CHAPTER XI

VENTILATION

The purity of air in any habitable enclosure is determined by the

amount of CO₂ (Carbonic acid gas) included in its composition. The

process of ventilation is that of adding fresh air to the impure

atmosphere of houses, until a desirable quality is attained. In the

opinion of hygienists, when air does not exceed 6 to 8 parts of CO₂, by

volume in 10,000, the ventilation is desirable. Ordinary outdoor air

contains about 4 parts of CO₂ to 10,000, while very bad air may contain

as high as 80 parts to the same quantity. The quantity of air required

for the ventilation of a building is determined by the number of people

to be provided. The amount of air required per individual per hour

necessary to produce a desired condition of ventilation is determined

by adopting a standard of purity to suit the prevailing circumstances.

In hospitals where pure air is considered of greatest importance 4000

and 5000 cubic feet per inmate per hour is not uncommon. The practice

of supplying 30 cubic feet of air per person per minute (1800 cubic

feet per hour) seems to fulfill the average requirements. It is the

amount commonly specified for school-rooms.

The quantity of fresh air required per person to insure good

ventilation will depend on the type of building to be supplied and

varies somewhat with different authorities. The De Chaumont standard

is that of 1 cubic foot of air per second or 3600 cubic feet per hour,

for each person to be accommodated. De Chaumont assumed a condition

of purity which will permit less than 2 parts in 10,000 of CO₂ over

that carried by country air. In considering the same problem from

the basis of permissible CO₂, if 6 parts of CO₂ in 10,000 represents

purity of the required air, then 3000 cubic feet per person per hour

is necessary. Likewise, the varying amounts for different degrees of

purity are given by Kent in the following table. The upper line gives

the permissible number of parts of CO₂ per 10,000, while below each

factor appears the number of cubic feet of air required per hour for

each person supplied.

-----+-----+-----+-----+-----+---+---+--------------------------

6 | 7 | 8 | 9 | 10 | 15| 20| = Parts of CO₂ per 10,000

-----+-----+-----+-----+-----+---+---+--------------------------

3,000|2,000|1,500|1,200|1,000|545|375| = Cubic feet of pure air

| | | | | | | per hour

-----+-----+-----+-----+-----+---+---+--------------------------

It is generally recognized, that it is possible to live under

conditions where no attempt is made to change the air in a building.

It is also an established fact that the only preventive and cure for

tuberculosis is that of living constantly in an atmosphere of the

purest air. The greatest attainable degree of health is enjoyed by

those who live in the open air, because oxidation is one of the most

efficient forms of prevention and elimination of disease, and an

abundance of pure air is the only assured means of sufficient oxidation.

The De Chaumont standard is intended to represent the limit beyond

which the sense of smell fails to detect body odors or “closeness”

in an occupied room. The amount of CO₂ that air contains is not an

absolute index of its purity, but it gives a standard under ordinary

conditions, makes possible the requirement of a definite quantity of

air. If it were possible to express the amount of oxygen contained in

the atmosphere, the same relative condition might be attained.

The ordinary man exhales 0.6 cubic foot of CO₂ per hour. Some forms of

lighting apparatus produces this gas in greater amounts. The ordinary

kerosene lamp gives out 1 cubic foot of CO₂ per hour. A gas light using

5 cubic feet of gas per hour produces 3.75 cubic feet of CO₂ in the

same time. Any form of combustion permitting the products to escape

into the air of the room tends to lower the quality of the atmosphere

by adding to its content of CO₂.

The prevailing impression that impure air is heavy and settles to

the floor is erroneous. Impurities in the form of gases and vapors

(principally carbonic acid gas and odors) diffuse throughout the

entire space, and the entering fresh air tends to dilute the entire

volume.

As a quantative problem, ventilation consists in admitting pure air

into an impure atmosphere in amount to give a definite degree of

purity. This is accomplished by admitting sufficient air to completely

change the atmosphere at stated intervals, or to provide a definite

quantity for each inhabitant.

The methods by which ventilation may be accomplished will depend on the

type of building to be ventilated and the apparatus it is possible to

use. When the use of mechanical ventilation appliances are permissible,

any desired degree of atmospheric purity may be maintained at all

times, under any condition of climate or change of weather.

In buildings where mechanical ventilation cannot be considered as that

of the average dwelling, the problem is one of producing an average

condition of reasonably pure air by natural convection. In the average

dwelling, ventilation is accomplished by the natural draft produced in

chimneys or air flues, by partially opened windows and by the force

produced by the movement of the outside air. In some buildings a better

condition of ventilation is attained by ordinary means than at first

sight seems possible.

The fact that it is difficult to keep a house at the desired

temperature during cold weather indicates that a considerable quantity

of outside air is constantly entering and heated air is leaving the

building. It may be, however, that the ventilation under such condition

is unsatisfactory, even though the amount of air which enters the

building is sufficient in quantity to produce a desirable atmosphere.

If the places of entrance and exit are so located that the entering air

has no opportunity to mix with the air of the building, the advantage

of its presence is lost.

In the burning of fuel in stoves and furnaces, the amount of oxygen

necessary for combustion is supplied by the air which is first taken

into the house and thus forms its atmosphere before it can enter the

heater. Theoretically, about 12 pounds of air are required for the

combustion of a pound of coal, but in practice a much larger amount

actually passes through the heater. As given by Suplee, from 18 to 24

pounds of air are actually used in burning 1 pound of coal. If 20

pounds of air per pound of fuel is taken as an average, there will

be required 198 cubic feet of air per pound of coal consumed. In a

building that requires 10 tons of coal to be used during the winter

months, this would necessitate the average use of 1977 cubic feet of

air per hour, which must be drawn into the house before it can enter

the stoves. This air acts as a means of ventilation and if it is used

to advantage would furnish a supply sufficient in amount to produce

excellent ventilation, considerably more than enough for two people.

The amount of air drawn into the house in this way is further increased

by that which passes into the chimney flue through the check-draft

dampers, when the fires are burning low.

