SUPPLY BY SECONDARY GENERATORS OR TRANSFORMERS.

The problem of electric lighting from central-stations is comparatively

easy if an area can be obtained immediately surrounding, and within a

short distance of, the station, with a right of way for laying down the

electric mains direct. This happy state of affairs has not yet been

attained, consequently the generating station has more often to be in

an out-of-the-way corner of the district to be lighted, and it would be

financially impossible to use low-tension currents with correspondingly

large mains. The difficulty has been overcome in several ways by the

use of high-tension currents in the mains, and has led to the adoption

of secondary generators or transformers of electricity, which by

induction supply a current of low potential in the house-service. The

first to make this plan a practical success was Mr. Goulard, to whom

the honour of the introduction is due, although his claims as the first

inventor have been recently upset by the decision of the Courts.

The relative economy of the supply of electricity by the use of a

transformer is clearly shown by the following diagram, Fig. 7. A, B,

and C give proportionately the area of cross section of the total mass

of copper necessary to supply 5000 16 candle-power glow lamps situated

at a mean distance of 4000 feet from the dynamo. A refers to the

Edison “three-wire” system, working at a potential or electrical

pressure of 200 volts with a fall of potential or loss of energy in the

distributing feeders of 10 per cent., average distance from dynamo 4000

feet—the usual conditions on which this system is worked. B shows the

size of conductor required for the same work in an installation based

on the transformer system, potential 1000 volts, allowing 2·5 per cent.

loss in the supply mains—only one-fourth as much as in the direct

Edison system at the same average distance from dynamo. If this loss

were increased to 10 per cent., and made equal to that in the direct

system, viz. 10 per cent., the size of the conductor would be that

shown at C.

[Illustration: FIG. 7.]

[Illustration: FIG. 8.]

The graphic diagram, Fig. 8, demonstrates what the relative cost would

be with each of the three conditions just named.

Mr. Goulard’s first practical application of the secondary generator

in this country was the lighting of the Underground Railway Stations,

in 1883, from Edgware Road to High Street, the generating dynamo being

fixed at the former place. These experiments, which were made by Mr.

Kenneth Mackenzie, attracted considerable attention at the time, but

it was not until the report of the jurors to the Turin International

Exhibition in 1885 was published that companies were formed to instal

the Goulard system for lighting an extensive district.

[Illustration: FIG. 9.]

The principle underlying all transformers is that of the induction

coil invented by Ruhmkorff in 1842, but described by Faraday in his

“Experimental Researches,” published in 1831-2.

Fig. 9 is a diagram of the ordinary induction coil; on a central core

is wound a short length of thick wire called the primary, and again

over this is wound a greater length of fine insulated copper wire which

forms the secondary coil. On sending a low-pressure current from the

generator round the thick wire, a much smaller high-tension current is

induced in the secondary. A contact breaker is employed to make and

break the current, or, as in the early instruments, a commutator may be

used to produce the alternations. When used as a transformer the action

is reversed, that is, a high-tension current is passed through the

primary coil, which is composed of a wire of small sectional area, the

high-pressure main connected to the dynamo also being small as compared

with the distributing cable leading from the transformer, which, acting

as a step-down induction coil, converts the electricity into a safe

working pressure.

[Illustration: FIG. 9A.]

Fig. 9 A shows the arrangement of the two separate and complete

circuits. D is the dynamo, P the primary coil, S the secondary, and L

the lamps arranged in parallel.

It is hardly necessary to go into the technical details of the various

improvements which have led up to the modern type of transformers; they

are summarised by Mr. Kapp into two classes:—

I. Core transformers, one core and two sets of coils.

II. Shell transformers, two cores and one set of coils.

No. I. are those in which the copper coils are spread over the surface

of the iron core enveloping the latter more or less completely; and No.

II. in which the core is spread over the surface of the copper coils

forming a shell over the winding.

[Illustration: FIG. 10.]

The original Goulard and Gibbs secondary generator was of the core

transformer type, it had an open magnetic circuit and cores which

could more or less be inserted into the coils so as to regulate the

electro-motive force of the secondary circuit. The transformers were

constructed with a number of copper disks or washers; these were

placed alternately primary and secondary in a vertical frame, through

the centre of which an iron core was fixed, consisting of a bundle of

straight iron wires. The core was movable in the coil in the manner of

the well-known induction coils, and thereby the electro-motive force

of the secondary current could be adjusted. In their latest design

the coils are circular in plan and rectangular in section and are

surrounded by groups of U-shaped soft iron stampings slipped over from

both sides and held together by two circular cast-iron plates with a

central bolt. The magnetic lines of force pass through the core, in at

one end and out at the other, and are then more or less disseminated

through space; it will thus be seen that the path of the lines lies

partly in iron and partly in air, and, since air has about seven

hundred times more magnetic resistance than iron, it is evident that

the number of lines created with a given current must be considerably

smaller than would be the case if the path of the lines contained iron

only. This constitutes the improvement in the Zippernowsky-Deri-Blathy

system of transformer, which has coils similar to the Goulard, but with

the iron of the core applied in the form of a ring-shaped shell,

surrounding both coils completely. This arrangement can best be

described by comparing it to a Gramme armature, in which the copper and

the iron have changed places. Imagine what is usually the core in an

armature replaced by the primary and secondary coils, and, instead of

the winding of insulated copper wire, wind iron wire around the coils,

and one of these transformers is the result. In consequence of the

lower magnetic resistance of the Class II. transformer, as compared to

that of Class I., the electrical output obtainable with equal weights

of copper and iron appears to be considerably greater in the former

apparatus. Professor Feraris, of Turin, has published some of the

results of comparative experiments made with Classes I. and II. and

finds that the coefficient of induction is 3·6 times as great with the

latter as with the former. There are many varieties of transformers

in the market which closely resemble each other; one of the most

practical is that designed by Kapp and Snell, of which Fig. 10 is an

illustration. U-shaped stampings form the shell and the cores are laid

in the double trough. The cover of these troughs is formed from the

metal removed from the interior of the stampings, and the whole is held

together in a cast-iron frame so arranged as to allow air to circulate

through the core and round the coils. The price of these transformers

is about £4 per indicated horse-power, and the efficiency under the

best conditions, namely, with full load, is, according to Professor

Ayrton, as high as 96 per cent., and when it is doing one quarter of

the full work 89 per cent.