THE EDISON SYSTEM AT MILAN.

The Santa Radegonda station at Milan is at the present moment the

second largest Edison station in Europe. The building, which was

formerly a theatre, is well adapted for the work required; the dynamos

and engines are fixed in a deep basement, while the boilers are a few

feet above the street level, the upper floors being used as stores and

testing-rooms. The dynamos, eight in number, are of the old Edison

type, with horizontal magnets; seven of these machines are connected to

the feeders which supply the mains, and these cover the district to be

lighted on the Edison network system. The motive power is furnished by

six Armington-Sims, and two Porter-Allen engines, each connected direct

to the armature of a dynamo, the speed being maintained at the uniform

rate of 350 revolutions per minute, except in the case of the spare

engine and dynamo, which is kept turning slowly, ready to be switched

on should occasion demand. The starting or cutting-out of circuit of

these large machines requires some care. In the first place, to start,

it is necessary to insert resistance into the shunt circuit of the

dynamo, which is done by a switch; but to throw 150 horse-power into

the main circuit would be dangerous to the lamps, so that the current

is first sent into a bank of one thousand lamps used as a resistance,

and these are cut out step by step; similar care is taken when a

machine is stopped. To control the electro-motive force, which varies

greatly from time to time, hand regulation is used during the day, with

the help of the Edison tell-tale, consisting of two lamps, a red and

white one, which light up when the current is high or low; but when the

night service comes on, as it may happen that two thousand lamps may be

turned out at once, an attendant has to carefully watch the electric

regulator, and be ready to insert resistance into the field-magnet

circuits by moving a wheel connected by a shaft and bevel-gear to a

system of commutators. The principal difficulty to be overcome, in

an installation where the current is distributed over a large area,

is the regulation of the electro-motive force at the various points,

as at Milan; there are no return galvanometer wires, which are now

used in both the two and the three-wire Edison systems in the United

States. The plan devised by the company’s electrician at Milan is very

ingenious, and enables the pressure at the ends of the various feeders

to be kept practically the same, although they are of different lengths

and sectional area. In the first place, resistance was added to each

feeder to equalise the resistance in each conductor; and, in order to

provide for the varying amount of current the feeder has to supply, a

peculiar form of commutator, having a guillotine-shaped contact-piece,

was inserted in the circuit. By moving this, suitable resistance is

inserted or cut out, and the attendant, having a series of numbers, has

only to set this instrument to the number shown by the ampère meter. By

far the largest amount of current is drawn off for the lighting of the

Scala Theatre, the stage-lighting alone taking more than one thousand

lights: if these were all turned on suddenly, the other lights in the

district would be dimmed; to obviate this, auxiliary feeders have been

run, which are used only when any great increase is expected;

commutators similar to those referred to above also regulate these

feeders without any special attention. The pressure at any point in the

system is by this means easily controlled, and affords an illustration

of what is perhaps not the most economical, but is found to be the most

practicable, way of maintaining a constant potential in a district

where the amount of output of current is suddenly doubled. Fig. 18 is a

plan of the network system of conductors laid through a large portion

of the city; the conductors are in outward appearance similar to

gas-pipes, the current passing through semicircular bars of copper,

embedded both for the flow and return in the same iron tube, which is

laid underground in a shallow trench. The house-supply is drawn from

the mains, and these are connected to the feeders by means of ordinary

junction-boxes, which each contain a fusible cut-out. The bridge-boxes

allow of expansion of the line, and have connections for testing

purposes. The insulation is extremely good, mainly on account of the

favourable nature of the ground, which is chiefly gravel; no trouble

has been experienced with leakage, nor has the service ever been

interrupted. The cut-outs are of an improved Edison form, but have the

disadvantage attending all lead plugs where the current is great, in

that, to guard against accidental melting due to the heating effect of

the current, the sectional area of the lead has to be much larger than

would be otherwise necessary. In fact, these cut-outs will protect the

cable against a bad short circuit, but nothing else.

[Illustration: FIG. 18.]

In addition to the glow lamps, eighty arc lamps are worked in

derivation, two in series; most of these lamps require 45 volts,

to which 10 per cent. of idle resistance is added, constituting a

total loss of current which is extremely low for a combined arc and

incandescent system of lighting. The service commenced in 1882 with

a little over one hundred lamps, and at present there are over ten

thousand glow lamps, and two hundred arc lamps are in use. At first the

new enterprise had to struggle against very great difficulties; not

only the technical difficulties of distribution by means of a network

of feeders and mains had to be overcome, but also those arising from

the prejudices of consumers and the competition of the gas company,

who tried to deter consumers from introducing electric light into

their houses. One of these means consisted in offering to the private

consumers, resident in the district which was threatened by competition

with electricity, an agreement by which the gas company bound itself to

supply gas at 5_s._ 8½_d._ per 1000 cubic feet, instead of 7_s._ 7_d._

as charged hitherto; and even now those inside the “charmed circle” of

the electric light conductors get their gas cheaper than the public

outside. One of the reasons which accelerated the adoption of electric

light was the introduction of the Edison meter, in consequence of which

consumers could be charged exactly for the amount of light they had

received, and were relieved from paying a lump sum according to the

number of lamps fixed, which was customary in the early days of the

company. The prices at which the company now provides light, at all

hours of the day and night, are as under:—

Installation Charge per

Type of Lamp. charge per lamp. lamp·hour.