The aim of architects is to construct buildings as completely windproof

as possible, but that such construction is attained in only a slight

degree is sometimes very evident during cold weather. No matter how

tightly constructed buildings may be, most of the contained air filters

through the cracks and crevices of the walls or through the joints

of the windows and door frames, because there is seldom any special

provision made for its entrance. During extremely cold and windy

weather the amount of air that enters the house in this way--because of

the air pressure on the windward side--is sometimes sufficient to keep

the temperature at an uncomfortably low degree. Under such conditions,

the air drifts through the building faster than it can be raised to the

desired temperature and the rooms on the windward side of the building

cannot be kept comfortably warm.

[Illustration: FIG. 162.--A simple expedient for the prevention of

drafts and improving ventilation.]

The common method of ventilation in dwellings is that of partially open

windows. The air thus admitted, being colder and consequently heavier

than that at the temperature of the room, sinks to the lowest level.

In so doing it creates drafts that produce discomfort and act only

in the smallest degree to produce the desired effect of ventilation.

The effect of window ventilation may be greatly improved by a simple

expedient illustrated in Fig. 162. In this, the entering air meets a

deflector in the form of a board or pane of glass that directs the

cold air upward where it mingles with the heated air with the least

production of a noticeable draft. This is the most efficient method of

house ventilating where no special provision is made for the admission

of fresh air.

The object sought in ventilating a room is to keep up the quality of

the air by constant addition of fresh air, and in order to bring about

a uniform purification of the entire atmosphere the entering air must

be mixed with that already in the enclosure. If the discomforts of

drafts are to be avoided, this mixing process must be brought about by

admitting the cold air at the upper part of the room.

[Illustration: FIG. 163.--A chimney flue used as a ventilator.]

Warm air rises to the top of the room because it is lighter than the

colder air beneath it. The coldest air is always lowest in point of

elevation and unless there is some means to stir up the entire volume

this condition will always remain the same.

When the easiest means of air for entering and leaving are near the

floor, the cold entering air and that which goes out will always be in

the lower part of the room, even when the supply is amply large. If no

opportunity is given for the fresh air to mix with that already in the

room, a poor average quality will result.

In the process of ventilation, the entering air should be admitted at,

or directed toward, the highest part of the room, so that the pure

cold air may have a chance to mix with that which is warmest. Air is

not a good conductor of heat, and in mixing warm and cold air the cold

particles will tend to float downward and take up heat from the warmer

air with which it comes into contact, and thus produces a more uniform

temperature.

[Illustration: FIG. 164.--Method of admitting cold air into rooms so as

to produce the best condition of ventilation.]

The condition most to be desired is that of admitting cold air at a

point where it will most readily mingle with the warm air from the

source of heat. The reduction in temperature that must take place from

this mixture will produce a gravitational circulation. Unfortunately

this is not always possible to attain in an old building, but in the

construction of a new building air ducts placed to admit air at points

near the ceiling and located with reference to the supply of heat will

bring about the best effect of ventilation.

The air which enters a room should, therefore, be near the top or so

directed that the entering shaft will carry it upward. The air which is

taken out of the room should leave from a point near the floor. In so

doing it will tend to produce a more uniform quality and a more even

distributor of the heat.

In order that the most desirable quality of atmosphere may be attained,

there should be a constant supply of pure air entering and an equal

amount discharging from the house. In the better-constructed dwelling

such a condition is often provided through a ventilating flue that is

a part of the chimney. This flue is arranged with registers placed to

take air from the parts of the house requiring the greatest amount of

air. Such an arrangement is shown in the picture in Fig. 163.

Fig. 164 shows the method of Fig. 163 combined with a direct means of

admitting fresh air from the inside. The fresh air ducts should be

provided with dampers to control the effect of extreme cold and wind.

=Quantity of Air Discharged by a Flue.=--Any change of temperature

of air produces a change equal to 1/491 part of its volume, for each

degree variation. If a cubic foot of air is raised in temperature 1°F.,

its volume is 1/491 part larger than the original volume, and its

buoyancy in the surrounding air is increased correspondingly. Air that

has a temperature higher than that surrounding it will tend to rise

because it is lighter. The air rising from a hot-air register or from a

heated surface are illustrations of this condition.

Since the change of volume--or what is the same thing, its tendency

to rise--increases 1/491 for each degree difference in temperature,

the upward velocity of highly heated air will be very great. In warm

air that fills a chimney flue or a room, the same tendency exists, the

warmest air rises to the highest point and if the air can escape, as in

the case of a chimney, a draft will result.

The draft of a chimney, in quiet air, is due to the difference in

temperature between the air inside the flue above that outside the

house. A chimney that does not “draw” and causes a stove to “smoke,”

will often produce sufficient draft after the flue has been warmed. The

upward movement of the warmer air in the flue produces a constantly

increasing velocity, until it reaches the top of the chimney. This is

an accelerated velocity that may be calculated by use of the formula

given in physics, to express the velocity of accelerated motion. The

well-known formula _V_ = √(2_gh_) may be modified to express the

conditions existing in a flue and permit of the calculation of the

quantity of air discharged.

The upward flow of air in a chimney flue being due to the difference

in temperature of the air in the flue over the outside air, the flow

of air from the rooms will continue as long as the difference in

temperature exists. Moreover, the air that is discharged from the

rooms will be replenished from the outside, and for the air sent out

of the flue a corresponding amount will be brought into the rooms

through any openings that exist--door or windows or through cracks

or crevices, depending on the completeness with which the house is

closed. In no case is a house air-tight. The air pressure registered by

the barometer is always the same inside as that outside the building.

During cold weather, when the windows and doors are closed, the air is

escaping through the chimney and also through every little crack and

chink in the top of the rooms where the air is warmest. The colder air

is entering at the same time through the joints about windows, door

casings, through the crevices in the walls and particularly through

the open joints made by the baseboards and the floor. This latter

entrance of cold air is one of the commonest causes of cold floors. The

shrinkage of the baseboards and floors from the quarter-round moulding

which forms the joint leaves openings through which cold air is freely

admitted from partitions and outside walls. The cold, heavier air

remains near the floor because it can rise only when heated or forced

upward by a draft. If the same air were permitted to enter at points

near the ceiling and mingle with the warmest air in the room, a more

uniform temperature would result, as well as better ventilation. The

entering cold air, mixing with the warm air at the top of the room,

would be reduced in its temperature and weight. The heavier air in

falling would diffuse with the air beneath it and thus improve the

general quality of the atmosphere.

