THE VIENNA CENTRAL-STATION.

The practical success of the Battery Transformer system has been

demonstrated at Vienna, where an installation of five thousand lamps

in the Opera House and Burg Theatre was maintained for the past year

from a distributing station 1,400 yards away. The boilers are fixed

in a basement formed by excavating the court-yard of a private house

to a depth of 15 feet 6 in. below the street level; the building

itself is utilised partly for offices and partly as a large dynamo and

engine-room. Each dynamo is designed to give an output of 72 kilowatts

or 120 ampères, at 600 volts pressure. The current is led by means of a

lead-covered cable underground to the accumulators, which are erected

in groups of 52 cells each, so as to give 100 volts to the lamps, with

a comfortable margin. The total pressure required to charge the four

groups of batteries in series varies from 430 volts at the time the

batteries are giving off work, to 480 volts for the short time during

which the charge is being completed. During five hours of lighting

about two-thirds of the current comes direct from the dynamos; but

during this time, for short periods, the demand for current often

increases to such an extent that these proportions may be reversed, and

the batteries supply two-thirds of the total.

The regulation of groups of batteries placed in series is not a

difficult matter, and will be understood by referring to the following

diagram, Fig. 27:—

[Illustration: FIG. 27.]

The four battery stations mentioned as arranged in series are

represented. The current may be supposed to enter at the right hand

corner, passing through the first battery with the lamps parallel to

it, and from that battery to the commencement of the next, and so on

through the third and fourth, the current being varied at will at the

central-station, or kept constant by means of an electrical governor.

The potential for each of the four groups of lamps is maintained in

the following manner:—In each group one terminal is kept permanently

connected to one of the discharge mains and to one of the charging

mains; the other terminal can be shifted from cell to cell according to

the E. M. F. required in the corresponding lamp circuit by means of a

contact regulator. This movable terminal is shown by the bunch of lines

at one extremity of each battery group. The rule for charge and

discharge is, that the terminal cell at the regulating end of the

battery is so arranged that it neither receives nor gives off current,

so that there is no loss of energy in the shape of E. M. F. The contact

regulator, which was designed by Mr. Crompton for use at Kensington

Court, is shown by Fig. 28:—

[Illustration: FIG. 28.

Central-Station Electric Lighting With Notes on the Methods Used for the Distribution of Electricity · 第 29 / 83 题