DIRECT-CURRENT TRANSFORMERS OR DYNAMOTORS.

The method of transforming by direct current without the aid of

batteries is not practically at work; but, as the advantages are so

obvious and its development is only a question of time, a description

of the system may not be considered out of place.

The electrical exhibition at Philadelphia in 1884 contained a dynamotor

which was exhibited by the Van de Poele Electric-Light Company, but,

as far as could be ascertained, was not worked, and, as it was simply

described as an induction machine for distributing currents for the use

of incandescent and other lights, it attracted little attention.

The advantages of an alternating current transformer system of

distribution, Class II., has been put forward in these pages,

especially that of simplicity and cheapness. An alternating current

dynamo for a given output is cheaper than a direct, and it takes less

labour to look after it, because it has no commutator.

An alternating transformer is also an exceedingly simple piece of

apparatus. If originally made with due care and kept in a dry place, it

never breaks down, as it has no moving parts, and so there is nothing

to go wrong.

The alternating system of distribution has, however, some very serious

disadvantages. In the first place, it is most important that motors

should be driven during the day when the lights are not in use. In the

second, batteries cannot be used in an alternating current system, so

any immunity from breakdown that they might ensure is wanting; and

steam must be kept up all day and all night.

If motors are wanted during the day, so that the load on the engine is

nearly constant, batteries are not so valuable, except with a view of

preventing a breakdown; but, if batteries cannot be used, the advantage

of using motors becomes enormous, as the plant has to be large enough

to supply the maximum load, and would otherwise be idle during the day.

In alternating current systems there are two difficulties in the way

of using motors. It is difficult to make an alternating current motor

that will start, and, if that difficulty is surmounted, it is difficult

to make an alternating current motor that will work on varying loads

without great waste of power. The question of the efficiency of

alternating current motors has never been really practically studied

yet; and, until these difficulties are overcome, we must regard

alternating current motors as non-existent. Several methods of working

alternating current transformers off direct currents by commutating the

primary have been proposed at different times; but they all seem to be

impracticable, and it seems impossible to get over the difficulties

that arise from sparking when it is attempted to break a high-tension

circuit.

One of the first methods of distribution over large areas proposed was

by means of motors and dynamos combined. For instance, suppose, in

order to keep down the size of the leads, 2,000 volts are used in the

mains, a motor capable of working with 2,000 volts is put down where

the lights are wanted, and this is made to drive a dynamo giving 100

volts and a large current. Instead of having a separate motor and a

dynamo connected by a belt or by coupling the spindles together, it is

simpler to make one machine with two armatures, or to have only one

armature with two circuits on it. One circuit is wound with fine wire

and takes the 2,000 volts and tends to turn the armature round. The

other circuit is wound with thick wire giving 100 volts and a large

current, and tends to stop the armature, thus absorbing the power

supplied by the high-pressure circuit. The direct-current transformer

or dynamotor is thus a sort of double dynamo, or dynamo and motor

combined. If it gets 2,000 volts and 10 ampères, it would, if there

were no waste, give 100 volts and 200 ampères; with a waste of 10 per

cent., it will give 100 volts and 180 ampères.

In the United States it is usual to place an alternating current motor

in each house to be lighted; but the conditions are quite different

there, overhead wires being used extensively. In this country this

system is not likely to find favour, and local sub-stations will be

used, the high pressure, which is always dangerous to life, will

thus be kept out of private houses and offices. There is, then,

very little difference in the cost of maintenance of alternating

current transformers and dynamotors, and the advantages possessed

by alternating current transformers in this respect are more than

counter-balanced by the use of motors on direct current circuits.

Dynamotors have not come into general use yet because no stations have

been started in this country of the size which demands them. No central

station with sub-stations is in operation, but there is every reason to

expect several will be soon; and it is very necessary to discuss the

various methods, not only in use at this moment but coming into use in

the immediate future. The dynamotor itself needs no working out, as

any maker of direct-current dynamos can, of course, make them. Messrs.

Paris and Scott of Norwich showed some in operation at the Newcastle

Exhibition in 1887; the most successful type is that recently invented

by Mr. Jas. Swinburne, illustrated by Fig. 29. The backward main round

primary or motor magnet is shown on the left, and the forward main

round the secondary or dynamo magnet on the right, the outside coil

round both magnets is the shunt.

[Illustration: FIG. 29.]

The dynamotor may be made with two circuits on one armature as

already explained, or it may have two armatures in separate fields,

still making up one machine. The first arrangement has two grave

disadvantages. There is difficulty about securing perfect insulation

between the two circuits, and this leads to chances of danger in the

houses. A dynamotor with two circuits on one armature cannot be

compounded, that is to say, it cannot be made to give constant

electrical pressure on the mains if the number of lamps is varied. A

Swinburne double armature machine can be compounded, not only to give

constant pressure with a varying load, but to give constant electrical

pressure even if both the load and the pressure on the primary circuit

vary. This makes a considerable difference in the copper of the primary

leads, as in large and complicated districts it is almost impossible

to arrange leads, even when working with high electrical pressure and

small currents, so that the electrical pressure remains constant,

or even nearly so. A very small variation of the pressure on an

incandescent lamp makes an enormous difference in the amount of light

it gives, and in its duration. It is, therefore, most important that

the E. M. F. on the lamps should be kept absolutely constant.

This difficulty is, of course, insurmountable in the case of

alternating current transformers. Alternating current transformers

cannot be made to compound, and the loss in leads cannot be corrected

by them, so that the lamps burn dull at full load.

If secondary batteries are used at the sub-stations, the reduction of

pressure might be effected by them. A number would be charged in series

and discharged in parallel. This arrangement needs at least two sets

of cells, and cells are expensive; and it is difficult to preserve the

insulation of cells with such electrical pressure as 2,000 volts. If

cells are used for the purpose of equalising the load or as a safety

reserve, it is better to charge them by means of a dynamotor.

Central-Station Electric Lighting With Notes on the Methods Used for the Distribution of Electricity · 第 31 / 83 题