It is important to remember that the discharge of air through a chimney

flue will depend, in considerable amount, on the rate the new air is

able to enter the house. In a new, tightly constructed house, the flue

is often capable of discharging air much faster than it can enter, when

it must find its way in through accidental openings. In such cases an

open door or window immediately improves the draft of the stove.

The ventilation in the average dwelling is and must be accomplished

by natural draft that is generated through difference in temperature

of the air. The possibility of providing an acceptable system of

continuous ventilation is confined to the draft of the chimney or to

a flue provided especially for that purpose. Such being the case, the

dimensions of flues constructed for ventilation should be the subject

of investigation. The work that a chimney or ventilating flue has to do

is continuous and will last throughout its lifetime; its proportions

should therefore be considered with more than passing care.

It has been stated that the method of calculating volumes of air that

will pass through a flue is based on the formula used to express the

velocity of accelerated motion. The fundamental formula must be changed

to suit the conditions produced when air is heated and made buoyant by

expansion.

As has been stated, the change in temperature of air 1°F. causes an

increase or decrease 1/491 part of its volume for each degree change.

Any portion of air, warmer than that which surrounds it, tends to rise

because of its lighter weight; the tendency to rise increases with

the difference in temperature. The draft of a flue is caused by this

condition of difference in temperature between the air inside the flue

and the outside atmosphere.

In order that this general condition may be expressed in the simplest

form let: _T_ = the temperature inside the flue in degrees F.

_t_ = the temperature outside the flue in degrees F.

_H_ = the height of the flue in feet.

The quantity (_T_-_t_)/491 expresses the difference in temperature in

degrees, divided by the change of volume for each degree. This gives

the constant upward tendency of the air in passing through the flue. If

this quantity is placed in the formula _V_ = √(2_gh_), so as to

exert its influence through the height of flue _H_, the condition may

be expressed:

_V_ = √(2_g_((_T_-_t_)/491)_H_)

The factor _g_, representing the acceleration of gravity, is constant

and equal to 32 feet per second. The quantity 2_g_ may be removed from

under the radical and the formula becomes:

_V_ = 8√(((_T_-_t_)/491)_H_)

The formula may now be used to express the volume of discharge of air

from a flue. Suppose such a flue contains an area of 1 square foot in

cross-section and that it is desired to estimate the air discharged

from the flue per hour. The value of _g_ is given in feet per second,

and in order to make the formula express the volume of air discharged

in cubic feet per hour, it must be multiplied by the number of seconds

in an hour. Volume discharged in cubic feet per hour

= 60 × 60 × 8√(((_T_-_t_)/491)_H_)

= 28,800√(((_T_-_t_)/491)_H_)

This formula applies to conditions such as will permit uniform movement

of the air in a straight flue, uninfluenced by irregular, odd-shaped

passages and rough surfaces. Moreover, it is supposed that the air may

enter the house as rapidly as it escapes. The theoretical discharge

will, in most instances, be less than the calculated amount, because

the air cannot enter the house as fast as it may be discharged by the

flue. It is a common custom to consider the theoretical flue only 50

per cent. efficient. As applied to the formula, the constant 28,800

when reduced 50 per cent. will become 14,400, and will be so used in

the calculations as follows.

As an illustration of the application of the formula, suppose that the

temperature in the house and in the flue is 70°F. and that the outside

temperature is 20°F. The height of the chimney is 30 feet. The area of

the flue is 1 square foot.

Volume = 14,400 √(((_T_ - _t_)/491)_H_)

= 14,400√(((70 - 20)/491) × 30)

= 25,140 cubic feet per hour.

Such a ventilating flue would be sufficient in size, under the

conditions given, to furnish air at the rate of 25,140 cubic feet per

hour or 30 cubic feet per minute to 13 persons, provided of course

that the air could enter the building at the rate demanded. Where no

provision is made for the air to enter the building it must find its

way by the accidental openings. A common illustration of this effect

may be noticed in the rate at which the fire of a stove will burn

in a tightly closed room. The opening of a door or window causes an

immediate increase of combustion, because of the extra air supply.

It is evident that in well-constructed houses other means should be

provided for admitting air than that of accidental opening.

The following table calculated by the above formula gives the quantity

of air in cubic feet per hour discharged through a flue of 1 square

foot cross-section. The table shows the calculated discharge from flues

of heights varying from 15 to 40 feet, and with temperature differences

from 10° to 100° between the outside air and that of the house.

--------+-------------------------------------------------------------

Height | Temperature of air in the flue above that of external air

of flue +--------+--------+--------+--------+--------+--------+-------

in feet | 10 | 15 | 20 | 25 | 30 | 50 | 100

--------+--------+--------+--------+--------+--------+--------+-------

15 | 7,980 | 9,720 | 11,280 | 12,550 | 13,800 | 17,820 | 25,140

--------+--------+--------+--------+--------+--------+--------+-------

20 | 9,180 | 11,180 | 13,080 | 14,520 | 15,900 | 20,520 | 29,040

--------+--------+--------+--------+--------+--------+--------+-------

25 | 10,260 | 12,600 | 14,520 | 16,260 | 17,820 | 22,980 | 32,460

--------+--------+--------+--------+--------+--------+--------+-------

30 | 11,280 | 13,800 | 15,900 | 17,825 | 19,500 | 25,140 | 35,580

--------+--------+--------+--------+--------+--------+--------+-------

35 | 12,180 | 14,880 | 17,160 | 19,200 | 21,060 | 27,180 | 38,400

--------+--------+--------+--------+--------+--------+--------+-------

40 | 13,020 | 15,900 | 18,360 | 20,520 | 22,500 | 29,040 | 40,980

--------+--------+--------+--------+--------+--------+--------+-------

In Fig. 163 is illustrated the form of chimney that is often used for

the ventilation of dwellings. This is built with three flues. The flue

to the left--marked _A_ at the top--is intended to carry away the smoke

and gases from the kitchen range. The flue to the right is that to

which is connected the smoke pipe from the furnace. The flue in the

middle marked _B_ is for ventilation. Occupying as it does the space

between the other two, it is kept warm by the heat of the other flues

and the draft is thus increased. Openings to the flue are shown in the

different floors at the points _R_ and _S_. The openings are furnished

with registers which may be regulated to suit the weather conditions.

