISH FEET. │

├─────────────────────┼─────┬─────┬─────┬─────┼─────┬─────┬─────┬─────┤

│ │ 1st │ 2nd │ 3rd │ 4th │ 1st │ 2nd │ 3rd │ 4th │

│ │Case.│Case.│Case.│Case.│Case.│Case.│Case.│Case.│

├─────────────────────┼─────┼─────┼─────┼─────┼─────┼─────┼─────┼─────┤

│Length of upper │ 1·5│ 3·4│ 1·5│ 2·3│ 5│ 11│ 5│ 8│

│ terminal, or height│ │ │ │ │ │ │ │ │

│ of point above │ │ │ │ │ │ │ │ │

│ that portion of the│ │ │ │ │ │ │ │ │

│ building on which │ │ │ │ │ │ │ │ │

│ the upper terminal │ │ │ │ │ │ │ │ │

│ was fixed. │ │ │ │ │ │ │ │ │

│Vertical height of │ 1·5│ 7·6│ 6·7│ 71·2│ 5│ 25│ 22│ 232│

│ point above the │ │ │ │ │ │ │ │ │

│ place struck. │ │ │ │ │ │ │ │ │

│Horizontal distance │ 15·2│ 7·3│ 17·4│ 59·9│ 50│ 24│ 57│ 197│

│ of place struck │ │ │ │ │ │ │ │ │

│ from the base of │ │ │ │ │ │ │ │ │

│ upper terminal. │ │ │ │ │ │ │ │ │

└─────────────────────┴─────┴─────┴─────┴─────┴─────┴─────┴─────┴─────┘

These instances show that we should be misled in considering, as being

protected, a circular space whose radius was double the height of the

lightning rod.

The protected radius appears to be only equal to double the simple

height of the upper terminal above any required point, and reckoned

horizontally from a point vertically under the conductor.

[It will be observed that M. Duprez here contradicts himself in two

consecutive sentences, and in a subsequent part of his work (p. 30) of

the Memoir, he again says: “Aucun des cas indiqués dans le numéro

précédent n’infirme la règle généralement admise, savoir que la sphère

d’action d’un paratonnerre s’étend, dans toutes les circonstances, à un

espace circulaire d’un rayon égal au double de la longeur de la tige,

c’est-a-dire de la hauteur de la pointe au-dessus de la partie du

bâtiment sur laquelle la tige est fixée.”

But the table given by M. Duprez gives two instances in which the stroke

fell within the radius of once the height.—Ed.]

RESUMÉ.

In the paragraphs which the author numbers 1, 2, 3, 4, and 6, he refers

to former statements as to the proportion of lightning rods struck, &c.

(_Vide_ page 91, &c.)

5. There being several terminals on an edifice does not seem to diminish

the chances of each being struck.

7. In vessels, when the three masts have lightning rods, the mainmast is

most frequently struck.

8. Refers to Sir W. S. Harris’s lightning rods as being without terminal

rods or points.

9. The points of ordinary lightning rods have been made too slight.

10. Out of fifty-one cases of lightning strokes, thirty points have been

more or less melted; and the fusion is not without danger to the

buildings.

11. The lightning often leaves traces of mechanical action more or less

decided.

12. Refers to defective constructions of ordinary lightning rods.

13. Lead plates in conductors composed of bars joined together are

dangerous.

14. So are abrupt bends.

15. Conductors should communicate with the masses of metal near.

16. And must not end in watertight tanks. But

17. Conductors often protect buildings, though the ground connections

are imperfect.

18. It is well for a conductor to have two branches, viz., one in water,

and the other on the surface of the ground.

19, 23. Refers to the complete efficiency of Sir W. S. Harris’s

conductors.

20. Mentions the noise, electric sparks, &c., given off during a stroke,

as before stated (page 95).

21. Mentions the efficacy of lightning rods generally.

22. Their failure being owing to defective construction.

24. There is no proof that the electricity being in the form of a ball

has been the cause of any conductor’s inefficiency.

25. The lightning rarely bursts on a building or ship without striking

the lightning rod placed on it. Exceptions have, however, occurred in

ten cases, as here described. But

26. None of these instances invalidate the rule generally admitted, that

the protective action of the lightning rod extends, under all

circumstances, to a circular space whose radius is equal to double the

length of the upper terminal, _i.e._, the height of the point above the

part of the building on which the upper terminal is fixed.

ON ATMOSPHERIC ELECTRICITY.

BY REUBEN PHILLIPS. LONDON, 1863.

(_Abstracted by W. H. Preece, C.E._)

This is a pamphlet of seven chapters, and fifty-seven pages, written to

ventilate the author’s own notions of the nature of electricity and its

production in the atmosphere. He considers electricity to be two fluids

of a species of substance, consisting of separated subsidiary atoms.

“Electricity is comparable to a flying bullet; the _vis vivâ_ of the

bullet is like electrical intensity, and the mass of the bullet answers

to the quantity of electricity.” What the subsidiary atoms are like he

does not say.

Chapter I. is a fair resumé of what is known of the electricity evolved

by the friction of wet steam against solids in the hydro-electric

machine. He agrees with Faraday that the cause of the evolution of

electricity by the liberation of confined steam, is not evaporation, but

the friction of the water particles against the sides of the jet-piece

or orifice. Pure gases do not excite electricity; but impure air, when

compressed does, from the friction against the orifice of those

particles of water which are suddenly condensed by the cooling influence

of the expanding air.

Lightning Rod Conference Report of the Delegates from the Following Societies, Viz.: Meteorological Society, Royal Institute of British Architects, Society of Telegraph Engineers and of Electricians, Physical Society. With a Code of Rules for the Erection of Lightning Conductors; and Various Appendices · 第 1 / 8 章