_s._ _d._

10-candle 18 0·26

16- ” 28 0·40

32- ” 56 0·80

that is, a little over ½_d._ per ampère-hour; the 10-candle lamps

requiring 0·5, the 16-candle lamps 0·75, and the 32-candle lamps 1·5

ampère.

The company lends meters for 50, 100, and 150 lamps, at an annual

rent of 4_s._ 10_d._, 7_s._ 3_d._, and 9_s._ 7_d._ respectively, and

replaces, without charge to the consumer, any lamp the filament of

which has broken, but it does not replace lamps where the glass is

broken. For arc lamps requiring 9 to 10 ampères, an annual rent of £2

must be paid for the lamp itself, and a charge of a little over ½_d._

per hour for every ampère-hour. The carbons are charged for at 1_d._

per pair, lasting for about seven hours. Now that the installation has

been in use for several years, and that the company has arrived at a

very accurate estimate of the time during which an average consumer

requires the light—about one thousand six hundred lamp-hours per

annum—it proposes to simplify the method of charging large consumers,

by omitting the initial charge of each lamp, and, instead, to charge

0·6_d._ for each 16-candle lamp-hour.

The Edison meters are based on the electrolytic action of a small

fraction of the current which passes through the meter. They are cells,

with rectangular zinc plates immersed in a solution of sulphate of zinc

of 1·054 density, the distance between the plates being a little over ¼

inch. The proportion of the current which passes through the meter to

that which passes directly into the consumer’s house is 1 to 973. The

resistance of the shunt circuit is 9·75 ohms, made up as follows: cell,

1·75 ohm; metallic portion, 8 ohms. The resistance of the metallic

portion rises with the temperature, whereas that of the cells falls

with a rising temperature; and in this manner the small variations of

resistance which might take place in the cell are counter-balanced

by the equally small variations in the resistance of the metallic

portion. A complete meter consists of two similar-sized cells of the

same resistance, placed in series. The object of employing two cells

is, that when little current is passing, as in the summer months, one

cell alone is used, and when the consumption is sufficiently large both

cells are employed, and the mean between the two indications is taken

as the basis for calculation in number of ampère-hours. The quantity of

electricity passed through the cell is calculated by the loss of weight

which has taken place in the positive plate. An employé of the society

visits every meter monthly, taking away the old cells and substituting

others freshly constructed. A book is kept in which the weights of the

new plates and those of the returned plates are entered, and on the

basis of these entries the accounts are made up. The largest plates are

those in the 100-light meter, and are intended for a maximum current

of 75 ampères in the main circuit; they are 6 inches long by 2 inches

wide. In cases where a larger amount of current is taken, the capacity

of the 100-light meter is increased by joining two or more copper

strips across the terminals of the cells. The weak point of the system

is the removal of the cells, which leaves the adjustment of the account

to be paid entirely in the hands of the Electric-Light Company; in

spite of this drawback, it is stated that there has not been a single

complaint from consumers during the four years in which the meter

system has been in use.

_Discovery of Faults._

It is evident that in so extensive a system of lighting a short circuit

now and then between the lamp wires and the earth cannot altogether be

avoided. Many of the lamps have been fitted to existing gas fittings,

and are beyond the daily supervision of the company’s officers; the

faulty place is often not easily accessible, so the first step taken is

to discover on which of the two circuits the trouble has occurred. This

is done at the station by joining two 16-candle lamps in series across

the main conductors and the point of junction between the two lamps is

connected to earth by a stout wire. As long as both circuits (positive

and negative) are perfectly insulated from earth no current flows

through this middle wire, and both lamps remain hardly incandescent;

but, if one of the circuits should be in connection with the earth, the

lamp which is joined on the other circuit will brighten up, because the

potential of the middle wire and that of the faulty circuit are both

zero, and consequently the lamp between the middle wire and the sound

circuit receives the full pressure of 110 volts. To localise the fault,

contact is made between the earth and the sound circuit by means of a

fusible plug of known melting point, say for a thirty-lamp supply. If

the fault is on a portion of the external circuit, supplying less than

thirty lamps, its fusible plug will melt as soon as the sound main is

put to earth. If, however, the fault is on a portion supplying more

than thirty lamps, the fusible plug which has been inserted at the

station between the sound main and the earth will melt instead. A

series of fusible plugs are thus tried, increasing in melting capacity

until one is found that does not go: in this case, the other plug on

the faulty portion has melted, and the consumer’s lamps on that branch

are extinguished; the position of the fault is thus localised, and

the company proceed to remedy the defect without interfering in the

slightest degree with the rest of their system.

Central-Station Electric Lighting With Notes on the Methods Used for the Distribution of Electricity · 第 15 / 83 题