The dimensions of such a flue may be calculated by the formula given

or the area may be taken from the table to correspond with required

conditions. In all cases flues should be made ample in size, as they

must often do their maximum work under the poorest conditions for the

production of good draft.

The amount of air discharged from the flue as given in the table is

due to the gravitational effect alone. The suction produced by the

wind adds in a very large degree to the amount of air discharged. The

quantity of air that will flow from a 30-foot flue, by reason of the

suction of the wind, blowing 7 miles per hour is equal to the same flue

working by gravity with a temperature difference of 20°. With a wind

velocity of 7 miles per hour and a temperature as given, the capacity

of the flue is doubled. It is easy, therefore, to understand why the

rate at which fires burn is so greatly increased by high winds. At the

time of very high winds, a chimney flue will carry away three and even

four times the volume discharged at the time of atmospheric calm.

=Cost of Ventilation.=--The cost of good ventilation is often looked

upon as prohibitive, because of the expense in heat necessary to keep

the inside atmosphere at standard purity. Cost of ventilation is

determined by analysis of the known conditions and calculations made of

the amount of extra heat necessary to warm the greater volume of air.

The common practice of estimating the quantity of heat used in any

form of heating or ventilation is by reference to the B.t.u. used in

producing the desired condition. This unit, as has already been stated,

is the amount of heat necessary to change a pound of water, 1°F.

In considering the cost of heating the air for ventilation, it must be

borne in mind that the heat used in raising the temperature of the air

contained in an enclosure is only a part of that necessary for warming

the building. Most of the heat used goes to keep up the loss due to

radiation and conduction which goes on from the windows, the walls and

other parts of the building that are exposed to the outside cold. The

material of which the building is composed must be heated and in turn

radiates its heat to the colder outside air.

The quantity of heat necessary to change the temperature of a

definite amount of air is easy of calculation. The problem is that of

determining the number of heat units required to warm the necessary air

to suit the average condition of weather. We will assume that the house

is heated to the normal temperature 70°, and that the additional cost

of heating the air for ventilation over the amount thus expended is the

cost of ventilation.

Assuming that the house is so constructed that it is possible to supply

air at the rate of 1000 cubic feet per hour to each person of a family

of five, this condition will necessitate 5000 cubic feet of air per

hour or 120,000 cubic feet of air per day.

The house is such that 10 tons of coal are required per year, at a

cost of $10 per ton. The period of winter weather will be considered 5

months of 30 days each. This will be 150 days, during which the fuel

for heating the house will cost 66-2/3 cents per day.

The average temperature of the outdoor air during the entire period

will be assumed to be 20°F., thus requiring the air for ventilation to

be changed 50° in order to raise it to the normal temperature, 70°.

The weight of a cubic foot of air at 70° is practically 0.075 pound.

The 120,000 cubic feet of air used per day will, therefore, weigh 0.075

× 120,000 = 9000 pounds which must be raised 50° in temperature.

In order to express in B.t.u. the necessary heat required to produce

the change of air temperature, the quantity of air is best stated in an

equivalent amount of water. The specific heat of air is 0.237; that is,

the amount of heat necessary to change a pound of air 1° is 0.237 of

the amount used in changing 1 pound of water 1°. The 9000 pounds of air

expressed as an equivalent amount of water will then be:

9000 × 0.237 = 2133 pounds of water.

This amount of water raised 1° is equivalent to raising 120,000 cubic

feet of air 1°. Now the average change in the temperature of the air is

50°, so that 50 × 2133 will be the number of heat units used.

50 × 2133 = 106,650 B.t.u.

That is, 106,650 B.t.u. will be required to heat the air for

ventilation one day.

In order to express this amount of heat in terms of fuel consumed, it

will be assumed that the coal contained 14,000 B.t.u. per pound, this

being a fair valuation of good coal. The average house-heating furnace

will turn into available heat about 50 per cent. of the fuel burned.

This value is taken from house-heating fuel tests made at the Iowa

State College. The available heat in each pound of coal then will be

7000 B.t.u.

106,650 ÷ 7000 = 15.2 pounds of coal.

That is, 15.2 pounds of coal per day must be burned in order to furnish

1000 cubic feet of air per person each hour at the desired temperature.

At $10 a ton of 2000 pounds, the fuel costs 1/2 cent per pound. The

cost of ventilation is, therefore, 1/2 × 15.2 = 7.60 cents a day, not

an extravagant amount for good air.

It is evident that with the use of hot-air furnaces which take their

entire amount of air from outdoors, the extra amount of heat necessary

for this improved quality of atmosphere is very well expended. The use

of ventilating devices adds only a relatively small amount to the total

cost of heating and provides for the well-being of the occupants of the

house--in the form of good air--an amount of healthfulness impossible

of calculation.

The best ventilation is attained where a constant supply of fresh air

is admitted to the house at points from which the best circulation may

be secured and equal quantities of vitiated air are removed from the

different apartments.

It is understood that in the process of natural ventilation the desired

condition can only be approximated and that the permissible ventilation

appliances are so placed as to give results such as to permit the air

to follow the natural laws that must prevail.

If the house is heated by stoves, the outside air is best admitted near

the ceiling, so that the cold air on entering may come into contact and

mingle with the warmest air in the room. The circulation will by this

method be effected by gravity.

In the use of the hot-air furnace, the air supply--as has already

been explained in the figures on pages 55 and 58--is brought from the

outside, where after being heated it enters the rooms through the

registers placed near the floor. Being warmer than the air in the room,

it tends to quickly rise. The currents set up by its motion help to

produce a uniform temperature and to diffuse the new air through the

entire space. The more evenly the air is distributed the more uniform

will be the condition of temperature of the room.

In hot-water and steam heating, the direct method of heating in Fig.

29 and the indirect method of Fig. 30 show two forms of apparatus

for admitting air to buildings that are quite generally employed

for ventilation of dwellings. In the use of all such devices for

ventilation purposes, there should be provided means of escape of air

corresponding in amount to the fresh air admitted. The exhaust air vent

should be located near the floor to bring about the best results. The

degree of success attending the use of such apparatus will depend on

the amount of care taken, to suit the position of the dampers to the

prevailing weather.

[Illustration: FIG. 165.--The Wolpert air tester; an instrument used to

determine the quality of air.]

=The Wolpert Air Tester.=--The purity of air is expressed by quantity

of carbonic acid gas included in its composition. In order to determine

the degree of purity of any atmosphere the amount of contained gas must

be determined. This is accomplished by use of simple apparatus that may

be successfully operated by those who are unacquainted with chemical

analytical methods. The process is due to chemical action but the

manipulation of the required apparatus is purely mechanical.

Fig. 165 shows the Wolpert air tester which is a form of this

apparatus that has given general satisfaction. The results attained

by its use are approximate but sufficiently exact for all practical

purposes. The apparatus consists of a graduated glass tube in which

fits a rubber piston mounted on a hollow glass rod, through which the

sample of air is admitted to the tube. The chemicals used for absorbing

the carbonic acid gas are furnished with the instrument but may be

replenished without difficulty. Directions for its use are furnished

with the tester that may be readily followed after a trial. The results

obtained are read directly from the side of the tube. The tester may be

obtained from any dealer in chemical or physical apparatus.

[Illustration: FIG. 166.--Thermostat regulator and motor-valve attached

to a radiator.]

=Pneumatic Temperature Regulation.=--Pneumatic temperature regulation

is very generally used in large and complicated heating systems,

because of its positive action and completeness of heat control. This

method of heat regulation utilizes the energy of compressed air, with

which to open and close the valves of the radiators. It may be adapted

to any mode of heating and can be used with any size of plant, but is

particularly suited to extended systems. The radiators, providing heat

for any particular space, are under control of separate thermostats,

which by means of motor valves admit heat only as required. A motor,

operated by compressed air, is attached directly to each radiator

valve. Any change in temperature of the room causes the thermostat to

correct in the radiator the required amount of heat.

With this method of regulation the temperature-controlling element

of the thermostat, like that of the electro-thermostatic system, is

a sensitive part, which by expanding and contracting with the heat

and cold directly controls the heat in any part of the building. The

motive power for opening and closing the valves of steam or hot-water

radiators or for operating the dampers in a hot-air system is supplied

by compressed air. The air supply is furnished by an air compressor

which automatically stores air under pressure in a pressure tank, from

which is drawn the necessary energy, as occasion demands. The air is

conducted to the motors through small pipes which are connected with

the regulating elements and also with the motors. The function of the

thermostat is to so govern the air which enters the motor as to correct

any change in the temperature of the rooms. This it does by opening and

closing the valves as occasion demands.

In Fig. 166 is shown the arrangement of the thermostat _T_ as it

appears on the wall. Air from the supply tank is conveyed by the pipe

_A_ through the thermostat _T_ to the motor valve _V_ attached to the

radiator. The function of the thermostat is that of so controlling the

radiator valve by means of the motor _V_ that the radiator will give

out just sufficient heat to keep the room at the desired temperature. A

closer view of the thermostat is given in Fig. 167.

[Illustration: FIG. 167.--Outside view of thermostat as it appears in

use.]

The thermostat illustrated in Fig. 167 is that employed by the National

Regulator Co. The drawing shows the exterior and interior construction

of the parts enclosed in the previous illustration. The pipe _C_ at

the right and opening _P_ at the left are the same as _A_ in Fig. 169;

likewise, the pipe _D_ connects at the opening _M_ of the motor valve

in Fig. 169.

Referring again to Fig. 168, the sensitive part consists of a tube

_A_ of vulcanized rubber. It is the dark-shaded part in the left-hand

drawing. Any change in the air temperature influences the length of

this tube. The changing length of the tube effects the air supply to

close the radiator valve when the temperature rises above the desired

amount and to reopen it when more heat is required. A finely threaded

screw passes through the plug _H_ at the top and to this is secured the

indicating disc _X_. The bottom of this screw is cupped to receive the

point of the rod _K_, which connects with the piece _L_. Any change in

length of the sensitive tube moves the valve lever _O_, and thus opens

or closes the air port _G_.

Air under pressure is supplied by the pipe _C_, connected to the

air supply, flowing into the thermostat through the filter _P_, the

restriction _S_, the passage _T_, and the port _G_. The adjustment of

the thermostat for different temperatures is provided for by the screw

_J_ through the top plug _H_, and the indicating disc _X_. The screw

_R_ in the connector _Q_ at the base of the thermostat is a needle

valve which opens or closes the connection with the air supply, and

is used as an air shut-off valve when it is desired to remove the

thermostat. The screw _S_ is a restriction valve which controls the

supply of air to the thermostat, and this screw is set so as to allow

the air to pass in a restricted quantity.

[Illustration: FIG. 168.--Internal construction of the National

Regulator Co.’s thermostatic regulator.]

When the temperature of the apartment has risen so as to expand the

thermostatic element _A_, the pressure on _K_ and _L_ is relieved

and the spring _N_ closes the port _G_. The air admitted through the

restriction screw _S_, since it cannot escape through the port _G_,

accumulates in the passage _Y_ and pipe _D_, filling the diaphragm and

moving the valve into the position to decrease the supply of heat.

When the temperature of the apartment has decreased so as to produce

pressure on the connecting rod _K_, through the contraction of the

thermostatic element _A_, the port _G_ will be opened by the valve

lever _O_, allowing the air in the pipe _D_, together with that which

flows through the restriction _S_, to escape through the passage _W_

to the atmosphere, allowing no air to accumulate in the pipe _D_, and

thus permitting the spring at the diaphragm to actuate the damper or

valve for more heat. The amount of air released through the port _G_ by

the valve lever _O_ varies the pressure accumulated in the pipe _D_ and

produces the graduated or intermediate action desired.

[Illustration: FIG. 169.--Cross-section of pneumatic radiator valve

showing its internal construction.]

[Illustration: FIG. 170.--Pneumatic motor valve for automatic control

of dampers, etc.]

A further application of air pressure in temperature regulation is

that of the type of motor shown in Fig. 170. This device is intended

to open and close dampers such as are used in the automatic regulation

of temperature where heated air is used to warm the buildings. The

operation of the motor is the same as that which controls the steam

valve. The pressure exerted by the diaphragm is applied at _A_ and the

attachment to the damper is made at _B_. The motors indicated at _V_

and _N_ in Fig. 174 and _D_ in Fig. 175 are examples of its application.

=Mechanical Ventilation.=--Draft ventilation produced by open windows,

flues and chimneys is influenced by extremes of temperature and by

the force and changing direction of the wind; it is, therefore, but

imperfectly controlled. The superiority of mechanical ventilation

is generally recognized because the amount of entering air may be

regulated to suit any circumstance and its temperature and humidity

varied to conform to any desired atmospheric conditions. Mechanical

ventilating plants are seldom employed in any but the more pretentious

dwellings, but their use has extended to a degree that they are

occasionally installed in apartment buildings and their further

application is likely to grow. Neither the cost of installation nor the

expense of operation is prohibitive in dwellings of the better types.

Mechanical ventilation is quite generally employed in school buildings,

auditoriums, hospitals, public buildings and others where means will

permit, and there is a universal recognition of the effects of the

agreeably conditioned air.

Mechanical ventilation may be accomplished by power-driven fans, either

by exhausting the air from the building or by forcing air into it, and

under some conditions a combination of the two methods is used.

[Illustration: FIG. 171.--Exhaust fan for induced ventilation.]

[Illustration: FIG. 172.--Ventilation apparatus in which is included

the heater coils, the fan and the motor.]

The exhaust method of ventilation is that in which air is blown out of

the building by a fan; and the supply, to replenish that taken away,

is conducted into the building through ducts prepared for the purpose.

In some cases the induced air supply leaks into the rooms through the

joints in the doors and windows, and through the accidental crevices.

In Fig. 171 is shown a simple exhaust fan installed to produce such a

change of air. It is suitable for kitchens and other places where it

is desired to eliminate smoke or gases rather than to produce a supply

of air. With this apparatus the air of the room is blown out by the

rotating fan and new air to take the place of that exhausted is drawn

in at any convenient opening.

=The Plenum Method.=--That form of mechanical ventilation by means of

which air is forced into the rooms is known as the plenum method. It is

the most positive means of air supply because its action is attended by

a slight pressure above the outside air; it is continuous in action and

the amount of entering air is under control. The escape of the expelled

air is made through vent flues especially constructed for the purpose.

=Ventilation Apparatus.=--Fig. 172 illustrates the form of apparatus

used for ventilating buildings where no attempt is made at washing or

humidifying the air. Enclosed in a sheet-iron case _C_ is a fan which

is driven by the electric motor _M_. The capacity of the fan, for the

delivery of air, is made to suit the requirements of the building. In

this case the fan is secured to an extension of the armature shaft of

the motor. Connecting with the case which encloses the fan is another

sheet-iron box _H_, containg coils of heating pipe. The heating

apparatus is designed to change the temperature of the entering air to

suit the requirements of the building.

This represents the draw-through or induced-draft type of ventilation

apparatus. The air delivered by the fan induces a flow of outside air

which is drawn through the heating coils and discharged through the

opening _E_. At this point it enters the main ventilation duct from

which it is distributed by branch conduits throughout the building.

The temperature of the air sent out from the fan is regulated by the

steam valves of the heater coils to suit the prevailing conditions.

Under some installations of this character the ventilating air is

made to furnish the heat necessary to warm the building as well as to

provide its air supply. As ordinarily used, however, the temperature of

the ventilating air is the same as that of the room.

The method of conveying air to the various apartments depends entirely

on local conditions. The conduits may be made of sheet iron, placed to

suit the existing conditions; but when a building is constructed with

a ventilating plant in view as a part of the building equipment, it is

customary to make the ducts part of the partitions. In brick buildings

the ducts are constructed, so far as it is practicable, in the walls.

These ducts are made in size and arrangement to suit the amount of

air required for each room. When the plant is put into operation each

duct is tested with an anemometer which indicates the velocity of the

entering air. The calculated amount of air, determined by the velocity

and area of the entering column, when compared with the necessary

quantity demanded for good ventilation, gives the efficiency of the

system.

=Air Conditioning.=--In addition to the possibility of a constant

supply of air, a combination of the exhaust and plenum methods admits

of air purification. With such a plant, the air may be washed free

from all suspended dust or gases and moistened to any degree of

humidity. The process of washing and humidifying air is known as air

conditioning. Apparatus for air conditioning is made in a variety

of forms to produce any desired extent of air purification and any

degree of humidity. The plant may be regulated by hand or it may be

made entirely automatic in its action. Air-conditioning plants may be

arranged to produce air that is purified, humidified and warmed during

winter weather and in summer the hot humid atmosphere may be cooled and

dehumidified to a temperature and percentage of moisture that is most

agreeable.

Conditioned air is often used in manufactories, not for the purpose of

supplying good air to the employees but because of the effect of the

atmospheric air on the products. The manufacture of textile fabrics

often demands a constant atmospheric humidity in order that the

material produced may be uniform in grade; this is particularly true in

the making of silks. Various manufactories require an atmosphere free

from lint and dust in order that the best quality of material may be

produced. The air for ventilation in such places is washed free from

all suspended matter before being sent into the building.

In Fig. 173 is indicated an application of apparatus similar in

construction to that just described. The arrangement of the parts

is such as to produce a Plenum hot-air system of ventilation and

temperature regulation.

The plant occupies a room in the basement and the drawing shows the

method of heating, together with the plan of distribution. The air

duct leading to the room above furnishes an example of the manner of

admitting the warmed air to the rooms. The dampers _C₁_, _C₂_, etc.,

are controlled by separate motors. The motor _M_ is under the control

of the thermostat _T_ in the room above. Any change of temperature in

the room is corrected by the damper to admit cold or warm air as is

desired.

[Illustration: FIG. 173.--Plenum hot-blast heating system with

temperature regulation.]

The power-driven fan _F_ draws in outdoor air from an opening _A_,

through a set of heater coils _H₁_, in which it is raised considerably

in temperature. The heater in this case is a coil of steam pipes. The

air--after being warmed--is taken into the fan and from it may be sent

through a second set of coils _H₂_, to receive additional heat, or if

already sufficiently warmed the air from the fan may pass under the

second set of coils and receive no heat from them. Under the first

heater coil is also a bypass which may be opened by the motor _N_ to

admit cold air that is drawn directly into the fan. The movement of

the air through these bypasses is under control of the thermostat,

which causes the motor _N_ to open or close the bypass to suit the

temperature of the room. When the bypass is opened the steam is shut

off from the heater coils.

Examination of the drawing will show that the air from the fan may pass

through a second heater _H₂_, to the place marked _warm air_, or it may

pass under the heater to the compartment marked _cold air_. The amount

of warm and cold air which enters the duct is regulated by the position

of the dampers _C_.

The position of the dampers _C_, which is controlled by the motors _M_,

is made to take amounts of cold or warm air to produce the desired

temperature in the rooms. The motors _C₁_, etc., are under control of

the thermostat in each room. Any change of temperature in the room will

immediately affect the thermostat. The effect on the thermostat will

so change the air pressure in the motor that the valve _C_ is moved to

correct the difference in room temperature. If warm air is demanded,

the motor changes the damper _C_ to close the cold-air supply and take

air that must pass through the heater coils _H₂_. If only cold air is

desired the damper will turn to shut off the course through the heaters

and admit air directly from outdoors.

=Humidifying Plants.=--Mechanical ventilation plants that are intended

for washing the air may be made up of parts similar to that of Fig.

173, but in addition to the apparatus shown provision is made for the

air to pass through a chamber filled with a spray of water. The air in

passing through this spray is washed free of dust and at the same time

absorbs water necessary for its desired humidity.

The humidity of air may be increased by the addition of moisture or

decreased (dehumidified) by raising its temperature, thereby increasing

its capacity for containing moisture. Suppose that air at 50° is

saturated with moisture; it will contain practically 4 grains of water

per cubic foot. If now the temperature of the air is raised to 70°, the

same amount of air is capable of containing 8 grains of water and is,

therefore, only 50 per cent. saturated.

Humidification is accomplished in air-conditioning plants through

one of two general methods: by the evaporation type of apparatus, in

which the passing air absorbs moisture from contact with a large area

of water; or the spray method, in which the water is broken into a

very fine spray by a specially devised nozzle and thus rendered easy

of absorption by the air to be moistened. A third method is sometimes

employed, in which steam is introduced into the air supply. Steam is

already vaporized water and immediately becomes a part of the air

without further change. The steam type of humidifying plant possesses

features that limit its application, in that the steam in some cases

may possess objectionable odor or includes the vapor of grease,

either of which would materially effect its use. Further, the heat

of vaporization liberated by the condensing steam is also a factor

that influences the temperature of the air and in case of direct

humidification must receive special attention.

=Vaporization as a Cooling Agent.=--The evaporation of water has a

distinct value aside from humidifying the air, in that the cooling

effect is in direct proportion to the added moisture. In the process of

evaporation the heat necessary to change the water into vapor is taken

from the surrounding air and the temperature is thus materially lowered.

In practical air-conditioning apparatus, of the evaporative or spray

types, the process consists of drawing the outside air into a chamber

filled with falling water that is broken up into drops like rain or

spray. In passing, every particle of the air comes into contact with

the water drops; the almost invisible particles of dust adhere to the

water and are carried away leaving the air washed clean. In addition

to freeing the air from dust, the intimate mixture of the air permits

of a ready absorption of the water, which is taken up to any per cent.

of saturation. After leaving the spray chamber, the moisture-laden

air passes through an eliminator in which any unabsorbed moisture

is extracted. It is possible for air to become not only completely

saturated with water under the conditions encountered in a humidifying

plant, but in addition, the movement of the air may carry along

unabsorbed particles that are precipitated directly after leaving the

spray chamber. For this reason the air is passed through an eliminator.

The eliminator is composed of a series of irregular sheet-metal

surfaces so arranged that the air is required to abruptly change its

direction several times in its passage of a short distance. The impact

of the air against the surfaces and the centrifugal force exerted by

the sudden changes of direction throw out the excess moisture and any

remaining suspended matter the air may contain.

The saturated air from the eliminator passes through a heater where the

temperature is raised to that of the rooms. In the rise of temperature

the air which is saturated is rendered capable of absorbing more

moisture, and hence has been dehumidified. The rise of temperature and

the corresponding decrease in relative humidity is intended to be such

as to leave in the finished air the desired percentage of moisture.

=Air-cooling Plants.=--The use of air-washing and humidifying plants

so far mentioned has been confined to elimination of dust and the

addition of moisture to air, under winter conditions. The same type of

apparatus, used in summer, becomes a cooling plant, and by observance

of the necessary requirements may be used to produce agreeable

atmospheric conditions during hot weather.

When used for such purpose the air is washed, by passing it through

falling water which frees it from dust and reduces its temperature.

It is then further cooled by passing over cold surfaces that take the

place of the heaters used in cold weather. The cooling surfaces are

pipe coils kept cold by the contained water which comes from the water

supply or from a refrigerating plant. The temperature and humidity are

thus changed to suit the requirements of the conditioned air.

During the hot weather of summer the most disagreeable atmospheric

condition is that caused by humidity near saturation, at a time of

relatively high temperature. Under such conditions the cooling plant

not only cools the air, but causes a precipitation of the moisture on

the cold surfaces which are kept below the dew-point. The air is cooled

and dehumidified to a point such that the conditioned air produces an

agreeable atmosphere. The regulation of the degree to which the air

is cooled is accomplished by the same general methods as are used in

heating.

=Humidity Control.=--The method of regulating atmospheric humidity in

a humidifying plant will be determined by the conditions under which

it is intended to work. There are a variety of means employed that may

be used to bring about the same effects, each of which is particularly

suited to certain requirements. The present object is to describe the

essential features of airconditioning plants, by use of illustrations

representing each of the three methods mentioned above. That of the

ventilation of a school building under winter conditions will be taken

as an example.

In Fig. 174 is shown a heating and ventilating system in which the

air conditioning is accomplished by automatic regulators for both

temperature and humidity. The plant occupies a room in the basement,

and a room directly above illustrates the conditions that prevail in

all of the other rooms of the building. The principal features of the

plant are the fan _G_, which supplies the air; the hot-air furnace _H_,

which furnishes the heat; and the water spray _S_, which provides the

moisture with which the air is humidified.

[Illustration: FIG. 174.--Furnace blast system of heating, with

temperature regulation and humidity control.]

The air is drawn in at _A_ to a room in which a motor-driven fan _G_

forces the supply through the heating apparatus into the building. The

air after leaving the fan passes through a cold-air duct _C_ to the

heating surfaces _H_ to be warmed. The air in passing over the heating

surfaces is raised to a degree considerably above the temperature of

the rooms. The hot air leaving the heater _H_ enters the tempered air

chamber _T_ through the passage _K_. A damper _M_ provides means for

also admitting cold air to the chamber _T_ directly from the fan. The

thermostat, located at _O_, is connected with a pneumatic motor _V_

(similar to Fig. 170) which regulates the supply of cold and hot air

from _K_ and _M_ to suit the desired temperature of the air supply

for the rooms above. The arm of the motor _V_ is so arranged that an

upward movement opens the cold-air and closes the hot-air passages;

the downward movement produces the opposite effect. The motor _V_ thus

controls the temperature of the air.

In this system the air is humidified by a direct water spray marked

_S_ in the drawing. A part of the hot air from the heater _H_ may

escape through the damper _W_ and absorb water on its way to the duct

_D_, which takes the air to the room above, where it enters through the

register _E_. This air as it comes from the heater, being hot, will

absorb a larger amount of water than the air could hold when cooled

to room temperature; for this reason only a part of the air supply is

humidified. The supply of the hot humid air is admitted to the duct _D_

in such quantity as will produce the desired degree of humidity in the

rooms.

The degree of room temperature is governed by the thermostat, in the

room, which, by means of the motor _N_, controls the damper _F_. This

damper admits hot humid air and the tempered air from the chamber _T_

in proper proportion. At any time the humidity of the air in the room

reaches the maximum amount for which it is set, the humidostat, through

its motor, closes the valve _R_, which controls the water supply to the

spray nozzle, and the moisture in the air is reduced until a further

amount is demanded. With apparatus of this kind the temperature and

humidity may be kept practically constant.

[Illustration: FIG. 175.--Direct steam heating system with mechanical

fan-blast ventilation, temperature regulation and humidity control.]

Fig. 175 shows another arrangement of a similarly controlled plant in

which steam is used for humidifying the air. The air is admitted at

_A_, from whence it passes through a steam-heating coil _S_, which

raises it to a predetermined temperature. The steam jets are arranged

at _H_, for providing the necessary moisture. The humidostat through a

motor valve _V_ governs the amount of steam that is permitted to enter

the humidifying chamber. A thermostat located in the air duct at _B_

controls the temperature of the air sent to the rooms by regulating the

amount of heat given out by the steam coils _S_. This control is made

still more sensitive by use of a cold-air bypass. The damper _D_ is

opened by a motor valve to admit cold air at the same time the steam is

shut off from the heater coils.

In this plant the ventilating air is not intended to supply all

of the heat to the rooms. A thermostat on the wall controls the

room temperature by regulating the amount of steam admitted to the

radiators. In the ventilating plant previously described, all of the

heat for the building is supplied through the ventilating system; in

the plant shown in Fig. 175, the heating apparatus which warms the

building is entirely separate and may be used when the ventilating

system is inoperative.

The humidity is controlled by admitting saturated air to the warmer air

of the rooms in such quantity as will produce the desired mixture. The

humidostat, on the left-hand wall, regulates the quantity of moisture

by opening or closing the steam valve _V_ as occasion requires.

Another example of air-conditioning plant similar in principle to that

just described is often called the dew-point system. It depends for

its action on a definite dew-point temperature at which the air is

saturated with moisture, before being heated to room temperature. The

air to be conditioned is first warmed, by passing through a set of

tempering coils, to a degree at which it will contain the necessary

moisture when saturated. After saturation the temperature is raised by

a second set of heating coils to the room temperature, the moisture

contained being right to give the desired humidity.

To illustrate, suppose that it is desired to maintain a constant

humidity of 50 per cent. saturation at 70°F. in the building. The

temperature at which the air must be saturated, to contain 4 grains of

moisture per cubic foot, is found in the table on page 199 to be 48°F.

The entering air must first be raised to that temperature by the

tempering coils. The air then enters the spray chamber where it absorbs

moisture to saturation, by contact with a multitude of water particles.

This saturated air now passes through a second set of heated coils and

takes up heat sufficient to raise it to the finished temperature.

The dew-point temperature at which the air enters the spray chamber

and the final temperature are kept constant by motor-operated valves

which supply the heating coils with the necessary heat in the form of

steam. The motors are controlled by thermostats, placed to measure the

temperature of the air as it enters the saturator and the finished air

as it enters the rooms. If these conditions are now kept constant, the

finished air will be constantly 50 per cent. saturated.

[Illustration: FIG. 176.--School building section showing a complete

air-conditioning plant.]

A plant of this character is illustrated in Fig. 176. The figure

shows the exterior of the casings which enclose the tempering coils

and saturator at _A_, the eliminator at _B_, and the heating coils at

_C_. This is another draw-through type of plant where a fan, enclosed

in _D_, draws the air through the conditioning apparatus and forces

it through the sheet-iron ducts _E_. The passages in the walls--as

indicated by the arrows--conduct the air through the register _R_, into

the room. The register _S_ represents the discharge duct through which

the vitiated air is forced from the room.

In this system of air conditioning, all of the ventilating air is to

be saturated with moisture at a temperature such that when raised to

room temperature will contain the desired percentage of humidity. The

saturator occupies the space between _A_ and _B_. A number of spray

jets are arranged to fill the entire space with water drops that are

moving in every direction. The air, as it passes, must come into

contact with the drops again and again, until by repeated impact each

particle is completely saturated and at the same time washed free from

dust. It has already been explained that the movement of the saturated

air through a mass of spray will carry with it a considerable amount

of unabsorbed water that must be taken out by an eliminator. A section

of the casing is broken out at _B_, showing the eliminator plates. The

irregular surfaces of these plates repeatedly change the direction of

the passing air, and the suspended water or remaining solid matter is

thrown against the surfaces where they adhere. The moisture accumulates

in drops of water that run down the plates to the bottom of the

enclosure and finally into the sewer.

From the eliminator the air passes through the heating coils enclosed

in _C_, where it is heated to the necessary temperature for admission

to the rooms.

The regulation of the temperature of the tempering coils and heating

coils is accomplished as in the other plants described. The thermostats

with their motors operate the valves of the heaters to admit steam

sufficient to keep constant temperatures at the different parts. The

humidity is maintained at a constant amount by saturating the air at a

constant temperature and therefore no humidostat is required.